STANDARD SUBMITTAL PACKAGE

SBP1300- &
FTA1300 Wye-Delta, Open Transition Starting Electric Fire Pump Controllers
Product Description

• Daylight Savings Time Option


• Weekly Test Timer
• Elapsed Time Meter
• Door mounted display/interface panel featuring a 128
x 64 pixel backlit LCD Graphical Display, Membrane
Type User Control Push-buttons and easy to read LED
Indicators for:
• POWER AVAILABLE
• ALARM
• TRANSFER SWITCH NORMAL (If unit ordered with
Automatic Power Transfer Switch)
• TRANSFER SWITCH EMERGENCY (If unit ordered with
Automatic Power Transfer Switch)
• SYSTEM PRESSURE LOW
• PUMP RUNNING
• DELUGE OPEN
• REMOTE START
Description—Firetrol® FTA1300 Wye-Delta, Open Transi- • INTERLOCK ON
tion Starting Fire Pump Controllers are used with delta-
wound squirrel cage motors. FTA1300 controllers are • FAIL TO START
of the open circuit transition type in which the motor • MOTOR OVERLOAD
circuit is opened during the transition from start to run. • EMERGENCY ISO SWITCH OFF (If unit ordered with
The controller monitors, displays and records fire pump Automatic Power Transfer Switch)
system information. • PHASE FAILURE
Actuating the controller by the pressure switch, START • PHASE REVERSAL
push-button or deluge valve contact closes the start • AUTOMATIC SHUTDOWN DISABLED
contactor connecting the motor to the line in the wye • OVERVOLTAGE
connection. The motor will draw approximately 33% of • UNDERVOLTAGE
its normal inrush current and develop approximately • Digital Pressure Display
33% of its normal starting torque. After a time delay, the • USB Host Controller and Port
motor is automatically reconnected in delta, applying • Solid State Pressure Transducer
full voltage to the motor windings. These controllers are • Data Log
recommended especially for use with generator sets. • Event Log (3000 Events)
Approvals – Firetrol fire pump controllers are listed by • True RMS Metering with simultaneous 3 Phase Display
Underwriters’ Laboratories, Inc., in accordance with of Amps, Volts, Frequency, Pressure and Alarm Mes-
UL218, Standard for Fire Pump Controllers, CSA, Standard sages
for Industrial Control Equipment, and approved by Factory • Disk Error message
Mutual. They are built to meet or exceed the require- • Disk Near Full message
ments of the approving authorities as well as NEMA and • Pressure Error message
the latest editions of NFPA 20, Installation of Centrifugal • Motor Over 320% message
Fire Pumps, and NFPA 70, National Electrical Code. • Local Start message
Standard Features—The following are included as stan- • Remote Start message
dard with each controller: • Emergency Start message
• Voltage surge protector • Fail To Start message
• Main Disconnect Switch sized for connected motor • Undervoltage message
horsepower and voltage • Overvoltage message
• Fire pump Circuit Breaker • NEMA Type 2 (IEC IP22) enclosure
• Single handle Isolating Disconnect Switch/Circuit • Suitable for use as Service Equipment
Breaker mechanism • Each standard controller comes with user set options
• Motor contactor for:
• Emergency Manual Run Mechanism to mechanically • Interlock Alarm • Low Pressure Audible
close motor contactor contacts in an emergency con- •Low Suction • Pump Run
dition • User Defined Input • Weekly Test
• Built-in Start and Stop push-buttons to bypass auto-
matic start circuits
• Minimum Run Timer / Off Delay Timer
FTA1000 — FTA1930 Electric Fire Pump Controllers
Specifications

Main Fire Pump Controller trip curve adjustment shall be factory set, tested and sealed for
The main fire pump controller shall be a factory assembled, the full load amps of the connected motor. The circuit breaker
wired and tested unit and shall conform to all the requirements shall be capable of being field tested to verify actual pick up,
of the latest edition of NFPA 20, Standard for the Installation locked rotor, and instantaneous trip points after field installa-
of Stationary Pumps for Fire Protection and NFPA 70, National tion without disturbing incoming line and load conductors.
Electrical Code.
The controller shall be listed by Underwriters Laboratories, Operator Interface
Inc., in accordance with UL218, Standard for Fire Pump Con- The fire pump controller shall feature an operator interface
trollers, CSA, and Canadian Standards Association CSA-C22.2, with user keypad. The interface shall monitor and display motor
Standard for Industrial Control Equipment (cULus), approved operating conditions, including all alarms, events, and pressure
by Factory Mutual and approved by the City of New York for conditions. All alarms, events, and pressure conditions shall
fire pump service. be displayed with a time and date stamp. The display shall be
a 128x64 Backlit LCD capable of customized graphics. The
Starting Method display and interface shall be NEMA rated for Type 2, 3R, 4, 4X,
The controller shall be of the combined manual and auto- and 12 protection and shall be fully accessible without opening
matic type designed for: the controller door. The display and user interface shall utilize
multiple levels of password protection for system security. A
Full Voltage Starting minimum of 3 password levels shall be provided.
Wye (Star)-Delta Open Transition Starting
Wye (Star)-Delta Closed Transition Starting Ammeter/Voltmeter
Part Winding Starting The fire pump controller operator interface shall be
Primary Resistance Reduced Voltage Starting capable of displaying true RMS digital motor voltage and
Autotransformer Reduced Voltage Starting current measurements for all three phases simultaneously.
Digital Soft Start Reduced Current Starting Displays requiring push-button and selector switches to
toggle between phases or current and voltage shall not be
of the fire pump motor having the horsepower, voltage, phase accepted.
and frequency rating shown on the plans and drawings. The Voltage and current shall be measured by True RMS
controller components shall be housed in a NEMA Type 2 (IEC technology to provide the most accurate measurement for
IP22) drip-proof, wall mounted enclosure. all sine waves, including non-sinusoidal waveforms. Average
responding meters will not be accepted.
Withstand Ratings (Short Circuit Current Ratings) Digital Status/Alarm Messages
All controller components shall be front mounted, wired The digital display shall indicate text messages for the
and front accessible for maintenance. The minimum withstand status and alarm conditions of:
rating of the controllers shall not be less than 100,000 Amps • Motor On • Sequential Start Time
RMS Symmetrical at 200-600 Volts*. If the available system • Minimum Run Time • Local Start
fault current exceeds these ratings, the controllers shall be / Off Delay Time • Remote Start
supplied with a withstand rating of 150,000 or 200,000 Amps • Fail to Start • System Battery Low
RMS Symmetrical, as required. • Under Voltage • Over Voltage
*Note: 100,000 Amp withstand rating not available in • Locked Rotor Trip • Over Frequency
some larger horsepowers. Consult factory for • Emergency Start • Motor Over 320%
details. • Drive Not Installed • Motor Overload
Isolation Switch and Circuit Breaker • Disk Error • Printer Error
The controller shall include a motor rated combination • Disk Near Full • Pressure Error
isolating disconnect switch/circuit breaker, mechanically inter- The Sequential Start Timer and Minimum Run Timer/Off Delay
locked and operated with a single, externally mounted handle. Timer shall be displayed as numeric values reflecting the value
When moving the handle from OFF to ON, the interlocking of the remaining time.
mechanism shall sequence the isolating disconnect switch ON
first, and then the circuit breaker. When the handle is moved LED Visual Indicators
from ON to OFF, the interlocking mechanism shall sequence LED indicators, visible with the door closed, shall indicate:
the circuit breaker OFF first, and then the isolating disconnect • Power Available • Alarm
switch. • Pump Running • System Pressure Low
The isolating disconnect switch/circuit breaker shall be • Remote Start • Transfer Switch Normal
mechanically interlocked so that the enclosure door cannot be • Deluge Open • Transfer Switch Emergency
opened with the handle in the ON position except by a hidden • Phase Failure • Phase Reversal
tool operated bypass mechanism. The isolating disconnect • Interlock On • Fail To Start
switch/circuit breaker shall be capable of being padlocked in • Motor Overload • Emerg. Iso. Switch Off
the OFF position for installation and maintenance safety, and • Automatic Shutdown Disabled
shall also be capable of being locked in the ON position without • Overvoltage • Undervoltage
affecting the tripping characteristics of the circuit breaker.
The controller door shall have a locking type handle and three
point cam and roller vault type hardware. The circuit breaker
Data Logging Seismic Certification
The digital display shall monitor the system and log the The controller shall be certified to meet or exceed the
following data: requirements of the 2006 International Building Code and
• Motor Calls/Starts • Pump Total Run Time the 2010 California Building Code for Importance Factor 1.5
• Pump Last Run Time • Total Controller Pwr On Time Electrical Equipment for Sds equal to 1.88 or less severe seismic
• Last Pump Start • Min/Max System Pressure regions. Qualifications shall be based upon successful tri-axial
• Last Phase Fail/Reversal • Last Locked Rotor Trip shake-table testing in accordance with ICC-ES AC-156. Certifi-
• Last Locked Rotor Current • Min/Max Frequency cation without testing shall be unacceptable. Controller shall
• Max Starting Currents • Max Run Currents be clearly labeled as rated for installation in seismic areas and a
• Min/Max Voltage per Phase while idle (not running) Certificate of Conformance shall be provided with the controller.
• Min Voltage per Phase during Start NOTE: Not available on Model FTA1500 Controllers
• Min/Max Voltage per Phase during Run
Operation
Event Recording A digitally set On Delay (Sequential Start) timer shall be
Memory - The controller shall record all operational and provided as standard. Upon a call to start, the user interface
alarm events to system memory. All events shall be time shall display a message indicating the remaining time value of
and date stamped and include an index number. The system the On Delay timer.
memory shall have the capability of storing 3000 events and The controller shall be field programmable for manual stop
allow the user access to the event log via the user interface. The or automatic stop. If set for automatic stopping, the controller
user shall have the ability to scroll through the stored messages shall allow the user to select either a Minimum Run Timer or an
in groups of 1 or 10. Off Delay Timer. Both timers shall be programmable through
the user interface.
USB Host Controller A nonadjustable restart delay timer shall be provided to
The controller shall have a built-in USB Host Controller. A allow the residual voltage of the motor to decay prior to restart-
USB port capable of accepting a USB Flash Memory Disk shall ing the motor. At least 2 seconds, but no more than 3 seconds,
be provided. The controller shall save all operational and alarm shall elapse between stopping and restarting the pump motor.
events to the flash memory on a daily basis. Each saved event A weekly test timer shall be provided as standard. The
shall be time and date stamped. The total amount of histori- controller shall have the ability to program the time, date, and
cal data saved shall solely depend on the size of the flash disk frequency of the weekly test. In addition, the controller shall
utilized. The controller shall have the capability to save settings have the capability to display a preventative maintenance mes-
and values to the flash disk on demand via the user interface. sage for a service inspection. The message text and frequency
of occurrence shall be programmable through the user inter-
Serial Communications face.
The controller shall feature a RS485 serial communications A Lamp Test feature shall be included. The user interface
port for use with 2 or 4 wire Modbus RTU communications. shall also have the ability to display the status of the system
inputs and outputs.
Solid State Pressure Transducer A Audible Test feature shall be included to test the opera-
The controller shall be supplied with a solid state pressure tion of the audible alarm device.
transducer with a range of 0-300 psi (0-20.7 bar) ±1 psi. The The controller shall not start the fire pump motor under a
solid state pressure switch shall be used for both display of single-phase condition. If the motor is already running when a
the system pressure and control of the fire pump controller. phase loss occurs, the controller shall continue to run the motor,
Systems using analog pressure devices or mercury switches but still display a Phase Failure alarm.
for operational control will not be accepted. The fire pump controller software shall be automatically
The START, STOP and SYSTEM PRESSURE shall be digi- upgradable through the USB port by simply inserting a flash
tally displayed and adjustable through the user interface. The disk with the new software. Fire pump controllers that require
pressure transducer shall be mounted inside the controller to laptop computers, handheld equipment or specialized devices
prevent accidental damage. The pressure transducer shall be for software upgrades shall be prohibited.
directly pipe mounted to a bulkhead pipe coupling without any The controller shall be a Firetrol brand.
other supporting members. Field connections shall be made
externally at the controller coupling to prevent distortion of
the pressure switch element and mechanism.

Emerson Network Power - Global Headquarters ASCO Power Technologies - Firetrol Brand Products
1050 Dearborn Drive 111 Corning Road, Suite 120
Columbus, OH 43085 Cary, NC 27518
Tel +1 614 888 0246 Tel +1 1 460 5200 FaY +1 1 460 5250

EmersonNetworkPower.com Firetrol.com

While every precaution has been taken to ensure accuracy and completeness herein, ASCO assumes no responsibility, and disclaims all liability, for damages resulting from use
of this information or for any errors or omissions. Information and specifications are subject to change without notice.
Emerson, Consider It Solved., Emerson Network Power, the Emerson Network Power Logo, ASCO, Firetrol and the Firetrol Logo are trademarks or registered trademarks of
Emerson Electric Co. All other names and logos referred to are trade names, trademarks, or registered trademarks of their respective owners. ©2013 Emerson Electric Co.
SP1000-50 (C)
3-PHASE
INCOMING ISOLATING CIRCUIT
LINES SWITCH BREAKER
4CT
LA 1M

5CT
LB 1M

6CT 1M
LC

2M
ST
2M

2M
SURGE
ARRESTER 1S
LA LB LC
1S

1S

6
1CR
7 1M
6CR 2M
8 1S
6CR 1S
9 2M

10

11

12

13

14

15

16 T1

17

18

19

20 1CR
2M
21 6CR
1M
22
2M
23

24

25

26

27

28

29

30

31
1PB
32

33

34

35

36

37
5PB
38

39 AA

40

41

42

A B C D E F
To page 2 To page 2 To page 2

ASCO
From Page 1 From Page 1 From Page 1
A B C D E F

43

44

45

46

47

48

49

50

51

52

53

54

55

56

57

58

59

60

61

62

63

64

65 3

66 4
5CR
67 26 5

68 25 6

69 25
5CR
70 24

71 23

72 22

73 21

74 20

75 19

76 19
4CR
77 18

78 17

79 17
4CR
80 16

81 15

82

83 H N 6 7 1 8 1 10

84

85
DV
86
NOTES
87

88

89