Mark IIXG Electric Fire

Pump Controllers

FTA1000
FTA1250
3412 Apex Peakway
Apex, NC 27502
FTA1300
Sales@Firetrol.com FTA1350
+1 919 460 5200
FTA1500
FTA1800
www.firetrol.com
FTA1930
Mark IIxg Electric Fire Pump Controllers

Side-by-side discon-
nect/circuit breaker
provides single handle
sequencing

Combined automatic and manual fire


pump controllers for starting electric mo-
tor driven fire pumps.
Firetrol® combined automatic and manual fire
pump controllers are intended for starting elec-
Operator Interface
The fire pump controllers feature an operator
tric motor driven fire pumps and are available interface with user keypad. The interface mon-
in the following configurations: itors and displays motor operating conditions,
FTA1000 – Full Voltage Starting including all alarms, events, and pressure con-
FTA1250 – Part Winding Reduced Current Start- ditions. All alarms, events, and pressure condi-
ing (Closed Circuit Transition) tions are displayed with a time and date stamp.
FTA1300 – Wye-Delta Reduced Voltage Starting The display is a 128x64 Backlit LCD capable of
(Open Circuit Transition) customized graphics and cryllic type character
FTA1350 – Wye-Delta Reduced Voltage Starting display. The display and interface are NEMA
(Closed Circuit Transition) rated for Type 2, 3R, 4, 4X, and 12 protection and
FTA1500 – Primary Resistance Reduced Voltage is fully accessible without opening the controller
Starting (Closed Circuit Transition) door. The user interface utilizes multiple levels
FTA1800 – Autotransformer Reduced Voltage of password protection for system security. A
Starting (Closed Circuit Transition) minimum of 3 password levels are provided.
FTA1930 – Digital Solid State Reduced Voltage
Starting (Closed Circuit Transition) Approvals
Firetrol fire pump controllers are listed by Un-
These Controllers are available assembled derwriters’ Laboratories, Inc., in accordance
with power transfer switches for use with an with UL218, Standard for Fire Pump Controllers,
emergency generator set or second power CSA, Standard for Industrial Control Equipment,
source. and approved by Factory Mutual. They are
built to meet or exceed the requirements of
the approving authorities as well as NEMA and
the latest editions of NFPA 20, Installation of
Centrifugal Fire Pumps, and NFPA 70, National
Electrical Code.

Digital Status/Alarm Messages


The digital display indicates text messages for
the stats and alarm conditions of:
• Motor On • Sequential Start Time
• Minimum Run Time • Local Start
/ Off Delay Time • Remote Start
• Fail to Start • System Battery Low
• Under Voltage • Over Voltage
• Locked Rotor Trip • Over Frequency
• Emergency Start • Motor Over 320%
• Drive Not Installed • Motor Overload
• Disk Error • Printer Error
• Disk Near Full • Pressure Error
Mark IIxg Electric Fire Pump Controllers

USB Host Port


and Flash
Disk
Standard features include:
• Voltage surge protector
• Main Disconnect Switch sized for connected motor
horsepower and voltage
• Fire pump Circuit Breaker
The Sequential Start Timer and Minimum Run • Single handle Isolating Disconnect Switch/Circuit
Timer/Off Delay Times are displayed as numeric Breaker mechanism
values reflecting the value of the remaining • Motor contactor
• Emergency Manual Run Mechanism to mechani-
time. cally close motor contactor contacts in an emer-
gency condition
LED Visual Indicators • Built-in Start and Stop push-buttons to bypass
LED indicators, visible with the door closed, automatic start circuits
• Minimum Run Timer / Off Delay Timer
indicate: • Daylight Savings Time Option
• Power Available • Alarm • Weekly Test Timer
• Pump Running • System Pressure Low • Elapsed Time Meter
• Remote Start • Transfer Switch Normal • Door mounted display/interface panel featuring a
128 x 64 pixel backlit LCD Graphical Display, Mem-
• Deluge Open • Transfer Switch Emergency brane Type User Control Push-buttons and easy to
• Phase Failure • Phase Reversal read LED Indicators for:
• Interlock On • Fail To Start • POWER AVAILABLE
• Motor Overload • Emerg. Iso. Switch Off • ALARM
• Automatic Shutdown Disabled • TRANSFER SWITCH NORMAL (If unit ordered with
Automatic Power Transfer Switch)
• Overvoltage • Undervoltage • TRANSFER SWITCH EMERGENCY (If unit ordered with
Automatic Power Transfer Switch)
Data Logging • SYSTEM PRESSURE LOW
• PUMP RUNNING
The user interface monitors the system • DELUGE OPEN
and logs the following data: • REMOTE START
•Motor Calls/Starts •Pump Total Run Time • INTERLOCK ON
•Pump Last Run Time •Total Controller Pwr On • FAIL TO START
Time •Last Phase Fail/Reversal •Last Locked • MOTOR OVERLOAD
• EMERGENCY ISO SWITCH OFF (If unit ordered with
Rotor Trip •Last Locked Rotor Current •Min/ Automatic Power Transfer Switch)
Max Frequency •Max Starting Currents •Max • PHASE FAILURE
Run Currents •Min/Max Voltage per Phase • PHASE REVERSAL
while idle (not running) • AUTOMATIC SHUTDOWN DISABLED
• OVERVOLTAGE
• Min Voltage per Phase during Start • UNDERVOLTAGE
• Min/Max Voltage per Phase during Run • Digital Pressure Display
• USB Host Controller and Port
Event Recording •

Solid State Pressure Transducer
Data Log
Memory - The controller records all oper- • Event Log (3000 Events)
ational and alarm events to system memory. • True RMS Metering with simultaneous 3 Phase Dis-
All events are time and date stamped and play of Amps, Volts, Frequency, Pressure and Alarm
include an index number. The system memory Messages
has the capability of storing 3000 events and • Disk Error message
• Disk Near Full message
allows the user access to the event log via the • Pressure Error message
user interface. The user can scroll through the • Motor Over 320% message
stored messages in groups of 1 or 10. • Local Start message
• Remote Start message
• Emergency Start message
USB Host Controller • Fail To Start message
The controller is equipped with a built-in • Undervoltage message
USB Host Controller. A USB port capable of ac- • Overvoltage message
• NEMA Type 2 enclosure
cepting a USB Flash Memory Disk is provided. • Suitable for use as Service Equipment
The controller saves all operational and alarm • Each standard controller comes with user config-
events to the flash memory on a daily basis. urable options for:
Each saved event is time and date stamped. • Interlock Alarm • Low Pressure Audible
The total amount of historical data saved de- •Low Suction • Pump Run
• User Defined Input • Weekly Test
pends on the size of the flash disk utilized. The
operator can save settings and values to the
flash disk on demand via the user interface.
Mark IIxg Electric Fire Pump Controllers

Audible Alarm
Mark IIxg Isolating Switch/
Circuit Breaker
Relay Board and Disconnect
Field Connection Handle
Terminals

Control Circuit Start/Stop/Test


Transformer and Push-buttons
Control Relays
Starting
Contactor(s)
Pressure
Emergency Run
Transducer and Assembly
Test Drain
Solenoid

Common Electric Components


Listed Above.
Controller Shown is FTA1300
Wye-Delta Open Transition

3412 Apex Peakway


Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages resulting from use of this
information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2019 Firetrol, Inc., All Rights Reserved. Cover designed by BiZkettE1 / Freepik
Publication CB1000-50 Rev. G