1. LOOP FOR A NEW MOTOR
The following pages will show the steps which are necessary to bring the motor
template in a runtime picture. It is an example for CW (Chip Washing) in the
FiberLine.
1.1 Description
Start the CAE Manager and open the project.
1
Open the archive FiberLine, select the archive CW (Chip Washing) with the right
mouse button and copy the motor template in the archive.
Select the new motor template with the right mouse button and click Rename.
Complete the New name and New description according the I/O-List an click OK.
2
This is the function chart of the motor template.
Select on the function chart with the right mouse button and click Properties.
Complete the Instance name with the short name of the plant component and the
next free instance number.
e. g. CW0015; CW… for Chip Washing
3
For example CW_111.
Select on the AAG_Motor M1 block with the right mouse button and click
Properties.
Complete the Name (Loop Nr. – Loop Description) and the LNR (Loopnumber).
4
Complete the InstBlock (blockinstance), same as the motorblock name.
Complete the InstPlan (planinstance), same as the instance name.
Complete the Error3_LT, Error4_LT, Error5_LT if they are connected (e.g. I/O-
Fault). (If the input Fault_3 connected, a text which describes the Alarm should be
enter at Error3_LT.)
2.1 Motorblock
2.1.1 Connector
Input:
• Show_LNR … show loopnumber;
Connectorname for Woodyard and Chip Handling: SHOW_LNR_WY
Connectorname for Fiberline, Chemicals, Evaporation: SHOW_LNR
5
Output:
• FbkOn … feedback on;
Connectorname = Loopnumber of the motor_outputname of the motor
block: e.g. ME2110_FbkOn
Input:
• AlarmGroup … Name for the Alarm Group;
Input:
• FbkOn … on response; feedback from motor
Hardware Input from the I/O-List
• Fault_1 … activate error; MCC fault
Hardware Input from the I/O-List
Output:
• OnCmd … off/on output;
Hardware Output from the I/O-List
2.2 Interlockblock
The interlock functions can be connected at 10 interlock signals.
2.2.1 Connector
Input:
• Language … change language;
Connectorname for Woodyard and Chip Handling: SYS010_Language_WY
Connectorname for Fiberline, Chemicals, Evaporation: SYS010_Language
• Mode01 … Interlock Mode (0 … 4);
0 … Interlock deactivate;
1 … Absolute (Valid in Manual and Auto mode);
2 … Limited (Valid in Auto mode);
3 … Absolute Start (Valid in Manual and Auto mode for motor start);
4 … Limited Start (Valid in Auto mode for motor start);
• Interlock01 … Interlock 01 activate;
6
2.2.2 Plant Constant
Input:
• ILName01_1 … Interlock Name 01, Text for Language 1;
• ILName01_2 … Interlock Name 01, Text for Language 2;
7
Open in the Picture block the archive CW (Chip Washing).
8
This drawing shows the symbols of the different picture blocks.