You are on page 1of 31

30RA 040-240 “B”

Air-Cooled Liquid Chillers


with Integrated Hydronic
Module
Nominal cooling capacity 39-245 kW

50 Hz

AQUASNAP

Carrier is participating in the


Eurovent Certification Programme.
Products are as listed in the
Eurovent Directory of Certified
Products.

For the operation of the control please refer to


the Pro-Dialog Control manual for the
30RA/RH - RY/RYH “B” series

Installation, operation and maintenance instructions


Contents
1 - INTRODUCTION........................................................................................................................................................................ 4
1.1 - Installation safety considerations................................................................................................................................................ .4
1.2 - Equipment and components under pressure............................................................................................................................... .4
1.3 - Maintenance safety considerations............................................................................................................................................. .5
1.4 - Repair safety considerations....................................................................................................................................................... .5
2 - Preliminary checks......................................................................................................................................................... 7
2.1 - Check equipment received.......................................................................................................................................................... .7
2.2 - Moving and siting the unit.......................................................................................................................................................... .7
3 - Dimensions/CLEARANCES.................................................................................................................................................. 9
4 - PHYSICAL DATA...................................................................................................................................................................... 11
5 - ELECTRICAL DATA................................................................................................................................................................ 11
6 - APPLICATION DATA............................................................................................................................................................... 13
6.1 - Unit operating range................................................................................................................................................................. .13
6.2 - Evaporator water flow rates...................................................................................................................................................... .13
6.3 - Minimum water flow rate......................................................................................................................................................... .13
6.4 - Maximum evaporator water flow rate....................................................................................................................................... .13
6.5 - Water loop volume.................................................................................................................................................................... .13
6.6 - Unit operating range at full and part load................................................................................................................................. .14
6.7 - Pressure drop in the plate heat exchangers............................................................................................................................... .14
7 - ELECTRICAL CONNECTION............................................................................................................................................... 15
7.1 - Control box............................................................................................................................................................................... .15
7.2 - Power supply............................................................................................................................................................................ .16
7.3 - Voltage phase imbalance (%).................................................................................................................................................... .16
8 - Recommended wire sections.................................................................................................................................... 17
8.1 - Field control wiring.................................................................................................................................................................. .17
9 - WATER CONNECTIONS......................................................................................................................................................... 18
9.1 - Operating precautions and recommendations........................................................................................................................... .18
9.2 - Hydronic connections............................................................................................................................................................... .18
9.3 - Frost protection......................................................................................................................................................................... .19
10 - NOMINAL SYSTEM WATER FLOW CONTROL.............................................................................................................. 21
10.1 - Water flow control procedure ................................................................................................................................................ .21
10.2 - Pump pressure/flow rate curves.............................................................................................................................................. .23
10.3 - Available static system pressure............................................................................................................................................. .23
11 - START-UP................................................................................................................................................................................. 24
11.1 - Preliminary checks................................................................................................................................................................. .24
11.2 - Actual start-up......................................................................................................................................................................... .24
11.3 - Operation of two units in master/slave mode......................................................................................................................... .24
12 - MAINTENANCE...................................................................................................................................................................... 25
12.1 - General maintenance of the refrigerant circuit....................................................................................................................... .25
12.2 - Refrigerant charge.................................................................................................................................................................. .25
12.3 - Electrical maintenance............................................................................................................................................................ .26
12.4 - Condenser coil........................................................................................................................................................................ .27
13 - AQUASNAP MAINTENANCE PROGRAMME................................................................................................................... 28
13.1 - Maintenance schedule............................................................................................................................................................. .28
13.2 - Description of the maintenance operations............................................................................................................................ .28
14 - start-up cHecklist for 30RA Liquid chillers (use for job file)....................................................... 30

The drawings in this document are for illustrative purposes only and is not part of any offer for sale or contract.


1 - INTRODUCTION In certain cases the globe stops are installed on ball valves.
These valves are factory-supplied lead-sealed in the open
Prior to the initial start-up of the 30RA units, the people involved position. This system permits isolating and removing the globe
in the on-site installation, start-up, operation, and maintenance of stop for checking and replacing. The globe stops are designed
this unit should be thoroughly familiar with these instructions and installed to ensure protection against fire risk. Removing
and the specific project data for the installation site. the globe stops is only permitted if the fire risk is fully controlled
and the responsibility of the user.
The 30RA liquid chillers are designed to provide a very high
level of safety during installation, start-up, operation and All factory-installed globe valves are lead-sealed to prevent
maintenance. They will provide safe and reliable service when any calibration change. If the globe valves are installed on a
operated within their application range. reversing valve (change-over), this is equipped with a globe
valve on each of the two outlets. Only one of the two glove
This manual provides the necessary information to familiarize valves is in operation, the other one is isolated. Never leave
yourself with the control system before performing start-up the reversing valve in the intermediate position, i.e. with both
procedures. The procedures in this manual are arranged in the ways open (locate the control element in the stop position). If
sequence required for machine installation, start-up, operation a globe stop is removed for checking or replacement please
and maintenance. ensure that there is always an active globe stop on each of the
reversing valves installed in the unit.
Be sure you understand and follow the procedures and safety
precautions contained in the instructions supplied with the Provide a drain in the discharge circuit, close to each valve,
machine, as well as those listed in this guide. to avoid an accumulation of condensate or rain water.

Earthquake resistance has not been verified for these units. The safety valves must be connected to discharge pipes. These
pipes must be installed in a way that ensures that people and
1.1 - Installation safety considerations property are not exposed to refrigerant leaks. These fluids
may be diffused in the air, but far away from any building air
This machine must be installed in a location that is not accessible intake, or they must be discharged in a quantity that is
to the public and protected against access by non-authorised appropriate for a suitably absorbing environment.
people.
Periodic check of the globe valves: See paragraph “Maintenance
After the unit has been received, when it is ready to be installed safety considerations”.
or reinstalled, and before it is started up, it must be inspected
for damage. Check that the refrigerant circuit(s) is (are) intact. Accumulation of refrigerant in an enclosed space can displace
Ensure especially that no components or pipes have shifted oxygen and cause asphyxiation or explosions.
(e.g. following a shock). If in doubt, carry out a leak tightness
check and verify with the manufacturer that the circuit integrity Inhalation of high concentrations of vapour is harmful and
has not been impaired. If damage is detected upon receipt, may cause heart irregularities, unconsciousness, or death.
immediately file a claim with the shipping company. Vapour is heavier than air and reduces the amount of oxygen
available for breathing. These products cause eye and skin
Do not remove the skid or the packaging until the unit is in irritation. Decomposition products are hazardous.
its final position. These units can be moved with a fork lift
truck, as long as the forks are positioned in the right place and 1.2 - Equipment and components under pressure
direction on the unit.
These products incorporate equipment or components under
The units can also be lifted with slings, using only the desig- pressure, manufactured by Carrier or other manufacturers. We
nated lifting points marked at the four corners at the unit base. recommend that you consult your appropriate national trade
association or the owner of the equipment or components under
These units are not designed to be lifted from above. Use pressure (declaration, re-qualification, retesting, etc.). The
slings with the correct capacity, and always follow the lifting characteristics of this equipment/these components are given
instructions on the certified drawings supplied with the unit. on the nameplate or in the required documentation, supplied
with the products.
Safety is only guaranteed, if these instructions are carefully
followed. If this is not the case, there is a risk of material Do not introduce high static and dynamic pressure compared
deterioration and injuries to personnel. with the existing operating pressures - either service or test
pressures in the refrigerant circuit or in the heat transfer circuit,
Never cover any safety devices. especially:
- limiting the elevation of the condensers or evaporators
This applies to the globe valve in the water circuit and the - taking the circulating pumps into consideration.
globe valve(s) in the refrigerant circuit(s).

Ensure that the valves are correctly installed, before operating


the unit.


1.3 - Maintenance safety considerations 1.4 - Repair safety considerations

Engineers working on the electric or refrigeration components All installation parts must be maintained by the personnel in
must be authorized and fully qualified to do so (electricians charge, in order to avoid material deterioration and injuries to
trained and qualified in accordance with IEC 60364 Classifica- people. Faults and leaks must be repaired immediately. The
tion BA4). authorized technician must have the responsibility to repair the
fault immediately. Each time repairs have been carried out to
All refrigerant circuit repairs must be carried out by a trained the unit, the operation of the safety devices must be re-checked.
person, fully qualified to work on these units. He must have
been trained and be familiar with the equipment and the If a leak occurs or if the refrigerant becomes polluted (e.g. by a
installation, and he must wear the necessary protective items short circuit in a motor) remove the complete charge using a
(gloves, glasses, protective clothes, safety shoes). recovery unit and store the refrigerant in mobile containers
(careful in case the refrigerant decomposes due to high tempera-
Soldering and welding: Component, piping and connection ture increases, as the decomposition products are dangerous).
soldering and welding operations must be carried out using the
correct procedures and by qualified operators. Pressurised con- If a leak occurs, evacuate all refrigerant, repair the leak detected
tainers must not be subjected to shocks, nor to large temperature and recharge the circuit with the total R407C charge, as
variations during maintenance and repair operations. indicated on the unit name plate. Never top up the charge. Only
charge liquid refrigerant R407C at the liquid line.
Never work on a unit that is still energized.
The 30RA 040 to 240 units use R407C refrigerant. These units
Never work on any of the electrical components, until the are essentially sold in Europe, and their operating range is
general power supply to the unit has been cut using the limited to an outside air temperature of approximately 45°C.
disconnect switch in the control box.
Always ensure you are using the correct refrigerant type
If any maintenance operations are carried out on the unit, before recharging the unit.
lock the power supply circuit in the open position ahead of
the machine. Charging any refrigerant other than the original charge type
(R407C) will impair machine operation and can even lead to
If the work is interrupted, always ensure that all circuits are a destruction of the compressors. The compressors operating
still deenergized before resuming the work. with R407C are charged with a synthetic polyolester oil.

ATTENTION: Even if the unit has been switched off, the R407C units have a hermetic refrigerant circuit and the origi-
power circuit remains energized, unless the unit or circuit nal charge needs not be topped up, as R407C is a zeotropic
disconnect switch is open. Refer to the wiring diagram for refrigerant.
further details. Attach appropriate safety labels.
Do not use oxygen to purge lines or to pressurize a machine
Operating checks: During the life-time of the system, inspection for any purpose. Oxygen gas reacts violently with oil, grease,
and tests must be carried out in accordance with national and other common substances.
regulations.
Never exceed the specified maximum operating pressures.
The information on operating inspections given in annex C of Verify the allowable maximum high- and low-side test pres-
standard EN378-2 can be used if no similar criteria exist in sures by checking the instructions in this manual and the
the national regulations. pressures given on the unit name plate.

Safety device checks (annex C6 – EN378-2): The safety Do not use air for leak testing. Use only refrigerant or dry
devices must be checked on site once a year for safety devices nitrogen.
(high-pressure switches), and every five years for external
overpressure devices (safety globe valves). Do not unweld or flamecut the refrigerant lines or any refri-
gerant circuit component until all refrigerant (liquid and
Contact Carrier Service for a detailed explanation of the vapour) has been removed from chiller. Traces of vapour
high-pressure switch test method. should be displaced with dry air nitrogen. Refrigerant in
contact with an open flame produces toxic gases.
If the machine operates in a corrosive environment, inspect
the protection devices more frequently. The necessary protection equipment must be available, and
appropriate fire extinguishers for the system and the
Regularly carry out leak tests and immediately repair any leaks. refrigerant type used must be within easy reach.

Do not siphon refrigerant.


Avoid spilling liquid refrigerant on skin or splashing it into Use mechanical lifting equipment (crane, hoist, etc.) to lift or
the eyes. Use safety goggles. Wash any spills from the skin move heavy components such as compressors or plate heat
with soap and water. If liquid refrigerant enters the eyes, exchangers. For lighter components, use lifting equipment
immediately and abundantly flush the eyes with water and when there is a risk of slipping or losing your balance.
consult a doctor.
Use only original replacement parts for any repair or compo-
Never apply an open flame or live steam to a refrigerant nent replacement. Consult the list of replacement parts that
container. Dangerous overpressure can result. If it is corresponds to the specification of the original equipment.
necessary to heat refrigerant, use only warm water.
Do not drain water circuits containing industrial brines,
During refrigerant removal and storage operations follow without informing the technical service department at the
applicable regulations. These regulations, permitting condition- installation site or a competent body first.
ing and recovery of halogenated hydrocarbons under optimum
quality conditions for the products and optimum safety Close the entering and leaving water shutoff valves and purge
conditions for people, property and the environment are the unit hydronic circuit, before working on the components
described in standard NFE 29795. installed on the circuit (screen filter, pump, water flow switch,
etc.).
Any refrigerant transfer and recovery operations must be
Periodically inspect all valves, fittings and pipes of the
carried out using a transfer unit. A 3/8” SAE connector on
refrigerant and hydronic circuits to ensure that they do not
the manual liquid line valve is supplied with all units for
show any corrosion or any signs of leaks.
connection to the transfer station. The units must never be
modified to add refrigerant and oil charging, removal and
purging devices. All these devices are provided with the units.
Please refer to the certified dimensional drawings for the units.

Do not re-use disposable (non-returnable) cylinders or attempt


to refill them. It is dangerous and illegal. When cylinders are
empty, evacuate the remaining gas pressure, and move the
cylinders to a place designated for their recovery. Do not
incinerate.

Do not attempt to remove refrigerant circuit components or


fittings, while the machine is under pressure or while it is
running. Be sure pressure is at 0 kPa before removing
components or opening a circuit.

Any manipulation (opening or closing) of a shut-off valve


must be carried out by a qualified and authorised engineer.
These procedures must be carried out with the unit shut-down.

NOTE: The unit must never be left shut down with the liquid
line valve closed, as liquid refrigerant can be trapped between
this valve and the expansion device. (This valve is situated on
the liquid line before the filter drier box.)

Do not attempt to repair or recondition any safety devices


when corrosion or build-up of foreign material (rust, dirt,
scale, etc.) is found within the valve body or mechanism. If
necessary, replace the device. Do not install safety valves in
series or backwards.

CAUTION
Do not step on refrigerant lines. The lines can break under
the weight and release refrigerant, causing personal injury.

No part of the unit must use feet, racks or supports during


operation. Periodically monitor and repair or if necessary
replace any component or piping that shows signs of damage.

Do not climb on a machine. Use a platform, or staging to


work at higher levels.


2 - Preliminary checks 2.2 - Moving and siting the unit

2.1 - Check equipment received 2.2.1 - Moving

• Inspect the unit for damage or missing parts. If damage is See chapter “Installation safety considerations”
detected, or if shipment is incomplete, immediately file a
claim with the shipping company. 2.2.2 - Siting the unit
• Confirm that the unit received is the one ordered. Compare
the name plate data with the order. Always refer to the chapter “Dimensions and clearances” to
• The unit name plate must include the following information: confirm that there is adequate space for all connections and
- Version number service operations. For the centre of gravity coordinates, the
- Model number position of the unit mounting holes, and the weight distribu-
- CE marking tion points, refer to the certified dimensional drawing supplied
- Serial number with the unit.
- Year of manufacture and test date
- Refrigerant used and refrigerant class CAUTION: Only use slings at the designated lifting points
- Refrigerant charge per circuit which are marked on the unit.
- Containment fluid to be used
- PS: Min./max. allowable pressure (high and low Before siting the unit check that:
pressure side) • the permitted loading at the site is adequate or that
- TS: Min./max. allowable temperature (high and low appropriate strengthening measures have been taken.
pressure side) • the surface is horizontal, flat and intact.
- Globe valve cut-out pressure • there is adequate space above the unit for air flow.
- Pressure switch cut-out pressure • there are adequate support points and that they are in the
- Unit leak test pressure right places.
- Voltage, frequency, number of phases • the location is not subject to flooding.
- Maximum current drawn • where heavy snowfall is likely and long periods of sub-
- Maximum power input zero temperatures are normal, provision has been made to
- Unit net weight prevent snow accumulating by raising the unit above the
height of drifts normally experienced.
High pressure Low pressure
Min. Max. Min. Max.
Baffles may be necessary to deflect strong winds and to
PS (bar) -0.9 32 -0.9 25
prevent snow from blowing directly into the unit. They
TS (°C) -20 72 -20 62 must not restrict air flow into the unit.
Pressure switch cut-out pressure (bar) 29 -
Valve cut-out pressure (bar) 32 25
Test pressure, unit leak test (bar) 15 CAUTION: Before lifting the unit, check that all casing
panels are securely fixed in place. Lift and set down the unit
• Confirm that all accessories ordered for on-site installation with great care. Tilting and jarring can damage the unit and
have been delivered, and are complete and undamaged. impair unit operation.
• The unit must be checked periodically during its whole
operating life to ensure that no shocks (handling accessories, The 30RA units can be hoisted with rigging. Coils should
tools etc.) have damaged it. If necessary, the damaged parts always be protected against crushing while a unit is being
must be repaired or replaced. See also chapter “Maintenance”. moved. Use struts or spreader bars to spread the slings above
the unit. Do not tilt a unit more than 15°.

WARNING: Never push or lever on any of the enclosure


panels of the unit. Only the base of the unit frame is designed
to withstand such stresses.


Checks before system start-up

Before the start-up of the refrigeration system, the complete


installation, including the refrigeration system must be verified
against the installation drawings, dimensional drawings, system
piping and instrumentation diagrams and the wiring diagrams.

During the installation test national regulations must be


followed. If no national regulation exists, paragraph 9-5 of
standard EN 378-2 can be used as a guide.

External visual installation checks:


• Compare the complete installation with the refrigeration
system and power circuit diagrams.
• Check that all components comply with the design
specifications.
• Check that all safety documents and equipments that are
required by current European standards are present.
• Verify that all safety and environmental protection devices
and arrangements are in place and comply with the current
European standard.
• Verify that all document for pressure containers, certificates,
name plates, files, instruction manuals that are required
documents required by the current European standards are
present.
• Verify the free passage of access and safety routes.
• Check that ventilation in the plant room is adequate.
• Check that refrigerant detectors are present.
• Verify the instructions and directives to prevent the
deliberate removal of refrigerant gases that are harmful to
the environment.
• Verify the installation of connections.
• Verify the supports and fixing elements (materials, routing
and connection).
• Verify the quality of welds and other joints.
• Check the protection against mechanical damage.
• Check the protection against heat.
• Check the protection of moving parts.
• Verify the accessibility for maintenance or repair and to
check the piping.
• Verify the status of the valves.
• Verify the quality of the thermal insulation and of the
vapour barriers.


3 - Dimensions/CLEARANCES

30RA 040-080

1081 2071
1329

1000
1000

1 2

1000
2

1000

30RA 090-160

2278 2071
1329

1000

2 2

1
1000

1000 1000


30RA 200-240

2279 3351
1674

1000

1 2

2
2

1000
1 2

1000 1000

Legend: NOTE:
All dimensions are given in mm
A Non-certified drawings.
Control box Refer to the certified dimensional drawings supplied with the unit or
available on request, when designing an installation.
Water inlet
For the location of fixing points, weight distribution and coordinates of
Water outlet the centre of gravity refer to the certified dimensional drawings.

Required clearances for air flow B In multiple-chiller installations (maximum four units), the side clearance
between the units should be increased from 1000 to 2000 mm.
Recommended clearances for maintenance
C The height of the solid surface must not exceed 2 m.
Air outlet, do not obstruct

Power cable entry

Multiple chiller installation


NOTE: If the walls are higher than 2 m, contact the factory.
Solid surface Solid surface
1000

1000
2000
2000
2000

1000 1000
2000

1000

10
4 - PHYSICAL DATA

30RA 040 050 060 070 080 090 100 120 140 160 200 240
Nominal cooling capacity* kW 39.4 49.0 57.0 67.0 79.0 89.0 97.0 115.0 135.0 151.0 198.0 245.0
Operating weight with hydronic module kg
Single pump 526 584 597 611 631 1093 1106 1205 1212 1248 2133 2305
Dual pump 606 664 677 691 708 1170 1183 1305 1312 1348 2221 2393
Operating weight without hydronic module 502 560 573 587 605 1062 1075 1167 1174 1210 1986 2158
Refrigerant charge kg R407C
Circuit A 10 13 15 12.5 18 10 10 15 12.5 18 21 28
Circuit B - - - - - 13 14 15 12.5 18 28 28
Compressors Hermetic scroll compressor, 48.3 r/s
Quantity, circuit A 1 2 2 2 2 1 1 2 2 2 2 3
Quantity, circuit B - - - - - 2 2 2 2 2 3 3
No. of capacity steps 1 2 2 2 2 3 3 4 4 4 5 6
Minimum capacity % 100 46 42 50 50 25 25 21 25 25 20 16.6
Control type PRO-DIALOG Plus
Condensers Grooved copper tubes, aluminium fins
Fans Axial Flying Bird fans with rotating shroud
Quantity 1 1 1 1 1 2 2 2 2 2 4 4
Total air flow (high speed) l/s 3945 3780 4220 5150 5800 7725 8165 8840 10300 11600 17343 20908
Speed (high/low speed) r/s 11.5/5.8 11.5/5.8 11.5/5.8 15.6/7.8 11.5/5.8 11.5/5.8 11.5/5.8 15.6/7.8 15.6/7.8 11.5/5.8 15.6/7.8
Evaporator Direct-expansion welded plate heat exchanger
Water volume l 3.6 4.6 5.9 6.5 7.6 7.2 8.2 9.8 11.4 13.0 22.0 26.0
Max. water-side operating pressure kPa
Option without hydronic module 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Unit with hydronic module 300 300 300 300 300 300 300 300 300 300 400 400
Hydronic module
Pump (one single centrifugal, 48.3 r/s) Monocell composite pump Monocell pump
Expansion tank volume l 12 12 12 12 12 35 35 35 35 35 50 50
Expansion tank pressure** kPa 100 100 100 100 100 150 150 150 150 150 150 150
Water connections Victaulic (connection sleeves supplied) Threaded male gas
(with and without hydronic module) connections
Diameter in 2 2 2 2 2 2 2 2-1/2 2-1/2 2-1/2 3 3
Outside tube diameter mm 60.3 60.3 60.3 60.3 60.3 60.3 60.3 76.1 76.1 76.1 88.9 88.9
* Nominal conditions: evaporator entering/leaving water temperature 12°C/7°C, outdoor air temperature 35°C.
** When delivered, the pre-inflation of the tank keeps the plated membrane in the upper part of the tank. To permit changing the water volume, change the inflation
pressure to a pressure that is close to the static head of the system (see below), fill the system with water (purging the air) to a pressure value that is 10 to 20 kPa
higher than the pressure in the tank.
Static head, m/Pressure, bar/Pressure, kPa
5 - 0,5 - 50 / 10 - 1 - 100 / 15 - 1,5 - 150 / 20 - 2 - 200 / 25 - 2,5 - 250

5 - ELECTRICAL DATA

30RA (without hydronic module) 040 050 060 070 080 090 100 120 140 160 200 240
Power circuit
Nominal power supply V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit supply The control circuit is supplied via the unit-mounted transformer
Maximum unit power input* kW 20.3 24.6 30.1 35.2 39.9 44.1 49.6 60.5 70.6 79.6 104.2 124.9
Nominal unit current draw** A 27.9 34.7 41.1 47.0 54.3 62.7 69.1 82.3 94.1 108.6 140.2 168.7
Maximum unit current draw at 360 V*** A 36.9 45.6 54.9 62.7 72.4 82.6 91.9 109.8 125.4 144.8 185.4 222.9
Maximum unit current draw at 400 V**** A 33.6 41.4 49.7 56.9 65.6 75.1 83.4 99.5 113.9 131.3 168.6 202.8
Maximum start-up current
Standard unit† A 158.4 151.0 168.9 176.1 190.4 199.8 208.1 218.6 233.0 256.1 293.4 327.6
With electronic starter control‡ A 99.0 101.0 113.0 120.0 128.0 - - - - - - -
Short-circuit stability and protection See table on the next page
* Power input of the compressor(s) + fan(s) at maximum unit operating conditions: entering/leaving water temperature = 15°C/10°C, maximum condensing
temperature of 67.8°C, and 400 V nominal voltage (values given on the unit name plate).
** Nominal unit current draw at nominal conditions: evaporator entering/leaving water temperature 12°C/7°C, outdoor air temperature 35°C. The current values are
given at 400 V nominal voltage.
*** Maximum unit operating current at maximum unit power input and 360 V.
**** Maximum unit operating current at maximum unit power input and 400 V (values given on the unit name plate).
† Maximum instantaneous starting current at 400 V nominal voltage and with compressor in across-the-line start (maximum operating current of the smallest
compressors + fan current + locked rotor current of the largest compressor).
‡ Maximum instantaneous starting current at 400 V nominal voltage and with compressor with electronic starter (maximum operating current of the smallest
compressor(s) + fan current + reduced start-up current of the largest compressor).

Hydronic module 040 050 060 070 080 090 100 120 140 160 200 240
Single pump
Shaft power kW 0.75 0.75 0.75 0.75 1.1 1.1 1.1 1.85 1.85 1.85 5.5 5.5
Power input* kW 1.1 1.1 1.1 1.1 1.4 1.4 1.4 2.5 2.5 2.5 6.6 6.6
Maximum current draw at 400 V** A 2.1 2.1 2.1 2.1 3.1 3.1 3.1 5.0 5.0 5.0 10.6 10.6
Dual pump
Shaft power kW 2.2 2.2 2.2 2.2 2.2 2.2 2.2 3.0 3.0 3.0 5.5 5.5
Power input* kW 2.7 2.7 2.7 2.7 2.7 2.7 2.7 4.0 4.0 4.0 6.6 6.6
Maximum current draw at 400 V** A 4.7 4.7 4.7 4.7 4.7 4.7 4.7 6.6 6.6 6.6 10.6 10.6
Note: The water pump power input values are given for guidance only.
* To obtain the maximum power input for a unit with hydronic module add the maximum unit power input from the top table to the pump power input (*) from the table
above.
** To obtain the maximum unit operating current draw for a unit with hydronic module add the maximum unit current draw from the top table to the pump current
draw from the table above.

11
Compressor usage and electrical data
COMPRESSOR 30RA
Reference code I Nom I Max LRA* Circuit 040 050 060 070 080 090 100 120 140 160 200 240
DQ 12 CA 001EE 14.0 19.1 130 A A1
B B1
DQ 12 CA 002EE 16.2 22.1 130 A A2 A1 A1
B B2 B1 B1
DQ 12 CA 031EE 21.9 28.3 145 A A2 A1+A2 A2 A1+A2
B B2 B2 B1+B2
DQ 12 CA 036EE 24.5 32.8 155 A A1 A1+A2 A1 A1 A1+A2 A1+A2 A1+A2+A3
B B1+B2 B1+B2+B3 B1+B2+B3
Legend:
I Nom Nominal current draw at Eurovent conditions (see definition of conditions under nominal unit current draw), A
I Max Maximum operating current at 360 V, A
LRA Locked rotor current, A

* With option 25 (electronic starter) the LRA value is reduced by 40%; the maximum start-up time per compresor is <0.8 seconds.

Short-circuit stability and protection

30RA Short-term short-circuit stability (1s) With fuse Other fuses Other protection type
Without fuse
rms value/peak rms value rms value I2t (A2s)/peak limit
kA* kA ** kA*** kA****
040-080 5/7.5 80A gL:50 100A gL:30 19200/12
125A gL:25
160A gL:6
090-160 8/15 160A gL:100 200A gL:35 155000/20
200 8/15 200A gL:100 224A gL:40 280000/20
250A gL:35
240 8/15 250A gL:50 N/A 550000/25

List of recommended components with Siemens reference details

30RA Fused disconnect Contact protection Control handle NH Fuses New protection level with fused
disconnect switch, rms value, kA**
040-080 80 A: 3KL7114-3AA00 3KX71-32-1AA00 Use from disconnect switch 80 A 00gL: 3NA3 824 (3 off) 100
090-160 160 A: 3KL7123-3DA00 3KX71-32-2AA00 of the standard unit 160 A 00gL: 3NA3 836 (3 off) 50
200-240 200 A: 3KL7131-3AA00 3KX71-32-3AA00 + 3KX7112-4AA00 200 A 1gL: 3NA3 140 (3 off) 200 A gL: 50
3KX71-31-3AA00 + 224 A 1gL: 3NA3 142 (3 off) 224 A gL: 50
3KX71-31-3AB00 250 A 1gL: 3NA3 144 (3 off) 250 A gL: 50
224 A + 250 A: 3KL7132-3AA00
240 315 A: 3KL7141-3AA00 3KX71-32-4AA00 + 3KX7112-4AA00 315 A 2gL: 3NA3 252 (3 off) 315 A gL: 40
400 A: 3KL7142-3AA00 3KX71-31-4AA00 + 400 A 2gL: 3NA3 260 (3 off) 400 A gL: 30

3KX71-31-4AB00
*  This value corresponds to the switch/disconnect capacity, to the power distribution bus bar system capacity (if used) and to the protection circuit capacity in the
standard unit.
**  If the short-circuit current is higher, the unit can be protected by the fuse shown for the specific level.
The fuses (not supplied for Carrier units) are as recommended, to be installed upstream of the unit.
For unit sizes 040 to 160 a fused disconnect switch, equipped with fuses, can be installed in place of the standard unit switch. This should be done on site; please
contact the local service department or a qualified electrician. Alternatively please order the special version from the factory by contacting your local Carrier dealer.
For unit sizes 200 and 240 the installation requires drilling a hole into the control box, changing of the front door, and adapting the bus bar to be able to install the
new fused disconnect switch which is larger than the one used for the standard units.To order this special version from the factory, contact your local Carrier office.
*** Shows the new protection values with higher-capacity fuses than those specified in the previous column. If such fuses are part of the electrical installation
upstream of the unit, this is sufficient as anti-short circuit protection to the specified level, without additional protection.
**** If a protection device, other than the recommended fuses above, is used for the installation to ensure that no additional protection is required, the protection
device must have the specified thermal limit (I2t) and limit effect characteristics for the short-circuit current. If the protection device does not have the specified
characteristics, one of the specified protection fuses from the previous columns must be installed.

12
Electrical data notes 30RA:
• 30RA 040-240 units have a single power connection point located at the ‑ altitude: ≤ 2000 m
main switch. ‑ presence of hard solids, class 4S2 (no significant dust present)
• The control box includes the following standard features: ‑ presence of corrosive and polluting substances, class 4C2 (negligible)
- a main disconnect switch, starter and motor protection devices for ‑ vibration and shock, class 4M2
each compressor, the fan and the pump b. Competence of personnel, class BA4* (trained personnel ‑ IEC 60364)
- the control devices 2. Power supply frequency variation: ± 2 Hz.
• Field connections: 3. The neutral (N) conductor must not be connected directly to the unit (if
All connections to the system and the electrical installations must be in full necessary use a transformer).
accordance with all applicable local codes. 4. Overcurrent protection of the power supply conductors is not provided with
• The Carrier 30RA units are designed and built to ensure conformance with the unit.
these codes. The recommendations of European standard EN 60204‑1 5. The factory-installed disconnect switch(es)/circuit breaker(s) is (are) of a type
(machine safety ‑ electrical machine components ‑ part 1: general regulations suitable for power interruption in accordance with EN 60947.
- corresponds to IEC 60204-1) are specifically taken into account, when 6. The units are designed for connection to TN networks (IEC 60364). For IT
designing the electrical equipment. networks the earth connection must not be at the network earth. Provide a
local earth, consult competent local organisations to complete the electrical
NOTES: installation.
• Generally the recommendations of IEC 60364 are accepted as compliance
with the requirements of the installation directives. Conformance with EN Caution: If particular aspects of an actual installation do not conform to the
60204 is the best means of ensuring compliance with the Machines conditions described above, or if there are other conditions which should be
Directive § 1.5.1. considered, always contact your local Carrier representative.
• Annex B of EN 60204‑1 describes the electrical characteristics used for the
operation of the machines. * The required protection level for this class is IP43BW (according to reference
document IEC 60529). All 30RA units are protected to IP44CW and fulfil this
1.The operating environment for the 30RA units is specified below: protection condition.
a. Environment* ‑ Environment as classified in EN 60721 (corresponds to
IEC 60721):
‑ outdoor installation*
‑ ambient temperature range: ‑10°C to +45°C, class 4K3*

6 - APPLICATION DATA 6.3 - Minimum water flow rate

6.1 - Unit operating range If the installation flow rate is below the minimum flow rate,
recirculation of the evaporator water flow may take place,
Evaporator Minimum °C Maximum °C leading to the risk of excessive fouling.
Water entering temp. (at start-up) 7.8* 30
Water leaving temp. (in operation) 5** 15
Water entering temp. (at shut down) - 55 6.4 - Maximum evaporator water flow rate
Condenser
Entering air temp. -10*** 46*** This is limited by the permitted evaporator pressure drop.
Do not exceed the maximum operating temperature. Also, a minimum evaporator ∆T of 2.8 K must be guaranteed,
* For a system requiring operation below 7,8°C, contact Carrier. which corresponds to a water flow rate of 0.9 l/s per kW.
** For a system requiring operation below 5°C, anti-freeze must be added to
the unit.
*** Maximum outside temperature: For transport and storage of the 30RA units 6.5 - Water loop volume
the minimum and maximum allowable temperatures are –20°C and +55°C. It
is recommended that these temperatures are used for transport by container.
6.5.1 - Minimum water loop volume
6.2 - Evaporator water flow rates The minimum water loop volume, in litres, is given by the
following formula:
30RA Evaporator water flow Volume = CAP (kW) x N* = litres, where CAP is the nominal
Min. flow rate Max. flow rate* Max. flow rate** cooling capacity at nominal operating conditions.
Single pump Dual pump
l/s l/s l/s l/s
Application N*
040 1.1 3.5 4.4 3.7
Air conditioning
050 1.1 4 5.2 4.6
30RA 040 3.5
060 1.4 4.4 6 5.8
30RA 050 to 240 2.5
070 1.5 4.6 6.4 6.4
080 1.7 5.5 6.8 7.3 Industrial process cooling
090 2.7 5.6 6.9 7.6 30RA 040 to 240 (See note)
100 3 5.8 7.4 8.8
120 3.6 8.5 10.5 10.8
140 4.2 8.8 11.4 12.7 Note: For industrial process cooling applications, where
160 4.8 9.1 11.9 14.4 high stability of the water temperature levels must be achieved,
200 5.6 15.3 15.3 19.1
240 6.8 23.4 23.4 24.2 the values above must be increased.
* Maximum flow rate at an available pressure of 50 kPa (unit with hydronic
module). This volume is required to obtain temperature stability and
** Maximum flow rate at a pressure drop of 100 kPa in the plate heat exchanger
(unit without hydronic module). precision.

13
To achieve this volume, it may be necessary to add a storage 6.7 - Pressure drop in the plate heat exchangers
tank to the circuit. This tank should be equipped with baffles to
10000
allow mixing of the fluid (water or brine). Please refer to the
1
examples below. 2
3
4
1000 5
6

Pressure drop, kPa


7
8
100
Bad Good 9

11 10
12
10

Bad Good 1
1 10 20 30 40
Water flow rate, l/s
6.5.2 - Maximum water loop volume
Legend
Units with hydronic module incorporate an expansion tank that 1 30 RA 040
limits the water loop volume. The table below gives the maximum 2 30 RA 050
3 30 RA 060
loop volume for pure water or ethylene glycol with various 4 30 RA 070
concentrations. 5 30 RA 080
6 30 RA 090
7 30 RA 100
30RA 040-080 30RA 090-160 30RA 200-240
8 30 RA 120
(in litres) (in litres) (in litres)
9 30 RA 140
Pure water 600 1500 2000 10 30 RA 160
EG 10% 450 1200 1600 11 30 RA 200
EG 20% 400 1000 1400 12 30 RA 240
EG 35% 300 800 1000

EG: Ethylene glycol

6.6 - Unit operating range at full and part load

˚C

46

45
Entering air temperature

44.5
44

-10

0 5 8 10 ˚C

Evaporator water leaving temperature

1 Evaporator ∆T = 5 K
2 The evaporator and the hydronic circuit pump are frost protected down to
-10°C outside air temperature.

Operating range with required anti-freeze solution and special Pro-Dialog


control configuration

14
7 - ELECTRICAL CONNECTION

7.1 - Control box

30RA 040-080
A A
X

68 33 33

5.5

95
PE
347

S
L1 L2 L3

30RA 090-160

589

552
X
499

1
363
402
441

Y
222

170

132

B
39

39

8.5

Legend
1 Main disconnect switch
PE
PE Earth connection
S Power supply cable section (see table “Recommended wire sections”).
X Disconnect switch position referred to the unit side
Y Control box position referred to the unit base

X (mm) Y (mm)
30RA 040 - 080 190 762
30RA 090 - 160 1415 762
30RA 200 - 240 1161 1107

15
30RA 200-240
783

718
X
652
C

365
404
442
Y
324

C 258
Legend
1 Main disconnect switch
PE Earth connection
193
S Power supply cable section (see table “Recommended wire sections”).
X Disconnect switch position referred to the unit side

39
Y Control box position referred to the unit base

X (mm) Y (mm)
39

30RA 040 - 080 190 762


30RA 090 - 160 1415 762 PE
30RA 200 - 240 1161 1107
8.5

NOTES:
The 30RA 040-240 units have only one power connection
point located at the main disconnect switch.

Before connecting electric power cables, it is imperative to


check the correct order of the 3 phases (L1 - L2 - L3).

Non-certified drawings. Refer to the certified drawings


supplied with the unit or available on request.

7.2 - Power supply 7.3 - Voltage phase imbalance (%)

The power supply must conform to the specification on the 100 x max. deviation from average voltage
chiller name plate. The supply voltage must be within the range Average voltage
specified in the electrical data table.
For connections refer to the wiring diagrams. Example:
On a 400 V - 3 ph - 50 Hz supply, the individual phase voltages
WARNING: Operation of the chiller with an improper supply were measured to be:
voltage or excessive phase imbalance constitutes abuse which
will invalidate the Carrier warranty. If the phase imbalance AB = 406 V ; BC = 399 ; AC = 394 V
exceeds 2% for voltage, or 10% for current, contact your local
electricity supply source at once and ensure that the chiller is Average voltage = (406 + 399 + 394)/3 = 1199/3
not switched on until corrective measures have been taken. = 399.7 say 400 V

Calculate the maximum deviation from the 400 V average:


(AB) = 406 - 400 = 6
(BC) = 400 - 399 = 1
(CA) = 400 - 394 = 6
Motor

The maximum deviation from the average is 6 V. The greatest


percentage deviation is:100 x 6/400 = 1.5 %

This is less than the permissible 2% and is therefore acceptable.

16
8 - Recommended wire sections 8.1 - Field control wiring

Wire sizing is the responsibility of the installer, and depends on For the field control wiring of the following elements please
the characteristics and regulations applicable to each installation refer to the 30RA/RH - RY/RYH “B” series Pro-Dialog Plus
site. The following is only to be used as a guideline, and does Control manual, and the certified wiring diagram supplied with
not make Carrier in any way liable. After wire sizing has been the unit:
completed, using the certified dimensional drawing, the instal- - Unit start/stop
ler must ensure easy connection and define any modifications - Heating/cooling selection
necessary on site. The connections provided as standard for the - Set-point selection
field-supplied power entry cables to the general disconnect/ - Customer interlock - (example: auxiliary contact of the
isolator switch are designed for the number and type of wires, chilled water pump contactor)
listed in the table below. - General alarm reporting, circuit A and circuit B

The calculations are based on the maximum machine current


(see electrical data tables) and the standard installation
practises, in accordance with IEC 60364, table 52C.

- For 30RA units, installed outside, the following standard


installation practises have been maintained:
No.17: suspended aerial lines, and No. 61: buried
conduit with a derating coefficient of 20.

The calculation is based on PVC or XLPE insulated


cables with copper core.

A maximum ambient temperature of 46°C has been


taken into consideration.

The given wire length limits the voltage drop to


< 5% (length L in metres - see table below).

IMPORTANT: Before connection of the main power cables


(L1 - L2 - L3) on the terminal block, it is imperative to check
the correct order of the 3 phases before proceeding to the
connection on the main disconnect/isolator switch.

Unit S Min. (mm2) Cable type L (m) S Max. (mm2) Cable type L (m)
by phase by phase
30RA 040 1x 6 XLPE Cu 90 1x 16 PVC Cu 245
30RA 050 1x 6 XLPE Cu 80 1x 25 PVC Cu 300
30RA 060 1x 10 XLPE Cu 110 1x 25 PVC Cu 300
30RA 070 1x 10 XLPE Cu 100 1x 35 PVC Cu 310
30RA 080 1x 16 XLPE Cu 125 1x 50 PVC Cu 350
30RA 090 1x 16 XLPE Cu 115 1x 70 PVC Cu 380
30RA 100 1x 25 XLPE Cu 145 1x 70 PVC Cu 380
30RA 120 1x 25 XLPE Cu 135 1x 95 PVC Cu 410
30RA 140 1x 35 XLPE Cu 150 1x 120 PVC Cu 435
30RA 160 1x 50 XLPE Cu 180 1x 120 XLPE Cu 400
30RA 200 1x 70 XLPE Cu 180 1x 150 XLPE Cu 335
30RA 240 1x 70 XLPE Cu 180 1x 185 XLPE Cu 345
S Power supply cable section (see the diagram in chapter: “Electrical connection”)

17
9 - WATER CONNECTIONS Charging and removing heat exchange fluids should be done
with devices that must be included on the water circuit by the
For size and position of the unit water inlet and outlet connec- installer. Never use the unit heat exchangers to add heat
tions refer to the certified dimensional drawings supplied with exchange fluid.
the unit. The water pipes must not transmit any radial or axial
force to the heat exchangers nor any vibration. 9.1 - Operating precautions and recommendations

The water supply must be analysed and appropriate filtering, The water circuit should be designed to have the least number
treatment, control devices, shutoff and bleed valves and circuits of elbows and horizontal pipe runs at different levels. Below
built in, to prevent corrosion (example: damage to the protection the main points to be checked for the connection:
of the tube surface if the fluid is polluted), fouling and deter- • Comply with the water inlet and outlet connections shown
ioration of the pump fittings. on the unit.
• Install manual or automatic air purge valves at all high
Before any start-up verify that the heat exchange fluid is points in the circuit.
compatible with the materials and the water circuit coating. • Use an expansion device to maintain pressure in the system
and install a safety valve as well as an expansion tank.
In case additives or other fluids than those recommended by Units with a hydronic module include the safety valve and
Carrier are used, ensure that the fluids are not considered as a the expansion tank.
gas, and that they belong to class 2, as defined in directive • Install thermometers in both the entering and leaving
97/23/EC. water connections.
• Install drain connections at all low points to allow the
Carrier recommendations on heat exchange fluids: whole circuit to be drained.
1. No NH4+ ammonium ions in the water, they are very • Install stop valves, close to the entering and leaving water
detrimental for copper. This is one of the most important connections.
factors for the operating life of copper piping. A content of • Use flexible connections to reduce vibration transmission.
several tenths of mg/l will badly corrode the copper over • Insulate all pipework, after testing for leaks, both to
time. reduce thermal leaks and to prevent condensation.
2. Cl- Chloride ions are detrimental for copper with a risk of • If the external unit water pipes are in an area, where the
perforations by corrosion by puncture. If possible keep ambient temperature is likely to fall below 0°C, insulate
below 10 mg/l. the piping and add an electric heater. The internal unit
3. SO42- sulphate ions can cause perforating corrosion, if piping is protected down to -20°C.
their content is above 30 mg/l.
4. No fluoride ions (<0.1 mg/l). NOTE: For units not equipped with a hydronic module a
5. No Fe2+ and Fe3+ ions with non negligible levels of dissolved screen filter must be installed as close to the heat exchanger
oxygen must be present. Dissolved iron < 5 mg/l with as possible, in a position that is easily accessible for removal
dissolved oxygen < 5 mg/l. and cleaning. Units with hydronic module are equipped with
6. Dissolved silicon: silicon is an acid element of water and this type of filter.
can also lead to corrosion risks. Content < 1mg/l.
7. Water hardness: TH >2.8 K. Values between 10 and 25 can The mesh size of the filter must be 1.2 mm.
be recommended. This will facilitate scale deposit that can
limit corrosion of copper. TH values that are too high can The plate heat exchanger can foul up quickly at the initial
cause piping blockage over time. A total alkalimetric titre unit start-up, as it complements the filter function, and the
(TAC) below 100 is desirable. unit operation will be impaired (reduced water flow rate due
8. Dissolved oxygen: Any sudden change in water oxygena- to increased pressure drop).
tion conditions must be avoided. It is as detrimental to
deoxygenate the water by mixing it with inert gas as it is Before the system start-up verify that the water circuits are
to over-oxygenate it by mixing it with pure oxygen. The connected to the appropriate heat exchangers (e.g. no
disturbance of the oxygenation conditions encourages reversal between evaporator and condenser).
destabilisation of copper hydroxides and enlargement of
particles. Do not introduce any significant static or dynamic pressure
9. Specific resistance – electric conductivity: the higher the into the heat exchange circuit (with regard to the design
specific resistance, the slower the corrosion tendency. operating pressures).
Values above 3000 Ohm/cm are desirable. A neutral environ-
ment favours maximum specific resistance values. For The products that may be added for thermal insulation of the
electric conductivity values in the order of 200-600 µS/cm containers during the water piping connection procedure
can be recommended. must be chemically neutral in relation to the materials and
10. pH: Ideal case pH neutral at 20-25°C (7 < pH < 8). coatings to which they are applied. This is also the case for
the products originally supplied by Carrier.
ATTENTION: Charging, adding or draining fluid from the
water circuit must be done by qualified personnel, using air 9.2 - Hydronic connections
vents and materials suitable for the products. The water
circuit charging devices are field-supplied. The diagram on page 20 shows a typical hydronic installation.
When charging the water circuit use air vents to evacuate any
residual air pockets.

18
9.3 - Frost protection IMPORTANT:
Depending on the atmospheric conditions in your area you
The plate heat exchangers, the piping and the hydronic module must do the following when switching the unit off in winter:
pump can be damaged by frost, despite the built-in anti-freeze - Add ethylene glycol with an adequate concentration to pro-
protection of the units. tect the installation up to a temperature of 10 K below the
The frost protection of plate heat exchanger and all hydronic lowest temperature likely to occur at the installation site.
module components is guaranteed down to -20°C by auto- - If the unit is not used for an extended period, it is
matically energized heaters and pump cycling. recommended to drain it, and as a safety precaution
Never switch off the evaporator and hydronic circuit heaters or introduce ethylene glycol in the heat exchanger, using
the pump, otherwise frost protection cannot be guaranteed. the water entering purge valve connection.
For this reason the main unit disconnect switch (QS101) as At the start of the next season, refill the unit with water
well as the auxiliary protection switch (QF101) for the heaters and add an inhibitor.
must always be left closed (for location of QS and QF 101 see - For the installation of auxiliary equipment, the installer
wiring diagram). must comply with basic regulations, especially for
To ensure frost protection down to -20°C, water circulation in minimum and maximum flow rates, which must be
the water circuit must be maintained by periodically switching between the values listed in the operating limit table
on the pump. If a shut-off valve is installed, a bypass must be (application data).
included as shown below. - To prevent corrosion by differential aeration, the complete
drained heat transfer circuit must be charged with
Winter position nitrogen for a period of one month. If the heat transfer
fluid does not comply with the Carrier regulations, the
F nitrogen charge must be added immediately.

A O F B

Legend
A Unit
B Water network
F Closed
O Open

19
Typical hydronic circuit diagram

2
12 17
14 15 1
10
4
13 3

18 6 11

7
17 5
13 14 15 9 8

19
16
Legend

Components of the unit and hydronic module Installation components


1 Victaulic screen filter 12 Air vent
2 Expansion tank 13 Thermometer sleeve
3 Safety valve 14 Flexible connection
4 Available pressure pump 15 Check valve
5 Purge valve and pressure tap 16 System water drain plug (on connection pipe supplied in the unit)
6 Pressure gauge to measure the plate heat exchanger pressure drop (to be 17 Pressure gauge
isolated with valve No. 5 if not used) 18 Freeze-up protection bypass valve (when valves 15 are closed during winter)
7 System air vent 19 Charge valve
8 Flow switch
9 Flow control valve --- Hydronic module (unit with hydronic module)
10 Plate heat exchanger
11 Evaporator defrost heater Note: Units without hydronic module (option) are equipped with a flow switch
and an internal piping heater.

Hydronic module

20
10 - NOMINAL SYSTEM WATER FLOW CONTROL Entering water pressure reading

The water circulation pumps of the 30RA units have been sized
to allow the hydronic modules to cover all possible configura-
O
tions based on the specific installation conditions, i.e. for various
temperature differences between the entering and the leaving
water (∆T) at full load, which can vary between 3 and 10°C.
F F

This required difference between the entering and leaving


water temperature determines the nominal system flow rate. It
is above all absolutely necessary to know the nominal system
flow rate to allow its control via a manual valve provided in the
Leaving water pressure reading
water leaving piping of the module (item 9 in the typical
hydronic circuit diagram).

With the pressure loss generated by the control valve in the F


hydronic system, the valve is able to impose the system pressure/
flow curve on the pump pressure/flow curve, to obtain the
desired operating point (see example for 30RA 100). The pres- O F
sure drop reading in the plate heat exchanger is used to control
and adjust the nominal system flow rate. The pressure drop is
measured with the pressure gauge connected to the heat
exchanger water inlet and outlet.
Air vent
Use this specification for the unit selection to know the system
operating conditions and to deduce the nominal air flow as well
as the plate heat exchanger pressure drop at the specified con-
ditions. If this information is not available at the system start- O

up, contact the technical service department responsible for the


installation to get it.
F O
These characteristics can be obtained from the technical litera-
ture using the unit performance tables for a ∆T of 5 K at the
evaporator or with the Electronic Catalogue selection program
for all ∆T conditions other than 5 K in the range of 3 to 10 K. Legend
O Open
F Closed
10.1 - Water flow control procedure
Water inlet

As the total system pressure drop is not known exactly at the Water outlet

start-up, the water flow rate must be adjusted with the control Pressure gauge
valve provided to obtain the specific flow rate for this applica-
tion.
NOTE: Applies to units 040 to 160
Proceed as follows:
Open the valve fully (approximately 9 turns counter-clockwise). If the pressure drop has increased, this indicates that the screen
filter must be removed and cleaned, as the hydronic circuit
Start-up the pump using the forced start command (refer to the contains solid particles. In this case close the shutoff valves at
controls manual) and let the pump run for two consecutive the water inlet and outlet and remove the screen filter after
hours to clean the hydronic circuit of the system (presence of emptying the hydronic section of the unit.
solid contaminants).
Renew, if necessary, to ensure that the filter is not contami-
Read the plate heat exchanger pressure drop by taking the nated. Purge the air from the circuit (see ‘Air vent’ diagram).
difference of the readings of the pressure gauge connected to
the plate heat exchanger inlet and outlet, using valves (see
diagrams below), and comparing this value after two hours of
operation.

21
When the circuit is cleaned, read the pressures at the Pump curve and water flow control as a function of
pressure gauge (entering water pressure - leaving water the system pressure drops
pressure), expressed in bar and convert this value to kPa
(multiply by 100) to find out the plate heat exchanger Example: 30RA 100 at Eurovent conditions of 4.8 l/s
pressure drop.
200
Compare the value obtained with the theoretical selection value. 4

If the pressure drop measured is higher than the value specified 175
this means that the flow rate in the plate heat exchanger (and 3
thus in the system) is too high. The pump supplies an excessive 150
flow rate based on the global pressure drop of the application. 1

Pressure drop, kPa


In this case close the control valve one turn and read the new 125
pressure difference.
100

Proceed by successively closing the control valve until you


obtain the specific pressure drop that corresponds to the 75

nominal flow rate at the required unit operating point. 2


- If the system has an excessive pressure drop in relation to 50

the available static pressure provided by the pump, the


resulting water flow rate will de reduced and the difference 25

between entering and leaving water temperature of the


0
hydronic module will be increased.
2 4 6 8 10

To reduce the pressure drops of the hydronic system, it is Water flow rate, l/s

necessary: Legend
1 Pump curve, 30RA 100
- to reduce the individual pressure drops as much as possible 2 Plate heat exchanger pressure drop (to be measured with the pressure
(bends, level changes, accessories, etc.) gauge installed at the water inlet and outlet)
3 Installation pressure drop with control valve wide open
- to use a correctly sized piping diameter. 4 Installation pressure drop after valve control to obtain nominal flow rate
- to avoid hydronic system extensions, wherever possible.

22
10.2 - Pump pressure/flow rate curves

Single pumps

250 Legend
1 30RA 040-070
225 2 30RA 080-100
3 30RA 120-160
200 4 30RA 200-240
175
Pressure supplied, kPa

150
125
1 2 3 4
100
75
50
0 2 4 6 8 10 12 14 16 18 20 22 24 26
Water flow rate, l/s

Dual pumps

250 Legend
1 30RA 040-100
225 2 30RA 120-160
3 30RA 200-240
200
175
Pressure supplied, kPa

150
125
1 2 3
100
75
50
0 2 4 6 8 10 12 14 16 18 20 22 24 26
Water flow rate, l/s

10.3 - Available static system pressure

Single pumps Dual pumps

250 250
225 225
Available static pressure, kPa

200
Available static pressure, kPa

200
175 175
150 150
125 1
125 4
100 100 5
1 4 6 7 9 2
75 6 10
75
50 2 3 5 8 10 11 3 7 8 9 11 12
50
0 2 4 6 8 10 12 14 16 18 20 22
0 2 4 6 8 10 12 14 16 18 20 22
Water flow rate, l/s
Water flow rate, l/s

Legend Legend
1 30RA 040 1 30RA 040
2 30RA 050 2 30RA 050
3 30RA 060 3 30RA 060
4 30RA 070 4 30RA 070
5 30RA 080-090 5 30RA 080
6 30RA 100 6 30RA 090
7 30RA 120 7 30RA 100
8 30RA 140 8 30RA 120
9 30RA 160 9 30RA 140
10 30RA 200 10 30RA 160
11 30RA 240 11 30RA 200
12 30RA 240

23
11 - START-UP Depending on the installation and control type, each unit can
control its own water pump. If there is only one common pump
11.1 - Preliminary checks for the two units, the master unit can control this. In this case
shut-off valves must be installed on each unit. They will be
- Never be tempted to start the chiller without reading fully, activated at the opening and closing by the control of each unit
and understanding, the operating instructions and without (and the valves will be controlled using the dedicated water
having carried out the following pre-start checks: pump outputs).
- Check the chilled water circulation pumps, air handling
units and all other equipment connected to the evaporator. 30RA 040 to 240 (standard configuration: return water
- Refer to the manufacturer’s instructions. control)
- For units without hydronic module, the water pump over-
heat protection device must be connected in series with 1 2
the pump contactor power supply. If the pump is not
supplied with the unit (unit without hydronic module),
verify that the power input of the field-installed pump does
not exceed the rating of the standard pump contactor,
supplied in the control box (max. 3 kW for sizes 040 to
160 and max. 5.5 kW for sizes 200 and 240).
- Refer to the wiring diagram supplied with the unit.
- Ensure that there are no refrigerant leaks.
- Confirm that all pipe securing bands are tight.
- Confirm the the electrical connections are secure.

11.2 - Actual start-up

IMPORTANT
• Commissioning and start-up of the chiller must be 30RA 090 to 240 (with configuration: leaving water
supervised by a qualified refrigeration engineer. control)
• Start-up and operating tests must be carried out with a
thermal load applied and water circulating in the
evaporator.
• All set-point adjustments and control tests must be
carried out before the unit is started up.
• Please refer to the controls section of this manual.

The unit should be started up in Local ON mode.


Ensure that all safety devices are satisfied, especially the high
pressure switches.

11.3 - Operation of two units in master/slave mode

The control of a master/slave assembly is in the entering water


and does not require any additional sensors (standard configura-
tion). It can also be located in the leaving water. In this case
two additional sensors must be added on the common piping.
Legend

All parameters, required for the master/slave function must be 1 Master unit
2 Slave unit
configured using the Service Configuration menu. All remote Additional CCN board (one per unit, with connection via communication
controls of the master/slave assembly (start/stop, set point, load bus)
shedding etc.) are controlled by the unit configured as master
Control boxes of the master and slave units
and must only be applied to the master unit.
Water inlet

Water outlet
Water pumps for each unit (included as standard for units with hydronic
module)
Additional sensors for leaving water control, to be connected to channel
1 of the slave boards of each master and slave unit
CCN communication bus
Connection of two additional sensors

24
12 - MAINTENANCE In order to measure the liquid refrigerant pressure and tempera-
ture ahead of the expansion device, an access port must be
Any technician attending the machine for any purpose must be opened on the expansion device which causes a slight air bypass
fully qualified to work on refrigerant and electrical circuits. on the condenser. Wait until unit operation has stabilized before
carrying out pressure and temperature measurements.
All refrigerant charging, removal and draining operations
must be carried out by a qualified technician and with the WARNING: To ensure proper operation of 30RA units there
correct material for the unit. Any inappropriate handling can must be at least 12 K of subcooling as the liquid refrigerant
lead to uncontrolled fluid or pressure leaks. enters the expansion valve.

WARNING: Before doing any work on the machine ensure The 30RA units use refrigerant. For your information, we are
that the power is switched off. If a refrigerant circuit is opened, reproducing here some extracts from the official publication
it must be evacuated, recharged and tested for leaks. Before dealing with the design, installation, operation and mainte-
any operation on a refrigerant circuit, it is necessary to remove nance of air conditioning and refrigeration systems and the
the complete refrigerant charge from the unit with a refrigerant training of people involved in these activities, agreed by the
charge recovery group. air conditioning and refrigeration industry.

12.1 - General maintenance of the refrigerant circuit Apparent and actual subcooling

• Keep the unit itself and the space around it clean and free
of obstructions. Remove all rubbish such as packing
5 4
materials, as soon as the installation is completed.
• Regularly clean the exposed pipework to remove all dust 3 2 1
and dirt. This makes detection of water leaks easier, and
they can be repaired before more serious faults develop.
• Confirm that all screwed and bolted connections and joints Pressure

are secure. Secure connections prevent leaks and vibration L 6 V


from developing.
• Check that all insulation joints are securely closed and that
all insulation is firmly in place. Check all heat exchangers
L+V
and all pipework.

12.2 - Refrigerant charge


Enthalpy

12.2.1 - Verification of the charge Legend


1 Saturated condensing temperature at the dew point
2 Saturated liquid temperature at the bubble point
CAUTION: The 30RA units are supplied with a precise 3 Liquid refrigerant temperature
R407C refrigerant charge (see Physical Data table). 4 Saturation curve at the dew point
5 Saturation curbe at the bubble point
6 Isotherms
To verify the correct system charge prodeed as follows: 7 Apparent subcooling (1 - 3)
Ensure that no bubbles appear in the sight-glass, when operat- 8 Real subcooling (2 - 3)
L Liquid
ing the unit at full load for a while, at a saturated condensing L + V Liquid + vapour
temperature of between 55 and 57°C. If necessary cover a sec- V Vapour
tion of the coil surface to obtain this condensing temperature.
Under these conditions the apparent subcooling which is equal
to the saturated condensing temperature (1 - on the saturated
dew point curve) minus the liquid refrigerant temperature (3)
ahead of the expansion device must be between 12 and 14°C.
This corresponds to an actual subcooling temperature of between
5 and 7 K at the condenser outlet, depending on the unit type.
Actual subcooling is equal the saturated liquid temperature (2 -
on the saturated bubble point curve) minus the liquid refrigerant
temperature (3) ahead of the expansion device. Use the pressure
tap supplied on the liquid piping to charge refrigerant and to
find out the pressure of the liquid refrigerant. If the subcooling
value is not correct, i.e. lower than the specified values, a leak
detection test must be carried out on the unit, as it no longer
contains its original charge.

25
12.2.2 - Principles 12.2.4 - Undercharge
Refrigeration installations must be inspected and maintained If there is not enough refrigerant in the system, this is indicated
regularly and rigorously by specialists. Their activities must be by gas bubbles in the moisture sight glass.
overseen and checked by properly trained people. To minimise
discharge to the atmosphere, refrigerants and lubricating oil must If the undercharge is significant, large bubbles appear in the
be transferred using methods which reduce leaks and losses to moisture sight glass, and the suction pressure drops. The
a minimum and with materials that are suitable for the products. compressor suction superheat is also high. The machine must
• Leaks must be repaired immediately be recharged after the leak has been repaired.
• All units are equipped with two special connections on the
suction and liquid line, which permit the connection of Find the leak and completely drain the system with a refrigerant
quick-connect recovery valves without loss of refrigerant. recovery unit. Carry out the repair, leak test and then recharge
• If the residual pressure is too low to make the transfer the system.
alone, a purpose-built refrigerant recovery unit must be
used. Important: After the leak has been repaired, the circuit
• Compressor lubricating oil contains refrigerant. Any oil must be tested, without exceeding the maximum low-side
drained from a system during maintenance must therefore operating pressure shown on the unit name plate.
be handled and stored accordingly.
• Refrigerant under pressure must never be discharged to The refrigerant must always be recharged in the liquid phase
the atmosphere. into the liquid line.
• If the refrigerant circuit is opened, plug all openings if the The refrigerant cylinder must always contain at least 10% of its
operation takes up to one day, or charge the circuit with initial charge.
nitrogen for longer operations. For the refrigerant quantity per circuit, refer to the data on the
unit name plate.
12.2.3 - Recharging liquid refrigerant
12.2.5 - Characteristics of R407C
CAUTION: 30RA units are charged with liquid HFC-407C See the table below.
refrigerant. Saturated bubble point temperatures (bubble point curve)
Saturated dew point temperatures (dew point curve)
This non-azeotropic refrigerant blend consists of 23% R-32,
25% of R-125 and 52% R-134a, and is characterised by the 12.3 - Electrical maintenance
fact that at the time of the change in state the temperature of
the liquid/vapour mixture is not constant, as with azeotropic When working on the unit comply with all safety precautions
refrigerants. All checks must be pressure tests, and the appro- decribed in section “Maintenance safety considerations”.
priate pressure/temperature ratio table must be used to deter- - It is strongly recommended to change the fuses in the
mine the corresponding saturated temperatures (saturated units every 15000 operating hours or every 3 years.
bubble point curve or saturated dew point curve). - It is recommended to verify that all electrical connections
are tight:
Leak detection is especially important for units charged with a. after the unit has been received at the moment of
refrigerant R407C. Depending on whether the leak occurs in installation and before the first start-up,
the liquid or in the vapour phase, the proportion of the b. one month after the first start-up,when the electrical
different components in the remaining liquid is not the same. components have reached their nominal operating
temperatures,
NOTE: Regularly carry out leak checks and immediately c. then regularly once a year.
repair any leak found. If there is a leak in the plate heat
exchanger, this part must be replaced.

26
R407C characteristics

Bar Saturated bubble Saturated dew Bar Saturated bubble Saturated dew Bar Saturated bubble Saturated dew
(relative) point temp. °C point temp. °C (relative) point temp. °C point temp. °C (relative) point temp. °C point temp. °C
1 -28.55 -21.72 10.5 23.74 29.35 20 47.81 52.55
1.25 -25.66 -18.88 10.75 24.54 30.12 20.25 48.32 53.04
1.5 -23.01 -16.29 11 25.32 30.87 20.5 48.83 53.53
1.75 -20.57 -13.88 11.25 26.09 31.62 20.75 49.34 54.01
2 -18.28 -11.65 11.5 26.85 32.35 21 49.84 54.49
2.25 -16.14 -9.55 11.75 27.6 33.08 21.25 50.34 54.96
2.5 -14.12 -7.57 12 28.34 33.79 21.5 50.83 55.43
2.75 -12.21 -5.7 12.25 29.06 34.5 21.75 51.32 55.9
3 -10.4 -3.93 12.5 29.78 35.19 22 51.8 56.36
3.25 -8.67 -2.23 12.75 30.49 35.87 22.25 52.28 56.82
3.5 -7.01 -0.61 13 31.18 36.55 22.5 52.76 57.28
3.75 -5.43 0.93 13.25 31.87 37.21 22.75 53.24 57.73
4 -3.9 2.42 13.5 32.55 37.87 23 53.71 58.18
4.25 -2.44 3.85 13.75 33.22 38.51 23.25 54.17 58.62
4.5 -1.02 5.23 14 33.89 39.16 23.5 54.64 59.07
4.75 0.34 6.57 14.25 34.54 39.79 23.75 55.1 59.5
5 1.66 7.86 14.5 35.19 40.41 24 55.55 59.94
5.25 2.94 9.11 14.75 35.83 41.03 24.25 56.01 60.37
5.5 4.19 10.33 15 36.46 41.64 24.5 56.46 60.8
5.75 5.4 11.5 15.25 37.08 42.24 24.75 56.9 61.22
6 6.57 12.65 15.5 37.7 42.84 25 57.35 61.65
6.25 7.71 13.76 15.75 38.31 43.42 25.25 57.79 62.07
6.5 8.83 14.85 16 38.92 44.01 25.5 58.23 62.48
6.75 9.92 15.91 16.25 39.52 44.58 25.75 58.66 62.9
7 10.98 16.94 16.5 40.11 45.15 26 59.09 63.31
7.25 12.02 17.95 16.75 40.69 45.71 26.25 59.52 63.71
7.5 13.03 18.94 17 41.27 46.27 26.5 59.95 64.12
7.75 14.02 19.9 17.25 41.85 46.82 26.75 60.37 64.52
8 14.99 20.85 17.5 42.41 47.37 27 60.79 64.92
8.25 15.94 21.77 17.75 42.98 47.91 27.25 61.21 65.31
8.5 16.88 22.68 18 43.53 48.44 27.5 61.63 65.71
8.75 17.79 23.57 18.25 44.09 48.97 27.75 62.04 66.1
9 18.69 24.44 18.5 44.63 49.5 28 62.45 66.49
9.25 19.57 25.29 18.75 45.17 50.02 28.25 62.86 66.87
9.5 20.43 26.13 19 45.71 50.53 28.5 63.27 67.26
9.75 21.28 26.96 19.25 46.24 51.04 28.75 63.67 67.64
10 22.12 27.77 19.5 46.77 51.55 29 64.07 68.02
10.25 22.94 28.56 19.75 47.29 52.05 29.25 64.47 68.39

12.4 - Condenser coil The two cleaning products can be used for any of the following
coil finishes: Cu/Cu, Cu/Al, Cu/Al with Polual, Blygold and/or
We recommend, that finned coils are inspected regularly to Heresite protection.
check the degree of fouling. This depends on the environment
where the unit is installed, and will be worse in urban and It is not necessary to rinse the coil, as the products used are pH
industrial installations and near trees that shed their leaves. neutral. To ensure that the coil is perfectly clean, we recom-
mend rinsing with a low water flow rate. The pH value of the
For coil cleaning proceed as follows: water used should be between 7 and 8.
• Remove fibres and dust collected on the condenser face
with a soft brush (or vacuum cleaner). WARNING: Never use pressurized water without a large
• Clean the coil with the appropriate cleaning agents. diffusor. Concentrated and/or rotating water jets are strictly
forbidden.
We recommend TOTALINE products for coil cleaning:
Part No. P902 DT 05EE: traditional cleaning method Correct and frequent cleaning (approximately every three
Part No. P902 CL 05EE: cleaning and degreasing. months) will prevent 2/3 of the corrosion problems.

These products have a neutral pH value, do not contain phos- Never use a fluid with a temperature above 45°C to clean the
phates, are not harmful to the human body, and can be disposed air heat exchangers.
of through the public drainage system. Depending on the degree
of fouling both products can be used diluted or undiluted.

For normal maintenance routines we recommend using 1 kg of


the concentrated product, diluted to 10%, to treat a coil surface
of 2 m2. This process can either be carried out with a TOTALINE
applicator gun (part No. TE01 WA 4000EE) or using a high-
pressure spray gun in the low-pressure position. With pressurised
cleaning methods care should be taken not to damage the coil
fins. The spraying of the coil must be done:
- in the direction of the fins
- in the opposite direction of the air flow direction
- with a large diffuser (25-30°)
- at a distance of 300 mm.

27
13 - AQUASNAP MAINTENANCE PROGRAMME 13.2 - Description of the maintenance operations

All maintenance operations must be carried out by technicians The equipment is supplied with polyolester oil (POE). Only use
who have been trained on Carrier products, observing all Carrier oil approved by Carrier. On request Carrier can carry out an oil
quality and safety standards. analysis of your installation.

Maintenance instructions Service A


During the unit operating life the service checks and tests must Full-load operating test
be carried out in accordance with applicable national regulations. Verify the following values:
- compressor high-pressure side discharge pressure
If there are no similar criteria in local regulations, the information - compressor low-pressure side suction pressure
on checks during operation in annex C of standard EN 378-2 - charge visible in the sight glass
can be used. - temperature difference between the heat exchanger water
entering and leaving temperature.
External visual checks: annex A and B of standard EN 378-2
Verify the alarm status
Corrosion checks: annex D of standard EN 378-2. These
controls must be carried out: Service B
- After an intervention that is likely to affect the resistance Carrier out the operations listed under Service A.
or a change in use or change of high-pressure refrigerant, Refrigerant circuit
or after a shut down of more than two years. Components - Verify the air heat exchanger cleanliness status and clean
that do not comply, must be changed. Test pressures above it at least once a year, or more often if the equipment
the respective component design pressure must not be environment is especially demanding. To clean the equip-
applied (annex B and D). ment, follow the Carrier recommendations. Among other
- After repair or significant modifications or significant things, this ensures that the unit performances can be
system or component extension (annex B) guaranteed.
- After re-installation at another site (annexes A, B and D) - Full-load operating test. In addition to the operations
- After repair following a refrigerant leak (annex D). The described under Service A, check the following values:
frequency of refrigerant leak detection can vary from once - compressor discharge pressure
per year for systems with less than 1% leak rate per year - compressor oil level
to once a day for systems with a leak rate of 35% per year - actual liquid subcooling
or more. The frequency is in proportion with the leak rate. - overheating at the expansion device
- on heat pumps verify correct defrost of the air heat
NOTE: High leak rates are not acceptable. The necessary exchanger.
steps must be taken to eliminate any leak detected. - Verify the charge status by checking the colour indicator
of the sight glass. If the colour has turned to yellow, change
NOTE 2: Fixed refrigerant detectors are not leak detectors, as the charge and replace the filter drier after carrying out a
they cannot locate the leak. leak test of the circuit.

13.1 - Maintenance schedule Electrical checks


- Check the tightening of the electric connections, contactors,
Regular maintenance is indispensable to optimise the operating disconnect switch and transformer.
life and reliability of the equipment. Maintenance operations - Check the status of the contactors, fuses and capacitators,
must be carried out in accordance with the schedules below: as required.
- Carry out a quick test (refer to the manual for the Aquasnap
Service Frequency Pro-Dialog Plus control).
A Weekly
B Monthly Mechanical checks
C Annually - Verify that nothing impedes the rotation of the fan impeller
D Special cases of the air heat exchanger.

If the equipment does not operate normally during maintenance Water circuit checks
operations, please refer to the paragraph on diagnostics and - Check the leak-tightness of the circuit.
breakdowns of the ‘30RA/RH - 30RY/RYH “B” Pro-Dialog
Plus’ controls manual.

IMPORTANT: Before each equipment maintenance


operation please ensure that:
- the unit is in the OFF position
- it is impossible for the unit to restart automatically
during maintenance.

28
Service C
Carry out the operations listed under Service B.
Refrigerant circuit
- Check the leak-tightness of the circuit and ensure that
there is no piping damage.
- Carry out an oil contamination test. If acid, water or metallic
particles are present replace the oil in the circuit.
- Verify the tightening of the thermostatic mechanism of the
expansion device.
- Full-load operating test. In addition to the checks carried
out under Service B, validate the values of the heat
exchanger inlet and outlet tightening.
- Check the operation of the high-pressure and low-pressure
switches. Replace them if there is a fault.
- Check the fouling of the filter drier (by checking the
temperature difference in the copper piping). Replace it if
necessary.

Electrical checks
- Check the status of the electrical cables and their insulation.
- Carry out an operating test of the electric evaporator heaters,
compressor crankcase heater, piping and expansion device, as
required.
- Check the phase/earth insulation of the compressors, fans
and pumps.
- Check the compressor, fan and pump winding status.

Mechanical checks
- Check the tightening of the fan tower, fan, compressor and
control box fixing bolts.
- Check that no water has penetrated into the control box.
- All metallic parts of the unit (chassis, casing panels, control
boxes, heat exchangers etc.) are protected against corrosion
by a coating of powder or liquid paint. To prevent the risk
of blistering corrosion that can appear when moisture
penetrates under the protective coatings, it is necessary to
carry out periodic checks of the coating (paint) condition.

Water circuit checks


- Clean the water filter.
- Purge the circuit with air.
- Verify the correct operation of the water flow switch.
- Check the status of the thermal piping insulation.
- Check the water flow by checking the heat exchanger
pressure difference (using a pressure gauge).
- Check the concentration of the anti-freeze protection
solution (ethylene glycol or polyethylene glycol).
- Check the satus of the heat transfer fluid or the water quality.
- Check the steel pipe corrosion.

Service D
- Single pump and dual pump.
- Mechanical seal: replace this every 13000 operating
hours.
- Bearing: replace this every 20000 operating hours.

29
14 - start-up cHecklist for 30RA Liquid chillers (use for job file)

Preliminary information
Job name:.................................................................................................................................................................................................
Location:..................................................................................................................................................................................................
Installing contractor:................................................................................................................................................................................
Distributor:...............................................................................................................................................................................................
Start-up preformed by:.................................................................. Date: ...............................................................................................

Equipment
Model 30RA:................................................................................... S/N................................................................................................

Compressors
Circuit A Circuit B
1. Model #........................................................................................ 1. Model #...................................................................................
S/N............................................................................................... S/N................................................................................................

2. Model #........................................................................................ 2. Model #...................................................................................


S/N............................................................................................... S/N................................................................................................

3. Model #........................................................................................ 3. Model #...................................................................................


S/N............................................................................................... S/N................................................................................................

Air handling equipment


Manufacturer............................................................................................................................................................................................
Model #............................................................................................ S/N................................................................................................

Additional air handling units and accessories..........................................................................................................................................


.................................................................................................................................................................................................................

Preliminary equipment check


Is there any shipping damage?......................................................... If so, where?.................................................................................
.................................................................................................................................................................................................................
Will this damage prevent unit start-up?...................................................................................................................................................

Unit is level in its installation


Power supply agrees with the unit name plate
Electrical circuit wiring has been sized and installed properly
Unit ground wire has been connected
Electrical circuit protection has been sized and installed properly
All terminals are tight
All cables and thermistors have been inspected for crossed wires
All plug assemblies are tight

Check air handling systems


All air handlers are operating
All chilled water valves are open
All fluid piping is connected properly
All air has been vented from the system
Chilled water pump is operating with the correct rotation. CWP amperage: Rated:.......................... Actual............ ...

30
Unit start-up
Chilled water pump starter has been properly interlocked with the chiller
Oil level is correct
Unit has been leak checked (including fittings)
Locate, repair, and report any refrigerant leaks
.................................................................................................................................................................................................................
.................................................................................................................................................................................................................
.................................................................................................................................................................................................................

Check voltage imbalance: AB..................... AC.................. BC...................


Average voltage = ...................................... (see installation instructions)
Maximum deviation = . .............................. (see installation instructions)
Voltage imbalance = . ................................. (see installation instructions)....

Voltage imbalance is less than 2%

warning
Do not start chiller if voltage imbalance is greater than 2%. Contact local power company for assistance.

All incoming power voltage is within rated voltage range

Check evaporator water loop


Water loop volume = ................... (litres)
Calculated volume = ................... (litres)
2.50 litres/nominal kW capacity for air conditioning (30RA 050 to 240)
3.50 litres/nominal kW capacity for air conditioning (30RA 040)

Proper loop volume established


Proper loop corrosion inhibitor included.................litres of............................
Proper loop freeze protection included (if required)..........................litres of...............................
Water piping includes electric tape heater up to the evaporator
Return water piping is equipped with a screen filter with a mesh size of 1.2 mm

Check pressure drop across the evaporator


Entering evaporator = ................................ (kPa)
Leaving evaporator = ................................. (kPa)
Pressure drop (entering - leaving) = .......... (kPa)

WARNING
Plot the pressure drop on the evaporator flow/pressure drop curve to determine the flow rate in l/s at the nominal operating
conditions for the installation.
If necessary use the control valve to impose the flow rate on the nominal value.

Flow rate from the pressure drop curve, l/s = . ...............


Nominal flow rate, l/s = .........................
The flow rate in l/s is higher than the minimum unit flow rate
The flow rate in l/s corresponds to the specification of ...........................(l/s)

31
Carry out the QUICK TEST function (see 30RA/RH - 30RY/RYH “B” Pro-Dialog Plus Control manual):

Check and log on to the user menu configuration

Load sequence selection..........................................................................................................................................................


Capacity ramp loading selection..............................................................................................................................................
Start-up delay...........................................................................................................................................................................
Burner section..........................................................................................................................................................................
Pump control............................................................................................................................................................................
Set-point reset mode................................................................................................................................................................
Night-time capacity setback.....................................................................................................................................................

Re-enter the set-points (see Controls section)

To start up the chiller

WARNING
Be sure that all service valves are open, and that the pump is on before attempting to start this machine. Once all checks have
been made, start the unit in the “LOCAL ON” position.

Unit starts and operates properly

Temperatures and pressures

warning
Once the machine has been operating for a while and the temperatures and pressures have stabilized, record the following
Evaporator entering water.......................................................................................................................................................
Evaporator leaving water........................................................................................................................................................
Ambient temperature .............................................................................................................................................................
Circuit A suction pressure.......................................................................................................................................................
Circuit B suction pressure.......................................................................................................................................................
Circuit A discharge pressure...................................................................................................................................................
Circuit B discharge pressure...................................................................................................................................................
Circuit A suction temperature ................................................................................................................................................
Circuit B suction temperature.................................................................................................................................................
Circuit A discharge temperature.............................................................................................................................................
Circuit B discharge temperature.............................................................................................................................................
Circuit A liquid line temperature............................................................................................................................................
Circuit B liquid line temperature............................................................................................................................................

notes:
................................................................................................................................................................................................
................................................................................................................................................................................................
................................................................................................................................................................................................

Order No.: 13435-76, 07.2007 - Supersedes order No.: 13435-76, 09.2003. Manufactured by: Carrier SCS, Montluel, France
Manufacturer reserves the right to change any product specificatiuons without notice. Printed in the Netherlands

You might also like