Professional Documents
Culture Documents
冢 冣
K1
G(s) c − K P + (A.1)
s
The power-system stabilizer (PSS) and governor control are not considered.
462
STUDY SYSTEM 463
5 4 3 2 1
Infinite
Bus
Gen. T1 T2
FC –TCR
SVC
CFC
(a)
XT 1 XL1 XL 2 XT 2
S
Xd″
Vg Vinf
S′
(b)
Figure A.1 (a) The single-machine infinite-bus (SMIB) study system and (b) an equiv-
alent circuit diagram.
The design of the SVC voltage regulator is undertaken by two methods: the
method of system gain [A.1] and eigenvalue analysis [A.2], [A.3].
464 DESIGN OF AN SVC VOLTAGE REGULATOR
The equivalent circuit of the system is shown in Fig. A.1(b). The line-resistance
and line-charging capacitances are neglected. The base quantities are 400 kV
and 500 MVA in the line.
4002
X base c c 320 Q
500
冢 冣 冢 320 冣 c 0.0676 pu
4002 1
X T 1 c X T 2 c 0.15
11102
冢 1110 冣 c 0.1405 pu
500
X ′′d c 0.312
500
Xc c − j c − j 1.667 pu
300
XN XC
XT H c c j 0.248
XN + XC
Thus the system gain of K N c V 0 X T H c 1.05 . 0.248 c 0.26 pu. Because only a
single-circuit transmission line is considered, the K N corresponds to the weakest
network state. Hence K N c K N max .
The proportional gain of the controller is obtained as
EIGENVALUE ANALYSIS 465
1
KP c −
2(K SL + K N max )
1
c− c − 1.85
2(0.01 + 0.26)
KP 1.85
K1 c − c− c − 370
TY 0.005
MVAo
Bn [in pu] c Bo [in pu] .
MVAn
500 .
c Bo c 5Bo
100
These values of optimal gains have been obtained on very simplistic assump-
tions without considering the dynamics of the generator.
Now, we obtain the optimal gains by the method of eigenvalue analysis,
which considers a detailed model of the system.
The power system is linearized about the operating point, and state equations
are developed for the following two cases:
The root loci with varying integral gain K I and proportional gain K P , each
taken one at a time, are shown in Figs. A.2(a) and (b), respectively, for a simplified
generator model; the same loci for a detailed generator model are shown in Figs.
A.3(a) and (b), respectively. The root loci are obtained for a generator-operating
power tranfer of 500 MW. The gains K P and K I are expressed on a 100-MVA
base.
It is observed from the root loci with varying K I (with K P c 0) displayed
in Fig. A.2(a) that a negative value of K I or a large positive value of K I
(>4000) renders the system unstable. In both K I values, the SVC controller
mode becomes destabilized. When the generator dynamics are modeled as
shown in Fig. A.3(a), the lower end on the stable range of K I is imposed by
the generator-rotor mode that tends to become unstable if K I is decreased from
200. The upper limit of K I continues to be dictated by the SVC controller mode,
and its stability range is determined to be 180 < K I < 3500 for K P c 0.
From the variation of roots with K P (with K I c 1200) shown in Fig. A.2(b), it
is seen that the stability range of K P is limited by an SVC controller mode in the
negative direction (K P < − 12) and by the TCR mode in the positive direction
(K P > 6). When the generator dynamics are considered, the stability range is
governed by similar considerations. The stability range for K P is obtained as
− 14 < K P < 5 for K I c 1200.
PTs KI 500
1 −0.1
2 100 450
3 500
4 800
5 1000 400
6 1200
12 8 7 −5 −1
7 1500 11 10 9 350
8 2000
9 3000
Im(l)
10 4000 300
11 5000 11 12
10
12 6000 200
9
8 150
7
6 100
5
4
50
12 3 3 2 25
1
−200 −100 −90 −80 −70 −60 −50 −40 −30 −20 −10 0 25 50
Re(l)
(a)
KP 500
PTs
1 −20
2 −15 450
3 −10 1
4 −5 2
400
3
5 −2 4
6 −1 567
8 9 10 11
7 0 350
8 1 12
9 2
Im(l)
300
10 4
11 6
12 8 200
150
12 8 7 6 5 4 3
9 2 100
1
10 75
50
25
11 11 11 12
−200 −100 −90 −80 −70 −60 −50 −40 −30 −20 −10 0 25 50
Re(l)
(b)
Figure A.2 (a) The root loci of a simplified model with varying K I (K P c 0) and (b)
the root loci of a simplified model with varying K P (K I c 1200).
468 DESIGN OF AN SVC VOLTAGE REGULATOR
PTs KI 450
1 100
2 200
3 500 400
4 800 6 −1
5 1000 12 87
6 1200 11 10 9 350
7 1500
8 2000
9 3000 300
10 4000 12
11 5000 11
12 6000 10
Im(l)
9 200
8 150
7
6 100
5
4 50
3 25
2 12 −3 2 1
5
2.5
1 2 3 1 1
−300 −200 −100 −90 −80 −70 −60 −50 −40 −30 −20 −10−5 −0.15 −0.1−0.05 0 0.05 0.1 25 50
Re(l)
PTs Kp
1 −20 450
2 −15 1
3 −12 2
4 −10 3 400
5 −5 4
5
6 −2 6
8 10
7 −1 35012 13
7 9
8 0 11 14
9 1
10 2
11 4 300
12 6 225
13 8
Im(l)
14 10 200
14 150
13 5
8 7 6 4 3 2
9 100
10 1
11
50
25
1 −14
5
12 12 12 13 14 2.5
−300 −200 −100 −90 −80 −70 −60 −50 −40 −30 −20 −10−5 −0.15−0.1−0.05 0 0.05 0.1 25 50
Re(l)
Figure A.3 (a) The root loci of a detailed model with varying K I (K P c 0) and (b)
the root loci of a detailed model with varying K P (K I c 1200).
EIGENVALUE ANALYSIS 469
chosen as 1200, which results in an acceptably small rise time, the minimum
possible settling time, and a reasonable overshoot of 16%.
Table A.2 shows that increasing magnitudes of K P in both the positive and
the negative direction affect the rise time and settling time detrimentally. For
large negative values of K P , a high value of peak overshoot is observed, whereas
for large positive values of K P , the response is very oscillatory and poorly
damped even though the overshoot is small. Figures A.5(a) and (b) illustrate
the step responses for K P c − 3 and +3 when K I c 1200.
Considering the minimum settling time and acceptable peak overshoot, the
best value of proportional gain K P is selected as +1. It is interesting to note
that the response is not very different in the range 0 ≤ K P ≤ 1. The best value
of K P can also be chosen as zero that reduces the controller to a purely integral
type for this example case.
The step-response studies show that for the foregoing system, the integral
gain K I is essentially the one that controls the speed of response. It is further
seen that the best values of K P and K I obtained from the detailed eigenvalue
analysis do not correlate with those values obtained from the simplified method
of system gain presented in Section A.2.
The optimization of voltage-regulator parameters is based on step-response
studies using a simplified generator model. However, the long-term step
response with optimized parameters using a detailed generator model is illus-
trated in Fig. A.6. The long-term oscillations visible in the response correspond
to the rotor-mode oscillations.
470 DESIGN OF AN SVC VOLTAGE REGULATOR
0.01 0.01
0.0075 0.0075
0.005 0.005
0.0025 0.0025
0 0
0.04 0.08 0.12 0.16 0.20 0.04 0.08 0.12 0.16 0.20
Time (s) Time (s)
(a) (b)
0.0125
Incremental Magnitude of
Incremental Magnitude of
SVS Bus Voltage (pu)
0.01 0.01
0.0075 0.0075
0.005 0.005
0.0025 0.0025
0 0
0.04 0.08 0.12 0.16 0.20 0.04 0.08 0.12 0.16 0.20
Time (s) Time (s)
(c) (d)
Figure A.4 The step responses of a simplified model with varying K I : (a) K I c 700;
(b) K I c 900; (c) K I c 1200; and (d) K I c 1800.
EIGENVALUE ANALYSIS 471
0.0125
0.01
Incremental Magnitude of
SVS Bus Voltage (pu)
0.0075
0.005
0.0025
0.0125
0.01
Incremental Magnitude of
SVS Bus Voltage (pu)
0.0075
0.005
0.0025
0.01
Incremental Magnitude of
SVS Bus Voltage (pu)
0.0075
0.005
0.0025
a rotor mode of frequency 4.36 rad/ s. On the other hand, the maximum transmis-
sible power with the optimized SVC is 610 MW, with the limit again imposed by a
rotor mode—in this case, one of frequency 4.58 rad/ s. The SVC with pure voltage
control thus improves the power transfer in the line by 29%.
0
−0.2 5 10 15 20 25 30 35
−0.4 0
−0.6 −0.5 2 4 6 8 10 12 14 16 18
B ref (volts)
Bref (volts)
−0.8 −1
−1 −1.5
−1.2 −2
−1.4
Time (s) Time (s)
(a) (e)
0
0
−0.5 5 10 15 20 25 30 35 40 45 50
−0.5 0.1 0.2 0.3 0.4 0.5
B ref (volts)
B ref (volts)
−1 −1
−1.5 −1.5
−2 −2
−2.5
Time (s) Time (s)
(b) ( f)
0 0
−0.5
0.1 0.2 0.3 0.4 0.5
2 4 6 8 10 12 14 16 18
−0.5
B ref (volts)
B ref (volts)
−1 −1
−1.5 −1.5
−2 −2
−2.5 −2.5
Time (s) Time (s)
(c) (g)
0
−0.5 2 4 6 8 10 12 14 16 18
B ref (volts)
−1
−1.5
−2
−2.5
Time (s)
(d)
Figure A.7 The long-duration step response of the SVC as obtained on the simulator:
(a) susceptance-order Bref for K I c 94.4 without the application of step input; (b) K I c
198.7; (c) K I c 632; (d) K I c 1415; (e) K I c 2831; (f ) susceptance-order Bref for K I
c 4246 without the application of step input; and (g) susceptance-order Bref for K I c
6321 without the application of step input.
oscillate even without the application of a step input. Moreover, the oscillations
in Bref have a frequency of 0.74 Hz (4.65 rad/ s), which tends to increase over
time. This increase implies that K I c 94.4 falls in the unstable range of K I .
For K I c 198.7, the oscillations in Bref following the application of the step
input diminish in magnitude, although very slowly. However, the steady state
is reached in a relatively smaller time period (typically 8–12 s) when K I is set
at values 632, 1415, and 2831.
These low-frequency oscillations are also observed in the step response
obtained from the linearized-system model of Fig. A.6. They are caused by
474 DESIGN OF AN SVC VOLTAGE REGULATOR
the generator-rotor mode and take a long time to decay because the mechanical
damping is neglected. If the synchronous machine is modeled as a constant-volt-
age source behind a reactance, such long-term oscillations are not observed.
As K I is increased to 4246, the susceptance Bref starts showing sustained
oscillations of large magnitude, even without the application of a step input.
The frequency of such oscillations is observed as 29.5 Hz (185.4 rad/ s). For
the next higher gain-knob setting corresponding to K I c 6321, these oscillations
start growing over time. However, this growth is not visible from Fig. A.6,
for the plot is taken over a short time period. As measured from the plot, the
frequency of these oscillations is 32.3 Hz (202.9 rad/ s).
From a study of the foregoing step responses involving long-term oscilla-
tions, it is concluded that the stability boundary for K I lies between 94.4 and
198.7 on the lower side and near 4246 on the higher side. It may be noted that
because the system is nonlinear, even sustained oscillations for K I c 4246 can
cause instability in the corresponding linearized model. The lower-side insta-
bility is caused by rotor-mode oscillations, whereas the higher-side instability
is caused by a mode of frequency 185.4 rad/ s. Also, it is concluded that for
stable operation, the integral gain K I must lie between 632 and 2831.
The SVC responses are now investigated in a time period that is much shorter
than that considered in the example of the preceding paragraph. The rise time
and percent of peak overshoot are obtained for different values of K I ; they are
based on which optimal magnitudes of integral gain are determined.
Figures A.8(a)–(d) display the step responses in which K I c 1120, 1415,
2239, and 3330, respectively, for the same 5% negative step input. The cor-
responding response data obtained from these plots are listed in Table A.3. It
is pertinent to note that measurement errors of 10% in the rise time and of
5–10% in the peak overshoot are likely in the values given in Table A.3. It
is observed that for higher values of K I , the rise time decreases as the peak
overshoot increases. The optimal value of K I that gives a fast response and an
acceptable peak overshoot (<20%) is determined to be 1120.
0 0
50 100 150 200 250 300 350 50 100 150 200 250 300 350
−1
−1.2 −1
−1.2
B ref (volts)
B ref (volts)
−1.4
−1.6 −1.4
−1.8 −1.6
−1.8
0
50 100 150 200 250 300 350 0
50 100 150 200 250 300 350
−1
−1.2 −1
B ref (volts)
−1.4 −1.2
B ref (volts)
−1.6 −1.4
−1.8 −1.6
−2 −1.8
−2
Time (ms)
Time (ms)
(c)
(d)
Figure A.8 The short-duration step response of the SVC as obtained on the simulator:
(a) K I c 1120; (b) K I c 1415; (c) K I c 2239; and (d) K I c 3330.
confirming that the rotor mode is indeed the one that limits the power-carrying
capability of the transmission system both with and without the SVC.
1000
Generator Power (MW)
800
600
522
400
200
0
0 5 10 15 20 25 30 35 40
Time (s)
(a)
1000
Generator Power (MW)
800
649
600
500
400
200
0
0 5 10 15 20 25 30 35 40
Time (s)
(b)
Figure A.9 The power-transfer limits obtained on the simulator: (a) without the SVC
and (b) with the SVC.
the simulator are higher than those computed from eigenvalue analysis. The
differences in power with and without the optimized SVC are observed to be
6% and 9%, respectively. A close correlation is also witnessed in the frequencies
obtained from both methods for the rotor mode that is critical in limiting the
stable transfer of power across the transmission line both with and without the
SVC.
Thus the design of the SVC voltage regulator as performed through lin-
earized analysis is validated from detailed simulation studies. This validation
can also be performed through digital simulation using EMTP/ EMTDC pro-
grams.
REFERENCES