Electrical data
—
01 ReliaGear
Integrated housing ground resistance Busway applications with harmonics
feeder busway ReliaGear busway all-aluminum housing provides For busway applications where non-linear loads
— an extremely low impedance ground path with less are present, first determine the specific non-linear
02 Bus bar sized options resistance (more continuous current capacity) than load condition for the application. Once the non-
based on Tables 1 and 2
internal ground bus bars for both copper and linear load condition is established, ReliaGear
aluminum systems. ReliaGear busway integrated busway should be derated in accordance with
housing ground resistance values exceed NEC 250- Option A; see Table 1 and Figure 01. Where full
94 standards for minimum ground conductors. nameplate loading is required, Spectra series
busway should be sized in accordance with
Plug-in outlet grounding may be supplied with Option B; see Table 2 and Figure 02.
optional tin-plated copper tabs bolted to the
aluminum housing for superior continuity through By increasing the width of both the phase and
standard bus plug ground stabs. An internal ground neutral bars equally, the busway will operate within
bus bar (50 percent capacity, .125 inch thick) is also UL heat rise limits at full nameplate rating, while
available to provide a complete system. also carrying up to twice the rated current in the
neutral conductor.
—
Table 2