Professional Documents
Culture Documents
net/publication/228774505
Article
CITATIONS READS
4 4,956
4 authors, including:
Some of the authors of this publication are also working on these related projects:
Online Localisation of Partial Discharge Using Pulse Propagation Parameters in Medium Voltage Cable Network View project
All content following this page was uploaded by N.H. Malik on 22 May 2014.
ABSTRACT
Electrical supply systems are grounded to improve safety of equipment and personnel
and to enhance reliability of power supply. The nature of soil, specifically the soil
resistivity, strongly influences the performance of a grounding system. This paper
discusses the methods and tools used for measuring soil resistivity. Using such tools,
soil resistivity measurements were carried out in more than 40 locations covering major
areas of Kingdom of Saudi Arabia. The results of these measurements are analyzed and
reported in this paper along with implications of measured parameters on the design and
performance of grounding installations in transmission and distribution networks. Steps
that must be taken to achieve acceptable grounding installations in high resistivity soils
are listed also.
KEYWORDS
INTRODUCTION
The earth is a poor conductor and, therefore, when it carries high magnitude current, a
large potential gradient will result and the earthing system will exhibit an earth potential
rise (EPR) or ground potential rise (GPR) which is defined as the voltage between an
earthing system and the reference earth [1-4].
The magnitude of power frequency earth fault currents can range from a few kA up to
several tens of kA, and earth impedances of electrical installations may lie in the range
from less than 0.1 Ω to over 100 Ω [5]. Consequently, there is a potential risk of
electrocution to people in the vicinity of a power network during earth faults, and
damage to equipment may also occur unless measures are taken to limit the earth
potential rise and/or to control the potential differences in critical places. Lightning
transients can also generate currents of several tens of kA in the earthing system, and
this requires the power system to be protected against over-voltages. The discharge of
transient current into earth may also present an electrocution hazard.
Thus, earthing systems are designed to control potential differences within and around
the electrical installation. These potential differences are specifically referred to as the
step and the touch voltages. Furthermore, consideration is also given to the maximum
earth potential rise of the grounding system. The extent of the rise of potential on the
ground surface around a substation can be described in terms of a hot zone, and this is
used to identify whether third party in the vicinity of the installation is affected.
Transferred potential levels are another important risk factor which is associated with
presence of metallic objects coming to the earthing installation under consideration
from other earthing installations and entering with it in the same earth fault current loop.
Thus, as mentioned above, although the purpose of earth connections in different parts
of the power system differs, generally the following requirements must be fulfilled for a
proper grounding [5]:
a) Proper Earth Fault Current Protection: the earth connection must provide a path
of low impedance and adequate thermal capacity for satisfactory operation of the
protective relays.
d) In order to provide safe discharge path for energy of lightning and switching
surges to dissipate to earth, proper lightning and protection grounding must be
provided.
The investigators have measured the earth resistivity in different parts of the Kingdom
with a view to develop a comprehensive data base that could be useful for the Saudi
Electricity Company in the design of transmission and distribution systems grounding
installations. This paper discusses the latest methods and equipment used for such
measurements [6-7]. It also presents the results of earth resistivity measurements along
with analysis and implications of the measured resistivity values for the design of
transmission and distribution systems groundings.
Earth resistivity measurements are useful for, (i) Estimating the ground resistance of a
proposed substation or grounding installation, (ii) Estimating potential gradients
including step and touch voltages, (iii) Computing the inductive coupling between
neighboring power and communication circuits.
Earth resistivity varies not only with the type of soil but also with temperature,
moisture, salt content, and compactness. The literature indicates that the values of earth
resistivity vary from 0.01 to 1 Ω.m for sea water and up to 109 Ω.m for sandstone. The
resistivity of the earth increases slowly with decreasing temperatures from 25°C to 0°C.
Below 0°C the resistivity increases rapidly. In frozen soil, the resistivity may be
exceptionally high in winter [6].
Several methods have been discussed in literature for measuring earth resistivity. The
most accurate method of measuring the average resistivity of large volumes of
undisturbed earth is the four-point method. In this method, four small electrodes spaced
at intervals a are driven vertically into ground, all at depth b. A test current I is passed
between the two outer electrodes and the potential V between the two inner electrodes is
measured. Then V/I gives the resistance R in ohms. Earth resistivity is related to R and
two different alternatives of the four-point method are often used:
ρ = 2πaR
Here ρ gives approximately an average value for the resistivity of the surface layer of
soil having a thickness a. A set of readings taken with various probe spacings gives a
set of resistivities which, when plotted against spacing, indicates whether there are
distinct layers of different soil or rock and gives an idea of their respective resistivities
and depth.
Fig. (1): Four-point method of resistivity measurement ; (a) Equally spaced, (b)
Unequally spaced electrodes.
ρ = πc(c+d)R/d
The ERT instrument works on the principal of 4-electrode technique mentioned earlier
but using induced polarization method. To carryout measurements, a multi-electrode
cable sets (MECS) are laid on the ground and connected to electrodes which are placed
in a straight line at pre-determined spacings. The instrument selects four equally spaced
electrodes at a time and sends current signal pulses to the two outer electrodes and
receives back the voltage pulses from the inner two electrodes. Thus, when the
instrument is switched ON it will scan the first four electrodes (e.g. 1,2,3, and 4), then
the computer will move to the next set of electrodes (i.e. 2,3,4, and 5) and so on. If the
spacing of these electrodes is 1m, these iterations will generate lateral resistivity profile
encompassing a depth of 1m. After going up to the last connected electrode, the
computer will then shift to scan lateral profile of soil resistivity at a depth of 2m. In this
case, it will select the electrodes (1,3,5, and 7), (2,4,6, and 8), (3,5,7, and 9) and so forth
till the last available electrode in the cable set is reached. Similarly to scan the lateral
resistivity profile at a depth of 3m it will scan electrodes (1,4,7, and 10), (2,5,8, and 11),
etc., while for a depth of 4m, electrodes (1,5,9, and 13) and (2,6,10, and 14) will be
scanned. With MECS containing 16 electrodes, 5 layers of earth will be investigated
for soil resistivity. Then using these measured resistivity values and software inversion
tools, a 2D-plot of earth resistivity with lateral distance and depth can be obtained. Fig.
(2) exhibits a 5-layer resistivity profile of a site in Riyadh area, while Fig. (3) provides
its 2D-inverted plot. With such an imager, 3-D plots of ρ can also be obtained if the
measurements at different lines are carried out and proper software tools are available.
Besides the 2-D and 3-D resistivity tomography, the resistivity data can be used to
determine variation of average earth resistivity with depth. Different types of soils
display different behaviors in this respect. Measurements show that in areas near sea or
water channels (e.g. Dammam, Jeddah, Jizan, Hafoof, Khafji) the average resistivity
strongly decreases with depth. In other areas, resistivity can increase with depth, it can
decrease with depth or it can approximately stay the same. This mainly depends upon
the geology of the test site. Fig. (5) shows same examples of resistivity variations with
depth at few selected sites in the Kingdom of Saudi Arabia.
120
60
30
0
3 6 9 12 15
Depth (m)
180 525
160
450
Soil resitivity (Ohm - Meter)
Soil resitivity (Ohm - Meter)
140
375
120
100 300
80 225
60
150
40
75
20
0
0
3 6 9 12 15
3 6 9 12 15
Depth (m)
Depth (m)
675
125
600
Soil resitivity (Ohm - Meter)
Soil resitivity (Ohm - Meter)
525
100
450
375
75
300
50 225
150
25
75
0
0
3 6 9 12 15
3 6 9 12 15
Depth (m)
Depth (m)
Since earthing installations usually make use of vertical rods that are driven into earth
for few meters only, the resistivity of earth for a 6m depth was determined at all test
locations. It was found that some sites have average resistivity of as low as 2Ωm,
whereas other sites had average resistivity of > 106 Ω.m. Reference [6] recommends
typical guidelines for soil resistivity range classification. Using this guideline, the soil
resistivity is classified as ρ ≤ 100 Ω.m. = Low, 100 Ω.m. < ρ ≤ 300 Ω.m. = Medium,
300 Ω.m. < ρ ≤ 1000 Ω.m. = High and ρ > 1000 Ω.m. = Very High. Table (1) shows
some examples of measured ρ and resistivity classifications. In areas that have low
resistivity, rod earthing electrodes may be sufficient for achieving satisfactory earthing
installation. For areas having medium soil resistivity, it may become essential to use
grounding grids. However, in areas that have high or very high earth resistivity, special
measures such as use of low resistivity material surrounding the earthing electrodes will
be required in many cases. Such materials are being developed and investigated at the
H.V. laboratory of King Saud University so that these may be used by Saudi Electricity
Company in earthing applications.
Table (1): Measured values of minimum, maximum and average soil resistivity at 6m
depth.
ACKNOWLEDGEMENT
The authors would like to thankfully acknowledge Saudi Electricity Company for
sponsoring this work through SEC Research Project No. S0803-R. Thanks are also
extended to Dr. Y. Khan and Eng. Nisar R. Wani for their support during this work.
REFERENCES
[1] ANSI/IEEE Std. 80-1986, IEEE Guide for Safety in Substation Grounding, 1986.
[3] ANSI/IEEE Std. 141-1986, IEEE Recommended Practice for Electric Power
Distribution for Industrial Plants, 1986.
[5] A.T. Johns and D.F. Warne (Editors), "Advances in High Voltage Engineering",
Chapter 8 by H. Griffiths and N. Pilling, "Earthing", IEE Power and Energy Series
40, UK, 2005.
[6] ANSI/IEEE Std. 81-1983, IEEE Guide for Measuring Earth Resistivity, Ground
Impedance, and Earth Surface Potentials of a Ground System, 1983.