PH23070013

The Product Certificate


for Capacitor Voltage Transformer

Product Type: TYD-170

Serial no.:PH23070013

ABB JIANGSU JINGKE INSTRUMENT


TRANSFORMER CO.,LTD
PH23070013

Test Item and Result


1.Visual and Antiseptic Layer Inspection
Inspection basis: IEC61869-5:2011 Result: passed
2.Tightness of Capacitor Voltage Divider
placed in oven,heated to 60℃ for 8h without leakage
Inspection basis: IEC61869-5:2011 Result: passed
3.Capacitor Voltage Divider Inspection
Inspection basis: IEC61869-5:2011
3.1 The power-frequency withstand test of capacitor voltage divider:
The power-frequency voltage 325kV being applied between two terminals of capacitor voltage
divider for 1 min.
Result: passed
3.2 Measurement of capacitance and tanδ on a capacitor voltage
divider:
Room Temperature: 29 ℃ Humidity: 65 %
Capacitance test No. Name U(kV) Capacitance(μF) tan δ(%)
before voltage
withstand PH23070013-1 CN 10 0.010711 0.075

PH23070013-1 CN 10 0.010712 0.075

Capacitance test CN 80 0.010712 0.088

after voltage withstand PH23070013-1 C1N 80 0.012442 0.092

C2N 4 0.077630 0.075

Result: passed
3.3 Partial discharge measurement of capacitor voltage divider:
No. U(kV) Duration(s) Partial discharge(pC)
Partial
discharge 170 30 ≤8
PH23070013-1
Measurement 118 30 ≤4

Result: passed
3.4 Power frequency withstand test between the low-voltage and earth
terminals of the capacitor voltage divider:
An Power frequency voltage of 5kV being applied between the low-voltage and earth
terminals of capacitor voltage divider for 1 min.
Result: passed
4 Inspection Test of Electromagnetic Unit
Inspection basis: IEC61869-5:2011
4.1 Polarity inspection:
Test result is "―" polarity. Result: passed
4.2 Induction withstand voltage test of transformer:
150 Hz AC voltage47.4kV being applied to primary side of transformer for48 sec.
Result: passed
PH23070013

4.3 Induction withstand voltage test of compensation reactor:


150 Hz AC voltage 10kV being applied to two ends of reactor for 48 sec.
Result: passed
4.4 Measurement of Excitation
Percentage of rated secondary voltage (%) 100 120 150
No-load secondary current(A) 0.223 0.267 1.201
No-load loss(W) 10.4 / /
Result: passed
4.5 Power-frequency withstand test between low-voltage windings and
earth:
Power-frequency voltage 3kV being applied between low-voltage windings and earth
on transformer for 1min.
Result: passed
4.6 Insulation resistance test of electromagnetic unit:
Primary windings to secondary windings and earth>1000 MΩ
Between secondary windings and to earth>1000 MΩ
Result: passed
5 Ferro-resonance Test
Inspection basis: IEC61869-5:2011
Primary voltage Number of short –circuiting at zhe secondary terminals Conclusion
0.8Upr 3
1.0Upr 3
Passed
1.2Upr 3
1.5Upr 3
6 Accuracy Check
Inspection basis: IEC61869-5:2011 , the result is shown in attached table:
Percentage Secondary Phase Phase
Secondary winding Ratio error Burden Ratio error
of rated winding displaceme displaceme
Accuracy class f(%) (VA) f(%)
voltage(%) Burden(VA) nt δ(´) nt δ(´)

80 -0.10 -1.7 0.08 0.7


1a 1n 1a 1n 30 1a 1n
100 -0.10 -1.8 0.08 0.6
0.2 2a 2n 30 7.5
120 -0.10 -1.9 0.08 0.5
2 -0.04 3.1 0.14 4.1

2a 2n 5 1a 1n 30 -0.04 3.1 2a 2n 0.14 4.1


3P 100 2a 2n 30 -0.10 -1.5 7.5 0.08 0.7
150 -0.10 -1.6 0.07 0.6
conclusion:The product comply with IEC61869-5:2011 after inspection, permitted to
leave the factory.
PH23070013

7 Measurement Secondary DC resistance


Room Temperature: 29 ℃

1a1n 2a2n 3a3n dadn


DC resistance Ω
0.04721 0.05026 / /

8 Insulating Oil Performance Test


8.1Puncture Voltage 53 kV,
8.2Dielectric Loss Ratio tanδ: 0.0011 (90℃)
8.3Water Content 9.2 mg/L
8.4 Gas Chromatography
单位 Unit:µL/L
H2 CO CO2 CH4 C2H6 C2H4 C2H2 C1+C2

0 0 219 0.40 0 0 0 0.40


PH23070014

The Product Certificate


for Capacitor Voltage Transformer

Product Type: TYD-170

Serial no.:PH23070014

ABB JIANGSU JINGKE INSTRUMENT


TRANSFORMER CO.,LTD
PH23070014

Test Item and Result


1.Visual and Antiseptic Layer Inspection
Inspection basis: IEC61869-5:2011 Result: passed
2.Tightness of Capacitor Voltage Divider
placed in oven,heated to 60℃ for 8h without leakage
Inspection basis: IEC61869-5:2011 Result: passed
3.Capacitor Voltage Divider Inspection
Inspection basis: IEC61869-5:2011
3.1 The power-frequency withstand test of capacitor voltage divider:
The power-frequency voltage 325kV being applied between two terminals of capacitor voltage
divider for 1 min.
Result: passed
3.2 Measurement of capacitance and tanδ on a capacitor voltage
divider:
Room Temperature: 29 ℃ Humidity: 65 %
Capacitance test No. Name U(kV) Capacitance(μF) tan δ(%)
before voltage
withstand PH23070014-1 CN 10 0.010719 0.076

PH23070014-1 CN 10 0.010720 0.076

Capacitance test CN 80 0.010720 0.088

after voltage withstand PH23070014-1 C1N 80 0.012450 0.093

C2N 4 0.077760 0.075

Result: passed
3.3 Partial discharge measurement of capacitor voltage divider:
No. U(kV) Duration(s) Partial discharge(pC)
Partial
discharge 170 30 ≤8
PH23070014-1
Measurement 118 30 ≤4

Result: passed
3.4 Power frequency withstand test between the low-voltage and earth
terminals of the capacitor voltage divider:
An Power frequency voltage of 5kV being applied between the low-voltage and earth
terminals of capacitor voltage divider for 1 min.
Result: passed
4 Inspection Test of Electromagnetic Unit
Inspection basis: IEC61869-5:2011
4.1 Polarity inspection:
Test result is "―" polarity. Result: passed
4.2 Induction withstand voltage test of transformer:
150 Hz AC voltage47.4kV being applied to primary side of transformer for48 sec.
Result: passed
PH23070014

4.3 Induction withstand voltage test of compensation reactor:


150 Hz AC voltage 10kV being applied to two ends of reactor for 48 sec.
Result: passed
4.4 Measurement of Excitation
Percentage of rated secondary voltage (%) 100 120 150
No-load secondary current(A) 0.217 0.266 0.998
No-load loss(W) 11.0 / /
Result: passed
4.5 Power-frequency withstand test between low-voltage windings and
earth:
Power-frequency voltage 3kV being applied between low-voltage windings and earth
on transformer for 1min.
Result: passed
4.6 Insulation resistance test of electromagnetic unit:
Primary windings to secondary windings and earth>1000 MΩ
Between secondary windings and to earth>1000 MΩ
Result: passed
5 Ferro-resonance Test
Inspection basis: IEC61869-5:2011
Primary voltage Number of short –circuiting at zhe secondary terminals Conclusion
0.8Upr 3
1.0Upr 3
Passed
1.2Upr 3
1.5Upr 3
6 Accuracy Check
Inspection basis: IEC61869-5:2011 , the result is shown in attached table:
Percentage Secondary Phase Phase
Secondary winding Ratio error Burden Ratio error
of rated winding displaceme displaceme
Accuracy class f(%) (VA) f(%)
voltage(%) Burden(VA) nt δ(´) nt δ(´)

80 -0.03 2.8 0.09 2.1


1a 1n 1a 1n 30 1a 1n
100 -0.03 2.7 0.08 2.0
0.2 2a 2n 30 7.5
120 -0.04 2.6 0.08 1.9
2 0.06 8.7 0.16 5.7

2a 2n 5 1a 1n 30 0.06 8.7 2a 2n 0.16 5.7


3P 100 2a 2n 30 -0.03 3.0 7.5 0.08 2.0
150 -0.04 2.8 0.08 2.0
conclusion:The product comply with IEC61869-5:2011 after inspection, permitted to
leave the factory.
PH23070014

7 Measurement Secondary DC resistance


Room Temperature: 29 ℃

1a1n 2a2n 3a3n dadn


DC resistance Ω
0.04700 0.04946 / /

8 Insulating Oil Performance Test


8.1Puncture Voltage 52 kV,
8.2Dielectric Loss Ratio tanδ: 0.0014 (90℃)
8.3Water Content 9.4 mg/L
8.4 Gas Chromatography
单位 Unit:µL/L
H2 CO CO2 CH4 C2H6 C2H4 C2H2 C1+C2

0 0 251 0.41 0 0 0 0.41


PH23070015

The Product Certificate


for Capacitor Voltage Transformer

Product Type: TYD-170

Serial no.:PH23070015

ABB JIANGSU JINGKE INSTRUMENT


TRANSFORMER CO.,LTD
PH23070015

Test Item and Result


1.Visual and Antiseptic Layer Inspection
Inspection basis: IEC61869-5:2011 Result: passed
2.Tightness of Capacitor Voltage Divider
placed in oven,heated to 60℃ for 8h without leakage
Inspection basis: IEC61869-5:2011 Result: passed
3.Capacitor Voltage Divider Inspection
Inspection basis: IEC61869-5:2011
3.1 The power-frequency withstand test of capacitor voltage divider:
The power-frequency voltage 325kV being applied between two terminals of capacitor voltage
divider for 1 min.
Result: passed
3.2 Measurement of capacitance and tanδ on a capacitor voltage
divider:
Room Temperature: 29 ℃ Humidity: 65 %
Capacitance test No. Name U(kV) Capacitance(μF) tan δ(%)
before voltage
withstand PH23070015-1 CN 10 0.010743 0.072

PH23070015-1 CN 10 0.010743 0.074

Capacitance test CN 80 0.010743 0.087

after voltage withstand PH23070015-1 C1N 80 0.012480 0.093

C2N 4 0.077810 0.075

Result: passed
3.3 Partial discharge measurement of capacitor voltage divider:
No. U(kV) Duration(s) Partial discharge(pC)
Partial
discharge 170 30 ≤8
PH23070015-1
Measurement 118 30 ≤4

Result: passed
3.4 Power frequency withstand test between the low-voltage and earth
terminals of the capacitor voltage divider:
An Power frequency voltage of 5kV being applied between the low-voltage and earth
terminals of capacitor voltage divider for 1 min.
Result: passed
4 Inspection Test of Electromagnetic Unit
Inspection basis: IEC61869-5:2011
4.1 Polarity inspection:
Test result is "―" polarity. Result: passed
4.2 Induction withstand voltage test of transformer:
150 Hz AC voltage47.4kV being applied to primary side of transformer for48 sec.
Result: passed
PH23070015

4.3 Induction withstand voltage test of compensation reactor:


150 Hz AC voltage 10kV being applied to two ends of reactor for 48 sec.
Result: passed
4.4 Measurement of Excitation
Percentage of rated secondary voltage (%) 100 120 150
No-load secondary current(A) 0.219 0.258 0.942
No-load loss(W) 11.0 / /
Result: passed
4.5 Power-frequency withstand test between low-voltage windings and
earth:
Power-frequency voltage 3kV being applied between low-voltage windings and earth
on transformer for 1min.
Result: passed
4.6 Insulation resistance test of electromagnetic unit:
Primary windings to secondary windings and earth>1000 MΩ
Between secondary windings and to earth>1000 MΩ
Result: passed
5 Ferro-resonance Test
Inspection basis: IEC61869-5:2011
Primary voltage Number of short –circuiting at zhe secondary terminals Conclusion
0.8Upr 3
1.0Upr 3
Passed
1.2Upr 3
1.5Upr 3
6 Accuracy Check
Inspection basis: IEC61869-5:2011 , the result is shown in attached table:
Percentage Secondary Phase Phase
Secondary winding Ratio error Burden Ratio error
of rated winding displaceme displaceme
Accuracy class f(%) (VA) f(%)
voltage(%) Burden(VA) nt δ(´) nt δ(´)

80 -0.10 -1.6 0.12 1.2


1a 1n 1a 1n 30 1a 1n
100 -0.09 -1.5 0.11 0.8
0.2 2a 2n 30 7.5
120 -0.09 -1.3 0.11 0.7
2 -0.05 2.5 0.18 5.1

2a 2n 5 1a 1n 30 -0.05 2.5 2a 2n 0.18 5.1


3P 100 2a 2n 30 -0.10 -1.3 7.5 0.11 1.1
150 -0.10 -1.4 0.11 0.9
conclusion:The product comply with IEC61869-5:2011 after inspection, permitted to
leave the factory.
PH23070015

7 Measurement Secondary DC resistance


Room Temperature: 29 ℃

1a1n 2a2n 3a3n dadn


DC resistance Ω
0.04755 0.04936 / /

8 Insulating Oil Performance Test


8.1Puncture Voltage 53 kV,
8.2Dielectric Loss Ratio tanδ: 0.0012 (90℃)
8.3Water Content 9.5 mg/L
8.4 Gas Chromatography
单位 Unit:µL/L
H2 CO CO2 CH4 C2H6 C2H4 C2H2 C1+C2

0 0 256 0.38 0 0 0 0.38


PH23070016

The Product Certificate


for Capacitor Voltage Transformer

Product Type: TYD-170

Serial no.:PH23070016

ABB JIANGSU JINGKE INSTRUMENT


TRANSFORMER CO.,LTD
PH23070016

Test Item and Result


1.Visual and Antiseptic Layer Inspection
Inspection basis: IEC61869-5:2011 Result: passed
2.Tightness of Capacitor Voltage Divider
placed in oven,heated to 60℃ for 8h without leakage
Inspection basis: IEC61869-5:2011 Result: passed
3.Capacitor Voltage Divider Inspection
Inspection basis: IEC61869-5:2011
3.1 The power-frequency withstand test of capacitor voltage divider:
The power-frequency voltage 325kV being applied between two terminals of capacitor voltage
divider for 1 min.
Result: passed
3.2 Measurement of capacitance and tanδ on a capacitor voltage
divider:
Room Temperature: 29 ℃ Humidity: 65 %
Capacitance test No. Name U(kV) Capacitance(μF) tan δ(%)
before voltage
withstand PH23070016-1 CN 10 0.010698 0.072

PH23070016-1 CN 10 0.010698 0.072

Capacitance test CN 80 0.010698 0.085

after voltage withstand PH23070016-1 C1N 80 0.012419 0.094

C2N 4 0.077850 0.077

Result: passed
3.3 Partial discharge measurement of capacitor voltage divider:
No. U(kV) Duration(s) Partial discharge(pC)
Partial
discharge 170 30 ≤8
PH23070016-1
Measurement 118 30 ≤4

Result: passed
3.4 Power frequency withstand test between the low-voltage and earth
terminals of the capacitor voltage divider:
An Power frequency voltage of 5kV being applied between the low-voltage and earth
terminals of capacitor voltage divider for 1 min.
Result: passed
4 Inspection Test of Electromagnetic Unit
Inspection basis: IEC61869-5:2011
4.1 Polarity inspection:
Test result is "―" polarity. Result: passed
4.2 Induction withstand voltage test of transformer:
150 Hz AC voltage47.4kV being applied to primary side of transformer for48 sec.
Result: passed
PH23070016

4.3 Induction withstand voltage test of compensation reactor:


150 Hz AC voltage 10kV being applied to two ends of reactor for 48 sec.
Result: passed
4.4 Measurement of Excitation
Percentage of rated secondary voltage (%) 100 120 150
No-load secondary current(A) 0.235 0.290 1.180
No-load loss(W) 11.0 / /
Result: passed
4.5 Power-frequency withstand test between low-voltage windings and
earth:
Power-frequency voltage 3kV being applied between low-voltage windings and earth
on transformer for 1min.
Result: passed
4.6 Insulation resistance test of electromagnetic unit:
Primary windings to secondary windings and earth>1000 MΩ
Between secondary windings and to earth>1000 MΩ
Result: passed
5 Ferro-resonance Test
Inspection basis: IEC61869-5:2011
Primary voltage Number of short –circuiting at zhe secondary terminals Conclusion
0.8Upr 3
1.0Upr 3
Passed
1.2Upr 3
1.5Upr 3
6 Accuracy Check
Inspection basis: IEC61869-5:2011 , the result is shown in attached table:
Percentage Secondary Phase Phase
Secondary winding Ratio error Burden Ratio error
of rated winding displaceme displaceme
Accuracy class f(%) (VA) f(%)
voltage(%) Burden(VA) nt δ(´) nt δ(´)

80 -0.05 0.3 0.12 1.4


1a 1n 1a 1n 30 1a 1n
100 -0.06 0.2 0.12 1.3
0.2 2a 2n 30 7.5
120 -0.06 0.1 0.12 1.3
2 -0.01 4.3 0.15 4.0

2a 2n 5 1a 1n 30 -0.01 4.3 2a 2n 0.15 4.0


3P 100 2a 2n 30 -0.06 0.5 7.5 0.12 1.4
150 -0.07 0.4 0.10 1.5
conclusion:The product comply with IEC61869-5:2011 after inspection, permitted to
leave the factory.
PH23070016

7 Measurement Secondary DC resistance


Room Temperature: 29 ℃

1a1n 2a2n 3a3n dadn


DC resistance Ω
0.04727 0.04929 / /

8 Insulating Oil Performance Test


8.1Puncture Voltage 52 kV,
8.2Dielectric Loss Ratio tanδ: 0.0010 (90℃)
8.3Water Content 9.4 mg/L
8.4 Gas Chromatography
单位 Unit:µL/L
H2 CO CO2 CH4 C2H6 C2H4 C2H2 C1+C2

0 0 232 0.39 0 0 0 0.39


PH23070017

The Product Certificate


for Capacitor Voltage Transformer

Product Type: TYD-170

Serial no.:PH23070017

ABB JIANGSU JINGKE INSTRUMENT


TRANSFORMER CO.,LTD
PH23070017

Test Item and Result


1.Visual and Antiseptic Layer Inspection
Inspection basis: IEC61869-5:2011 Result: passed
2.Tightness of Capacitor Voltage Divider
placed in oven,heated to 60℃ for 8h without leakage
Inspection basis: IEC61869-5:2011 Result: passed
3.Capacitor Voltage Divider Inspection
Inspection basis: IEC61869-5:2011
3.1 The power-frequency withstand test of capacitor voltage divider:
The power-frequency voltage 325kV being applied between two terminals of capacitor voltage
divider for 1 min.
Result: passed
3.2 Measurement of capacitance and tanδ on a capacitor voltage
divider:
Room Temperature: 29 ℃ Humidity: 65 %
Capacitance test No. Name U(kV) Capacitance(μF) tan δ(%)
before voltage
withstand PH23070017-1 CN 10 0.010678 0.078

PH23070017-1 CN 10 0.010678 0.078

Capacitance test CN 80 0.010679 0.088

after voltage withstand PH23070017-1 C1N 80 0.012392 0.092

C2N 4 0.077820 0.075

Result: passed
3.3 Partial discharge measurement of capacitor voltage divider:
No. U(kV) Duration(s) Partial discharge(pC)
Partial
discharge 170 30 ≤8
PH23070017-1
Measurement 118 30 ≤4

Result: passed
3.4 Power frequency withstand test between the low-voltage and earth
terminals of the capacitor voltage divider:
An Power frequency voltage of 5kV being applied between the low-voltage and earth
terminals of capacitor voltage divider for 1 min.
Result: passed
4 Inspection Test of Electromagnetic Unit
Inspection basis: IEC61869-5:2011
4.1 Polarity inspection:
Test result is "―" polarity. Result: passed
4.2 Induction withstand voltage test of transformer:
150 Hz AC voltage47.4kV being applied to primary side of transformer for48 sec.
Result: passed
PH23070017

4.3 Induction withstand voltage test of compensation reactor:


150 Hz AC voltage 10kV being applied to two ends of reactor for 48 sec.
Result: passed
4.4 Measurement of Excitation
Percentage of rated secondary voltage (%) 100 120 150
No-load secondary current(A) 0.224 0.265 0.975
No-load loss(W) 11.0 / /
Result: passed
4.5 Power-frequency withstand test between low-voltage windings and
earth:
Power-frequency voltage 3kV being applied between low-voltage windings and earth
on transformer for 1min.
Result: passed
4.6 Insulation resistance test of electromagnetic unit:
Primary windings to secondary windings and earth>1000 MΩ
Between secondary windings and to earth>1000 MΩ
Result: passed
5 Ferro-resonance Test
Inspection basis: IEC61869-5:2011
Primary voltage Number of short –circuiting at zhe secondary terminals Conclusion
0.8Upr 3
1.0Upr 3
Passed
1.2Upr 3
1.5Upr 3
6 Accuracy Check
Inspection basis: IEC61869-5:2011 , the result is shown in attached table:
Percentage Secondary Phase Phase
Secondary winding Ratio error Burden Ratio error
of rated winding displaceme displaceme
Accuracy class f(%) (VA) f(%)
voltage(%) Burden(VA) nt δ(´) nt δ(´)

80 -0.06 2.6 0.08 1.8


1a 1n 1a 1n 30 1a 1n
100 -0.07 2.4 0.08 1.8
0.2 2a 2n 30 7.5
120 -0.07 2.3 0.08 1.9
2 -0.01 6.3 0.18 6.4

2a 2n 5 1a 1n 30 -0.01 6.3 2a 2n 0.18 6.4


3P 100 2a 2n 30 -0.07 2.6 7.5 0.07 1.9
150 -0.07 2.6 0.07 1.9
conclusion:The product comply with IEC61869-5:2011 after inspection, permitted to
leave the factory.
PH23070017

7 Measurement Secondary DC resistance


Room Temperature: 29 ℃

1a1n 2a2n 3a3n dadn


DC resistance Ω
0.04716 0.04943 / /

8 Insulating Oil Performance Test


8.1Puncture Voltage 54 kV,
8.2Dielectric Loss Ratio tanδ: 0.0010 (90℃)
8.3Water Content 9.5 mg/L
8.4 Gas Chromatography
单位 Unit:µL/L
H2 CO CO2 CH4 C2H6 C2H4 C2H2 C1+C2

0 0 190 0.43 0 0 0 0.43


PH23070018

The Product Certificate


for Capacitor Voltage Transformer

Product Type: TYD-170

Serial no.:PH23070018

ABB JIANGSU JINGKE INSTRUMENT


TRANSFORMER CO.,LTD
PH23070018

Test Item and Result


1.Visual and Antiseptic Layer Inspection
Inspection basis: IEC61869-5:2011 Result: passed
2.Tightness of Capacitor Voltage Divider
placed in oven,heated to 60℃ for 8h without leakage
Inspection basis: IEC61869-5:2011 Result: passed
3.Capacitor Voltage Divider Inspection
Inspection basis: IEC61869-5:2011
3.1 The power-frequency withstand test of capacitor voltage divider:
The power-frequency voltage 325kV being applied between two terminals of capacitor voltage
divider for 1 min.
Result: passed
3.2 Measurement of capacitance and tanδ on a capacitor voltage
divider:
Room Temperature: 29 ℃ Humidity: 65 %
Capacitance test No. Name U(kV) Capacitance(μF) tan δ(%)
before voltage
withstand PH23070018-1 CN 10 0.010710 0.074

PH23070018-1 CN 10 0.010710 0.074

Capacitance test CN 80 0.010711 0.085

after voltage withstand PH23070018-1 C1N 80 0.012435 0.091

C2N 4 0.077880 0.074

Result: passed
3.3 Partial discharge measurement of capacitor voltage divider:
No. U(kV) Duration(s) Partial discharge(pC)
Partial
discharge 170 30 ≤8
PH23070018-1
Measurement 118 30 ≤4

Result: passed
3.4 Power frequency withstand test between the low-voltage and earth
terminals of the capacitor voltage divider:
An Power frequency voltage of 5kV being applied between the low-voltage and earth
terminals of capacitor voltage divider for 1 min.
Result: passed
4 Inspection Test of Electromagnetic Unit
Inspection basis: IEC61869-5:2011
4.1 Polarity inspection:
Test result is "―" polarity. Result: passed
4.2 Induction withstand voltage test of transformer:
150 Hz AC voltage47.4kV being applied to primary side of transformer for48 sec.
Result: passed
PH23070018

4.3 Induction withstand voltage test of compensation reactor:


150 Hz AC voltage 10kV being applied to two ends of reactor for 48 sec.
Result: passed
4.4 Measurement of Excitation
Percentage of rated secondary voltage (%) 100 120 150
No-load secondary current(A) 0.232 0.274 0.943
No-load loss(W) 10.8 / /
Result: passed
4.5 Power-frequency withstand test between low-voltage windings and
earth:
Power-frequency voltage 3kV being applied between low-voltage windings and earth
on transformer for 1min.
Result: passed
4.6 Insulation resistance test of electromagnetic unit:
Primary windings to secondary windings and earth>1000 MΩ
Between secondary windings and to earth>1000 MΩ
Result: passed
5 Ferro-resonance Test
Inspection basis: IEC61869-5:2011
Primary voltage Number of short –circuiting at zhe secondary terminals Conclusion
0.8Upr 3
1.0Upr 3
Passed
1.2Upr 3
1.5Upr 3
6 Accuracy Check
Inspection basis: IEC61869-5:2011 , the result is shown in attached table:
Percentage Secondary Phase Phase
Secondary winding Ratio error Burden Ratio error
of rated winding displaceme displaceme
Accuracy class f(%) (VA) f(%)
voltage(%) Burden(VA) nt δ(´) nt δ(´)

80 -0.05 2.5 0.07 1.9


1a 1n 1a 1n 30 1a 1n
100 -0.05 2.4 0.06 1.8
0.2 2a 2n 30 7.5
120 -0.05 2.3 0.06 1.7
2 0.01 7.4 0.14 6.1

2a 2n 5 1a 1n 30 0.01 7.4 2a 2n 0.14 6.1


3P 100 2a 2n 30 -0.05 2.6 7.5 0.06 1.9
150 -0.06 2.5 0.06 2.0
conclusion:The product comply with IEC61869-5:2011 after inspection, permitted to
leave the factory.
PH23070018

7 Measurement Secondary DC resistance


Room Temperature: 29 ℃

1a1n 2a2n 3a3n dadn


DC resistance Ω
0.04739 0.04920 / /

8 Insulating Oil Performance Test


8.1Puncture Voltage 54 kV,
8.2Dielectric Loss Ratio tanδ: 0.0012 (90℃)
8.3Water Content 9.7 mg/L
8.4 Gas Chromatography
单位 Unit:µL/L
H2 CO CO2 CH4 C2H6 C2H4 C2H2 C1+C2

0 0 247 0.40 0 0 0 0.40


PH23070019

The Product Certificate


for Capacitor Voltage Transformer

Product Type: TYD-170

Serial no.:PH23070019

Hitachi Energy Jiangsu High Voltage


Apparatus Co., Ltd.
PH23070019

Test Item and Result


1.Visual and Antiseptic Layer Inspection
Inspection basis: IEC61869-5:2011 Result: passed
2.Tightness of Capacitor Voltage Divider
placed in oven,heated to 60℃ for 8h without leakage
Inspection basis: IEC61869-5:2011 Result: passed
3.Capacitor Voltage Divider Inspection
Inspection basis: IEC61869-5:2011
3.1 The power-frequency withstand test of capacitor voltage divider:
The power-frequency voltage 325kV being applied between two terminals of capacitor voltage
divider for 1 min.
Result: passed
3.2 Measurement of capacitance and tanδ on a capacitor voltage
divider:
Room Temperature: 27 ℃ Humidity: 62 %
Capacitance test No. Name U(kV) Capacitance(μF) tan δ(%)
before voltage
withstand PH23070019-1 CN 10 0.010693 0.074

PH23070019-1 CN 10 0.010693 0.074

Capacitance test CN 79.7 0.010695 0.094

after voltage withstand PH23070019-1 C1N 79.7 0.012419 0.100

C2N 4 0.077680 0.074

Result: passed
3.3 Partial discharge measurement of capacitor voltage divider:
No. U(kV) Duration(s) Partial discharge(pC)
Partial
discharge 170 30 ≤8
PH23070019-1
Measurement 118 30 ≤4

Result: passed
3.4 Power frequency withstand test between the low-voltage and earth
terminals of the capacitor voltage divider:
An Power frequency voltage of 5kV being applied between the low-voltage and earth
terminals of capacitor voltage divider for 1 min.
Result: passed
4 Inspection Test of Electromagnetic Unit
Inspection basis: IEC61869-5:2011
4.1 Polarity inspection:
Test result is "―" polarity. Result: passed
4.2 Induction withstand voltage test of transformer:
150 Hz AC voltage47.4kV being applied to primary side of transformer for48 sec.
Result: passed
PH23070019

4.3 Induction withstand voltage test of compensation reactor:


150 Hz AC voltage 10kV being applied to two ends of reactor for 48 sec.
Result: passed
4.4 Measurement of Excitation
Percentage of rated secondary voltage (%) 100 120 150
No-load secondary current(A) 0.217 0.259 1.055
No-load loss(W) 12.1 / /
Result: passed
4.5 Power-frequency withstand test between low-voltage windings and
earth:
Power-frequency voltage 3kV being applied between low-voltage windings and earth
on transformer for 1min.
Result: passed
4.6 Insulation resistance test of electromagnetic unit:
Primary windings to secondary windings and earth>1000 MΩ
Between secondary windings and to earth>1000 MΩ
Result: passed
5 Ferro-resonance Test
Inspection basis: IEC61869-5:2011
Primary voltage Number of short –circuiting at zhe secondary terminals Conclusion
0.8Upr 3
1.0Upr 3
Passed
1.2Upr 3
1.5Upr 3
6 Accuracy Check
Inspection basis: IEC61869-5:2011 , the result is shown in attached table:
Percentage Secondary Phase Phase
Secondary winding Ratio error Burden Ratio error
of rated winding displaceme displaceme
Accuracy class f(%) (VA) f(%)
voltage(%) Burden(VA) nt δ(´) nt δ(´)

80 -0.03 1.3 0.12 2.1


1a 1n 1a 1n 30 1a 1n
100 -0.03 1.4 0.11 2.3
0.2 2a 2n 30 7.5
120 -0.04 1.5 0.11 2.3
2 0.03 5.3 0.17 4.9

2a 2n 5 1a 1n 30 0.03 5.3 2a 2n 0.17 4.9


3P 100 2a 2n 30 -0.03 1.7 7.5 0.12 2.2
150 -0.04 1.8 0.11 2.4
conclusion:The product comply with IEC61869-5:2011 after inspection, permitted to
leave the factory.
PH23070019

7 Measurement Secondary DC resistance


Room Temperature: 24 ℃

1a1n 2a2n 3a3n dadn


DC resistance Ω
0.04696 0.04981 / /

8 Insulating Oil Performance Test


8.1Puncture Voltage 53 kV,
8.2Dielectric Loss Ratio tanδ: 0.0020 (90℃)
8.3Water Content 9.2 mg/L
8.4 Gas Chromatography
单位 Unit:µL/L
H2 CO CO2 CH4 C2H6 C2H4 C2H2 C1+C2

2 2 159 0.50 0 0 0 0.50


PH23070020

The Product Certificate


for Capacitor Voltage Transformer

Product Type: TYD-170

Serial no.:PH23070020

Hitachi Energy Jiangsu High Voltage


Apparatus Co., Ltd.
PH23070020

Test Item and Result


1.Visual and Antiseptic Layer Inspection
Inspection basis: IEC61869-5:2011 Result: passed
2.Tightness of Capacitor Voltage Divider
placed in oven,heated to 60℃ for 8h without leakage
Inspection basis: IEC61869-5:2011 Result: passed
3.Capacitor Voltage Divider Inspection
Inspection basis: IEC61869-5:2011
3.1 The power-frequency withstand test of capacitor voltage divider:
The power-frequency voltage 325kV being applied between two terminals of capacitor voltage
divider for 1 min.
Result: passed
3.2 Measurement of capacitance and tanδ on a capacitor voltage
divider:
Room Temperature: 27 ℃ Humidity: 62 %
Capacitance test No. Name U(kV) Capacitance(μF) tan δ(%)
before voltage
withstand PH23070020-1 CN 10 0.010698 0.076

PH23070020-1 CN 10 0.010698 0.075

Capacitance test CN 79.7 0.010699 0.099

after voltage withstand PH23070020-1 C1N 79.7 0.012428 0.107

C2N 4 0.077580 0.074

Result: passed
3.3 Partial discharge measurement of capacitor voltage divider:
No. U(kV) Duration(s) Partial discharge(pC)
Partial
discharge 170 30 ≤8
PH23070020-1
Measurement 118 30 ≤4

Result: passed
3.4 Power frequency withstand test between the low-voltage and earth
terminals of the capacitor voltage divider:
An Power frequency voltage of 5kV being applied between the low-voltage and earth
terminals of capacitor voltage divider for 1 min.
Result: passed
4 Inspection Test of Electromagnetic Unit
Inspection basis: IEC61869-5:2011
4.1 Polarity inspection:
Test result is "―" polarity. Result: passed
4.2 Induction withstand voltage test of transformer:
150 Hz AC voltage47.4kV being applied to primary side of transformer for48 sec.
Result: passed
PH23070020

4.3 Induction withstand voltage test of compensation reactor:


150 Hz AC voltage 10kV being applied to two ends of reactor for 48 sec.
Result: passed
4.4 Measurement of Excitation
Percentage of rated secondary voltage (%) 100 120 150
No-load secondary current(A) 0.224 0.268 1.300
No-load loss(W) 12.0 / /
Result: passed
4.5 Power-frequency withstand test between low-voltage windings and
earth:
Power-frequency voltage 3kV being applied between low-voltage windings and earth
on transformer for 1min.
Result: passed
4.6 Insulation resistance test of electromagnetic unit:
Primary windings to secondary windings and earth>1000 MΩ
Between secondary windings and to earth>1000 MΩ
Result: passed
5 Ferro-resonance Test
Inspection basis: IEC61869-5:2011
Primary voltage Number of short –circuiting at zhe secondary terminals Conclusion
0.8Upr 3
1.0Upr 3
Passed
1.2Upr 3
1.5Upr 3
6 Accuracy Check
Inspection basis: IEC61869-5:2011 , the result is shown in attached table:
Percentage Secondary Phase Phase
Secondary winding Ratio error Burden Ratio error
of rated winding displaceme displaceme
Accuracy class f(%) (VA) f(%)
voltage(%) Burden(VA) nt δ(´) nt δ(´)

80 -0.04 1.0 0.11 1.8


1a 1n 1a 1n 30 1a 1n
100 -0.04 1.2 0.11 1.8
0.2 2a 2n 30 7.5
120 -0.04 1.6 0.11 2.1
2 0.05 7.0 0.20 5.6

2a 2n 5 1a 1n 30 0.05 7.0 2a 2n 0.20 5.6


3P 100 2a 2n 30 -0.05 1.6 7.5 0.11 2.0
150 -0.06 1.8 0.10 2.4
conclusion:The product comply with IEC61869-5:2011 after inspection, permitted to
leave the factory.
PH23070020

7 Measurement Secondary DC resistance


Room Temperature: 24 ℃

1a1n 2a2n 3a3n dadn


DC resistance Ω
0.04690 0.04954 / /

8 Insulating Oil Performance Test


8.1Puncture Voltage 54 kV,
8.2Dielectric Loss Ratio tanδ: 0.0020 (90℃)
8.3Water Content 9.4 mg/L
8.4 Gas Chromatography
单位 Unit:µL/L
H2 CO CO2 CH4 C2H6 C2H4 C2H2 C1+C2

1 4 142 0.57 0 0 0 0.57


PH23070021

The Product Certificate


for Capacitor Voltage Transformer

Product Type: TYD-170

Serial no.:PH23070021

Hitachi Energy Jiangsu High Voltage


Apparatus Co., Ltd.
PH23070021

Test Item and Result


1.Visual and Antiseptic Layer Inspection
Inspection basis: IEC61869-5:2011 Result: passed
2.Tightness of Capacitor Voltage Divider
placed in oven,heated to 60℃ for 8h without leakage
Inspection basis: IEC61869-5:2011 Result: passed
3.Capacitor Voltage Divider Inspection
Inspection basis: IEC61869-5:2011
3.1 The power-frequency withstand test of capacitor voltage divider:
The power-frequency voltage 325kV being applied between two terminals of capacitor voltage
divider for 1 min.
Result: passed
3.2 Measurement of capacitance and tanδ on a capacitor voltage
divider:
Room Temperature: 27 ℃ Humidity: 62 %
Capacitance test No. Name U(kV) Capacitance(μF) tan δ(%)
before voltage
withstand PH23070021-1 CN 10 0.010702 0.073

PH23070021-1 CN 10 0.010702 0.073

Capacitance test CN 79.7 0.010703 0.091

after voltage withstand PH23070021-1 C1N 79.7 0.012428 0.099

C2N 4 0.077720 0.075

Result: passed
3.3 Partial discharge measurement of capacitor voltage divider:
No. U(kV) Duration(s) Partial discharge(pC)
Partial
discharge 170 30 ≤8
PH23070021-1
Measurement 118 30 ≤4

Result: passed
3.4 Power frequency withstand test between the low-voltage and earth
terminals of the capacitor voltage divider:
An Power frequency voltage of 5kV being applied between the low-voltage and earth
terminals of capacitor voltage divider for 1 min.
Result: passed
4 Inspection Test of Electromagnetic Unit
Inspection basis: IEC61869-5:2011
4.1 Polarity inspection:
Test result is "―" polarity. Result: passed
4.2 Induction withstand voltage test of transformer:
150 Hz AC voltage47.4kV being applied to primary side of transformer for48 sec.
Result: passed
PH23070021

4.3 Induction withstand voltage test of compensation reactor:


150 Hz AC voltage 10kV being applied to two ends of reactor for 48 sec.
Result: passed
4.4 Measurement of Excitation
Percentage of rated secondary voltage (%) 100 120 150
No-load secondary current(A) 0.223 0.266 1.109
No-load loss(W) 12.0 / /
Result: passed
4.5 Power-frequency withstand test between low-voltage windings and
earth:
Power-frequency voltage 3kV being applied between low-voltage windings and earth
on transformer for 1min.
Result: passed
4.6 Insulation resistance test of electromagnetic unit:
Primary windings to secondary windings and earth>1000 MΩ
Between secondary windings and to earth>1000 MΩ
Result: passed
5 Ferro-resonance Test
Inspection basis: IEC61869-5:2011
Primary voltage Number of short –circuiting at zhe secondary terminals Conclusion
0.8Upr 3
1.0Upr 3
Passed
1.2Upr 3
1.5Upr 3
6 Accuracy Check
Inspection basis: IEC61869-5:2011 , the result is shown in attached table:
Percentage Secondary Phase Phase
Secondary winding Ratio error Burden Ratio error
of rated winding displaceme displaceme
Accuracy class f(%) (VA) f(%)
voltage(%) Burden(VA) nt δ(´) nt δ(´)

80 -0.07 1.0 0.08 1.6


1a 1n 1a 1n 30 1a 1n
100 -0.07 0.9 0.08 1.6
0.2 2a 2n 30 7.5
120 -0.07 0.9 0.08 1.6
2 -0.01 5.4 0.13 4.4

2a 2n 5 1a 1n 30 -0.01 5.4 2a 2n 0.13 4.4


3P 100 2a 2n 30 -0.07 1.1 7.5 0.08 1.7
150 -0.08 1.1 0.08 1.7
conclusion:The product comply with IEC61869-5:2011 after inspection, permitted to
leave the factory.
PH23070021

7 Measurement Secondary DC resistance


Room Temperature: 24 ℃

1a1n 2a2n 3a3n dadn


DC resistance Ω
0.04690 0.04927 / /

8 Insulating Oil Performance Test


8.1Puncture Voltage 52 kV,
8.2Dielectric Loss Ratio tanδ: 0.0018 (90℃)
8.3Water Content 9.7 mg/L
8.4 Gas Chromatography
单位 Unit:µL/L
H2 CO CO2 CH4 C2H6 C2H4 C2H2 C1+C2

2 3 137 0.52 0 0.08 0 0.60