ROUTINE Page 1 of 15

TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01A

Customer
Hitachi Energy Peru S.A.

Customer reference Country

Reference Project
502886514

Breaker type Serial number


LTB245E1 1361731593-01A

Mechanism type Serial number


BLK222 1361731593-01-A1

Standard Test completed


IEC62271-100 8/4/2023

We hereby certify that the above objects have passed all routine tests in accordance with the
standard referred to in above and with the terms of the contract.

Hitachi Energy High Voltage Switchgear Company


Limited,Beijing
Quality Department

........................................................... Date: 8/4/2023


bnj

Test witnessed by

........................................................... .............................................................

........................................................... .............................................................

...........................................................
ROUTINE Page 2 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01A

Rated data
Rated filling pressure for operation: 0.80 MPa(abs)

Check of rating plates Approved: bnj

MECHANISM RESULTS

Resistance in ohms of auxiliary circuits


Description Mechanism No. Mechanism No. Mechanism No.
1361731593-01-A1
Closing coil 1 53
Opening coil 1 53
Opening coil 2 52
Antipumping relay 1 7710
Heater anticondense 687
Heater total 231

All resistances checked Approved bnj


ROUTINE Page 3 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01A

Check of Approved
Wiring acc. To circuit diagram bnj
Local/remote operation bnj
Blocking relays bnj
On-line-motor starter does not trip for 10 consecutive operations bnj
Auxiliary contacts bnj
Thermostat settings bnj
Counter bnj
All adjustments and paint marking bnj

Settings
Description Unit Mech. 1 Mech. 2 Mech. 3
Thermostat °C 10.0
Closing spring charge ° 133.0
Trip spring setting mm 12.0

Approved: bnj

Spring charge at nominal voltage


Description Unit Mech. 1 Mech. 2 Mech. 3
Charging time s 8.1
Motor current A 14.3

Approved: bnj

Lowest operating voltage


Description Unit Mech. 1 Mech. 2 Mech. 3
Close coil 1 VDC 67
Trip coil 1 VDC 46
Trip coil 2 VDC 46

Approved: bnj

Power frequency test of auxiliary circuits


1 second 50 Hz 2.5 kV Approved: bnj
1 second 50 Hz 2.0 kV,motor Approved: bnj
ROUTINE Page 4 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01A

POLE RESULTS

Resistance in main circuit


Phase Unit Part 1 Part 2
A µOhm 36
Approved: bnj

Power frequency test


72 seconds 50 Hz breaking unit 460 kV Approved: bnj
72 seconds 50 Hz to earth: 460 / kV Approved: bnj

Overpressure test on each pole


10 minutes duration 1.15 MPa(abs) Approved: bnj

Tightness test on each pole Approved: bnj

OPERATING TEST

Test assumptions
Technical provision: 1HSB732008-11CN
Fill pressure: 0.80 MPa(abs)

Operations Voltage Motor Close 1 Close 2 Trip 1 Trip 2 Trip 3


level VDC VDC VDC VDC VDC VDC
5 Close and Open Min 94 94 77 77
5 Close and Open Max 121 121 121 121
5 Close and Open Nom 110 110 110 110
5 Close-Open Nom 110 110 110 110
5 Open-0.3s-Close Nom 110 110 110 110

Operating test
At least 25 operations as above Approved: bnj
Stored energi test O – 0.3s- CO- 3min- CO Approved: -
ROUTINE Page 5 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01A

Test Samples
Oper. Oper. Volt Cc Tc Operation times Cont. Cont. Cont. Over Re- Damp Time
No. Level phase stroke speed speed travel bounce time difference
A B C 1 2 a b
ms ms ms mm m/s m/s mm mm ms ms ms
Close 5 Min. 1 - 28.5 160.0 7.3 2.8 2.9 1.1 2.2 -12.0
Open 6 Min. - 1 20.2 160.1 8.5 -3.5 15.3 46.1 -2.6 10.4
Close 15 Max. 1 - 27.0 160.1 7.4 2.6 2.8 1.2 2.2 -11.9
Open 16 Max. - 1 17.7 160.1 8.5 -3.7 15.7 48.3 -2.6 10.3
Close 25 Nom. 1 - 27.5 160.1 7.3 2.6 2.8 1.2 2.0 -11.9
Open 26 Nom. - 1 18.1 160.0 8.5 -3.8 15.8 48.8 -2.6 10.3
Open 40 Nom. - 2 18.1 160.0 8.5 -3.4 15.6 47.9 -2.5 10.5

Oper. Oper. Volt Cc Tc Interval times 1 Interval times 2 Time


No. Level phase phase difference
A B C A B C a b
ms ms ms ms ms ms ms
C-O 31 Nom. 1 1 26.9 2.3 -11.8
O-C 37 Nom. 1 1 259.4 -2.5 10.6
ROUTINE Page 6 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01A

Main Test sequence Close Min. Operation No 5

160

140 A1
1a

120 1b

100
mm

80

60

40

20

T1
0
2.5
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
94 VDC 94 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 28.5 (0.0 - 30.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 30.7 2.2 (0.0 - 8.0)
1b 16.5 -12.0
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 7.3 (7.2 - 7.6)
Travel speed 2 m/s 2.8
Contact Stroke mm 160.0 (157.0 - 163.0)
OverTravel mm 2.9
Rebounce mm 1.1
ROUTINE Page 7 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01A

Main Test sequence Open Min. Operation No 6

T1
160

140
A1
1a
120 1b

100
mm

80

60

40

20

2.5
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
94 VDC - 77 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 20.2 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 17.6 -2.6
1b 30.6 10.4
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.5 (8.0 - 8.7)
Contact Stroke mm 160.1 (157.0 - 163.0)
OverTravel mm -3.5 (-6.5 - 1.5)
Rebounce mm 15.3 (0.0 - 22.0)
Damping time ms 46.1
ROUTINE Page 8 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01A

Main Test sequence Close Max. Operation No 15

160

140 A1
1a

1b
120

100
mm

80

60

40

20

0 T1
2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
121 VDC 121 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 27.0 (0.0 - 30.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 29.2 2.2 (0.0 - 8.0)
1b 15.1 -11.9
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 7.4 (7.2 - 7.6)
Travel speed 2 m/s 2.6
Contact Stroke mm 160.1 (157.0 - 163.0)
OverTravel mm 2.8
Rebounce mm 1.2
ROUTINE Page 9 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01A

Main Test sequence Open Max. Operation No 16

T1
160

140
A1
1a
120 1b

100
mm

80

60

40

20

2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
121 VDC - 121 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 17.7 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 15.1 -2.6
1b 28.0 10.3
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.5 (8.0 - 8.7)
Contact Stroke mm 160.1 (157.0 - 163.0)
OverTravel mm -3.7 (-6.5 - 1.5)
Rebounce mm 15.7 (0.0 - 22.0)
Damping time ms 48.3
ROUTINE Page 10 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01A

Main Test sequence Close Nom. Operation No 25

160

140 A1
1a

120 1b

100
mm

80

60

40

20

0 T1
2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
110 VDC 110 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 27.5 (0.0 - 30.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 29.5 2.0 (0.0 - 8.0)
1b 15.6 -11.9
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 7.3 (7.2 - 7.6)
Travel speed 2 m/s 2.6
Contact Stroke mm 160.1 (157.0 - 163.0)
OverTravel mm 2.8
Rebounce mm 1.2
ROUTINE Page 11 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01A

Main Test sequence Open Nom. Operation No 26

T1
160

140
A1
1a
120 1b

100
mm

80

60

40

20

2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
110 VDC - 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 18.1 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 15.5 -2.6
1b 28.4 10.3
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.5 (8.0 - 8.7)
Contact Stroke mm 160.0 (157.0 - 163.0)
OverTravel mm -3.8 (-6.5 - 1.5)
Rebounce mm 15.8 (0.0 - 22.0)
Damping time ms 48.8
ROUTINE Page 12 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01A

Main Test sequence Close-Open Nom. Operation No 31

160

140
A1
1a

120 1b

100
mm

80

60

40

20

T1
0
2
1
A

Ic1
0

0 20 40 60 80 100 120 140 160 180 200 220 240


ms

Operation data
Motor Close coil 1 Trip coil 1
110 VDC 110 VDC 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 27.2 (0.0 - 30.0) 26.9 (23.0 - 29.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 29.5 22.4 2.3 (0.0 - 8.0)
1b 15.4 47.7 -11.8
ROUTINE Page 13 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01A

Main Test sequence Open-0.3s-Close Nom. Operation No 37

T1
160

140 A1
1a

120 1b

100
mm

80

60

40

20

0
2
1
A

Ic1
0

0 50 100 150 200 250 300 350 400


ms

Operation data
Motor Close coil 1 Trip coil 1
110 VDC 110 VDC 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 18.0 (15.0 - 19.0) 259.4
Aux. Contact time Close/Open Close/Open Aux-Main
1a 15.5 264.2 -2.5
1b 28.6 236.9 10.6
ROUTINE Page 14 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01A

Main Test sequence Open Nom. Operation No 40

T1
160

140
A1
1a
120 1b

100
mm

80

60

40

20

2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 2
110 VDC - 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 18.1 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 15.6 -2.5
1b 28.6 10.5
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.5 (8.0 - 8.7)
Contact Stroke mm 160.0 (157.0 - 163.0)
OverTravel mm -3.4 (-6.5 - 1.5)
Rebounce mm 15.6 (0.0 - 22.0)
Damping time ms 47.9
ROUTINE Page 15 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01A

Free Test Spring charge Nom. Mechanism No 1 Operation No 1


20

18

16

14

12

10
A

Im1
0

-2
0 1 2 3 4 5 6 7 8 9 10
s

Operation data
Motor Close coil 1 Trip coil -
110 VDC 110 VDC -

Spring charge for mechanism 1


Description Unit Result Limits
Charge current A 14.3
Charge time s 8.1
ROUTINE Page 1 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01B

Customer
Hitachi Energy Peru S.A.

Customer reference Country

Reference Project
502886514

Breaker type Serial number


LTB245E1 1361731593-01B

Mechanism type Serial number


BLK222 1361731593-01-B1

Standard Test completed


IEC62271-100 8/3/2023

We hereby certify that the above objects have passed all routine tests in accordance with the
standard referred to in above and with the terms of the contract.

Hitachi Energy High Voltage Switchgear Company


Limited,Beijing
Quality Department

........................................................... Date: 8/3/2023


bnj

Test witnessed by

........................................................... .............................................................

........................................................... .............................................................

...........................................................
ROUTINE Page 2 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01B

Rated data
Rated filling pressure for operation: 0.80 MPa(abs)

Check of rating plates Approved: bnj

MECHANISM RESULTS

Resistance in ohms of auxiliary circuits


Description Mechanism No. Mechanism No. Mechanism No.
1361731593-01-B1
Closing coil 1 53
Opening coil 1 53
Opening coil 2 52
Antipumping relay 1 7860
Extra relay 1 8070
Extra relay 2 8040
Extra relay 3 11080
Extra relay 4 10770
Density blocking relay 1 8070
Density blocking relay 2 8040
Heater anticondense 686
Heater total 231

All resistances checked Approved bnj


ROUTINE Page 3 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01B

Check of Approved
Wiring acc. To circuit diagram bnj
Local/remote operation bnj
Blocking relays bnj
On-line-motor starter does not trip for 10 consecutive operations bnj
Auxiliary contacts bnj
Thermostat settings bnj
Counter bnj
All adjustments and paint marking bnj

Settings
Description Unit Mech. 1 Mech. 2 Mech. 3
Thermostat °C 10.0
Closing spring charge ° 135.0
Trip spring setting mm 10.0

Approved: bnj

Spring charge at nominal voltage


Description Unit Mech. 1 Mech. 2 Mech. 3
Charging time s 7.3
Motor current A 14.1

Approved: bnj

Lowest operating voltage


Description Unit Mech. 1 Mech. 2 Mech. 3
Close coil 1 VDC 64
Trip coil 1 VDC 43
Trip coil 2 VDC 43

Approved: bnj

Power frequency test of auxiliary circuits


1 second 50 Hz 2.5 kV Approved: bnj
1 second 50 Hz 2.0 kV,motor Approved: bnj
ROUTINE Page 4 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01B

POLE RESULTS

Resistance in main circuit


Phase Unit Part 1 Part 2
B µOhm 36
Approved: bnj

Power frequency test


72 seconds 50 Hz breaking unit 460 kV Approved: bnj
72 seconds 50 Hz to earth: 460 / kV Approved: bnj

Overpressure test on each pole


10 minutes duration 1.15 MPa(abs) Approved: bnj

Tightness test on each pole Approved: bnj

OPERATING TEST

Test assumptions
Technical provision: 1HSB732008-11CN
Fill pressure: 0.80 MPa(abs)

Operations Voltage Motor Close 1 Close 2 Trip 1 Trip 2 Trip 3


level VDC VDC VDC VDC VDC VDC
5 Close and Open Min 94 94 77 77
5 Close and Open Max 121 121 121 121
5 Close and Open Nom 110 110 110 110
5 Close-Open Nom 110 110 110 110
5 Open-0.3s-Close Nom 110 110 110 110

Operating test
At least 25 operations as above Approved: bnj
Stored energi test O – 0.3s- CO- 3min- CO Approved: -
ROUTINE Page 5 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01B

Test Samples
Oper. Oper. Volt Cc Tc Operation times Cont. Cont. Cont. Over Re- Damp Time
No. Level phase stroke speed speed travel bounce time difference
A B C 1 2 a b
ms ms ms mm m/s m/s mm mm ms ms ms
Close 5 Min. 1 - 29.9 159.7 7.3 2.9 3.1 1.7 1.7 -12.2
Open 6 Min. - 1 20.2 160.0 8.3 -4.6 13.8 16.4 -2.2 9.8
Close 15 Max. 1 - 27.2 160.0 7.3 2.9 2.9 1.9 1.7 -12.1
Open 16 Max. - 1 17.9 160.0 8.3 -4.5 13.6 16.4 -2.1 9.8
Close 25 Nom. 1 - 27.5 160.0 7.3 3.0 2.9 1.8 2.0 -12.1
Open 26 Nom. - 1 18.3 160.0 8.2 -4.5 13.8 16.5 -2.2 9.6
Open 40 Nom. - 2 17.9 160.1 8.3 -4.4 13.8 16.4 -1.9 10.1

Oper. Oper. Volt Cc Tc Interval times 1 Interval times 2 Time


No. Level phase phase difference
A B C A B C a b
ms ms ms ms ms ms ms
C-O 31 Nom. 1 1 26.4 1.6 -12.1
O-C 37 Nom. 1 1 260.1 -1.9 10.0
ROUTINE Page 6 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01B

Main Test sequence Close Min. Operation No 5

160

140
B1
2a
120
2b

100
mm

80

60

40

20

T1
0
2.5
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
94 VDC 94 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
B1 29.9 (0.0 - 30.0)
Aux. Contact time Close/Open Close/Open Aux-Main
2a 31.6 1.7 (0.0 - 8.0)
2b 17.7 -12.2
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 7.3 (7.2 - 7.6)
Travel speed 2 m/s 2.9
Contact Stroke mm 159.7 (157.0 - 163.0)
OverTravel mm 3.1
Rebounce mm 1.7
ROUTINE Page 7 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01B

Main Test sequence Open Min. Operation No 6

T1
160

140

B1

120 2a
2b

100
mm

80

60

40

20

2.5
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
94 VDC - 77 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
B1 20.2 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
2a 18.0 -2.2
2b 30.0 9.8
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.3 (8.0 - 8.7)
Contact Stroke mm 160.0 (157.0 - 163.0)
OverTravel mm -4.6 (-6.5 - 1.5)
Rebounce mm 13.8 (0.0 - 22.0)
Damping time ms 16.4
ROUTINE Page 8 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01B

Main Test sequence Close Max. Operation No 15

160

140
B1
2a
120
2b

100
mm

80

60

40

20

0 T1
2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
121 VDC 121 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
B1 27.2 (0.0 - 30.0)
Aux. Contact time Close/Open Close/Open Aux-Main
2a 28.9 1.7 (0.0 - 8.0)
2b 15.1 -12.1
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 7.3 (7.2 - 7.6)
Travel speed 2 m/s 2.9
Contact Stroke mm 160.0 (157.0 - 163.0)
OverTravel mm 2.9
Rebounce mm 1.9
ROUTINE Page 9 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01B

Main Test sequence Open Max. Operation No 16

T1
160

140

B1

120 2a
2b

100
mm

80

60

40

20

2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
121 VDC - 121 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
B1 17.9 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
2a 15.8 -2.1
2b 27.7 9.8
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.3 (8.0 - 8.7)
Contact Stroke mm 160.0 (157.0 - 163.0)
OverTravel mm -4.5 (-6.5 - 1.5)
Rebounce mm 13.6 (0.0 - 22.0)
Damping time ms 16.4
ROUTINE Page 10 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01B

Main Test sequence Close Nom. Operation No 25

160

140
B1
2a
120
2b

100
mm

80

60

40

20

0 T1
2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
110 VDC 110 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
B1 27.5 (0.0 - 30.0)
Aux. Contact time Close/Open Close/Open Aux-Main
2a 29.5 2.0 (0.0 - 8.0)
2b 15.4 -12.1
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 7.3 (7.2 - 7.6)
Travel speed 2 m/s 3.0
Contact Stroke mm 160.0 (157.0 - 163.0)
OverTravel mm 2.9
Rebounce mm 1.8
ROUTINE Page 11 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01B

Main Test sequence Open Nom. Operation No 26

T1
160

140

B1

120 2a
2b

100
mm

80

60

40

20

2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
110 VDC - 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
B1 18.3 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
2a 16.1 -2.2
2b 27.9 9.6
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.2 (8.0 - 8.7)
Contact Stroke mm 160.0 (157.0 - 163.0)
OverTravel mm -4.5 (-6.5 - 1.5)
Rebounce mm 13.8 (0.0 - 22.0)
Damping time ms 16.5
ROUTINE Page 12 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01B

Main Test sequence Close-Open Nom. Operation No 31

160

140

B1

120 2a
2b

100
mm

80

60

40

20

T1
0
2
1
A

Ic1
0

0 20 40 60 80 100 120 140 160 180 200 220 240


ms

Operation data
Motor Close coil 1 Trip coil 1
110 VDC 110 VDC 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
B1 27.4 (0.0 - 30.0) 26.4 (23.0 - 29.0)
Aux. Contact time Close/Open Close/Open Aux-Main
2a 29.0 23.7 1.6 (0.0 - 8.0)
2b 15.3 47.8 -12.1
ROUTINE Page 13 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01B

Main Test sequence Open-0.3s-Close Nom. Operation No 37

T1
160

140
B1
2a
120
2b

100
mm

80

60

40

20

0
2
1
A

Ic1
0

0 50 100 150 200 250 300 350 400


ms

Operation data
Motor Close coil 1 Trip coil 1
110 VDC 110 VDC 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
B1 17.8 (15.0 - 19.0) 260.1
Aux. Contact time Close/Open Close/Open Aux-Main
2a 15.9 263.4 -1.9
2b 27.8 237.9 10.0
ROUTINE Page 14 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01B

Main Test sequence Open Nom. Operation No 40

T1
160

140

B1

120 2a
2b

100
mm

80

60

40

20

2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 2
110 VDC - 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
B1 17.9 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
2a 16.0 -1.9
2b 28.0 10.1
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.3 (8.0 - 8.7)
Contact Stroke mm 160.1 (157.0 - 163.0)
OverTravel mm -4.4 (-6.5 - 1.5)
Rebounce mm 13.8 (0.0 - 22.0)
Damping time ms 16.4
ROUTINE Page 15 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01B

Free Test Spring charge Nom. Mechanism No 2 Operation No 1


20

18

16

14

12

10
A

Im1
0

-2
0 1 2 3 4 5 6 7 8 9
s

Operation data
Motor Close coil 1 Trip coil -
110 VDC 110 VDC -

Spring charge for mechanism 2


Description Unit Result Limits
Charge current A 14.1
Charge time s 7.3
ROUTINE Page 1 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01C

Customer
HITACHI ENERGY PERU S.A.

Customer reference Country

Reference Project
502886514

Breaker type Serial number


LTB245E1 1361731593-01C

Mechanism type Serial number


BLK222 1361731593-01-C1

Standard Test completed


IEC62271-100 8/2/2023

We hereby certify that the above objects have passed all routine tests in accordance with the
standard referred to in above and with the terms of the contract.

Hitachi Energy High Voltage Switchgear Company Limited,Beijing


Quality Department

........................................................... Date: 8/2/2023


swq

Test witnessed by

...........................................................

........................................................... .............................................................

...........................................................
ROUTINE Page 2 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01C

Rated data
Rated filling pressure for operation: 0.80 MPa(abs)

Check of rating plates Approved: swq

MECHANISM RESULTS

Resistance in ohms of auxiliary circuits


Description Mechanism No. Mechanism No. Mechanism No.
1361731593-01-C1
Closing coil 1 53
Opening coil 1 53
Opening coil 2 53
Antipumping relay 1 7700
Heater anticondense 687
Heater total 231

All resistances checked Approved swq


ROUTINE Page 3 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01C

Check of Approved
Wiring acc. To circuit diagram swq
Local/remote operation swq
Blocking relays swq
Extra relays swq
On-line-motor starter does not trip for 10 consecutive operations swq
Auxiliary contacts swq
Thermostat settings swq
Counter swq
All adjustments and paint marking swq

Settings
Description Unit Mech. 1 Mech. 2 Mech. 3
Thermostat °C 10.0
Closing spring charge ° 131.0
Trip spring setting mm 10.0

Approved: swq

Spring charge at nominal voltage


Description Unit Mech. 1 Mech. 2 Mech. 3
Charging time s 8.1
Motor current A 13.7

Approved: swq

Lowest operating voltage


Description Unit Mech. 1 Mech. 2 Mech. 3
Close coil 1 VDC 49
Trip coil 1 VDC 49
Trip coil 2 VDC 49

Approved: swq

Power frequency test of auxiliary circuits


1 second 50 Hz 2.5 kV Approved: swq
1 second 50 Hz 2.0 kV,motor Approved: -
ROUTINE Page 4 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01C

POLE RESULTS

Resistance in main circuit


Phase Unit Part 1 Part 2
C µOhm 39
Approved: swq

Power frequency test


72 seconds 50 Hz breaking unit 460 kV Approved: swq
72 seconds 50 Hz to earth: 460 / kV Approved: swq

Overpressure test on each pole


10 minutes duration 1.15 MPa(abs) Approved: swq

Tightness test on each pole Approved: swq

OPERATING TEST

Test assumptions
Technical provision: 1HSB732008-11CN
Fill pressure: 0.80 MPa(abs)

Operations Voltage Motor Close 1 Close 2 Trip 1 Trip 2 Trip 3


level VDC VDC VDC VDC VDC VDC
5 Close and Open Min 94 94 77 77
5 Close and Open Max 121 121 121 121
5 Close and Open Nom 110 110 110 110
5 Close-Open Nom 110 110 110 110
5 Open-0.3s-Close Nom 110 110 110 110

Operating test
At least 25 operations as above Approved: swq
Stored energi test O – 0.3s- CO- 3min- CO Approved: -
ROUTINE Page 5 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01C

Test Samples
Oper. Oper. Volt Cc Tc Operation times Cont. Cont. Cont. Over Re- Damp Time
No. Level phase stroke speed speed travel bounce time difference
A B C 1 2 a b
ms ms ms mm m/s m/s mm mm ms ms ms
Close 5 Min. 1 - 28.7 159.3 7.2 2.8 3.4 1.0 2.2 -12.5
Open 6 Min. - 1 20.7 159.7 8.1 -5.0 16.3 48.0 -2.1 10.3
Close 15 Max. 1 - 27.5 159.6 7.2 2.7 3.1 1.2 2.2 -12.5
Open 16 Max. - 1 17.9 159.6 8.1 -4.7 16.3 47.9 -2.1 10.3
Close 25 Nom. 1 - 27.9 159.5 7.2 2.7 3.1 1.1 2.3 -12.5
Open 26 Nom. - 1 18.3 159.6 8.1 -4.9 16.0 47.8 -2.1 10.6
Open 40 Nom. - 2 18.4 159.7 8.1 -4.7 16.1 45.8 -2.2 10.3

Oper. Oper. Volt Cc Tc Interval times 1 Interval times 2 Time


No. Level phase phase difference
A B C A B C a b
ms ms ms ms ms ms ms
C-O 31 Nom. 1 1 26.5 2.7 -12.5
O-C 37 Nom. 1 1 259.5 -2.2 10.3
ROUTINE Page 6 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01C

Main Test sequence Close Min. Operation No 5

180

160

140 C1
3a

120 3b

100
mm

80

60

40

20

T1
0

2
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
94 VDC 94 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
C1 28.7 (0.0 - 30.0)
Aux. Contact time Close/Open Close/Open Aux-Main
3a 30.9 2.2 (0.0 - 8.0)
3b 16.2 -12.5
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 7.2 (7.2 - 7.6)
Travel speed 2 m/s 2.8
Contact Stroke mm 159.3 (157.0 - 163.0)
OverTravel mm 3.4
Rebounce mm 1.0
ROUTINE Page 7 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01C

Main Test sequence Open Min. Operation No 6

180

160 T1

140
C1
3a
120 3b

100
mm

80

60

40

20

2
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
94 VDC - 77 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
C1 20.7 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
3a 18.6 -2.1
3b 31.0 10.3
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.1 (8.0 - 8.7)
Contact Stroke mm 159.7 (157.0 - 163.0)
OverTravel mm -5.0 (-6.5 - 1.5)
Rebounce mm 16.3 (0.0 - 22.0)
Damping time ms 48.0
ROUTINE Page 8 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01C

Main Test sequence Close Max. Operation No 15

180

160

140 C1
3a

120 3b

100
mm

80

60

40

20

T1
0

2
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
121 VDC 121 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
C1 27.5 (0.0 - 30.0)
Aux. Contact time Close/Open Close/Open Aux-Main
3a 29.7 2.2 (0.0 - 8.0)
3b 15.0 -12.5
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 7.2 (7.2 - 7.6)
Travel speed 2 m/s 2.7
Contact Stroke mm 159.6 (157.0 - 163.0)
OverTravel mm 3.1
Rebounce mm 1.2
ROUTINE Page 9 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01C

Main Test sequence Open Max. Operation No 16

180

160 T1

140
C1
3a
120 3b

100
mm

80

60

40

20

2
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
121 VDC - 121 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
C1 17.9 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
3a 15.8 -2.1
3b 28.2 10.3
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.1 (8.0 - 8.7)
Contact Stroke mm 159.6 (157.0 - 163.0)
OverTravel mm -4.7 (-6.5 - 1.5)
Rebounce mm 16.3 (0.0 - 22.0)
Damping time ms 47.9
ROUTINE Page 10 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01C

Main Test sequence Close Nom. Operation No 25

180

160

140 C1
3a

120 3b

100
mm

80

60

40

20

T1
0

2
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
110 VDC 110 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
C1 27.9 (0.0 - 30.0)
Aux. Contact time Close/Open Close/Open Aux-Main
3a 30.2 2.3 (0.0 - 8.0)
3b 15.4 -12.5
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 7.2 (7.2 - 7.6)
Travel speed 2 m/s 2.7
Contact Stroke mm 159.5 (157.0 - 163.0)
OverTravel mm 3.1
Rebounce mm 1.1
ROUTINE Page 11 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01C

Main Test sequence Open Nom. Operation No 26

180

160 T1

140
C1
3a
120 3b

100
mm

80

60

40

20

2
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
110 VDC - 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
C1 18.3 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
3a 16.2 -2.1
3b 28.9 10.6
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.1 (8.0 - 8.7)
Contact Stroke mm 159.6 (157.0 - 163.0)
OverTravel mm -4.9 (-6.5 - 1.5)
Rebounce mm 16.0 (0.0 - 22.0)
Damping time ms 47.8
ROUTINE Page 12 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01C

Main Test sequence Close-Open Nom. Operation No 31

180

160

140
C1
3a
120 3b

100
mm

80

60

40

20

T1
0

2
A

Ic1
0

0 20 40 60 80 100 120 140 160 180 200 220 240


ms

Operation data
Motor Close coil 1 Trip coil 1
110 VDC 110 VDC 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
C1 27.8 (0.0 - 30.0) 26.5 (23.0 - 29.0)
Aux. Contact time Close/Open Close/Open Aux-Main
3a 30.5 22.7 2.7 (0.0 - 8.0)
3b 15.3 49.0 -12.5
ROUTINE Page 13 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01C

Main Test sequence Open-0.3s-Close Nom. Operation No 37

180

160 T1

140 C1
3a

120 3b

100
mm

80

60

40

20

2
A

Ic1
0

0 50 100 150 200 250 300 350 400


ms

Operation data
Motor Close coil 1 Trip coil 1
110 VDC 110 VDC 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
C1 18.3 (15.0 - 19.0) 259.5
Aux. Contact time Close/Open Close/Open Aux-Main
3a 16.1 264.2 -2.2
3b 28.6 236.8 10.3
ROUTINE Page 14 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01C

Main Test sequence Open Nom. Operation No 40

180

160 T1

140
C1
3a
120 3b

100
mm

80

60

40

20

2
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 2
110 VDC - 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
C1 18.4 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
3a 16.2 -2.2
3b 28.7 10.3
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.1 (8.0 - 8.7)
Contact Stroke mm 159.7 (157.0 - 163.0)
OverTravel mm -4.7 (-6.5 - 1.5)
Rebounce mm 16.1 (0.0 - 22.0)
Damping time ms 45.8
ROUTINE Page 15 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-01C

Free Test Spring charge Nom. Mechanism No 3 Operation No 1


40

35

30

25

20
A

15

10

Im1
0

0 1 2 3 4 5 6 7 8 9 10
s

Operation data
Motor Close coil 1 Trip coil -
110 VDC 110 VDC -

Spring charge for mechanism 3


Description Unit Result Limits
Charge current A 13.7
Charge time s 8.1
ROUTINE Page 1 of 16
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02A

Customer
HITACHI ENERGY PERU S.A.

Customer reference Country

Reference Project
502886514

Breaker type Serial number


LTB245E1 1361731593-02A

Mechanism type Serial number


BLK222 1361731593-02-A1

Standard Test completed


IEC62271-100 8/3/2023

We hereby certify that the above objects have passed all routine tests in accordance with the
standard referred to in above and with the terms of the contract.

Hitachi Energy High Voltage Switchgear Company Limited,Beijing


Quality Department

........................................................... Date: 8/3/2023


clq

Test witnessed by

........................................................... .............................................................

........................................................... .............................................................

...........................................................
ROUTINE Page 2 of 16
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02A
ROUTINE Page 3 of 16
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02A

Rated data
Rated filling pressure for operation: 0.80 MPa(abs)

Check of rating plates Approved: clq

MECHANISM RESULTS

Resistance in ohms of auxiliary circuits


Description Mechanism No. Mechanism No. Mechanism No.
1361731593-02-A1
Closing coil 1 53
Opening coil 1 53
Opening coil 2 54
Antipumping relay 1 7750
Heater anticondense 687
Heater total 230

All resistances checked Approved clq


ROUTINE Page 4 of 16
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02A

Check of Approved
Wiring acc. To circuit diagram clq
Local/remote operation clq
Blocking relays clq
On-line-motor starter does not trip for 10 consecutive operations clq
Auxiliary contacts clq
Thermostat settings clq
Counter clq
All adjustments and paint marking clq

Settings
Description Unit Mech. 1 Mech. 2 Mech. 3
Thermostat °C 10.0
Closing spring charge ° 137.0
Trip spring setting mm 12.0

Approved: clq

Spring charge at nominal voltage


Description Unit Mech. 1 Mech. 2 Mech. 3
Charging time s 7.1
Motor current A 13.9

Approved: clq

Lowest operating voltage


Description Unit Mech. 1 Mech. 2 Mech. 3
Close coil 1 VDC 55
Trip coil 1 VDC 46
Trip coil 2 VDC 46

Approved: clq

Power frequency test of auxiliary circuits


1 second 50 Hz 2.5 kV Approved: clq
1 second 50 Hz 2.0 kV,motor Approved: clq
ROUTINE Page 5 of 16
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02A

POLE RESULTS

Resistance in main circuit


Phase Unit Part 1 Part 2
A µOhm 38
Approved: clq

Power frequency test


72 seconds 50 Hz breaking unit 460 kV Approved: clq
72 seconds 50 Hz to earth: 460 / kV Approved: clq

Overpressure test on each pole


10 minutes duration 1.15 MPa(abs) Approved: clq

Tightness test on each pole Approved: clq

OPERATING TEST

Test assumptions
Technical provision: 1HSB732008-11CN
Fill pressure: 0.80 MPa(abs)

Operations Voltage Motor Close 1 Close 2 Trip 1 Trip 2 Trip 3


level VDC VDC VDC VDC VDC VDC
5 Close and Open Min 94 94 77 77
5 Close and Open Max 121 121 121 121
5 Close and Open Nom 110 110 110 110
5 Close-Open Nom 110 110 110 110
5 Open-0.3s-Close Nom 110 110 110 110

Operating test
At least 25 operations as above Approved: clq
Stored energi test O – 0.3s- CO- 3min- CO Approved: -
ROUTINE Page 6 of 16
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02A

Test Samples
Oper. Oper. Volt Cc Tc Operation times Cont. Cont. Cont. Over Re- Damp Time
No. Level phase stroke speed speed travel bounce time difference
A B C 1 2 a b
ms ms ms mm m/s m/s mm mm ms ms ms
Close 5 Min. 1 - 28.4 159.6 7.4 2.9 3.3 1.8 1.5 -12.2
Open 6 Min. - 1 20.3 159.8 8.1 -4.8 14.0 16.7 -1.8 10.0
Close 15 Max. 1 - 26.9 159.7 7.5 2.8 3.2 1.9 1.5 -12.1
Open 16 Max. - 1 17.8 159.8 8.0 -4.7 14.1 16.7 -1.8 10.1
Close 25 Nom. 1 - 27.4 159.6 7.5 3.0 3.3 1.7 1.5 -12.1
Open 26 Nom. - 1 18.1 159.8 8.0 -5.1 14.2 16.7 -1.8 10.5
Open 40 Nom. - 2 18.0 159.8 8.1 -5.0 14.4 16.7 -1.8 10.2

Oper. Oper. Volt Cc Tc Interval times 1 Interval times 2 Time


No. Level phase phase difference
A B C A B C a b
ms ms ms ms ms ms ms
C-O 31 Nom. 1 1 26.3 1.6 -12.0
O-C 37 Nom. 1 1 259.3 -1.8 10.3
ROUTINE Page 7 of 16
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02A

Main Test sequence Close Min. Operation No 5

160

140 A1
1a

1b
120

100
mm

80

60

40

20

T1
0
2.5
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
94 VDC 94 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 28.4 (0.0 - 30.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 29.9 1.5 (0.0 - 8.0)
1b 16.2 -12.2
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 7.4 (7.2 - 7.6)
Travel speed 2 m/s 2.9
Contact Stroke mm 159.6 (157.0 - 163.0)
OverTravel mm 3.3
Rebounce mm 1.8
ROUTINE Page 8 of 16
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02A

Main Test sequence Open Min. Operation No 6

160 T1

140
A1
1a

120 1b

100
mm

80

60

40

20

2.5
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
94 VDC - 77 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 20.3 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 18.5 -1.8
1b 30.3 10.0
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.1 (8.0 - 8.7)
Contact Stroke mm 159.8 (157.0 - 163.0)
OverTravel mm -4.8 (-6.5 - 1.5)
Rebounce mm 14.0 (0.0 - 22.0)
Damping time ms 16.7
ROUTINE Page 9 of 16
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02A

Main Test sequence Close Max. Operation No 15

160

140 A1
1a

1b
120

100
mm

80

60

40

20

0 T1
2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
121 VDC 121 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 26.9 (0.0 - 30.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 28.4 1.5 (0.0 - 8.0)
1b 14.8 -12.1
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 7.5 (7.2 - 7.6)
Travel speed 2 m/s 2.8
Contact Stroke mm 159.7 (157.0 - 163.0)
OverTravel mm 3.2
Rebounce mm 1.9
ROUTINE Page 10 of 16
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02A

Main Test sequence Open Max. Operation No 16

160 T1

140
A1
1a

120 1b

100
mm

80

60

40

20

2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
121 VDC - 121 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 17.8 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 16.0 -1.8
1b 27.9 10.1
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.0 (8.0 - 8.7)
Contact Stroke mm 159.8 (157.0 - 163.0)
OverTravel mm -4.7 (-6.5 - 1.5)
Rebounce mm 14.1 (0.0 - 22.0)
Damping time ms 16.7
ROUTINE Page 11 of 16
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02A

Main Test sequence Close Nom. Operation No 25

160

140 A1
1a

1b
120

100
mm

80

60

40

20

0 T1
2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
110 VDC 110 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 27.4 (0.0 - 30.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 28.9 1.5 (0.0 - 8.0)
1b 15.3 -12.1
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 7.5 (7.2 - 7.6)
Travel speed 2 m/s 3.0
Contact Stroke mm 159.6 (157.0 - 163.0)
OverTravel mm 3.3
Rebounce mm 1.7
ROUTINE Page 12 of 16
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02A

Main Test sequence Open Nom. Operation No 26

160 T1

140
A1
1a

120 1b

100
mm

80

60

40

20

2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
110 VDC - 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 18.1 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 16.3 -1.8
1b 28.6 10.5
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.0 (8.0 - 8.7)
Contact Stroke mm 159.8 (157.0 - 163.0)
OverTravel mm -5.1 (-6.5 - 1.5)
Rebounce mm 14.2 (0.0 - 22.0)
Damping time ms 16.7
ROUTINE Page 13 of 16
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02A

Main Test sequence Close-Open Nom. Operation No 31

160

140
A1
1a

120 1b

100
mm

80

60

40

20

T1
0
2
1
A

Ic1
0

0 20 40 60 80 100 120 140 160 180 200 220 240


ms

Operation data
Motor Close coil 1 Trip coil 1
110 VDC 110 VDC 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 27.3 (0.0 - 30.0) 26.3 (23.0 - 29.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 28.9 23.7 1.6 (0.0 - 8.0)
1b 15.3 48.0 -12.0
ROUTINE Page 14 of 16
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02A

Main Test sequence Open-0.3s-Close Nom. Operation No 37

160 T1

140 A1
1a

120 1b

100
mm

80

60

40

20

0
2
1
A

Ic1
0

0 50 100 150 200 250 300 350 400


ms

Operation data
Motor Close coil 1 Trip coil 1
110 VDC 110 VDC 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 18.0 (15.0 - 19.0) 259.3
Aux. Contact time Close/Open Close/Open Aux-Main
1a 16.2 263.0 -1.8
1b 28.3 236.9 10.3
ROUTINE Page 15 of 16
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02A

Main Test sequence Open Nom. Operation No 40

160 T1

140
A1
1a

120 1b

100
mm

80

60

40

20

2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 2
110 VDC - 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 18.0 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 16.2 -1.8
1b 28.2 10.2
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.1 (8.0 - 8.7)
Contact Stroke mm 159.8 (157.0 - 163.0)
OverTravel mm -5.0 (-6.5 - 1.5)
Rebounce mm 14.4 (0.0 - 22.0)
Damping time ms 16.7
ROUTINE Page 16 of 16
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02A

Free Test Spring charge Nom. Mechanism No 1 Operation No 1


20

18

16

14

12

10
A

Im1
0

-2
0 1 2 3 4 5 6 7 8 9
s

Operation data
Motor Close coil 1 Trip coil -
110 VDC 110 VDC -

Spring charge for mechanism 1


Description Unit Result Limits
Charge current A 13.9
Charge time s 7.1
ROUTINE Page 1 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02B

Customer
HITACHI ENERGY PERU S.A.

Customer reference Country

Reference Project
502886514

Breaker type Serial number


LTB245E1 1361731593-02B

Mechanism type Serial number


BLK222 1361731593-02-B1

Standard Test completed


IEC62271-100 2023-08-03

We hereby certify that the above objects have passed all routine tests in accordance with the
standard referred to in above and with the terms of the contract.

Hitachi Energy High Voltage Switchgear Company


Limited,Beijing
Quality Department

........................................................... Date: ..03/08/2023.........................................

Test witnessed by

........................................................... .............................................................

........................................................... .............................................................
ROUTINE Page 2 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02B

Rated data
Rated filling pressure for operation: 0.80 MPa(abs)

Check of rating plates Approved: swq

MECHANISM RESULTS

Resistance in ohms of auxiliary circuits


Description Mechanism No. Mechanism No. Mechanism No.
1361731593-02-B1
Closing coil 1 52
Opening coil 1 52
Opening coil 2 51
Antipumping relay 1 7750
Extra relay 1 7820
Extra relay 2 7760
Extra relay 3 10980
Extra relay 4 10840
Density blocking relay 1 7840
Density blocking relay 2 8040
Heater anticondense 686
Heater total 230

All resistances checked Approved swq


ROUTINE Page 3 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02B

Check of Approved
Wiring acc. To circuit diagram swq
Local/remote operation swq
Blocking relays swq
Extra relays swq
On-line-motor starter does not trip for 10 consecutive operations swq
Auxiliary contacts swq
Thermostat settings swq
Counter swq
All adjustments and paint marking swq

Settings
Description Unit Mech. 1 Mech. 2 Mech. 3
Thermostat °C 10.0
Closing spring charge ° 135.0
Trip spring setting mm 10.0

Approved: swq

Spring charge at nominal voltage


Description Unit Mech. 1 Mech. 2 Mech. 3
Charging time s 7.8
Motor current A 13.9

Approved: swq

Lowest operating voltage


Description Unit Mech. 1 Mech. 2 Mech. 3
Close coil 1 VDC 64
Trip coil 1 VDC 43
Trip coil 2 VDC 52

Approved: swq

Power frequency test of auxiliary circuits


1 second 50 Hz 2.5 kV Approved: swq
1 second 50 Hz 2.0 kV,motor Approved: -
ROUTINE Page 4 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02B

POLE RESULTS

Resistance in main circuit


Phase Unit Part 1 Part 2
B µOhm 38
Approved: swq

Power frequency test


72 seconds 50 Hz breaking unit 460 kV Approved: swq
72 seconds 50 Hz to earth: 460 / kV Approved: swq

Overpressure test on each pole


10 minutes duration 1.15 MPa(abs) Approved: swq

Tightness test on each pole Approved: swq

OPERATING TEST

Test assumptions
Technical provision: 1HSB732008-11CN
Fill pressure: 0.80 MPa(abs)

Operations Voltage Motor Close 1 Close 2 Trip 1 Trip 2 Trip 3


level VDC VDC VDC VDC VDC VDC
5 Close and Open Min 94 94 77 77
5 Close and Open Max 121 121 121 121
5 Close and Open Nom 110 110 110 110
5 Close-Open Nom 110 110 110 110
5 Open-0.3s-Close Nom 110 110 110 110

Operating test
At least 25 operations as above Approved: swq
Stored energi test O – 0.3s- CO- 3min- CO Approved: -
ROUTINE Page 5 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02B

Test Samples
Oper. Oper. Volt Cc Tc Operation times Cont. Cont. Cont. Over Re- Damp Time
No. Level phase stroke speed speed travel bounce time difference
A B C 1 2 a b
ms ms ms mm m/s m/s mm mm ms ms ms
Close 5 Min. 1 - 29.3 160.1 7.4 2.9 2.9 1.3 1.9 -12.7
Open 6 Min. - 1 19.5 160.3 8.4 -4.2 15.3 44.3 -1.6 10.7
Close 15 Max. 1 - 27.4 0.0 0.0 0.0 0.0 0.0 1.9 -12.5
Open 16 Max. - 1 17.4 0.0 0.0 0.0 0.0 0.0 -1.6 10.9
Close 25 Nom. 1 - 27.8 160.2 7.4 2.9 2.8 1.3 1.9 -12.5
Open 26 Nom. - 1 17.7 160.1 8.3 -4.8 14.5 16.8 -1.6 11.0
Open 40 Nom. - 2 17.9 160.1 8.2 -5.1 16.5 45.9 -1.6 10.8

Oper. Oper. Volt Cc Tc Interval times 1 Interval times 2 Time


No. Level phase phase difference
A B C A B C a b
ms ms ms ms ms ms ms
C-O 31 Nom. 1 1 26.8 1.8 -12.4
O-C 37 Nom. 1 1 260.0 -1.6 10.9
ROUTINE Page 6 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02B

Main Test sequence Close Min. Operation No 5

160

140
B1
2a
120
2b

100
mm

80

60

40

20

T1
0
2.5
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
94 VDC 94 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
B1 29.3 (0.0 - 30.0)
Aux. Contact time Close/Open Close/Open Aux-Main
2a 31.2 1.9 (0.0 - 8.0)
2b 16.6 -12.7
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 7.4 (7.2 - 7.6)
Travel speed 2 m/s 2.9
Contact Stroke mm 160.1 (157.0 - 163.0)
OverTravel mm 2.9
Rebounce mm 1.3
ROUTINE Page 7 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02B

Main Test sequence Open Min. Operation No 6

T1
160

140

B1

120 2a
2b

100
mm

80

60

40

20

2.5
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
94 VDC - 77 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
B1 19.5 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
2a 17.9 -1.6
2b 30.2 10.7
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.4 (8.0 - 8.7)
Contact Stroke mm 160.3 (157.0 - 163.0)
OverTravel mm -4.2 (-6.5 - 1.5)
Rebounce mm 15.3 (0.0 - 22.0)
Damping time ms 44.3
ROUTINE Page 8 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02B

Main Test sequence Close Max. Operation No 15

160

140
B1
2a
120
2b

100
mm

80

60

40

20

0 T1
2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
121 VDC 121 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
B1 27.4 (0.0 - 30.0)
Aux. Contact time Close/Open Close/Open Aux-Main
2a 29.3 1.9 (0.0 - 8.0)
2b 14.9 -12.5
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 0.0 (7.2 - 7.6)
Travel speed 2 m/s 0.0
Contact Stroke mm 0.0 (157.0 - 163.0)
OverTravel mm 0.0
Rebounce mm 0.0
ROUTINE Page 9 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02B

Main Test sequence Open Max. Operation No 16

T1
160

140

B1

120 2a
2b

100
mm

80

60

40

20

2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
121 VDC - 121 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
B1 17.4 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
2a 15.8 -1.6
2b 28.3 10.9
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 0.0 (8.0 - 8.7)
Contact Stroke mm 0.0 (157.0 - 163.0)
OverTravel mm 0.0 (-6.5 - 1.5)
Rebounce mm 0.0 (0.0 - 22.0)
Damping time ms 0.0
ROUTINE Page 10 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02B

Main Test sequence Close Nom. Operation No 25

160

140
B1
2a
120
2b

100
mm

80

60

40

20

0 T1
2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
110 VDC 110 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
B1 27.8 (0.0 - 30.0)
Aux. Contact time Close/Open Close/Open Aux-Main
2a 29.7 1.9 (0.0 - 8.0)
2b 15.3 -12.5
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 7.4 (7.2 - 7.6)
Travel speed 2 m/s 2.9
Contact Stroke mm 160.2 (157.0 - 163.0)
OverTravel mm 2.8
Rebounce mm 1.3
ROUTINE Page 11 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02B

Main Test sequence Open Nom. Operation No 26

T1
160

140

B1

120 2a
2b

100
mm

80

60

40

20

2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
110 VDC - 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
B1 17.7 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
2a 16.1 -1.6
2b 28.7 11.0
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.3 (8.0 - 8.7)
Contact Stroke mm 160.1 (157.0 - 163.0)
OverTravel mm -4.8 (-6.5 - 1.5)
Rebounce mm 14.5 (0.0 - 22.0)
Damping time ms 16.8
ROUTINE Page 12 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02B

Main Test sequence Close-Open Nom. Operation No 31

160

140

B1

120 2a
2b

100
mm

80

60

40

20

T1
0
2
1
A

Ic1
0

0 20 40 60 80 100 120 140 160 180 200 220 240


ms

Operation data
Motor Close coil 1 Trip coil 1
110 VDC 110 VDC 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
B1 27.5 (0.0 - 30.0) 26.8 (23.0 - 29.0)
Aux. Contact time Close/Open Close/Open Aux-Main
2a 29.3 23.6 1.8 (0.0 - 8.0)
2b 15.1 48.7 -12.4
ROUTINE Page 13 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02B

Main Test sequence Open-0.3s-Close Nom. Operation No 37

T1
160

140
B1
2a
120
2b

100
mm

80

60

40

20

0
2
1
A

Ic1
0

0 50 100 150 200 250 300 350 400


ms

Operation data
Motor Close coil 1 Trip coil 1
110 VDC 110 VDC 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
B1 17.7 (15.0 - 19.0) 260.0
Aux. Contact time Close/Open Close/Open Aux-Main
2a 16.1 263.5 -1.6
2b 28.6 236.8 10.9
ROUTINE Page 14 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02B

Main Test sequence Open Nom. Operation No 40

T1
160

140

B1

120 2a
2b

100
mm

80

60

40

20

2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 2
110 VDC - 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
B1 17.9 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
2a 16.3 -1.6
2b 28.7 10.8
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.2 (8.0 - 8.7)
Contact Stroke mm 160.1 (157.0 - 163.0)
OverTravel mm -5.1 (-6.5 - 1.5)
Rebounce mm 16.5 (0.0 - 22.0)
Damping time ms 45.9
ROUTINE Page 15 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02B

Free Test Spring charge Nom. Mechanism No 2 Operation No 1


25

20

15
A

10

Im1
0

0 1 2 3 4 5 6 7 8 9
s

Operation data
Motor Close coil 1 Trip coil -
110 VDC 110 VDC -
Spring charge for mechanism 2
Description Unit Result Limits
Charge current A 13.9
Charge time s 7.8
ROUTINE Page 1 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02C

Customer
HITACHI ENERGY PERU S.A.

Customer reference Country

Reference Project
502886514

Breaker type Serial number


LTB245E1 1361731593-02C

Mechanism type Serial number


BLK222 1361731593-02-C1

Standard Test completed


IEC62271-100 8/3/2023

We hereby certify that the above objects have passed all routine tests in accordance with the
standard referred to in above and with the terms of the contract.

Hitachi Energy High Voltage Switchgear Company Limited,Beijing


Quality Department

........................................................... Date: 8/3/2023


clq

Test witnessed by

........................................................... .............................................................

........................................................... .............................................................

...........................................................
ROUTINE Page 2 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02C

Rated data
Rated filling pressure for operation: 0.80 MPa(abs)

Check of rating plates Approved: clq

MECHANISM RESULTS

Resistance in ohms of auxiliary circuits


Description Mechanism No. Mechanism No. Mechanism No.
1361731593-02-C1
Opening coil 1 53
Opening coil 2 54
Antipumping relay 1 7720
Heater anticondense 687
Heater total 231

All resistances checked Approved clq


ROUTINE Page 3 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02C

Check of Approved
Wiring acc. To circuit diagram clq
Local/remote operation clq
Blocking relays clq
On-line-motor starter does not trip for 10 consecutive operations clq
Auxiliary contacts clq
Thermostat settings clq
Counter clq
All adjustments and paint marking clq

Settings
Description Unit Mech. 1 Mech. 2 Mech. 3
Thermostat °C 10.0
Closing spring charge ° 135.0
Trip spring setting mm 12.0

Approved: clq

Spring charge at nominal voltage


Description Unit Mech. 1 Mech. 2 Mech. 3
Charging time s 7.9
Motor current A 13.6

Approved: clq

Lowest operating voltage


Description Unit Mech. 1 Mech. 2 Mech. 3
Close coil 1 VDC 64
Trip coil 1 VDC 52
Trip coil 2 VDC 46

Approved: clq

Power frequency test of auxiliary circuits


1 second 50 Hz 2.5 kV Approved: clq
1 second 50 Hz 2.0 kV,motor Approved: clq
ROUTINE Page 4 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02C

POLE RESULTS

Resistance in main circuit


Phase Unit Part 1 Part 2
C µOhm 36
Approved: clq

Power frequency test


72 seconds 50 Hz breaking unit 460 kV Approved: clq
72 seconds 50 Hz to earth: 460 / kV Approved: clq

Overpressure test on each pole


10 minutes duration 1.15 MPa(abs) Approved: clq

Tightness test on each pole Approved: clq

OPERATING TEST

Test assumptions
Technical provision: 1HSB732008-11CN
Fill pressure: 0.80 MPa(abs)

Operations Voltage Motor Close 1 Close 2 Trip 1 Trip 2 Trip 3


level VDC VDC VDC VDC VDC VDC
5 Close and Open Min 94 94 77 77
5 Close and Open Max 121 121 121 121
5 Close and Open Nom 110 110 110 110
5 Close-Open Nom 110 110 110 110
5 Open-0.3s-Close Nom 110 110 110 110

Operating test
At least 25 operations as above Approved: clq
Stored energi test O – 0.3s- CO- 3min- CO Approved: -
ROUTINE Page 5 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02C

Test Samples
Oper. Oper. Volt Cc Tc Operation times Cont. Cont. Cont. Over Re- Damp Time
No. Level phase stroke speed speed travel bounce time difference
A B C 1 2 a b
ms ms ms mm m/s m/s mm mm ms ms ms
Close 5 Min. 1 - 29.1 160.1 7.4 2.7 2.9 1.5 2.4 -11.7
Open 6 Min. - 1 21.5 160.2 8.0 -4.8 17.9 55.5 -2.6 9.9
Close 15 Max. 1 - 27.3 160.2 7.4 2.7 2.8 1.6 2.3 -11.8
Open 16 Max. - 1 18.1 160.2 8.0 -4.8 18.2 55.7 -2.5 10.1
Close 25 Nom. 1 - 27.8 160.2 7.3 2.6 2.7 1.6 2.4 -11.8
Open 26 Nom. - 1 18.6 160.3 8.0 -5.0 18.5 56.0 -2.6 10.2
Open 40 Nom. - 2 18.4 160.2 8.0 -4.8 18.4 56.2 -2.6 10.1

Oper. Oper. Volt Cc Tc Interval times 1 Interval times 2 Time


No. Level phase phase difference
A B C A B C a b
ms ms ms ms ms ms ms
C-O 31 Nom. 1 1 23.9 2.4 -11.8
O-C 37 Nom. 1 1 259.4 -2.6 10.3
ROUTINE Page 6 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02C

Main Test sequence Close Min. Operation No 5

160

140

C1
120 3a

3b

100
mm

80

60

40

20

T1
0
2.5
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
94 VDC 94 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
C1 29.1 (0.0 - 30.0)
Aux. Contact time Close/Open Close/Open Aux-Main
3a 31.5 2.4 (0.0 - 8.0)
3b 17.4 -11.7
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 7.4 (7.2 - 7.6)
Travel speed 2 m/s 2.7
Contact Stroke mm 160.1 (157.0 - 163.0)
OverTravel mm 2.9
Rebounce mm 1.5
ROUTINE Page 7 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02C

Main Test sequence Open Min. Operation No 6

T1
160

140

120 C1
3a
3b

100
mm

80

60

40

20

2.5
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
94 VDC - 77 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
C1 21.5 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
3a 18.9 -2.6
3b 31.4 9.9
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.0 (8.0 - 8.7)
Contact Stroke mm 160.2 (157.0 - 163.0)
OverTravel mm -4.8 (-6.5 - 1.5)
Rebounce mm 17.9 (0.0 - 22.0)
Damping time ms 55.5
ROUTINE Page 8 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02C

Main Test sequence Close Max. Operation No 15

160

140

C1
120 3a

3b

100
mm

80

60

40

20

0 T1
2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
121 VDC 121 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
C1 27.3 (0.0 - 30.0)
Aux. Contact time Close/Open Close/Open Aux-Main
3a 29.6 2.3 (0.0 - 8.0)
3b 15.5 -11.8
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 7.4 (7.2 - 7.6)
Travel speed 2 m/s 2.7
Contact Stroke mm 160.2 (157.0 - 163.0)
OverTravel mm 2.8
Rebounce mm 1.6
ROUTINE Page 9 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02C

Main Test sequence Open Max. Operation No 16

T1
160

140

120 C1
3a
3b

100
mm

80

60

40

20

2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
121 VDC - 121 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
C1 18.1 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
3a 15.6 -2.5
3b 28.2 10.1
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.0 (8.0 - 8.7)
Contact Stroke mm 160.2 (157.0 - 163.0)
OverTravel mm -4.8 (-6.5 - 1.5)
Rebounce mm 18.2 (0.0 - 22.0)
Damping time ms 55.7
ROUTINE Page 10 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02C

Main Test sequence Close Nom. Operation No 25

160

140

C1
120 3a

3b

100
mm

80

60

40

20

0 T1
2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
110 VDC 110 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
C1 27.8 (0.0 - 30.0)
Aux. Contact time Close/Open Close/Open Aux-Main
3a 30.2 2.4 (0.0 - 8.0)
3b 16.0 -11.8
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 7.3 (7.2 - 7.6)
Travel speed 2 m/s 2.6
Contact Stroke mm 160.2 (157.0 - 163.0)
OverTravel mm 2.7
Rebounce mm 1.6
ROUTINE Page 11 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02C

Main Test sequence Open Nom. Operation No 26

T1
160

140

120 C1
3a
3b

100
mm

80

60

40

20

2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
110 VDC - 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
C1 18.6 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
3a 16.0 -2.6
3b 28.8 10.2
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.0 (8.0 - 8.7)
Contact Stroke mm 160.3 (157.0 - 163.0)
OverTravel mm -5.0 (-6.5 - 1.5)
Rebounce mm 18.5 (0.0 - 22.0)
Damping time ms 56.0
ROUTINE Page 12 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02C

Main Test sequence Close-Open Nom. Operation No 31

160

140

120 C1
3a
3b
100
mm

80

60

40

20

T1
0
2
1
A

Ic1
0

0 20 40 60 80 100 120 140 160 180 200 220 240


ms

Operation data
Motor Close coil 1 Trip coil 1
110 VDC 110 VDC 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
C1 27.6 (0.0 - 30.0) 23.9 (23.0 - 29.0)
Aux. Contact time Close/Open Close/Open Aux-Main
3a 30.0 19.9 2.4 (0.0 - 8.0)
3b 15.8 45.2 -11.8
ROUTINE Page 13 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02C

Main Test sequence Open-0.3s-Close Nom. Operation No 37

T1
160

140

C1
120 3a

3b

100
mm

80

60

40

20

0
2
1
A

Ic1
0

0 50 100 150 200 250 300 350 400


ms

Operation data
Motor Close coil 1 Trip coil 1
110 VDC 110 VDC 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
C1 18.5 (15.0 - 19.0) 259.4
Aux. Contact time Close/Open Close/Open Aux-Main
3a 15.9 264.4 -2.6
3b 28.8 237.1 10.3
ROUTINE Page 14 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02C

Main Test sequence Open Nom. Operation No 40

T1
160

140

120 C1
3a
3b

100
mm

80

60

40

20

2
1
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 2
110 VDC - 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
C1 18.4 (15.0 - 19.0)
Aux. Contact time Close/Open Close/Open Aux-Main
3a 15.8 -2.6
3b 28.5 10.1
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 8.0 (8.0 - 8.7)
Contact Stroke mm 160.2 (157.0 - 163.0)
OverTravel mm -4.8 (-6.5 - 1.5)
Rebounce mm 18.4 (0.0 - 22.0)
Damping time ms 56.2
ROUTINE Page 15 of 15
TEST REPORT
Breaker LTB245E1 Order No: 502886514
Mechanism: BLK222 Serial No: 1361731593-02C

Free Test Spring charge Nom. Mechanism No 3 Operation No 1


20

18

16

14

12

10
A

Im1
0

-2
0 1 2 3 4 5 6 7 8 9 10
s

Operation data
Motor Close coil 1 Trip coil -
110 VDC 110 VDC -

Spring charge for mechanism 3


Description Unit Result Limits
Charge current A 13.6
Charge time s 7.9