Professional Documents
Culture Documents
CONSULTANT
CONTRACTOR
VENDOR
CONTRACT NO.
EEP/33.20/58/14
DOCUMENT NAME
E. Mechanical drawings
- Outline drawing
- Foundation drawing
- Shipping drawing
Application Outdoor
Rated(Ur) 230 kV
Rated
voltage
Rating Max. continuous(Um) 245 kV (106.5% of rated voltage)
B.S.L 850 kV
B.I.L
Applied voltage 38 kV
Characteristics Induced voltage(P-G)
240(1.8xUr/√3)/210 kV (1.58xUr/√3)
(Enhancement/1hour)
3918.5 Ohm (13.5 MVAR)
Reactance (at rated voltage) 3206.1 Ohm (16.5 MVAR)
(Tolerance ±5% as per IEC60076-6 std.)
Load Losses at rated voltage 54 kW (230kV 16.5MVAR)
(Tolerance +10% as per IEC60076-6
(75℃ reference temp.)
std.)
Load loss at 75°G, at nominal tap position and rated voltage, KW N/A
Total loss
54 (at 230kV
Load loss at 75°G & at tap position for maximum (+10%) voltage, KW 16.5MVAR, 75°C)
(tolerance follow as per
IEC std)
Load loss at 75°G & at tap position for minimum voltage (-10%), KW N/A
Construction of core.
a) With/without core With core With core
with magnetic return
b) With/without magnetic return without magnetic return
(3ph 5legs)
Air' gaps in magnetic circuit
a) Material used for gaps Marble or Ceramic
b) Number of Individual gaps 8EA
c) Length of individual gaps, mm 10~40mm
2
flux density distributions W/mm 1.33 <1.33(Bundle)
Impulse test voltage full wave 1.2/50 micro sec. 1050 1050
460
Power frequency withstand voltage, 1min, kV 460
(Not test value)
< 70 Rev.B
Noise level at rated conditions (distance of 3m), dBA < 70
(at 230kV 16.5MVAR)
RMS Symmetrical short circuit at 230kV terminals, KA 40 40
Type of tap changer used for overload conditions off load tap changer off load tap changer
Number of no-Load tap-changer positions 3 (±1) 3(+/-1)
Range of no-load tap-change positions, % ± 10% +/- 10%
Bushing
a) 230kV bushing
1) Manufacturer TRENCH (FRANCE)
b) Type OIP
Max. residual voltage with current wave of (30/70 micro sec.) at 1kA (kV) > 40.4 > 40
Energy capability
a) line discharge class (IEC) 2 2
b) 2 impulses, as per IEC 99-4, kJ/kV, Ur 8
c) Pressure relief withstand 50kA
Standards applied IEC 600994 IEC 60099-4
Weights
a) Core and windings. kg 30200
b) Oil kg 22000
22800
c) Tank without heat exchanger. kg (excluding Radiator
2000)
d) Total weight of shunt reactor with oil and including
77000
all acessories, ready for commissioning kg
e) Transport weight of heaviest part, kg 47900
Dimensions Overall dimension
a) Length (mm) 7580
b) Width (mm) 5140 Rev.C
c) Height (mm) 8540
Note :- The filled guaranteed data for shunt reactor should be proven by attaching the catalogue of the proposed
type of shunt reactor.
TBA01022G
4. Grounding Bushing 2 sets TY Tech / KOREA
1.2kV 30kV BIL
MT-ST160, Compact type
5. Winding Temperature Indicator 1 Set MESSKO / GERMANY
(4 contact)
MT-ST160, Compact type
6. Oil Temperature Indicator 1 Set MESSKO / GERMANY
(4 contact)
XPRD, 12 PSI
7. PRD 1 Set QUALITROL / U.S.A
(2 contact : Alarm / Trip)
Buchholz Relay Double float type
8. 1 Set EMB / GERMANY
with gas sampling device (2 contact : Alarm / Trip)
DIAL Type
9. Oil Level Gauge 1 Set TAIJIN / KOREA
(1 contact : Low level alarm)
10 Air Seal Cell Rubber Bag RB-2000 type 1 Set HANSOL / KOREA
General specifications
Altitude 1300 m Mounting angle (from vertical) 30 °
Length under flange L1 984 mm Product information 44497672E
CT length L4 300 mm IEC 60137-2017
Standard
Temperature range -30 +40 °C -
Electrical specifications
Rated lightning impulse withstand voltage (BIL) 1200 kV Rated highest voltage for equipment (Um) 245 kV
Rated current (Ir) 1000 A Phase to earth voltage 142 kV
Rated short-circuit current (Ith) 31,5 kA 3s Power frequency withstand voltage (AC) dry 505 kV
Dry switching impulse withstand voltage (SIL dry) 850 kV wet 460 kV
Rated frequency 50/60 Hz
Head
Oil level indicator type Optical
Insulator
Cantilever test load 500 daN
Insulator material Brown porcelain
Arcing distance AD 2400 mm
Creepage distance 9300 mm
USCD (IEC 60815) 53,7 mm/kV
Flange
Flange Round 12xø22 BCD 400 mm
Other
Standard sparkgaps
TECHNICAL DATASHEET 41431108 V1
General specifications
Altitude 2000 m Mounting angle (from vertical) 30 °
Length under flange L1 640 mm Product information 44497653E
CT length L4 500 mm IEC 60137-2017
Standard
Temperature range -30 +40 °C -
Electrical specifications
Rated lightning impulse withstand voltage (BIL) 250 kV Rated highest voltage for equipment (Um) 52 kV
Rated current (Ir) 800 A Phase to earth voltage 30 kV
Rated short-circuit current (Ith) 25 kA 3s Power frequency withstand voltage (AC) dry 105 kV
wet 95 kV
Rated frequency 50/60 Hz
Head
Oil level indicator type Optical
Insulator
Cantilever test load 200 daN
Insulator material Brown porcelain
Arcing distance AD 515 mm
Creepage distance 1612 mm
USCD (IEC 60815) 53,7 mm/kV
Flange
Flange Round 6xø16 BCD 185 mm
1. Scope
2. Surface pre-treatment
3. Application of Coatings
4. Inspection
(1) Coating Materials
(2) Environmental Conditions
(3) Surface Preparation
(4) Coating adhesion test
(5) Visual test
5. Painting Specification
1. Scope
This document shows the procedure of HYOSUNG’s Painting System. This painting procedure is written based on
ISO12944 standard, SSPC standard.
2. Surface pre-treatment
(2) Hand Tool Cleaning (SSPC-SP2) & Power Tool Cleaning (SSPC-SP3)
The Hand Tool Cleaning or Power Tool Cleaning is applied where blasting is not possible and repairs are
required.
- Hand Tool Cleaning: Use hand wire brushing, hand abrading, hand scraping, or other similar non-impact
methods to remove all loose mill scale, all loose or non-adherent rust, and all loose paint.
- Power Tool Cleaning: Use power wire brushing, power abrading, power impact, or other power rotary
tools to remove all loose mill scale, all loose or non-adherent rust, and all loose paint.
After surface pre-treatment, clean surface by wiping with a clean cloth dampened with solvent.
If, as the result of sanding, bare metal is exposed restore the finish system pretreatment and primer using
approved touch-up procedures.
(5) Brush-Off Blast Cleaning of Coated and Uncoated Galvanized Steel, Stainless Steel and
Non-Ferrous Metals (SSPC SP16)
After blasting, the surface shall be free of all visible oil, grease, dirt, dust, loose mill scale, loose rust, loose
paint. Bare metal substrates shall have a minimum 19 microns (0.75 mil) of uniform surface profile.
3. Application of Coatings
(1) Oil, grease, salt deposits, soil dust, or foreign matter deposited on the surface after surface preparation has
been completed shall be removed prior to painting. If rusting occurs after completion of surface preparation,
the surface shall be re-cleaned in accordance with the original method
(2) Painting shall be carried out in an atmosphere where relative humidity is less than 85 %.
(No application if the difference between the steel surface temperature and Dew Point is less than 3℃.)
(4) Paint shall not be force dried so as to cause checking, wrinkling, blistering, pore formation, or any condition
detrimental to its appearance. Newly painted surfaces shall be protected to the fullest extent feasible from rain,
condensation, contamination, snow, and freezing until the coating has dried.
(5) Spot repairs shall be carried out such that the patch painting extends at least 25 mm beyond the damaged
areas. Spot repairs shall reinstate each of the previous coats and shall commence directly after surface
preparation.
(6) Paints containing metallic lead, or zinc shall not be used to overcoat stainless steel materials.
4. Inspection
<Fig.1 Grooved surface> <Fig.2 Without groove surface> <Fig.3 Manhole cover>
Description Outside
Surface treatment SSPC-SP10
Type of paint Epoxy
1st Coating Dry film thickness 80 ㎛
(Primer) Color Red Brown
Paint product name Jotacote F60
Paint manufacturer JOTUN
NOTES:
C B A
395
125
320 204
"A"
A B C
278
267
497
439
680
335 VIEW "A"
418
DETAIL OF CORE & CORE CLAMP GROUNDING
N
REFERENCE DRAWINGS
REV.NO. DRAWING NAME DRAWING NO.
ALL BOLTING JOINTS ARE PROPERLY
GROUNDED
PROJECT NAME
SOUTHERN EXTENSION OF THE NATIONAL ELECTRICITY
GRID POWER TRANSMISSION PROJECT UNDER EDCF
CLIENT
HYOSUNG HEAVY
INDUSTRIES
SUBSTATION NAME
DWG. NAME
FRONT VIEW OUTLINE DRAWING
DWG. NO. SHT. NO. E-1
LEFT VIEW EEP-SENEG-SH-SS-12-TS01
REV. NO. C
KEYPLAN
M30
90
45 45 2-M12 TAP
420 420 100
210 210 210 210
25
400
190
150
50
315
400
25
125
20
12
150
2. DIMENSION TOLERANCE : ± 5%
DETAIL DESIGN.
2336 2670
WHEEL LEGEND & ABBREVIATIONS
1834 1834 FIG-1
1475 1475
200 1065 1065 200 4-JACKING POSITION
POSITION FOR
XPRD PIPE TR CENTER 625
400
CENTRE OF CONTROL
1295
1095
1079
REFERENCE DRAWINGS
RAIL GAGUE=1500
2190
TR CENTER
971
1079
1095
1295
RAIL
FIG-2
400
750 750
RAIL GAUGE=1500
C 19.06.2023 REVISED BY COMMENT J.H.CHOI Y.C.CHOI Y.C.CHOI E.J.HONG
4095
B 07.04.2023 REVISED BY COMMENT J.H.CHOI Y.C.CHOI Y.C.CHOI E.J.HONG
CONTRACTOR
HYOSUNG HEAVY
INDUSTRIES
VENDOR
HYOSUNG HEAVY
INDUSTRIES
SUBSTATION NAME
DWG. NAME
(RAIL ℄-℄) 1600
FOUNDATION DRAWING
400 965 965 400
DWG. NO. SHT. NO. E-2
EEP-SENEG-SH-SS-12-TS01
REV. NO. C
KEYPLAN
NOTES:
REFERENCE DRAWINGS
REV.NO. DRAWING NAME DRAWING NO.
4000
161 66 C 19.06.2023 REVISED BY COMMENT J.H.CHOI Y.C.CHOI Y.C.CHOI E.J.HONG
1722
CONSULTANT
HYOSUNG HEAVY
INDUSTRIES
VENDOR
HYOSUNG HEAVY
INDUSTRIES
SUBSTATION NAME
2015 1500 2400 3100
SHIGDAN 230/132/33kV Substation
3515
5500 CLIENT DWG. NO.
UNIT
CONTRACT NO.
EEP/33.20/58/14 SCALE
DWG. NAME
SHIPPING DRAWING
DWG. NO. SHT. NO. E-3
EEP-SENEG-SH-SS-12-TS01
REV. NO. C
KEYPLAN
NOTES:
C B A
A B C
TOP VIEW
350
BACK VIEW
B
A C REFERENCE DRAWINGS
REV.NO. DRAWING NAME DRAWING NO.
HYOSUNG HEAVY
500 INDUSTRIES
VENDOR
HYOSUNG HEAVY
INDUSTRIES
SUBSTATION NAME
CONTRACT NO.
EEP/33.20/58/14 SCALE
DWG. NAME
10
THREE PHASE NOTES:
SHUNT REACTOR
REFERENCE DRAWINGS
500
REV.NO. DRAWING NAME DRAWING NO.
VECTOR GROUP
YN
HYOSUNG HEAVY
INDUSTRIES
VENDOR
HYOSUNG HEAVY
INDUSTRIES
SUBSTATION NAME
CONTRACT NO.
EEP/33.20/58/14 SCALE
10 10 DWG. NAME
300 RATING PLATE DRAWING
DWG. NO. SHT. NO. E-5
EEP-SENEG-SH-SS-12-TS01
REV. NO. C
F. LCP Schematic drawings