You are on page 1of 37

Manufacturing Drawing and Document for

230 kV 13.5~16.5MVAR Shunt Reactors,


for Shigdan 230/132/33kV Substation

C 26-06-2023 ISSUED FOR APPROVAL J.H CHOI D.H.KIM DYKIM KWKIM

B 13-04-2023 ISSUED FOR APPROVAL J.H CHOI D.H.KIM DYKIM KWKIM


A 14-03-2023 ISSUED FOR APPROVAL J.H CHOI D.H.KIM DYKIM KWKIM
REV.NO. DATE DESCRIPTION DSN CHKD RVD APPD
PROJECT NAME

SOUTHERN EXTENSION OF THE NATIONAL ELECTRICITY GRID POWER


TRANSMISSION PROJECT UNDER EDCF
CLIENT

CONSULTANT

CONTRACTOR

VENDOR

SUBSTATION / TRANSMISSION LINE NAME

Shigdan 230/132/33 kV Substation


CLIENT DOC. NO.

CONTRACT NO.

EEP/33.20/58/14
DOCUMENT NAME

Manufacturing Drawing and Document


DOCUMENT NO. SHT. NO 01/37
EEP-SENEG-SH-SS-12-TS01 REV. NO C
CONTENTS

A. Shunt Reactor Specification

B. Technical Data Sheet

C. Shunt Reactor Bill of Materials

- HV Bushing Drwaing and specification

- HVN Bushing Drwaing and specification

D. Shunt Reactor- Painting specification.

E. Mechanical drawings

- Outline drawing

- Foundation drawing

- Shipping drawing

- Valve Location Plate drawing

- Rating Plate drawing

F. LCP Schematic drawings


A. Shunt Reactor Specification
HYOSUNG REF No. : 10230795_0015,16 (Rev.C)

A. SHUNT REACTOR SPECIFICATION

Application Outdoor

Applicable standards IEC Standard


General
Ambient temp. Max. 40℃, Avg. 30℃, Min. -0℃
Service
condition
Altitude Below 1,000meter above sea level Rev.B
Oil Immersed
Shunt Reactor type
3-ph 5-legs/ Gapped Core type
MVA Rating 13.5 ~ 16.5 MVAR

Phase/Rated frequency 3 phases / 50Hz

Rated(Ur) 230 kV
Rated
voltage
Rating Max. continuous(Um) 245 kV (106.5% of rated voltage)

Tap Steps ±1 (Total 3 position)

Tap changing method DETC(De-Energized Tap Changer)

Cooling class ONAN

Connection Wye with Neutral brought out

Top oil temp. rise 50K at 106.5% of rated voltage


Temp rise
Limits(K)
Avg. Winding temp. rise 55K at 106.5% of rated voltage

B.I.L (Line/Neutral) 1050 / 95 kV

B.S.L 850 kV
B.I.L
Applied voltage 38 kV
Characteristics Induced voltage(P-G)
240(1.8xUr/√3)/210 kV (1.58xUr/√3)
(Enhancement/1hour)
3918.5 Ohm (13.5 MVAR)
Reactance (at rated voltage) 3206.1 Ohm (16.5 MVAR)
(Tolerance ±5% as per IEC60076-6 std.)
Load Losses at rated voltage 54 kW (230kV 16.5MVAR)
(Tolerance +10% as per IEC60076-6
(75℃ reference temp.)
std.)

Sound Pressure level (dB) < 70 dB at 230kV 16.5MVAR

Oil preservation system Air seal cell Conservator

Construction HV Tank cover


Bushing
Location
HVN Tank cover

Printed in KOREA 2023


B. Technical Data Sheet
Southern Extension of the National Electricity B_4_Part-1_SE_4_Schedule_K_Technical_particula_SR_Rev.C(230620).xls
Grid Power Transmission Project

Schedule K - Technical Particular and Guarantee - Substation

5. Shunt Reactor (230KV, 15MVar)

Description Required Guaranteed


Manufacturer HYOSUNG
Type OIL IMMERSED
Standard applied IEC 60076-6
Method of cooling ONAN ONAN
Installation Outdoor Outdoor
Rated voltage (kV) 230 230
Maximum allowable continuous voltage (kV) 245 245
Rated Frequency, Hz 50 50
Rated current (A) 37.7 37.7 (@15MVAR)
Min 13.5MVAR
Rated power Mvar 15 Rated. 15MVAR
Max. 16.5MVAR
Connection of winding YN YN
Number of Phases 3 3

Load loss at 75°G, at nominal tap position and rated voltage, KW N/A
Total loss
54 (at 230kV
Load loss at 75°G & at tap position for maximum (+10%) voltage, KW 16.5MVAR, 75°C)
(tolerance follow as per
IEC std)

Load loss at 75°G & at tap position for minimum voltage (-10%), KW N/A

Construction of core.
a) With/without core With core With core
with magnetic return
b) With/without magnetic return without magnetic return
(3ph 5legs)
Air' gaps in magnetic circuit
a) Material used for gaps Marble or Ceramic
b) Number of Individual gaps 8EA
c) Length of individual gaps, mm 10~40mm
2
flux density distributions W/mm 1.33 <1.33(Bundle)
Impulse test voltage full wave 1.2/50 micro sec. 1050 1050
460
Power frequency withstand voltage, 1min, kV 460
(Not test value)
< 70 Rev.B
Noise level at rated conditions (distance of 3m), dBA < 70
(at 230kV 16.5MVAR)
RMS Symmetrical short circuit at 230kV terminals, KA 40 40
Type of tap changer used for overload conditions off load tap changer off load tap changer
Number of no-Load tap-changer positions 3 (±1) 3(+/-1)
Range of no-load tap-change positions, % ± 10% +/- 10%
Bushing
a) 230kV bushing
1) Manufacturer TRENCH (FRANCE)
b) Type OIP

BYUCKSAN POWER Co., Ltd. _______________________________________


Tenderer's stamp and signature 1 - 1/3
Southern Extension of the National Electricity B_4_Part-1_SE_4_Schedule_K_Technical_particula_SR_Rev.C(230620).xls
Grid Power Transmission Project

Schedule K - Technical Particular and Guarantee - Substation

5. Shunt Reactor (230KV, 15MVar)

Description Required Guaranteed


c) Rated current, A 1000
d) Rated voltage. kV 245
e) Power frequency test voltage, kV 460 505(Dry) / 460(Wet)
f) Impulse test voltage, kV 1200 1200
g) Creepage distance, mm 31mm/kVRev.B
APAR/INDIA
Shell DJALA B or Shell
Type and quality of oil 1020-60U(Uninhibited)
DIALAB eqauivalent
24400 Liters
Current Transformer (built-in 230kV bushings)
a) Manufacturer HYOSUNG
b) Type BCT

c) Ratio 50-100/1/1A 200-400/1ARev.C

d) Accuracy for metering core 0.5 - Rev.C


e) Accuracy for protection core 10P10 PX Class Rev.C
f) Burden (metering core I protection core) 15VA - Rev.C

g) Number of cores 2 2Rev.C

Current Transformer (neutral point)


a) Manufacturer ITL / U.K Rev.C
b) Type EXTERNALRev.C

c) Ratio 50-100/1/1A 100-50/1A

d) Accuracy 10P10 PX Class Rev.C


e) Burden (metering core I protection core) 15VA - Rev.C
f) Number of cores 2 2
Integrated Lighting Arrestor
Refer to Proposed
Manufacturer
Manufactures
Refer to Proposed
Country of Origin
Manufactures
Refer to Proposed
Type
Manufactures
Insulation material As per Spec
Installation outdoor outdoor
Nominal system voltage (kV) 230 230
Highest system voltage (kV) 245 245
Rated voltage of arrestor (kV), Ur 198 198
TOV capability : for 1 second, kVrms > 228 > 228
for 10 second, kVrms > 214 > 214
Max. permissible line to ground voltage (kV) 158 > 158
Rated frequency (Hz) 50 50
Power frequency withstand voltage, 1min., kV 460 460

BYUCKSAN POWER Co., Ltd. _______________________________________


Tenderer's stamp and signature 1 - 2/3
Southern Extension of the National Electricity B_4_Part-1_SE_4_Schedule_K_Technical_particula_SR_Rev.C(230620).xls
Grid Power Transmission Project

Schedule K - Technical Particular and Guarantee - Substation

5. Shunt Reactor (230KV, 15MVar)

Description Required Guaranteed


Impulse voltage (1.2/50 microsecond) (kV) 1050 1050
Residual voltage at 8/20 microsecond and at 10kA, (kV) > 475 475
Rated discharge current (kA) 10 10
Maximum discharge current (kA) > 40 > 40
Creepage distance (mm) 31mm/kV 31mm/kVRev.B
Overall dimensions (mm) (height) 2910
Overall weight (kg) 325

Max. residual voltage with current wave of (30/70 micro sec.) at 1kA (kV) > 40.4 > 40

Energy capability
a) line discharge class (IEC) 2 2
b) 2 impulses, as per IEC 99-4, kJ/kV, Ur 8
c) Pressure relief withstand 50kA
Standards applied IEC 600994 IEC 60099-4
Weights
a) Core and windings. kg 30200
b) Oil kg 22000
22800
c) Tank without heat exchanger. kg (excluding Radiator
2000)
d) Total weight of shunt reactor with oil and including
77000
all acessories, ready for commissioning kg
e) Transport weight of heaviest part, kg 47900
Dimensions Overall dimension
a) Length (mm) 7580
b) Width (mm) 5140 Rev.C
c) Height (mm) 8540

Note :- The filled guaranteed data for shunt reactor should be proven by attaching the catalogue of the proposed
type of shunt reactor.

BYUCKSAN POWER Co., Ltd. _______________________________________


Tenderer's stamp and signature 1 - 3/3
C. Shunt Reactor-Bill of Materials
HYOSUNG REF No. : 10230795_0015,16 (Rev.C)

C. SHUNT REACTOR – BILL OF MATERIALS

NO. ITEM TYPE Q'TY MAKER


OIP type, COT 1200-1000
245kV, 1200kV BIL, 1000A
1. HV Bushing (Oil to Air) 3 Sets TRENCH / FRANCE
Oil to Air, Angle Mounting
With Arcing horns & Creepage 9300mm
OIP type, COT 250-800
52kV, 250kV BIL, 800A
2. HVN Bushing (Oil to Air) 1 Set TRENCH / FRANCE
Oil to Air, Vertical Mounting
With Arcing horns & Creepage 1612mm

3. De-Energized Tap Changer A TYPE 1 Set SUNGLIM / KOREA

TBA01022G
4. Grounding Bushing 2 sets TY Tech / KOREA
1.2kV 30kV BIL
MT-ST160, Compact type
5. Winding Temperature Indicator 1 Set MESSKO / GERMANY
(4 contact)
MT-ST160, Compact type
6. Oil Temperature Indicator 1 Set MESSKO / GERMANY
(4 contact)
XPRD, 12 PSI
7. PRD 1 Set QUALITROL / U.S.A
(2 contact : Alarm / Trip)
Buchholz Relay Double float type
8. 1 Set EMB / GERMANY
with gas sampling device (2 contact : Alarm / Trip)
DIAL Type
9. Oil Level Gauge 1 Set TAIJIN / KOREA
(1 contact : Low level alarm)
10 Air Seal Cell Rubber Bag RB-2000 type 1 Set HANSOL / KOREA

11 BREATHER Silica-gel Type 1 Set TAIJIN / KOREA

12 Radiator Wide fin Type 1 Lot HYOSUNG / KOREA

13 Insulation Oil TO 1020-60U (Uninhibited type) 1 Lot APAR / INDIA

14 Mechanical Impact Recorder RM-3WE 1 Set Impact Register / U.S.A

15 Digital Impact Recorder RD298 1 Set Lamerholm Electronics/UK

Printed in KOREA 2022


TECHNICAL DATASHEET 41431070 V1

Bushing Type OIL/AIR COT 1200-1000 L300

Connection type Cable

General specifications
Altitude 1300 m Mounting angle (from vertical) 30 °
Length under flange L1 984 mm Product information 44497672E
CT length L4 300 mm IEC 60137-2017
Standard
Temperature range -30 +40 °C -

Electrical specifications
Rated lightning impulse withstand voltage (BIL) 1200 kV Rated highest voltage for equipment (Um) 245 kV
Rated current (Ir) 1000 A Phase to earth voltage 142 kV
Rated short-circuit current (Ith) 31,5 kA 3s Power frequency withstand voltage (AC) dry 505 kV
Dry switching impulse withstand voltage (SIL dry) 850 kV wet 460 kV
Rated frequency 50/60 Hz

Routine tests (Up to 1000m)


Measurement of dielectric dissipation factor and capacitance at ambient temperature 182/300 kV
Measurement of partial discharge quantity 10Pc 300 kV
Dry lightning impulse voltage withstand test 1260 kV
Dry power-frequency voltage withstand test 50 Hz 60s 505 kV
Test tap 2 kV
Voltage withstand test
Voltage tap - kV
Tightness test 1,5 barg
Top Terminal (air side)
Flat pad Aluminium 100x100 4xø14,5 / 44.5x44.5 Thickness 15 mm

Head
Oil level indicator type Optical

Insulator
Cantilever test load 500 daN
Insulator material Brown porcelain
Arcing distance AD 2400 mm
Creepage distance 9300 mm
USCD (IEC 60815) 53,7 mm/kV

Flange
Flange Round 12xø22 BCD 400 mm

Draw lead stud


Standard draw lead stud drilling ø8x35 Lemb 2.750 (mm)

Other
Standard sparkgaps
TECHNICAL DATASHEET 41431108 V1

Bushing Type OIL/AIR COT 250-800 L500

Connection type Cable

General specifications
Altitude 2000 m Mounting angle (from vertical) 30 °
Length under flange L1 640 mm Product information 44497653E
CT length L4 500 mm IEC 60137-2017
Standard
Temperature range -30 +40 °C -

Electrical specifications
Rated lightning impulse withstand voltage (BIL) 250 kV Rated highest voltage for equipment (Um) 52 kV
Rated current (Ir) 800 A Phase to earth voltage 30 kV
Rated short-circuit current (Ith) 25 kA 3s Power frequency withstand voltage (AC) dry 105 kV
wet 95 kV
Rated frequency 50/60 Hz

Routine tests (Up to 1000m)


Measurement of dielectric dissipation factor and capacitance at ambient temperature 32/52 kV
Measurement of partial discharge quantity 10Pc 52 kV
Dry lightning impulse voltage withstand test - kV
Dry power-frequency voltage withstand test 50 Hz 60s 105 kV
Test tap 2 kV
Voltage withstand test
Voltage tap - kV
Tightness test 1,5 barg
Top Terminal (air side)
Flat pad Aluminium 100x100 4xø14,5 / 44.5x44.5 Thickness 15 mm

Head
Oil level indicator type Optical

Insulator
Cantilever test load 200 daN
Insulator material Brown porcelain
Arcing distance AD 515 mm
Creepage distance 1612 mm
USCD (IEC 60815) 53,7 mm/kV

Flange
Flange Round 6xø16 BCD 185 mm

Draw lead stud


Standard draw lead stud drilling ø8x35 Lemb 760 (mm)
D. Shunt Reactor- Painting specification
CONTENTS

1. Scope

2. Surface pre-treatment

(1) Solvent Cleaning (SSPC-SP1)


(2) Hand Tool Cleaning (SSPC-SP2) & Power Tool Cleaning (SSPC-SP3)
(3) Near-White Blast Cleaning (SSPC-SP10)
(4) Pickling (SSPC-SP8)
(5) Brush-Off Blast Cleaning of Coated and Uncoated Galvanized Steel, Stainless Steel and
Non-Ferrous Metals (SSPC SP16)

3. Application of Coatings

4. Inspection
(1) Coating Materials
(2) Environmental Conditions
(3) Surface Preparation
(4) Coating adhesion test
(5) Visual test

5. Painting Specification
1. Scope

This document shows the procedure of HYOSUNG’s Painting System. This painting procedure is written based on
ISO12944 standard, SSPC standard.

2. Surface pre-treatment

(1) Solvent Cleaning (SSPC-SP1)


The removal of foreign matter (oil, grease, soil, drawing and cutting compounds, and other contaminants)
from a surface by the use of solvents, emulsions, cleaning compounds, steam cleaning, or similar materials
and methods that involve a solvent or cleaning action.
Prior to solvent cleaning, soil, cement spatter, salts, or other foreign matter (other than grease or oil) shall be
removed using a stiff fiber brush or wire brush, or by scraping.

(2) Hand Tool Cleaning (SSPC-SP2) & Power Tool Cleaning (SSPC-SP3)
The Hand Tool Cleaning or Power Tool Cleaning is applied where blasting is not possible and repairs are
required.

- Hand Tool Cleaning: Use hand wire brushing, hand abrading, hand scraping, or other similar non-impact
methods to remove all loose mill scale, all loose or non-adherent rust, and all loose paint.

- Power Tool Cleaning: Use power wire brushing, power abrading, power impact, or other power rotary
tools to remove all loose mill scale, all loose or non-adherent rust, and all loose paint.

After surface pre-treatment, clean surface by wiping with a clean cloth dampened with solvent.
If, as the result of sanding, bare metal is exposed restore the finish system pretreatment and primer using
approved touch-up procedures.

(3) Near-White Blast Cleaning (SSPC-SP10)


After blasting, the surface shall be free of oil, grease, dirt, mill scale, rust, corrosion products, oxides, paint,
or other foreign matter. Exceptions to this rule include light shadows or streaks or slight discolorations
caused by rust stain; mill scale; oxides; or thin, tight residues of paint or coating that may remain.
At least 95 percent of the surface area shall be free of all visible residues; the remainder shall be limited to
the slight discolorations noted above. SSPC VIS 1 (Sa 2 1/2) and the equivalent Swedish standards provide
a visual reference for comparison.
· Blast cleaning shall be carried out in an atmosphere where relative humidity is less than 85 %.
· All surfaces that are blast cleaned shall be coated with a primer coat within 8 hours.
· The surface roughness should not exceed a maximum of 100 ㎛ at least 40 ㎛.

(4) Pickling (SSPC-SP8)


Pickling is a method of preparing steel surfaces by chemical reaction, electrolysis, or both. The surfaces
when viewed without magnification shall be free of all visible mill scale and rust

(5) Brush-Off Blast Cleaning of Coated and Uncoated Galvanized Steel, Stainless Steel and
Non-Ferrous Metals (SSPC SP16)
After blasting, the surface shall be free of all visible oil, grease, dirt, dust, loose mill scale, loose rust, loose
paint. Bare metal substrates shall have a minimum 19 microns (0.75 mil) of uniform surface profile.
3. Application of Coatings

(1) Oil, grease, salt deposits, soil dust, or foreign matter deposited on the surface after surface preparation has
been completed shall be removed prior to painting. If rusting occurs after completion of surface preparation,
the surface shall be re-cleaned in accordance with the original method

(2) Painting shall be carried out in an atmosphere where relative humidity is less than 85 %.
(No application if the difference between the steel surface temperature and Dew Point is less than 3℃.)

(3) Paint shall be applied by one, or a combination, of the following methods:


· Brushing, Roller coating, Air Spraying, Airless Spraying, Flow Coating

(4) Paint shall not be force dried so as to cause checking, wrinkling, blistering, pore formation, or any condition
detrimental to its appearance. Newly painted surfaces shall be protected to the fullest extent feasible from rain,
condensation, contamination, snow, and freezing until the coating has dried.

(5) Spot repairs shall be carried out such that the patch painting extends at least 25 mm beyond the damaged
areas. Spot repairs shall reinstate each of the previous coats and shall commence directly after surface
preparation.

(6) Paints containing metallic lead, or zinc shall not be used to overcoat stainless steel materials.

4. Inspection

(1) Coating Materials


a) Verify that particular coating system and solvents for thinning are as specified and from the
same Coating Manufacturer.
b) Verify that “Shelf Life” of coating materials has not been exceeded.

(2) Environmental Conditions


Confirm that substrate, ambient and dew point temperatures are as specified for proper surface preparation
and coating application

(3) Surface Preparation


a) Verify cleanliness of surface prior to blast cleaning operations.
The presence of oil and grease shall be checked by visual or rubbing a clean white cloth on
steel surface to detect oil or grease, or by sprinkling water on the steel surface. Contaminants shall be
removed from the surface in accordance with SSPC SP1
b) Verify cleanliness of surface after blast cleaning.
Inspect correctness of surface preparation for specified cleanliness prior to coating. Verify anchor profile
in accordance with comparator or ASTM D4417 method C or ISO 8503-5 by using a Spring-loaded
micrometer and either a coarse or extra coarse replica tape as required by the anchor profile depth.

(4) Coating Thickness


a) The dry film thickness of primer, intermediate, finish coats and total thickness shall be checked using a
properly calibrated electromagnetic induction type or eddy current type gauge in accordance with Society
for Protective Coatings (SSPC)-PA2.
b) Coating thickness on stainless steel shall be checked using an eddy current type gauge suitable for use
on non-ferrous substrates.
c) The allowable thickness shall not exceed the allowable thickness recommended by the Coating
Manufacturer.

(5) Visual test


Visual inspection for pinholes/holidays, dry spray, sags and other flaws shall be performed after each coat is
applied. All such flaws shall be corrected before application of next coat.
5. Painting Specification [ISO12944-5, C3-Medium]

5.1 Main Tank & Conservator: Liquid Coating


Description Inside Outside
Surface treatment SSPC-SP10 SSPC-SP10
Type of paint Epoxy Epoxy Zinc
1st Coating Dry film thickness 40 ㎛ 60 ㎛
(Primer) Color Red Brown Gray
Paint product name Jotacote F60 Barrier 80
Type of paint Epoxy
2nd Coating Dry film thickness 100 ㎛
N/A
(Intermediate) Color Red Brown
Paint product name Jotacote F60
Type of paint Polyurethane Polyurethane
3rd Coating Dry film thickness 40 ㎛ 40 ㎛
(Top) Color N 9.5 (White) RAL7032
Paint product name Futura Classic 2 Futura Classic 2
Total film thickness 80 ㎛ 200 ㎛
Paint manufacturer JOTUN
Note) The color of the top coat inside the tank cover is applied the same as the outside.

5.2 Radiator: Hot-dip galvanized


Description Outside
Surface treatment SSPC-SP8
Total film thickness 60 ㎛

5.3 Control panel: Powder Coating


Description Inside Outside
Surface treatment SSPC-SP8 SSPC-SP8
Type of paint Polyester
1st Coating Dry film thickness 100 ㎛
(Primer) Color RAL7032
Paint product name N/A PE210
Type of paint
2nd Coating Dry film thickness
-
(Intermediate) Color
Paint product name
Type of paint Polyester Polyester
3rd Coating Dry film thickness 80 ㎛ 100 ㎛
(Top) Color RAL7032 RAL7032
Paint product name PE210 PE210
Total film thickness 80 ㎛ 200 ㎛
Paint manufacturer JOTUN
5.4 End frame: Liquid Coating
Description Outside
Surface treatment SSPC-SP10
Type of paint Epoxy
Dry film thickness 80 ㎛
1st Coating
Color N9.5 (White)
Paint product name Jotacote F60
Paint manufacturer JOTUN

5.5 Oil Sealing surface of flange

<Fig.1 Grooved surface> <Fig.2 Without groove surface> <Fig.3 Manhole cover>

Description Outside
Surface treatment SSPC-SP10
Type of paint Epoxy
1st Coating Dry film thickness 80 ㎛
(Primer) Color Red Brown
Paint product name Jotacote F60
Paint manufacturer JOTUN

5.6 Non-ferrous (stainless, hot-dip galvanized, aluminum, etc.) surface


Description Outside
Surface treatment SSPC-SP16
Type of paint Epoxy
1st Coating Dry film thickness 40 ㎛
(Primer) Color Red Brown
Paint product name Jotacote F60
Type of paint Polyurethane
2nd Coating Dry film thickness 40 ㎛
(Top) Color RAL7032
Paint product name Futura Classic 2
Total film thickness 80 ㎛
Paint manufacturer JOTUN
E. Mechanical drawings
KEYPLAN
PARTLIST

NOTES:

C B A

LEGEND & ABBREVIATIONS


A B C

BACK VIEW TOP VIEW

395
125
320 204
"A"
A B C

278

267

497
439

680
335 VIEW "A"
418
DETAIL OF CORE & CORE CLAMP GROUNDING
N
REFERENCE DRAWINGS
REV.NO. DRAWING NAME DRAWING NO.
ALL BOLTING JOINTS ARE PROPERLY
GROUNDED

C 19.06.2023 REVISED BY COMMENT J.H.CHOI Y.C.CHOI Y.C.CHOI E.J.HONG

B 07.04.2023 REVISED BY COMMENT J.H.CHOI Y.C.CHOI Y.C.CHOI E.J.HONG

A 23.02.2023 ISSUED FOR APPROVAL J.H.CHOI Y.C.CHOI Y.C.CHOI E.J.HONG


REV. NO. DATE DESCRIPTION DSN CHKD RVD APPD

PROJECT NAME
SOUTHERN EXTENSION OF THE NATIONAL ELECTRICITY
GRID POWER TRANSMISSION PROJECT UNDER EDCF
CLIENT

ETHIOPIAN ELECTRIC POWER


CONSULTANT

BYUCKSAN POWER Co Ltd.


CONTRACTOR

HYOSUNG HEAVY
INDUSTRIES

RAIL GAUGE=1500 RAIL GAUGE=1500


VENDOR
RAIL GAUGE=1500
(RAIL ℄-℄) 1600 (RAIL ℄-℄) 1600
(RAIL ℄- ℄) 1600
HYOSUNG HEAVY
INDUSTRIES

SUBSTATION NAME

SHIGDAN 230/132/33kV Substation


CLIENT DWG. NO.
UNIT

RIGHT VIEW CONTRACT NO.


EEP/33.20/58/14 SCALE

DWG. NAME
FRONT VIEW OUTLINE DRAWING
DWG. NO. SHT. NO. E-1
LEFT VIEW EEP-SENEG-SH-SS-12-TS01
REV. NO. C
KEYPLAN
M30
90

45 45 2-M12 TAP
420 420 100
210 210 210 210

25
400
190

150

50
315

400

25
125

20

12
150

100 100 125


NOTES:
RAIL DETAIL
400 400 22 22 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE NOTED.

2. DIMENSION TOLERANCE : ± 5%

3. ANGLE OF PROJECTION: 3RD

4. DIMENSION AND WEIGHT WILL BE CHANGED SLIGHTLY AFTER

DETAIL DESIGN.

2336 2670
WHEEL LEGEND & ABBREVIATIONS
1834 1834 FIG-1
1475 1475
200 1065 1065 200 4-JACKING POSITION
POSITION FOR
XPRD PIPE TR CENTER 625

400
CENTRE OF CONTROL
1295

1095
1079

CABLE TO REMOTE / LOCAL


971
825

REFERENCE DRAWINGS

RAIL GAGUE=1500

(RAIL ℄-℄) 1600


REV.NO. DRAWING NAME DRAWING NO.

2190
TR CENTER
971
1079

1095
1295

RAIL
FIG-2

400
750 750
RAIL GAUGE=1500
C 19.06.2023 REVISED BY COMMENT J.H.CHOI Y.C.CHOI Y.C.CHOI E.J.HONG
4095
B 07.04.2023 REVISED BY COMMENT J.H.CHOI Y.C.CHOI Y.C.CHOI E.J.HONG

A 23.02.2023 ISSUED FOR APPROVAL J.H.CHOI Y.C.CHOI Y.C.CHOI E.J.HONG


REV. NO. DATE DESCRIPTION DSN CHKD RVD APPD
PROJECT NAME
SOUTHERN EXTENSION OF THE NATIONAL ELECTRICITY
GRID POWER TRANSMISSION PROJECT UNDER EDCF
CLIENT

ETHIOPIAN ELECTRIC POWER


CONSULTANT

PLINTH LEVEL BYUCKSAN POWER Co Ltd.


587

CONTRACTOR

HYOSUNG HEAVY
INDUSTRIES

VENDOR

HYOSUNG HEAVY
INDUSTRIES

SUBSTATION NAME

SHIGDAN 230/132/33kV Substation


CLIENT DWG. NO.
UNIT

RAIL GAGUE=1500 CONTRACT NO.


EEP/33.20/58/14 SCALE

DWG. NAME
(RAIL ℄-℄) 1600
FOUNDATION DRAWING
400 965 965 400
DWG. NO. SHT. NO. E-2
EEP-SENEG-SH-SS-12-TS01
REV. NO. C
KEYPLAN

NOTES:

LEGEND & ABBREVIATIONS

REFERENCE DRAWINGS
REV.NO. DRAWING NAME DRAWING NO.

4000
161 66 C 19.06.2023 REVISED BY COMMENT J.H.CHOI Y.C.CHOI Y.C.CHOI E.J.HONG

B 07.04.2023 REVISED BY COMMENT J.H.CHOI Y.C.CHOI Y.C.CHOI E.J.HONG

A 23.02.2023 ISSUED FOR APPROVAL J.H.CHOI Y.C.CHOI Y.C.CHOI E.J.HONG


REV. NO. DATE DESCRIPTION DSN CHKD RVD APPD
PROJECT NAME
SOUTHERN EXTENSION OF THE NATIONAL ELECTRICITY
GRID POWER TRANSMISSION PROJECT UNDER EDCF
CLIENT

ETHIOPIAN ELECTRIC POWER


1722

1722

CONSULTANT

BYUCKSAN POWER Co Ltd.


CONTRACTOR

HYOSUNG HEAVY
INDUSTRIES

VENDOR

HYOSUNG HEAVY
INDUSTRIES

SUBSTATION NAME
2015 1500 2400 3100
SHIGDAN 230/132/33kV Substation
3515
5500 CLIENT DWG. NO.
UNIT

CONTRACT NO.
EEP/33.20/58/14 SCALE

DWG. NAME

SHIPPING DRAWING
DWG. NO. SHT. NO. E-3
EEP-SENEG-SH-SS-12-TS01
REV. NO. C
KEYPLAN

VALVE LOCATION PLATE


10

NOTES:
C B A

N LEGEND & ABBREVIATIONS

A B C

TOP VIEW
350

BACK VIEW

B
A C REFERENCE DRAWINGS
REV.NO. DRAWING NAME DRAWING NO.

C 19.06.2023 REVISED BY COMMENT J.H.CHOI Y.C.CHOI Y.C.CHOI E.J.HONG

B 07.04.2023 REVISED BY COMMENT J.H.CHOI Y.C.CHOI Y.C.CHOI E.J.HONG

A 23.02.2023 ISSUED FOR APPROVAL J.H.CHOI Y.C.CHOI Y.C.CHOI E.J.HONG


REV. NO. DATE DESCRIPTION DSN CHKD RVD APPD
PROJECT NAME
LEFT VIEW FRONT VIEW RIGHT VIEW SOUTHERN EXTENSION OF THE NATIONAL ELECTRICITY
10

GRID POWER TRANSMISSION PROJECT UNDER EDCF


CLIENT

ETHIOPIAN ELECTRIC POWER


CONSULTANT

BYUCKSAN POWER Co Ltd.


10 10 CONTRACTOR

HYOSUNG HEAVY

500 INDUSTRIES

VENDOR

HYOSUNG HEAVY
INDUSTRIES

SUBSTATION NAME

SHIGDAN 230/132/33kV Substation


CLIENT DWG. NO.
UNIT

CONTRACT NO.
EEP/33.20/58/14 SCALE

DWG. NAME

VALVE LOCATION PLATE DRAWING


DWG. NO. SHT. NO. E-4
EEP-SENEG-SH-SS-12-TS01
REV. NO. C
KEYPLAN

10
THREE PHASE NOTES:
SHUNT REACTOR

LEGEND & ABBREVIATIONS

REFERENCE DRAWINGS

500
REV.NO. DRAWING NAME DRAWING NO.

VECTOR GROUP
YN

C 19.06.2023 REVISED BY COMMENT J.H.CHOI Y.C.CHOI Y.C.CHOI E.J.HONG

B 07.04.2023 REVISED BY COMMENT J.H.CHOI Y.C.CHOI Y.C.CHOI E.J.HONG

A 23.02.2023 ISSUED FOR APPROVAL J.H.CHOI Y.C.CHOI Y.C.CHOI E.J.HONG


REV. NO. DATE DESCRIPTION DSN CHKD RVD APPD
PROJECT NAME
SOUTHERN EXTENSION OF THE NATIONAL ELECTRICITY
GRID POWER TRANSMISSION PROJECT UNDER EDCF
CLIENT

ETHIOPIAN ELECTRIC POWER


CONSULTANT

BYUCKSAN POWER Co Ltd.


CONTRACTOR

HYOSUNG HEAVY
INDUSTRIES

VENDOR

HYOSUNG HEAVY
INDUSTRIES

SUBSTATION NAME

SHIGDAN 230/132/33kV Substation


CLIENT DWG. NO.
UNIT
10

CONTRACT NO.
EEP/33.20/58/14 SCALE

10 10 DWG. NAME
300 RATING PLATE DRAWING
DWG. NO. SHT. NO. E-5
EEP-SENEG-SH-SS-12-TS01
REV. NO. C
F. LCP Schematic drawings