Section 1. General
1. General scope
2. Applicable standards
3. Service conditions
4. Construction
5. Packing and Shipment
6. Painting Specification
7. Insulation Oil
8. Insulation Level
9. External Clearance
This specification describes three phase, oil immersed transformers suitable for outdoor installation
under the service conditions mentioned herein and the information about the following power
transformer which will be supplied by HYOSUNG.
2. Applicable standard
Electrical equipment covered by this specification will be complied with the following standards.
3. Service conditions
These transformers are suitable for operation under the following service conditions.
3.1 Altitude Up to 1000 meter above sea level
3.2 Designed Ambient temperature
Maximum ambient temperature + 40℃
Min ambient temperature 0℃
4. Construction
4.1 Core
The core consists of three columns, parallel, laminated cold-rolled and non-aging silicon-steel
having high permeability and low hysteresis loss.
The steel sheet is thoroughly coated on both sides of each sheet with insulating properties to
reduce eddy current losses to minimum.
Structural rigidity is given to the core by the use of steel plates at the bottom of the core. So that
distortion due to short circuit stresses or transport handling is prevented.
4.2 Windings
Coil is designed and manufactured to withstand the impulse voltage, prevent it from distortion
when a short circuit occurs.
Permanent current carrying joints or splices will be welded or clamped, formed, finished and
insulated to avoid concentration of dielectric stresses.
The conductors will be transposed at sufficient intervals to minimize currents and equalize the
current and temperature distribution along the winding.
The material of conductor is copper.
4.3 Tank
The transformer is provided with a suitable steel tank of substantial construction which is oil-tight
and gas-tight. All gaskets are made of materials which do not deteriorate under service conditions.
The tank has sufficient strength to withstand an internal pressure of full vacuum and vacuum
drying without damage or permanent deformation.
The transformer tank is provided with manholes and hand holes of suitable size to afford easy
access to the lower ends of bushing terminals, upper portions of the coils and side position of tap
changer.
In the case of core-form transformer the joint between the tank and cover is provided with suitable
flange and gaskets at top of the tank so that the assembly service is oil-tight and gas-tight.
The transformer is provided with lugs for lifting the essential parts also for lifting the completely
assembled transformer filled with oil.
4.4 Conservators
In air seal cell type conservator, the oil surface is completely isolated from the atmosphere by
installing an oil-resistant rubber cell in the interior of the conservator, so that atmospheric
pressure is always maintained without the necessity of employing intervening mediums.
The outside of the rubber cell attached on the inside of the conservator is filled with insulating
oil. The inside is open to the atmosphere through the silica gel breather.
(Refer to the Figure 1.)
Namely, during the operation the insulating oil is always isolated from the air by the oil-resistant
rubber and there is no oxidation or moisture contamination of the oil at all.
And this type conservator allows also the main tank to remain full oil level despite of oil
expansion and contraction with temperature changes.
A pipe connection between the lowest part of the conservator and the cover of main tank permits
the gas from main tank to pass into the conservator through Buchholz relay, so that the
transformer tank will be completely filled with oil.
The transformers are shipped without oil. Instead of oil, the tank is filled with dry air. And pressure
gauge and stop valve are provided, so as to enable the pressure of the inert gas within the tank to be
read before installation site.
All opening for transformer components, e.g. bushings which have been removed from the transformer
during transport, are covered by means of blanking off plates. All parts are carefully packed for
transport in such a manner that they are protected against mechanical injury and injurious effect of
climatic conditions encountered during transit to their destination, as well as during long storage
before erection.
6. Painting Specification
Description Outside
Surface treatment SSPC-SP8
Type of paint Epoxy
1st Coating Dry film thickness 40 ㎛
(Primer) Color Gray
Paint product name Jotacote F60
Type of paint Polyurethane
2nd Coating Dry film thickness 40 ㎛
(Top) Color RAL 7032
Paint product name Futura Classic 2
Total film thickness 80 ㎛
Paint manufacturer JOTUN
8. Insulation Level
Insulation level will be as follows in accordance with rated voltage.
8.1 Windings
Transformer Rated Voltage Impulse withstand voltage
(1.2/50 ms)
230kV 1050kV
132kV 650kV
Neutral 95kV
8.2 Bushings
Impulse withstand voltage
Transformer Bushing Rated
(1.2/50 ms) Altitude
Rated Voltage Voltage
Required Applied
HV: 230kV 245kV 1200kV 1200kV * Up to 1000 meter
XV: 132kV 132kV 750kV 750kV ** Up to 1000 meter
Neutral 36.0kV 95kV 170kV*** Up to 1000 meter
* The test voltage of HV BUSHING is 1260KV at 1000meter.
** The test voltage of XV BUSHING is 788KV at 1000meter.
*** The test voltage of NEUTRAL BUSHING is 170KV at 1000meter.
9. External clearances
Since the site altitude is less than 1000m, external clearances are in accordance with IEC60076-3.
Manufacturer HYOSUNG
Outdoor, Oil filled,
Type
Core-form
Standards applied IEC 76 IEC 60076
Method of cooling ONAN/ONAF ONAN/ONAF
Number of Phases 3 3
Frequency, Hz 50 50
Rated voltage:
a) 230kV winding, kV 230 230
b) 132kV winding, KV 132 132
Rated Continuous Power on all taps at ONAN :
a) 230kV winding, kV 100 100
b) 132kV winding, KV 100 100
Rated Continuous Power on all taps at ONAF :
a) 230kV winding, kV 125 125
b) 132kV winding, KV 125 125
Voltage regulation by onload tap changer on 400kV winding, range (%) + 10 taps @1.25% + 10 taps @1.25%
Number of tap positions of on load tapchanger 21 21
Vector group (Connection symbol) YNa0d11 YNa0d11
No-load losses at rated voltage, frequency and at nominal tap position, kW 23.5
Apar 1020-60U
Type and quality of oil Shell DIALA B
54,100 Liters
Transformer tank
a) Type Bolted cover Bolted cover
b) thickness of side wall, mm 12
c) thickness of bottom, mm 16
d) thickness of cover, mm 16
e) filling medium for shipment Nitrogen Nitrogen
230kV regulation
d) Voltage class, kV (OLTC Um is 170kV on end
of series winding)
Bushings
1) 230kV bushing
1) Manufacturer Trench
2) Type COT
3) Rated current, A as per S.L.D 1000
245(Name plate)
4) Rated voltage, kV 230
300(Test voltage)
505(Name plate)
5) Power frequency test voltage, kV 460
505(Test voltage)
1200(Name plate)
6) Impulse test voltage, kV 1200
1260(Test voltage)
20
7) creepage distance, mm/kV 31
(31)
b) 132kV bushing
1) Manufacturer Trench
2) Type COT
3) Rated current, A as per S.L.D 1000
170(Name plate)
4) Rated voltage, kV 132
170(Test voltage)
355(Name plate)
5) Power frequency test voltage, kV 315
355(Test voltage)
750(Name plate)
6) Impulse test voltage, kV 750
788(Test voltage)
20
7) creepage distance, mm 31
(31)
c) Bushing Current Transformer (neutral) 200-100/1/1A 800-600-400/1/1A
Weights :
a) Core and windings, kg 57,100
b) Oil, kg 48,700
NOTES:
HV SIDE
Y1 R S T
Y2
N
Y3 r s t
XV SIDE
BACK VIEW
(VIEW LOOKING FROM HV SIDE)
"A"
VIEW "A"
r s t
PROJECT NAME
SOUTHERN EXTENSION OF THE NATIONAL ELECTRICITY
GRID POWER TRANSMISSION PROJECT UNDER EDCF
CLIENT
HYOSUNG HEAVY
INDUSTRIES
HYOSUNG HEAVY
INDUSTRIES
SUBSTATION NAME
RAIL GAGUE=2800 RAIL GAGUE=1500
Shigdan 230/132/33 kV Substation
(RAIL ℄-℄) 2900 (RAIL ℄-℄) 1600
CLIENT DWG. NO.
UNIT
CONTRACT NO.
EEP/33.20/58/14 SCALE
DWG. NAME
LEFT SIDE VIEW
OUTLINE
FRONT VIEW RIGHT SIDE VIEW
(VIEW LOOKING FROM XV SIDE) DWG. NO. SHT. NO. B
C41-4177-202209-5596-2000-001
REV. NO. 1/1
M36
90
=
415
518
150
274
50
35
500
12
150
4284
6896 2-GROUNDING PAD POSITION
2773 4123
3686 (JACKING POINT)
2115 (JACKING POINT) 3300 (GROUNDING POSITION)
POSITION FOR
200 825 1025 200 POSITION FOR
XPRD PIPE FOR OLTC
4-JACKING POSITION 756 XPRD PIPE FOR MAIN TANK
WHEEL
TR CENTER
FIG-1
400
1752 (JACKING POINT)
1277 (JACKING POINT)
1624
1561
1370
1170
1600
875
RAIL CENTER
2540
3490
1277 (JACKING POINT)
TR CENTER
1170
1370
1561
400
225
8-ANCHOR POSITION POSITION FOR RAIL
1728 786
REFER FIG-3 FIG-2
XPRD PIPE FOR MAIN TANK
CENTRE OF CONTROL
4654 CABLE TO REMOTE / LOCAL
HYOSUNG HEAVY
INDUSTRIES
677
HYOSUNG HEAVY
INDUSTRIES
SUBSTATION NAME
CONTRACT NO.
EEP/33.20/58/14 SCALE
400 825 825 400 DWG. NAME
FOUNDATION
DWG. NO. SHT. NO. 1/1
C41-4177-202209-5596-2000-002
REV. NO. A
HV SIDE
NOTES:
XV SIDE
TOP VIEW
PROJECT NAME
SOUTHERN EXTENSION OF THE NATIONAL ELECTRICITY
GRID POWER TRANSMISSION PROJECT UNDER EDCF
CLIENT
HYOSUNG HEAVY
INDUSTRIES
VENDOR
HYOSUNG HEAVY
INDUSTRIES
SUBSTATION NAME
CONTRACT NO.
EEP/33.20/58/14 SCALE
DWG. NAME
SHIPPING OUTLINE
DWG. NO. SHT. NO. 1/1
C41-4177-202209-5596-2000-003
REV. NO. B
R r S s T t N
THREE PHASE
PX CLASS
NOTES:
HV 230,000 V AUTO + + +
LV 132,000 V TRANSFORMER - - -
HV 1,050 kV
LV 650 kV HV-LV %
BCT 06
200-100/1A
5P20 15-7.5VA
NEUTRAL 95 kV
ONAN ONAF
R r S s T t N
B
560/1A 370/2A 560/2A 800-600-400/1A
CL3.0 15VA CL3.0 15VA CL3.0 15VA PX CLASS
FOR AVR FOR WTI FOR WTI
800-600-400/1A
PX CLASS
+ + +
- - -
200-100/1A
5P20 15-7.5VA
VECTOR GROUP
B 30.06.2023 ISSUED FOR APPROVAL J.H.CHOI I.H.HONG I.H.HONG E.J.HONG
YNa0(d11) A 24.03.2023 ISSUED FOR APPROVAL J.H.CHOI I.H.HONG I.H.HONG E.J.HONG
REV. NO. DATE DESCRIPTION DSN CHKD RVD APPD
PROJECT NAME
SOUTHERN EXTENSION OF THE NATIONAL ELECTRICITY
GRID POWER TRANSMISSION PROJECT UNDER EDCF
CLIENT
HYOSUNG HEAVY
INDUSTRIES
VENDOR
HYOSUNG HEAVY
INDUSTRIES
SUBSTATION NAME
CONTRACT NO.
EEP/33.20/58/14 SCALE
DWG. NAME
MAIN NAME PLATE
DWG. NO. SHT. NO. 1/1
C41-4177-202209-5596-2000-004
REV. NO. B
VALVE LOCATION PLATE
NOTES:
PROJECT NAME
SOUTHERN EXTENSION OF THE NATIONAL ELECTRICITY
GRID POWER TRANSMISSION PROJECT UNDER EDCF
CLIENT
HYOSUNG HEAVY
INDUSTRIES
VENDOR
HYOSUNG HEAVY
INDUSTRIES
SUBSTATION NAME
CONTRACT NO.
EEP/33.20/58/14 SCALE
DWG. NAME
X1 PE 1 5 6 2 2A 3 4 17 19
300
301
X1:29 X1:31
/2.A2 /3.B3
220
200
500
502
B B
101
108
113
21
S10
22
221
1 3 5
1
X20 4
Q1 B2
/2.G10 2
204
(< 40°C)
222
C 2 4 6 X2 1 2 C
X3 1 21 73
114
Q1 K20
205
233
223
109 /2.G10 22 /2.G6 74
102 1
501
503
1 3 5 1 3 5 1 1
K1 K2 E1
PE PE
/2.F5 2 4 6 /2.F7 2 4 6
R1 R3 214
2
D D
X2 PE
Fuer diese technische Unterlage behalten wir uns gemaess
224
2 2
206
213
X2 4 5 X3 2
DIN 34 Abschnitt 2.1 und 2.2 alle Rechte vor.
TAP-CHANGER IN OPERATION
225
110
115
E E
X20 5
K1:A2 X1:50
226
/2.F2 /3.E3
116
X20 1 2 3
104
C C
330
304
S8A S8B
NC NO NC NO X1 7 7A 8 9 18 20
105
111
117
C C
S6A S6B L- N
F NC NO NC NO F
106
118
U1 V1 W1
M1
M
3
PE
G G
H H
DATE 22.05.2023 LANGUAGE: PROJECT: =
EXEC. WAM MOTOR DRIVE UNIT EN +
VERIFIED SO SHEET 1
NO. MODIFICATION DATE NAME STANDARD ORIGIN. REPL. REPL.BY
10357962_00 7 SH.
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
TO POS. 21 LOWER WITH STEP-BY-STEP OPERATION TO POS. 1 RAISE Q1 "OFF"
A A
REMOTE
X1 29 30 10 11 12 13 14 15
X1:2 300
344
/1.B5
331
363 LOCAL
2 4 1 3
13
S3 S32
Q1 339 1 3 346 /4.G1 2 4
/2.G10 14
345
332
B B
53 53
K1 K2
332
/2.G5 54 /2.G7 54
339 346
21 13 43 31
K20
/2.G6 22 14 44 32
369
340
366
X20 6 7 15 8
338
352
C 333 333 C
353
C C C C C C
S14 S4 S13B S13A S5 S12
NC NO NC NO NC NO NC NO NC NO NC NO
341
334 348 354
C C C
S37 S1 S2
NC NO NC NO NC NO
342
D D
355
356
Fuer diese technische Unterlage behalten wir uns gemaess
X20 9 10 11 14 12 13
357 358
61 83 83 61
54
K1 K2
336
350
DIN 34 Abschnitt 2.1 und 2.2 alle Rechte vor.
361
359
347
360
13
E 22 22 84 62 E
K2 K37H K1 K20
343
/2.F9 14
/2.G7 21 /2.G5 21 /2.G6 83 353 61
337
351
A1 A1 A1 A1 C1
343
K1 K20 K2 K37H Q1
330 /2.F5 A2 /2.F6 A2 330 /2.F7 A2 /2.F9 A2 /2.G10 C2
/1.E5
X1:7
F F
K1 K20 K2 K37H Q1
/2.E4 A1 A2 /2.E6 A1 A2 /2.E7 A1 A2 /2.E8 A1 A2
H H
DATE 22.05.2023 CONTROL LANGUAGE: PROJECT: =
EXEC. WAM MOTOR DRIVE UNIT EN +
VERIFIED SO SHEET 2
NO. MODIFICATION DATE NAME STANDARD ORIGIN. REPL. REPL.BY
10357962_00 7 SH.
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
A A
X1 31 34 35 36 37
301
406
386
390
/1.B6 /5.A2 /5.A8
X1:2A U5:11 U7:11
381
B B
31
Q1
/2.G10 32
407
X20 40
382
C C
C
383
X20 41
D D
Fuer diese technische Unterlage behalten wir uns gemaess
384
DIN 34 Abschnitt 2.1 und 2.2 alle Rechte vor.
X1
MCB1
RED X2
E E
A1
K30
X1:7A /3.F5 A2 U5:10 U7:10
/1.E6 /5.F2 /5.F8
304
385
408
387
391
X1 50 47 46 45 44
F F
K30
/3.E5 A2 A1
16
/4.C4 15
18
26
25
28
G G
H H
DATE 22.05.2023 CONTROL POTENTIAL TERMINALS LANGUAGE: PROJECT: =
EXEC. WAM MOTOR DRIVE UNIT EN +
VERIFIED SO SHEET 3
NO. MODIFICATION DATE NAME STANDARD ORIGIN. REPL. REPL.BY
10357962_00 7 SH.
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
A A
B B
580
583
592
508
520
540
C C
6 8 15 43 C C C
S32 K30 Q1 S26A S27A S15
/4.G1 5 7 /3.G5 16 18 44 NC NO NC NO NC NO
581
582
584
585
593
594
509
510
521
522
541
D D
Fuer diese technische Unterlage behalten wir uns gemaess
TAP-CHANGER IN OPERATION
E E
F F
X1 241 242 X1 180 181 X1 177 X1 291 292 293 294 X1 299 300
S32
2 1
/2.B8
4 3
6 5
/4.C1
8 7
G G
DO NOT MODIFY MANUALLY
DRAWING BY CAD
H H
DATE 22.05.2023 INDICATION CIRCUITS LANGUAGE: PROJECT: =
EXEC. WAM MOTOR DRIVE UNIT EN +
VERIFIED SO SHEET 4
NO. MODIFICATION DATE NAME STANDARD ORIGIN. REPL. REPL.BY
10357962_00 7 SH.
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
633
634
635
390
638
639
640
9 9
8 8
10 10
9 9
11 11
10 10
12 12
11A 11A
2 5 4 1 13 2 5 4 1 13
11B 11B
11 11
C U5 14 U7 14 C
11C 11C
10 10
20 X 10 OHM
20 X 10 OHM
15 15
12 12
+
+
-
-
7 8 16 7 8 16
13 13
17 17
14 14
18 18
15 15
19 19
16 16
20 20
D 17 17
D
Fuer diese technische Unterlage behalten wir uns gemaess
21 21
18 18
22 22
19 19
391
641
642
387
636
637
23 23
20 20
DIN 34 Abschnitt 2.1 und 2.2 alle Rechte vor.
24 24
21 21
25 25
26 26
E 27 27
E
28 28
29 29
30 30
/3.E6 /3.E7
X1:45 X1:44
X1 211 212 31 X1 213 214 31
4...20 mA 32 4...20 mA 32
33 33
F F
34 34
35 35
36 36
37 37
G G
DO NOT MODIFY MANUALLY
DRAWING BY CAD
H H
DATE 22.05.2023 REMOTE POSITION INDICATION LANGUAGE: PROJECT: =
EXEC. WAM MOTOR DRIVE UNIT EN +
VERIFIED SO SHEET 5
NO. MODIFICATION DATE NAME STANDARD ORIGIN. REPL. REPL.BY
10357962_00 7 SH.
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
3 2 4 4 X 2 4 4 X 2
4 3 5 8 X X 3 5 8 X X 3
5 4 6 10(-) X 4 6 10(-) X 4
6 5 7 20(+) X X 5 7 20(+) X X 5
B 7 6 X X 6 X X 6 B
8 7 X X X 7 X X X 7
9 8 X 8 X 8
10 9 X X 9 X X 9
11 10 X 10 X 10
15 12 X X 12 X X 12
16 13 X X X 13 X X X 13
17 14 X X 14 X X 14
18 15 X X X 15 X X X 15
19 16 X X X 16 X X X 16
D 20 17 X X X X 17 X X X X 17
D
Fuer diese technische Unterlage behalten wir uns gemaess
21 18 X X 18 X X 18
22 19 X X X 19 X X X 19
23 20 X 20 X 20
DIN 34 Abschnitt 2.1 und 2.2 alle Rechte vor.
24 21 X X 21 X X 21
25
26
E E
27
28
BCD
BCD
29
30
31
32
F 33 F
34
35
36
G G
DO NOT MODIFY MANUALLY
DRAWING BY CAD
H H
DATE 22.05.2023 REMOTE POSITION INDICATION LANGUAGE: PROJECT: =
EXEC. WAM MOTOR DRIVE UNIT EN +
VERIFIED SO SHEET 6
NO. MODIFICATION DATE NAME STANDARD ORIGIN. REPL. REPL.BY
10357962_00 7 SH.
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
B2 THERMOSTAT
E1 HAND LAMP 33 1 2 3 4 5 6 - 11 - 15 16 17 18 - 24 25 26 27 28 29 30 31 32 33 1 2 3 4
A A
K1 MOTOR CONTACTOR
S1/C-NO
K2 MOTOR CONTACTOR
S1/C-NC
K20 AUXILIARY CONTACTOR
S2/C-NO
K30 TIMING RELAY
S2/C-NC
K37H AUXILIARY CONTACTOR FOR AUTOMATIC PASSAGE OF POSITIONS S12,S14/C-NO
M1 MOTOR S13A,S13B/C-NO
MCB1 SIGNALLING LAMP
Q1 MOTOR PROTECTIVE SWITCH S15/C-NO
R1 HEATER S15/C-NC
B B
R3 HEATER WITH PTC RESISTOR
S1 CAM-OPERATED SWITCH
S2 CAM-OPERATED SWITCH
S3 RAISE/LOWER CONTROL SWITCH
S4 END POSITION SWITCH
S5 END POSITION SWITCH
S6A END POSITION SWITCH
S6B END POSITION SWITCH
C S8A HAND CRANK SAFETY SWITCH S24/C-NO C
S8B HAND CRANK SAFETY SWITCH S24/C-NC
S10 DOOR CONTACT
S12 CAM-OPERATED DIRECTIONAL SWITCH
S13A CAM-OPERATED DIRECTIONAL SWITCH
S13B CAM-OPERATED DIRECTIONAL SWITCH
S14 CAM-OPERATED DIRECTIONAL SWITCH
S15 CAM-OPERATED NON-DIRECTIONAL SWITCH
S24 CAM-OPERATED NON-DIRECTIONAL SWITCH
D S26A END POSITION SIGNALLING SWITCH D
Fuer diese technische Unterlage behalten wir uns gemaess
G G
/2.A11
/4.A11
/1.A12
/1.A12
/4.F11
/4.F11
/1.F12
/1.F12
/1.A1
/1.A1
/4.A1
/1.A2
/1.A2
/1.A5
/1.A6
/1.A7
/1.A9
/1.A2
/1.A3
/2.A7
/2.A9
/2.A9
/2.A9
/2.A3
/2.A3
/3.A5
/3.A5
/3.A5
/3.A7
/4.A7
/4.F1
/4.A9
/4.A9
/2.A4
/3.A4
/4.A4
/1.F5
/1.F6
/1.F7
/1.F9
/2.F5
/3.F7
/3.F5
/3.F5
/3.F5
/4.F7
/5.F3
/5.F3
/5.F8
/5.F9
/4.F2
/4.F9
/4.F9
/4.F9
/4.F9
/3.F4
/4.F4
/4.F4
S15 :NO
291 S26A :NC
S15 :NC
Q1:C1
K1:A2
46 MCB1:X2
K30 :A2
X1:2A
X1:7A
X1:31
S10 :21
Q1:21
Q1:31
U5 :11
U7 :11
X1:29
X1:50
K2 :53
Q1:22
K20 :73
Q1:13
X20 :40
U7 :10
U5 :10
Q1:43
K30 :15
K30 :16
K30 :18
16 K37H:14
K20 :74
Q1:44
272 S26A :C
273 S27A :C
S15 :C
Q1:1
B2 :1
S3 :1
Q1:3
Q1:5
X20 :5
S3 :3
S32 :3
S32 :2
X1:2
U5 :7
U5 :8
U7 :7
U7 :8
S32 :6
S32 :5
S32 :7
X2 :4
1
11
31
181
211
241
PE
PE
PE
5
6
7
8
9
10
12
13
15
17
18
19
20
29
30
35
36
37
45
47
50
152
155
177
180
212
213
215
242
276
299
300
4
14
34
44
214
2A
7A
X1
DO NOT MODIFY MANUALLY
L1:
L+ :
L1:
L2 :
L3 :
L- :
N:
-:
+:
-:
+:
DRAWING BY CAD
H H
DATE 22.05.2023 LANGUAGE: PROJECT: =
EXEC. WAM MOTOR DRIVE UNIT EN +
VERIFIED SO SHEET 7
NO. MODIFICATION DATE NAME STANDARD ORIGIN. REPL. REPL.BY 10357962_00 7 SH.
1 2 3 4 5 6 7 8 9 10 11 12
Section 6. Bill of Material With Sub-Vendor List
- COT 1200-1000
TRENCH/
1 HV BUSHING 3 EA - 245kV, 1200kV BIL, 1000A
FRANCE
- Up to 1000meter
- COT 750-1000
TRENCH/
2 XV BUSHING 3 EA - 170kV, 750kV BIL, 1000A
FRANCE
- Up to 1000meter
- COT 170-1000
TRENCH/
3 NEUTRAL BUSHING 1 EA - 36kV, 170kV BIL, 1000A
FRANCE
- Up to 1000meter
- KMA3452000 KYEMYUNG/
4 TV BUSHING 2 EA - 34.5kV, 200kV BIL, 2000A KOREA
- Up to 1000meter
MR/
5 ON LOAD TAP CHANGER 1 EA - 3 X VM I 651-170/C-12 23 3W
GERMANY
WINDING TEMPERATURE - Compact type MESSKO /
6 2 EA
INDICATOR - Measuring range: 0~160°C GERMANY
OIL TEMPERATURE - Compact type MESSKO /
7 1 EA
INDICATOR - Measuring range: 0~160°C GERMANY
PRESSURE RELIEF - XPRD Type QUALITROL /
8 2 EA
- Operating pressure: 12 PSI USA
DEVICE FOR MAIN
PRESSURE RELIEF - XPRD Type QUALITROL /
9 3 EA
- Operating pressure: 20 PSI USA
DEVICE FOR OLTC
EMB/
10 BUCHHOLZ RELAY 1 EA - Double float type
GERMANY
TAIJIN /
11 FAN MOTOR 10 EA - 3PH 50HZ 380V
KOREA
SUDDEN PRESSURE RISE QUALITROL /
12 1 EA - 900 Type
RELAY USA
TAIJIN /
13 OIL LEVEL GAUGE 1 EA
KOREA
DEHYDRATING TAIJIN /
14 1 EA - Silica Gel Type
BREATHER KOREA
APAR /
16 INSULATION OIL -
INDIA
HV BUSHING
TECHNICAL DATASHEET 41431070 V1
General specifications
Altitude 1300 m Mounting angle (from vertical) 30 °
Length under flange L1 984 mm Product information 44497672E
CT length L4 300 mm IEC 60137-2017
Standard
Temperature range -30 +40 °C -
Electrical specifications
Rated lightning impulse withstand voltage (BIL) 1200 kV Rated highest voltage for equipment (Um) 245 kV
Rated current (Ir) 1000 A Phase to earth voltage 142 kV
Dry switching impulse withstand voltage (SIL dry) 850 kV Power frequency withstand voltage (AC) dry 505 kV
wet 460 kV
Rated short-circuit current (Ith) 31,5 kA 3s Rated frequency 50/60 Hz
Head
Oil level indicator type Optical
Insulator
Cantilever test load 500 daN
Insulator material Brown porcelain
Arcing distance AD 2400 mm
Creepage distance 9300 mm
USCD (IEC 60815) 53,7 mm/kV
Flange
Flange Round 12xø22 BCD 400 mm
Other
Standard sparkgaps
XV BUSHING
TECHNICAL DATASHEET 41431268 V1
General specifications
Altitude 1300 m Mounting angle (from vertical) 30 °
Length under flange L1 720 mm Product information 44497653E
CT length L4 300 mm IEC 60137-2017
Standard
Temperature range -30 +40 °C -
Electrical specifications
Rated lightning impulse withstand voltage (BIL) 750 kV Rated highest voltage for equipment (Um) 170 kV
Rated current (Ir) 1000 A Phase to earth voltage 98 kV
Head
Oil level indicator type Optical
Insulator
Cantilever test load 400 daN
Insulator material Brown porcelain
Arcing distance AD 1460 mm
Creepage distance 5270 mm
USCD (IEC 60815) 53,7 mm/kV
Flange
Flange Round 12xø16 BCD 290 mm
Shield
Bayonet shield H195 ø240/160 (mm)
Type of coating : Epoxy
Other
Standard sparkgaps
NEUTRAL BUSHING
TECHNICAL DATASHEET 41431092 V2
General specifications
Altitude 3000 m Mounting angle (from vertical) 30 °
Length under flange L1 440 mm Product information 44497653E
CT length L4 300 mm IEC 60137-2017
Standard
Temperature range -30 +40 °C -
Electrical specifications
Rated lightning impulse withstand voltage (BIL) 170 kV Rated highest voltage for equipment (Um) 36 kV
Rated current (Ir) 1000 A Phase to earth voltage 21 kV
Head
Oil level indicator type Optical
Insulator
Cantilever test load 200 daN
Insulator material Brown porcelain
Arcing distance AD 340 mm
Creepage distance 1116 mm
USCD (IEC 60815) 53,7 mm/kV
Flange
Flange Round 4xø24 BCD 184 mm
Other
Standard sparkgaps
ON LOAD TAP CHANGER
A_TEMP
MASCHINENFABRIK REINHAUSEN GMBH COPYRIGHT RESERVED
gepr.
The reproduction, distribution and utilization of this document as well as the communication of its contents to others without explicid authorization is
prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or design.
312
313
311
305
514
314
513
512
505
SELECTOR / SIDE OF
414
413
412
160
411
405
CHANGE-OVER SELECTOR
310 301 170
10
POLE A ( H1 )
308
300
510
90
500
501
508
80
410
400
401
408
120
40
50
POLE B ( H2 )
Overview representation
10366418_200_00
1/5
DIN A1
0 DRIVE SHAFT ARRANGEMENT
10 Drive: TAPMOTION® ED100S
40 Drive shafts 1.990 mm , revolutions: 16,50
50 Gear CD6400, 2:1, A
prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or design.
The reproduction, distribution and utilization of this document as well as the communication of its contents to others without explicid authorization is
80 Drive shafts 1.851 mm , revolutions: 8,25
90 Gear OGST, 16,5:1, B
120 Drive shafts 1.846 mm , revolutions: 8,25
130 Gear OGST, 16,5:1, B
160 Drive shafts 1.851 mm , revolutions: 8,25
170 Gear OGST, 16,5:1, B
300 Tap-changer cover
301 Tap-changer head, head version 1
305 Safety bleeder valve
308 Tap-changer head, lower part in bell-type tank design
310 Inspection window
311 Pipe connection R (NO 140X82)
312 Pipe connection S (NE 140X82)
313 Cover Q
314 Cover E2
400 Tap-changer cover
COPYRIGHT RESERVED
2/5
Tag
10366418_200_00
Än. In
DIN A1
MASCHINENFABRIK REINHAUSEN GMBH COPYRIGHT RESERVED
gepr.
The reproduction, distribution and utilization of this document as well as the communication of its contents to others without explicid authorization is
prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or design.
2462
10366418_200_00
3/5
DIN A1