You are on page 1of 58

Manufacturing Drawing and Document

230/132kV, 100/125 MVA Transformer,


for Shigdan 230/132/33 kV Substation

B 30-06-2023 ISSUED FOR APPROVAL I.H.H Y.M.K M.K.K E.J.H


A 24-03-2023 ISSUED FOR APPROVAL I.H.H Y.M.K M.K.K E.J.H
REV.NO. DATE DESCRIPTION DSN CHKD RVD APPD
PROJECT NAME

SOUTHERN EXTENSION OF THE NATIONAL ELECTRICITY GRID POWER


TRANSMISSION PROJECT UNDER EDCF
CLIENT

CONSULTANT

CONTRACTOR

VENDOR

SUBSTATION / TRANSMISSION LINE NAME

Shigdan 230/132/33 kV Substation


CLIENT DOC. NO.

CONTRACT NO.

EEP/33.20/58/14
DOCUMENT NAME

Manufacturing Drawing and Document


DOCUMENT NO. SHT. NO 54
EEP-SENEG-SH-SS-10-TS02 REV. NO B
Contents

Section 1. General

1. General scope
2. Applicable standards
3. Service conditions
4. Construction
5. Packing and Shipment
6. Painting Specification
7. Insulation Oil
8. Insulation Level
9. External Clearance

Section 2. Technical data

Section 3. Transformer Outline

Section 4. Local Control Panel Drawing

Section 5. OLTC MDU Drawing

Section 6. Bill of Material With Sub-Vendor List


1. General scope

This specification describes three phase, oil immersed transformers suitable for outdoor installation
under the service conditions mentioned herein and the information about the following power
transformer which will be supplied by HYOSUNG.

Substation Name Description Q’ty

Shigdan 3ph 50Hz 230/132kV 100/125MVA


2 sets
230/132/33 kV Substation ONAN/ONAF Cooling

2. Applicable standard

Electrical equipment covered by this specification will be complied with the following standards.

2.1 IEC 60076-1 General


2.2 IEC 60076-2 Temperature rise for liquid-immersed transformers
2.3 IEC 60076-3 Insulation levels, dielectric tests and external clearances in air

3. Service conditions
These transformers are suitable for operation under the following service conditions.
3.1 Altitude Up to 1000 meter above sea level
3.2 Designed Ambient temperature
 Maximum ambient temperature + 40℃
 Min ambient temperature 0℃
4. Construction

4.1 Core

The core consists of three columns, parallel, laminated cold-rolled and non-aging silicon-steel
having high permeability and low hysteresis loss.
The steel sheet is thoroughly coated on both sides of each sheet with insulating properties to
reduce eddy current losses to minimum.
Structural rigidity is given to the core by the use of steel plates at the bottom of the core. So that
distortion due to short circuit stresses or transport handling is prevented.

4.2 Windings

Coil is designed and manufactured to withstand the impulse voltage, prevent it from distortion
when a short circuit occurs.
Permanent current carrying joints or splices will be welded or clamped, formed, finished and
insulated to avoid concentration of dielectric stresses.
The conductors will be transposed at sufficient intervals to minimize currents and equalize the
current and temperature distribution along the winding.
The material of conductor is copper.

4.3 Tank

The transformer is provided with a suitable steel tank of substantial construction which is oil-tight
and gas-tight. All gaskets are made of materials which do not deteriorate under service conditions.
The tank has sufficient strength to withstand an internal pressure of full vacuum and vacuum
drying without damage or permanent deformation.
The transformer tank is provided with manholes and hand holes of suitable size to afford easy
access to the lower ends of bushing terminals, upper portions of the coils and side position of tap
changer.
In the case of core-form transformer the joint between the tank and cover is provided with suitable
flange and gaskets at top of the tank so that the assembly service is oil-tight and gas-tight.
The transformer is provided with lugs for lifting the essential parts also for lifting the completely
assembled transformer filled with oil.
4.4 Conservators

In air seal cell type conservator, the oil surface is completely isolated from the atmosphere by
installing an oil-resistant rubber cell in the interior of the conservator, so that atmospheric
pressure is always maintained without the necessity of employing intervening mediums.

The outside of the rubber cell attached on the inside of the conservator is filled with insulating
oil. The inside is open to the atmosphere through the silica gel breather.
(Refer to the Figure 1.)

Namely, during the operation the insulating oil is always isolated from the air by the oil-resistant
rubber and there is no oxidation or moisture contamination of the oil at all.
And this type conservator allows also the main tank to remain full oil level despite of oil
expansion and contraction with temperature changes.

A pipe connection between the lowest part of the conservator and the cover of main tank permits
the gas from main tank to pass into the conservator through Buchholz relay, so that the
transformer tank will be completely filled with oil.

Figure 1. Structural diagram of Air Seal Cell Conservator


5. Packing and Shipment

The transformers are shipped without oil. Instead of oil, the tank is filled with dry air. And pressure
gauge and stop valve are provided, so as to enable the pressure of the inert gas within the tank to be
read before installation site.

All opening for transformer components, e.g. bushings which have been removed from the transformer
during transport, are covered by means of blanking off plates. All parts are carefully packed for
transport in such a manner that they are protected against mechanical injury and injurious effect of
climatic conditions encountered during transit to their destination, as well as during long storage
before erection.
6. Painting Specification

6.1 Main Tank & Conservator: Liquid Coating

Description Inside Outside


Surface treatment SSPC-SP10 SSPC-SP10
Type of paint Epoxy Epoxy Zinc
1st Coating Dry film thickness 40 ㎛ 60 ㎛
(Primer) Color Red Brown Gray
Paint product name Jotacote F60 Barrier 80
Type of paint Epoxy
2st Coating Dry film thickness 100 ㎛
N/A
(Intermediate) Color Red Brown
Paint product name Jotacote F60
Type of paint Polyurethane Polyurethane
2 nd
Coating Dry film thickness 40 ㎛ 40 ㎛
(Top) Color N 9.5 (White) RAL 7032
Paint product name Futura Classic 2 Futura Classic 2
Total film thickness 80 ㎛ 200 ㎛
Paint manufacturer JOTUN
Note) The color of the top coat inside the tank cover is applied the same as the outside.

6.2 Radiator: Hot dip galvanizing(60 ㎛) +Liquid Coating

Description Outside
Surface treatment SSPC-SP8
Type of paint Epoxy
1st Coating Dry film thickness 40 ㎛
(Primer) Color Gray
Paint product name Jotacote F60
Type of paint Polyurethane
2nd Coating Dry film thickness 40 ㎛
(Top) Color RAL 7032
Paint product name Futura Classic 2
Total film thickness 80 ㎛
Paint manufacturer JOTUN

6.3 Control panel: Powder Coating

Description Inside Outside


Surface treatment SSPC-SP8 SSPC-SP8
Type of paint Polyester Polyester
Dry film thickness 80 ㎛ 200 ㎛
1st Coating
Color RAL 7032 RAL 7032
Paint product name PE210 PE210
Paint manufacturer CHOKWANG
7. Insulation Oil
The transformer will be filled with mineral insulating oil in accordance with IEC60296
Uninhibited type. The oil will be a highly refined mineral oil suitable for use as an
insulating and cooling medium in transformers.
* Insulating Oil containing Poly-chlorinated biphenyls (PCB) will not be used

8. Insulation Level
Insulation level will be as follows in accordance with rated voltage.

8.1 Windings
Transformer Rated Voltage Impulse withstand voltage
(1.2/50 ms)
230kV 1050kV
132kV 650kV
Neutral 95kV

8.2 Bushings
Impulse withstand voltage
Transformer Bushing Rated
(1.2/50 ms) Altitude
Rated Voltage Voltage
Required Applied
HV: 230kV 245kV 1200kV 1200kV * Up to 1000 meter
XV: 132kV 132kV 750kV 750kV ** Up to 1000 meter
Neutral 36.0kV 95kV 170kV*** Up to 1000 meter
* The test voltage of HV BUSHING is 1260KV at 1000meter.
** The test voltage of XV BUSHING is 788KV at 1000meter.
*** The test voltage of NEUTRAL BUSHING is 170KV at 1000meter.
9. External clearances
Since the site altitude is less than 1000m, external clearances are in accordance with IEC60076-3.

BIL Minimum clearances Applied clearances


(below 1000meter)
LINE TO PHASE TO LINE TO EARTH PHASE TO
EARTH PHASE PHASE
HV 1050 KV 1900 2600 1900 2600
XV 650 KV 1300 1500 1300 1500
NEUTRAL 95 KV 160 160 160 160
Section 2. Technical data
Southern Extension of the National Electricity 2.1 230-132kV 125MVA TR_shigdan
Grid Power Transmission Project

Schedule K - Technical Particular and Guarantee - Substation

2. Power Transformer (230/132kV, 125 MVA)

DESCRIPTION Required Offered

Manufacturer HYOSUNG
Outdoor, Oil filled,
Type
Core-form
Standards applied IEC 76 IEC 60076
Method of cooling ONAN/ONAF ONAN/ONAF
Number of Phases 3 3
Frequency, Hz 50 50
Rated voltage:
a) 230kV winding, kV 230 230
b) 132kV winding, KV 132 132
Rated Continuous Power on all taps at ONAN :
a) 230kV winding, kV 100 100
b) 132kV winding, KV 100 100
Rated Continuous Power on all taps at ONAF :
a) 230kV winding, kV 125 125
b) 132kV winding, KV 125 125
Voltage regulation by onload tap changer on 400kV winding, range (%) + 10 taps @1.25% + 10 taps @1.25%
Number of tap positions of on load tapchanger 21 21
Vector group (Connection symbol) YNa0d11 YNa0d11

No-load losses at rated voltage, frequency and at nominal tap position, kW 23.5

Load losses at maximum tap position between


178
230kV and 132kV winding, @ ONAN base, kW
Load losses at nominal tap position between
163
230kV and 132kV winding, @ ONAN base, Kw
Load losses at minimum tap position between
200
230kV and 132kV winding, @ ONAN base, kW
Load losses at maximum tap position between
277
230kV and 132kV winding, @ ONAF base, kW
Load losses at nominal tap position between
254
230kV and 132kV winding, @ ONAF base, kW
Load losses at minimum tap position between
311
230kV and 132kV winding, @ ONAF base, kW
Maximum load losses at mean tap position between
163
230kV and 132kV and @ ONAN base, Kw (@ Rated Tap Position)
Maximum load losses at mean tap position between
254
230kV and 132kV and @ ONAF base, kW (@ Rated Tap Position)
Total losses at mean tap position between
186.5
230kV and 132kV and @ ONAN base, kW
Total losses at mean tap position between
277.5
230kV and 132kV and @ ONAF base, kW
Total losses at tap giving maximum losses between
223.5
230kV and 132kV @ ONAN base, kW
Total losses at tap giving maximum losses between
334.5
230kV and 132kV @ ONAF base, kW

BYUCKSAN POWER Co., Ltd. _______________________________________


Tenderer's stamp and signature 1 - 1/6
Southern Extension of the National Electricity 2.1 230-132kV 125MVA TR_shigdan
Grid Power Transmission Project

Schedule K - Technical Particular and Guarantee - Substation

2. Power Transformer (230/132kV, 125 MVA)

DESCRIPTION Required Offered

Efficiency referred to 75°C at rated voltage tapping and at :


a) 100% rated output and unity power factor, % > 99.5 99.77
b) 75% rated output and unity power factor, % > 99.5 99.82
c) 50% rated output and unity power factor, % > 99.5 99.86
d) 25% rated output and unity power factor, % > 99.5 99.87
e) 100% rated output and 0.8 power factor, % > 99.5 99.72
f) 75% rated output and 0.8 power factor, % > 99.5 99.77
g) 50% rated output and 0.8 power factor, % > 99.5 99.82
h) 25% rated output and 0.8 power factor, % > 99.5 99.84
No load current at nominal tap position as percent of rated current
@ ONAN base :
a) at 90% voltage, % 0.09
b) at 100% voltage, % 0.13
c) at 110% voltage, % 0.19
No load current at nominal tap position as percent of rated current
@ ONAF base :
a) at 90% voltage, % 0.07
b) at 100% voltage, % 0.1
c) at 110% voltage, % 0.15
Content of harmonics as percent of noload current at 100% rated voltage

a) 3rd harmonics, % Approx. 30%

b) 5th harmonics, % Approx. 25%


th
c) 7 harmonics, % Approx. 10%
Impedance voltage at 75°C for nominal tap position between
standard mimimum 10.4
230kV and 132kV windings, at ONAN, (%)
Impedance voltage at 75°C for minimum tap position between
10.9
230kV and 132kV windings, at ONAN, (%)
Impedance voltage at 75°C for maximum tap position between
13.2
230kV and 132kV windings, at ONAF, (%)
Impedance voltage at 75°C for nominal tap position between
standard mimimum 13
230kV and 132kV windings, at ONAF, (%)
Impedance voltage at 75°C for minimum tap position between
13.6
230kV and 132kV windings, at ONAF, (%)
Resistance voltage at 75°C for maximum tap position between
0.178
230kV and 132kV windings, at ONAN, (%)
Resistance voltage at 75°C for nominal tap position between
standard mimimum 0.163
230kV and 132kV windings, at ONAN, (%)
Resistance voltage at 75°C for minimum tap position between
0.200
230kV and 132kV windings, at ONAN, (%)
Resistance voltage at 75°C for maximum tap position between
0.222
230kV and 132kV windings, at ONAF, (%)
Resistance voltage at 75°C for nominal tap position between
standard mimimum 0.203
230kV and 132kV windings, at ONAF, (%)
Resistance voltage at 75°C for minimum tap position between
0.249
230kV and 132kV windings, at ONAF, (%)
Zero sequence impedance at nominal tap position between
9.4(Reference Value)
230kV and 132kV windings, at ONAN, (%)

BYUCKSAN POWER Co., Ltd. _______________________________________


Tenderer's stamp and signature 1 - 2/6
Southern Extension of the National Electricity 2.1 230-132kV 125MVA TR_shigdan
Grid Power Transmission Project

Schedule K - Technical Particular and Guarantee - Substation

2. Power Transformer (230/132kV, 125 MVA)

DESCRIPTION Required Offered

Efficiency referred to 75°C at rated voltage, tapping and at :


a) 100% rated output and unity power factor, % > 99.5 99.77
b) 75% rated output and unity power factor, % > 99.5 99.82
c) 50% rated output and unity power factor, % > 99.5 99.86
d) 25% rated output and unity power factor, % > 99.5 99.87
e) 100% rated output and 0.8 power factor, % > 99.5 99.72
f) 75% rated output and 0.8 power factor, % > 99.5 99.77
g) 50% rated output and 0.8 power factor, % > 99.5 99.82
h) 25% rated output and 0.8 power factor, % > 99.5 99.84
No load current at nominal tap position as percent of rated current
@ ONAN base :
a) at 90% voltage, % 0.09
b) at 100% voltage, % 0.13
c) at 110% voltage, % 0.19
No load current at nominal tap position as percent of rated current
@ ONAF base :
a) at 90% voltage, % 0.07
b) at 100% voltage, % 0.1
c) at 110% voltage, % 0.15
Content of harmonics as percent of no-load current at 100% rated voltage

a) 3rd harmonics, % Approx. 30%

b) 5th harmonics, % Approx. 25%


th
c) 7 harmonics, % Approx. 10%
Voltage ratio at no-load and at nominal tap position 230 /132 230/132
Permissible overload occurring once a day at regular hours :
a) Continuous loading after 100% output
1) 30minutes duration
Percent overload, % 150%
Winding temperature, °C <160℃
2) 2hours duration
Percent overload, % 130%
Winding temperature, °C <140℃
b) Continuous loading after 75% output
1) 30minutes duration
Percent overload, % 150%
Winding temperature, °C <160℃
2) 2hours duration
Percent overload, % 130%
Winding temperature, °C <140℃
c) Continuous loading after 50% output
1) 30minutes duration

BYUCKSAN POWER Co., Ltd. _______________________________________


Tenderer's stamp and signature 1 - 3/6
Southern Extension of the National Electricity 2.1 230-132kV 125MVA TR_shigdan
Grid Power Transmission Project

Schedule K - Technical Particular and Guarantee - Substation

2. Power Transformer (230/132kV, 125 MVA)

DESCRIPTION Required Offered

Percent overload, % 150%


Winding temperature, °C <160℃
2) 2hours duration
Percent overload, % 130%
Winding temperature, °C <140℃
Permissible exceptional overload for duration of 30minutes :
a) Continuous loading after 100% output
Percent overload, % 150%
Winding temperature, °C <160℃
b) Continuous loading after 75% output
Percent overload, % 150%
Winding temperature, °C <160℃
c) Continuous loading after 50% output
Percent overload, % 150%
Winding temperature, °C <160℃
Maximum output without forced cooling at 40°C ambient temperature at
100 100
230kV side, (MVA)
Maximum output without forced cooling at 40°C ambient temperature at
100 100
132kV side, (MVA)
Temperature rise (referred to 40°C ambient temperature) at continuous
rated output :
a) Winding, °C 55
b) Oil, °C 50
c) Core, °C 90
Thermally upgraded paper
Class and material of winding insulation
(Class E)
Class and material of insulation of iron core laminations Pressboard(Class A)

Apar 1020-60U
Type and quality of oil Shell DIALA B
54,100 Liters

Magnetic flux density at rated voltage and 50Hz in :-

a) legs, W/.m2 < 1.75 1.62


2
b) yokes, W/.m < 1.75 1.62
Current density at rated output and at mid - position of tap

a) 230kV winding, A/mm2 3.1


2
b) 132kV winding, A/mm 3.2
May the transformer and all accessories and components be loaded in
Yes Yes
accordance with IEC publication 354, (Yes/No)
Specific core losses at 50Hz and :-

a) 10000 gauss, W/kg 0.28

b) 15000 gauss, W/kg 0.61

BYUCKSAN POWER Co., Ltd. _______________________________________


Tenderer's stamp and signature 1 - 4/6
Southern Extension of the National Electricity 2.1 230-132kV 125MVA TR_shigdan
Grid Power Transmission Project

Schedule K - Technical Particular and Guarantee - Substation

2. Power Transformer (230/132kV, 125 MVA)

DESCRIPTION Required Offered

Transformer tank
a) Type Bolted cover Bolted cover
b) thickness of side wall, mm 12
c) thickness of bottom, mm 16
d) thickness of cover, mm 16
e) filling medium for shipment Nitrogen Nitrogen

f) vacuum which tank will safely withstand, mm/kg 1 torr

Oil conservator capacity, litters 3500


Test voltage
a) Induced voltage test
1) 230kV winding at 200Hz, kV as per IEC 239 (Enhancement)
2) 132kV winding at 200Hz cycles, kV as per IEC 137.2 (Enhancement)
b) Separate source voltages test
1) 230kV winding at 60sec., kV as per IEC 50
2) 32kV winding at 60sec., kV as per IEC 50
c) Impulse test voltage full wave 1.2/50 micro sec.
1) 230kV winding, kV 1050 1050
2) 132kV winding, kV 650 650
R.M.S. symmetrical short circuit current,
a) at 230kV terminals, kA 31.5kA 31.5kA
b) at 132kV terminals, Ka 31.5kA 31.5kA
Time to withstand short circuit, sec. 3 3
Noise level at 3Mts with all fans working., dBA < 70 <70
On-load tap-changer
a) Manufacturer MR Germany MR Germany
b) Type Vacuum type
c) Current rating, A 650

230kV regulation
d) Voltage class, kV (OLTC Um is 170kV on end
of series winding)

e) System of design, kV 245kV(regulation winding)

f) Life time of contact ≥800000 600,000


g) Total number of voltage steps 21 21
h) Total range of voltage variation, % +10*1.25% +10*1.25%
I) Voltage variation per step, V 1659.9
j) Supply voltage of drive motor (A.C. or D.C., V) 380 V, AC 380 V, AC
k) Permissible number of duty cycles per hour 338
l) Control circuit voltage , V, DC 125 , DC 125 , DC

BYUCKSAN POWER Co., Ltd. _______________________________________


Tenderer's stamp and signature 1 - 5/6
Southern Extension of the National Electricity 2.1 230-132kV 125MVA TR_shigdan
Grid Power Transmission Project

Schedule K - Technical Particular and Guarantee - Substation

2. Power Transformer (230/132kV, 125 MVA)

DESCRIPTION Required Offered

Bushings
1) 230kV bushing
1) Manufacturer Trench
2) Type COT
3) Rated current, A as per S.L.D 1000

245(Name plate)
4) Rated voltage, kV 230
300(Test voltage)

505(Name plate)
5) Power frequency test voltage, kV 460
505(Test voltage)
1200(Name plate)
6) Impulse test voltage, kV 1200
1260(Test voltage)
20
7) creepage distance, mm/kV 31
(31)
b) 132kV bushing
1) Manufacturer Trench
2) Type COT
3) Rated current, A as per S.L.D 1000

170(Name plate)
4) Rated voltage, kV 132
170(Test voltage)

355(Name plate)
5) Power frequency test voltage, kV 315
355(Test voltage)
750(Name plate)
6) Impulse test voltage, kV 750
788(Test voltage)
20
7) creepage distance, mm 31
(31)
c) Bushing Current Transformer (neutral) 200-100/1/1A 800-600-400/1/1A
Weights :
a) Core and windings, kg 57,100

b) Oil, kg 48,700

c) Tank without heat exchanger, kg 27,100


d) Total power transformer with oil and including all accessories,
149,300 kg
ready for commissioning, kg
e) Transport weight of heaviest part, kg 85,000
Dimensions
a) Overall length, mm 10,700
b) Overall width, mm 6,720
c) Overall height, mm 8,500
d) Height without bushings, mm 7,800
e) Un tanking height, mm 10,300
f) Transportation dimension of heaviest part
1) Length, mm 8,700
2) Width, mm 5,100
3) Height, mm 4,200
g) Transportation dimension of largest part
1) Length, mm 8,700
2) Width, mm 5,100
3) Height, mm 4,200

h) Outline drawing No. C41-4177-202209-5596-2000-001

Wiring and Terminal Cabinets


a) Low Voltage supply, V, AC 380/220 380/220
b) Control voltage, V, DC 125 125

BYUCKSAN POWER Co., Ltd. _______________________________________


Tenderer's stamp and signature 1 - 6/6
Section 3. Transformer Outline
PARTLIST

NOTES:

HV SIDE

Y1 R S T
Y2
N
Y3 r s t

XV SIDE

BACK VIEW
(VIEW LOOKING FROM HV SIDE)

"A"

VIEW "A"

DETAIL OF CORE AND CORE CLAMP GROUNDING R S T

r s t

B 30.06.2023 ISSUED FOR APPROVAL J.H.CHOI I.H.HONG S.R.YU E.J.HONG

A 24.03.2023 ISSUED FOR APPROVAL J.H.CHOI I.H.HONG S.R.YU E.J.HONG


REV. NO. DATE DESCRIPTION DSN CHKD RVD APPD

PROJECT NAME
SOUTHERN EXTENSION OF THE NATIONAL ELECTRICITY
GRID POWER TRANSMISSION PROJECT UNDER EDCF
CLIENT

ETHIOPIAN ELECTRIC POWER


CONSULTANT

BYUCKSAN POWER Co Ltd.


CONTRACTOR

HYOSUNG HEAVY
INDUSTRIES

DETAIL OF LHD SUPPORT PAD VENDOR

HYOSUNG HEAVY
INDUSTRIES

SUBSTATION NAME
RAIL GAGUE=2800 RAIL GAGUE=1500
Shigdan 230/132/33 kV Substation
(RAIL ℄-℄) 2900 (RAIL ℄-℄) 1600
CLIENT DWG. NO.
UNIT

CONTRACT NO.
EEP/33.20/58/14 SCALE

DWG. NAME
LEFT SIDE VIEW
OUTLINE
FRONT VIEW RIGHT SIDE VIEW
(VIEW LOOKING FROM XV SIDE) DWG. NO. SHT. NO. B
C41-4177-202209-5596-2000-001
REV. NO. 1/1
M36
90

100 = = 2-M12 TAP


254 254
141

=
415

518
150
274

50
35
500

12
150

100 100 140


RAIL DETAIL NOTES:
DETAIL OF BI-DIRECTIONAL WHEEL 400 400 22 22
(OUT OF SCOPE)
ANCHOR DETAIL DETAIL OF GROUND PAD

4284
6896 2-GROUNDING PAD POSITION
2773 4123
3686 (JACKING POINT)
2115 (JACKING POINT) 3300 (GROUNDING POSITION)
POSITION FOR
200 825 1025 200 POSITION FOR
XPRD PIPE FOR OLTC
4-JACKING POSITION 756 XPRD PIPE FOR MAIN TANK
WHEEL
TR CENTER
FIG-1

400
1752 (JACKING POINT)
1277 (JACKING POINT)

1624
1561
1370

1170
1600
875
RAIL CENTER
2540

3490
1277 (JACKING POINT)

TR CENTER

1752 (JACKING POINT)


1149

1170
1370

1561

400
225
8-ANCHOR POSITION POSITION FOR RAIL
1728 786
REFER FIG-3 FIG-2
XPRD PIPE FOR MAIN TANK
CENTRE OF CONTROL
4654 CABLE TO REMOTE / LOCAL

A 24.03.2023 ISSUED FOR APPROVAL J.H.CHOI I.H.HONG S.R.YU E.J.HONG


TR CENTER REV. NO. DATE DESCRIPTION DSN CHKD RVD APPD
EARTHING PAD FOR NEUTRAL RAIL CENTER PROJECT NAME
SOUTHERN EXTENSION OF THE NATIONAL ELECTRICITY
GROUNDING BUSBAR GRID POWER TRANSMISSION PROJECT UNDER EDCF
CLIENT

ETHIOPIAN ELECTRIC POWER


CONSULTANT

BYUCKSAN POWER Co Ltd.


CONTRACTOR
1012

HYOSUNG HEAVY
INDUSTRIES
677

100 PLINTH LEVEL


VENDOR

HYOSUNG HEAVY
INDUSTRIES

SUBSTATION NAME

Shigdan 230/132/33 kV Substation


CLIENT DWG. NO.
UNIT

CONTRACT NO.
EEP/33.20/58/14 SCALE
400 825 825 400 DWG. NAME

FOUNDATION
DWG. NO. SHT. NO. 1/1
C41-4177-202209-5596-2000-002
REV. NO. A
HV SIDE

NOTES:

XV SIDE

TOP VIEW

B 30.06.2023 ISSUED FOR APPROVAL J.H.CHOI I.H.HONG S.R.YU E.J.HONG

A 24.03.2023 ISSUED FOR APPROVAL J.H.CHOI I.H.HONG S.R.YU E.J.HONG


REV. NO. DATE DESCRIPTION DSN CHKD RVD APPD

PROJECT NAME
SOUTHERN EXTENSION OF THE NATIONAL ELECTRICITY
GRID POWER TRANSMISSION PROJECT UNDER EDCF
CLIENT

ETHIOPIAN ELECTRIC POWER


CONSULTANT

BYUCKSAN POWER Co Ltd.


CONTRACTOR

HYOSUNG HEAVY
INDUSTRIES

VENDOR

HYOSUNG HEAVY
INDUSTRIES

SUBSTATION NAME

LEFT SIDE VIEW FRONT VIEW Shigdan 230/132/33 kV Substation


CLIENT DWG. NO.
UNIT

CONTRACT NO.
EEP/33.20/58/14 SCALE

DWG. NAME

SHIPPING OUTLINE
DWG. NO. SHT. NO. 1/1
C41-4177-202209-5596-2000-003
REV. NO. B
R r S s T t N

BCT 01 BCT 02 BCT 03 B BCT 04


560/1A 370/2A 560/2A 800-600-400/1A
CL3.0 15VA CL3.0 15VA CL3.0 15VA PX CLASS
FOR AVR FOR WTI FOR WTI
BCT 05
800-600-400/1A

THREE PHASE
PX CLASS

NOTES:
HV 230,000 V AUTO + + +

LV 132,000 V TRANSFORMER - - -

HV 1,050 kV
LV 650 kV HV-LV %
BCT 06
200-100/1A
5P20 15-7.5VA

NEUTRAL 95 kV

ONAN ONAF

HV 100 MVA 125 MVA

LV 100 MVA 125 MVA

R r S s T t N

B
560/1A 370/2A 560/2A 800-600-400/1A
CL3.0 15VA CL3.0 15VA CL3.0 15VA PX CLASS
FOR AVR FOR WTI FOR WTI
800-600-400/1A
PX CLASS

+ + +

- - -

200-100/1A
5P20 15-7.5VA

VECTOR GROUP
B 30.06.2023 ISSUED FOR APPROVAL J.H.CHOI I.H.HONG I.H.HONG E.J.HONG
YNa0(d11) A 24.03.2023 ISSUED FOR APPROVAL J.H.CHOI I.H.HONG I.H.HONG E.J.HONG
REV. NO. DATE DESCRIPTION DSN CHKD RVD APPD
PROJECT NAME
SOUTHERN EXTENSION OF THE NATIONAL ELECTRICITY
GRID POWER TRANSMISSION PROJECT UNDER EDCF
CLIENT

ETHIOPIAN ELECTRIC POWER


CONSULTANT

BYUCKSAN POWER Co Ltd.


CONTRACTOR

HYOSUNG HEAVY
INDUSTRIES

VENDOR

HYOSUNG HEAVY
INDUSTRIES

SUBSTATION NAME

Shigdan 230/132/33 kV Substation


CLIENT DWG. NO.
UNIT

CONTRACT NO.
EEP/33.20/58/14 SCALE

DWG. NAME
MAIN NAME PLATE
DWG. NO. SHT. NO. 1/1
C41-4177-202209-5596-2000-004
REV. NO. B
VALVE LOCATION PLATE
NOTES:

B 30.06.2023 ISSUED FOR APPROVAL J.H.CHOI I.H.HONG S.R.YU E.J.HONG

A 24.03.2023 ISSUED FOR APPROVAL J.H.CHOI I.H.HONG S.R.YU E.J.HONG


REV. NO. DATE DESCRIPTION DSN CHKD RVD APPD

PROJECT NAME
SOUTHERN EXTENSION OF THE NATIONAL ELECTRICITY
GRID POWER TRANSMISSION PROJECT UNDER EDCF
CLIENT

FRONT VIEW BACK VIEW ETHIOPIAN ELECTRIC POWER


LEFT SIDE VIEW RIGHT SIDE VIEW
(VIEW LOOKING FROM LV SIDE) (VIEW LOOKING FROM HV SIDE)
CONSULTANT

BYUCKSAN POWER Co Ltd.


CONTRACTOR

HYOSUNG HEAVY
INDUSTRIES

VENDOR

HYOSUNG HEAVY
INDUSTRIES

SUBSTATION NAME

Shigdan 230/132/33 kV Substation


CLIENT DWG. NO.
UNIT

CONTRACT NO.
EEP/33.20/58/14 SCALE

DWG. NAME

VALVE LOCATION PLATE


DWG. NO. SHT. NO. 1/1
C41-4177-202209-5596-2000-005
REV. NO. B
Section 4. Local Control Panel Drawing
Section 5. OLTC MDU Drawing
1 2 3 4 5 6 7 8 9 10 11 12
380V, 50HZ, 3AC/N, PE 125V DC 220V, 50HZ
L1 L+ L1
L2
L3
A N A
PE

X1 PE 1 5 6 2 2A 3 4 17 19

300

301
X1:29 X1:31
/2.A2 /3.B3

220
200

500

502
B B
101

108

113
21
S10
22

221
1 3 5
1
X20 4
Q1 B2
/2.G10 2

204
(< 40°C)

222
C 2 4 6 X2 1 2 C
X3 1 21 73
114
Q1 K20

205

233

223
109 /2.G10 22 /2.G6 74
102 1

501

503
1 3 5 1 3 5 1 1
K1 K2 E1
PE PE
/2.F5 2 4 6 /2.F7 2 4 6
R1 R3 214
2
D D
X2 PE
Fuer diese technische Unterlage behalten wir uns gemaess

224
2 2

206

213
X2 4 5 X3 2
DIN 34 Abschnitt 2.1 und 2.2 alle Rechte vor.

TAP-CHANGER IN OPERATION
225

SIGNAL MOTOR CIRCUIT


207
103

110

115

E E
X20 5

K1:A2 X1:50

226
/2.F2 /3.E3
116

X20 1 2 3
104

C C
330

304

S8A S8B
NC NO NC NO X1 7 7A 8 9 18 20
105

111

117

C C
S6A S6B L- N
F NC NO NC NO F
106

118

U1 V1 W1

M1
M
3

PE

G G

DRIVE HEATER LIGHTING


DO NOT MODIFY MANUALLY
DRAWING BY CAD

H H
DATE 22.05.2023 LANGUAGE: PROJECT: =
EXEC. WAM MOTOR DRIVE UNIT EN +
VERIFIED SO SHEET 1
NO. MODIFICATION DATE NAME STANDARD ORIGIN. REPL. REPL.BY
10357962_00 7 SH.

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
TO POS. 21 LOWER WITH STEP-BY-STEP OPERATION TO POS. 1 RAISE Q1 "OFF"

A A

REMOTE
X1 29 30 10 11 12 13 14 15
X1:2 300

344
/1.B5

331
363 LOCAL
2 4 1 3
13
S3 S32
Q1 339 1 3 346 /4.G1 2 4
/2.G10 14
345
332
B B
53 53
K1 K2

332
/2.G5 54 /2.G7 54

339 346
21 13 43 31
K20
/2.G6 22 14 44 32

369
340

366
X20 6 7 15 8

338

352
C 333 333 C

353
C C C C C C
S14 S4 S13B S13A S5 S12
NC NO NC NO NC NO NC NO NC NO NC NO

341
334 348 354
C C C
S37 S1 S2
NC NO NC NO NC NO

342
D D

355

356
Fuer diese technische Unterlage behalten wir uns gemaess

X20 9 10 11 14 12 13
357 358
61 83 83 61
54
K1 K2
336

350
DIN 34 Abschnitt 2.1 und 2.2 alle Rechte vor.

K20 /2.G5 62 84 /2.G7 84 62


/2.G6 53

361
359

347

360
13
E 22 22 84 62 E
K2 K37H K1 K20

343
/2.F9 14
/2.G7 21 /2.G5 21 /2.G6 83 353 61
337

351
A1 A1 A1 A1 C1
343

K1 K20 K2 K37H Q1
330 /2.F5 A2 /2.F6 A2 330 /2.F7 A2 /2.F9 A2 /2.G10 C2
/1.E5
X1:7

TO POS. 21 LOWER X1 16 TO POS. 1 RAISE

F F
K1 K20 K2 K37H Q1
/2.E4 A1 A2 /2.E6 A1 A2 /2.E7 A1 A2 /2.E8 A1 A2

/1.D2 1 2 /2.C5 13 14 /1.D3 1 2 /2.E5 13 14 1 2


/1.D2 3 4 /2.C4 21 22 /1.D3 3 4 21 22
/1.D3 5 6 /2.C7 31 32 /1.D4 5 6 31 32 3 4
/2.E7 21 22 /2.C6 43 44 /2.E4 21 22 43 44 /1.C2
/2.B4 53 54 /2.E5 53 54 /2.B7 53 54 53 54 5 6
/2.E9 61 62 /2.E10 61 62 /2.E10 61 62 61 62
71 72 /1.C12 73 74 71 72 71 72
/2.B3 13 14
/2.E9 83 84 /2.E9 83 84 /2.E10 83 84 83 84
G /1.C12 21 22
G
/4.C7 43 44
/3.B5 31 32
/2.E10 C1 C2
DO NOT MODIFY MANUALLY
DRAWING BY CAD

H H
DATE 22.05.2023 CONTROL LANGUAGE: PROJECT: =
EXEC. WAM MOTOR DRIVE UNIT EN +
VERIFIED SO SHEET 2
NO. MODIFICATION DATE NAME STANDARD ORIGIN. REPL. REPL.BY
10357962_00 7 SH.

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12

A A

X1 31 34 35 36 37

301

406

386

390
/1.B6 /5.A2 /5.A8
X1:2A U5:11 U7:11

381
B B
31
Q1
/2.G10 32

407
X20 40

382
C C
C

TRIPPING MOTOR PROTECTIVE SWITCH


S24
NC NO

383
X20 41
D D
Fuer diese technische Unterlage behalten wir uns gemaess

384
DIN 34 Abschnitt 2.1 und 2.2 alle Rechte vor.

X1
MCB1
RED X2
E E
A1
K30
X1:7A /3.F5 A2 U5:10 U7:10
/1.E6 /5.F2 /5.F8
304

385

408

387

391
X1 50 47 46 45 44

F F
K30
/3.E5 A2 A1

16
/4.C4 15
18

26
25
28
G G

INCOMPLETE SWITCHING OPERATION


DO NOT MODIFY MANUALLY
DRAWING BY CAD

H H
DATE 22.05.2023 CONTROL POTENTIAL TERMINALS LANGUAGE: PROJECT: =
EXEC. WAM MOTOR DRIVE UNIT EN +
VERIFIED SO SHEET 3
NO. MODIFICATION DATE NAME STANDARD ORIGIN. REPL. REPL.BY
10357962_00 7 SH.

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12

A A

X1 215 X1 155 X1 152 X1 272 273 X1 276

B B

580

583

592
508

520

540
C C
6 8 15 43 C C C
S32 K30 Q1 S26A S27A S15
/4.G1 5 7 /3.G5 16 18 44 NC NO NC NO NC NO

581

582

584

585

593

594
509

510

521

522

541
D D
Fuer diese technische Unterlage behalten wir uns gemaess

END POSITION SWITCH 21

END POSITION SWITCH 1


DIN 34 Abschnitt 2.1 und 2.2 alle Rechte vor.

INCOMPLETE SWITCHING OPERATION

TAP-CHANGER IN OPERATION
E E

SIGNAL MOTOR CIRCUIT


REMOTE
LOCAL

F F

X1 241 242 X1 180 181 X1 177 X1 291 292 293 294 X1 299 300

S32

2 1
/2.B8
4 3
6 5
/4.C1
8 7
G G
DO NOT MODIFY MANUALLY
DRAWING BY CAD

H H
DATE 22.05.2023 INDICATION CIRCUITS LANGUAGE: PROJECT: =
EXEC. WAM MOTOR DRIVE UNIT EN +
VERIFIED SO SHEET 4
NO. MODIFICATION DATE NAME STANDARD ORIGIN. REPL. REPL.BY
10357962_00 7 SH.

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12

S38M S38P S39M S39P


1 1
A b a b a A
1 1
2 2
2 2
3 1 3 1
X1:36 3 X1:37 3
/3.B6 2 /3.B7 2
4 4
3 3
5 5
4 4
6 6
5 5
7 7
B 6 6 B
8 8
7 7
386

633

634

635

390

638

639

640
9 9
8 8
10 10
9 9
11 11
10 10
12 12
11A 11A
2 5 4 1 13 2 5 4 1 13
11B 11B
11 11
C U5 14 U7 14 C
11C 11C
10 10

20 X 10 OHM

20 X 10 OHM
15 15
12 12
+

+
-

-
7 8 16 7 8 16
13 13
17 17
14 14
18 18
15 15
19 19
16 16
20 20
D 17 17
D
Fuer diese technische Unterlage behalten wir uns gemaess

21 21
18 18
22 22
19 19

391

641

642
387

636

637

23 23
20 20
DIN 34 Abschnitt 2.1 und 2.2 alle Rechte vor.

24 24
21 21
25 25

26 26
E 27 27
E
28 28

29 29

30 30
/3.E6 /3.E7
X1:45 X1:44
X1 211 212 31 X1 213 214 31

4...20 mA 32 4...20 mA 32

33 33
F F
34 34

35 35

36 36

37 37

G G
DO NOT MODIFY MANUALLY
DRAWING BY CAD

H H
DATE 22.05.2023 REMOTE POSITION INDICATION LANGUAGE: PROJECT: =
EXEC. WAM MOTOR DRIVE UNIT EN +
VERIFIED SO SHEET 5
NO. MODIFICATION DATE NAME STANDARD ORIGIN. REPL. REPL.BY
10357962_00 7 SH.

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12

S40M S40P S61M S61P S62M S62P


1 1
A A
1 2 1 2 1
20 10 8 4 2 1 20 10 8 4 2 1
+ - + -
2 1 3 2 X 1 3 2 X 1

3 2 4 4 X 2 4 4 X 2

4 3 5 8 X X 3 5 8 X X 3

5 4 6 10(-) X 4 6 10(-) X 4

6 5 7 20(+) X X 5 7 20(+) X X 5

B 7 6 X X 6 X X 6 B
8 7 X X X 7 X X X 7

9 8 X 8 X 8

10 9 X X 9 X X 9

11 10 X 10 X 10

12 11A X X 11A X X 11A

13 11B X X 11B X X 11B


C C
14 11C X X 11C X X 11C

15 12 X X 12 X X 12

16 13 X X X 13 X X X 13

17 14 X X 14 X X 14

18 15 X X X 15 X X X 15

19 16 X X X 16 X X X 16

D 20 17 X X X X 17 X X X X 17
D
Fuer diese technische Unterlage behalten wir uns gemaess

21 18 X X 18 X X 18

22 19 X X X 19 X X X 19

23 20 X 20 X 20
DIN 34 Abschnitt 2.1 und 2.2 alle Rechte vor.

24 21 X X 21 X X 21

25

26
E E
27

28
BCD

BCD
29

30

31

32

F 33 F
34

35

36

G G
DO NOT MODIFY MANUALLY
DRAWING BY CAD

H H
DATE 22.05.2023 REMOTE POSITION INDICATION LANGUAGE: PROJECT: =
EXEC. WAM MOTOR DRIVE UNIT EN +
VERIFIED SO SHEET 6
NO. MODIFICATION DATE NAME STANDARD ORIGIN. REPL. REPL.BY
10357962_00 7 SH.

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12

B2 THERMOSTAT
E1 HAND LAMP 33 1 2 3 4 5 6 - 11 - 15 16 17 18 - 24 25 26 27 28 29 30 31 32 33 1 2 3 4
A A
K1 MOTOR CONTACTOR
S1/C-NO
K2 MOTOR CONTACTOR
S1/C-NC
K20 AUXILIARY CONTACTOR
S2/C-NO
K30 TIMING RELAY
S2/C-NC
K37H AUXILIARY CONTACTOR FOR AUTOMATIC PASSAGE OF POSITIONS S12,S14/C-NO
M1 MOTOR S13A,S13B/C-NO
MCB1 SIGNALLING LAMP
Q1 MOTOR PROTECTIVE SWITCH S15/C-NO
R1 HEATER S15/C-NC
B B
R3 HEATER WITH PTC RESISTOR
S1 CAM-OPERATED SWITCH
S2 CAM-OPERATED SWITCH
S3 RAISE/LOWER CONTROL SWITCH
S4 END POSITION SWITCH
S5 END POSITION SWITCH
S6A END POSITION SWITCH
S6B END POSITION SWITCH
C S8A HAND CRANK SAFETY SWITCH S24/C-NO C
S8B HAND CRANK SAFETY SWITCH S24/C-NC
S10 DOOR CONTACT
S12 CAM-OPERATED DIRECTIONAL SWITCH
S13A CAM-OPERATED DIRECTIONAL SWITCH
S13B CAM-OPERATED DIRECTIONAL SWITCH
S14 CAM-OPERATED DIRECTIONAL SWITCH
S15 CAM-OPERATED NON-DIRECTIONAL SWITCH
S24 CAM-OPERATED NON-DIRECTIONAL SWITCH
D S26A END POSITION SIGNALLING SWITCH D
Fuer diese technische Unterlage behalten wir uns gemaess

S27A END POSITION SIGNALLING SWITCH


S32 LOCAL/REMOTE SWITCH
S37 SWITCH FOR AUTOMATIC PASSAGE OF POSITIONS
DIN 34 Abschnitt 2.1 und 2.2 alle Rechte vor.

S38M POSITION TRANSMITTER MODULE, RESISTOR-TYPE


S38P POSITION TRANSMITTER BOARD
S39M POSITION TRANSMITTER MODULE, RESISTOR-TYPE
S39P POSITION TRANSMITTER BOARD
S40M POSITION TRANSMITTER MODULE WITH N/O CONTACT RANGE E
E
S40P POSITION TRANSMITTER BOARD
S61M MODULE WITH DIODE MATRIX
S61P POSITION TRANSMITTER BOARD
S62M MODULE WITH DIODE MATRIX S4,S5/C-NC
S62P POSITION TRANSMITTER BOARD
S37/C-NO
U5 MEASURING TRANSDUCER
11C 11A
U7 MEASURING TRANSDUCER
S26A/C-NC
X1 TERMINAL S26A/C-NO
F X2 TERMINAL S27A/C-NC F
X3 TERMINAL S27A/C-NO
X20 TERMINAL
S6A,S6B/C-NC

G G
/2.A11

/4.A11
/1.A12

/1.A12

/4.F11
/4.F11
/1.F12

/1.F12
/1.A1
/1.A1

/4.A1
/1.A2
/1.A2
/1.A5
/1.A6
/1.A7
/1.A9
/1.A2
/1.A3

/2.A7
/2.A9
/2.A9
/2.A9

/2.A3
/2.A3

/3.A5
/3.A5
/3.A5
/3.A7

/4.A7

/4.F1

/4.A9
/4.A9
/2.A4

/3.A4

/4.A4
/1.F5
/1.F6
/1.F7
/1.F9

/2.F5

/3.F7
/3.F5
/3.F5
/3.F5

/4.F7

/5.F3
/5.F3
/5.F8
/5.F9

/4.F2

/4.F9
/4.F9
/4.F9
/4.F9
/3.F4

/4.F4
/4.F4

292 S26A :NO

294 S27A :NO

S15 :NO
291 S26A :NC

293 S27A :NC

S15 :NC
Q1:C1
K1:A2

46 MCB1:X2
K30 :A2
X1:2A

X1:7A
X1:31

S10 :21

Q1:21

Q1:31
U5 :11
U7 :11
X1:29

X1:50

K2 :53

Q1:22
K20 :73

Q1:13

X20 :40

U7 :10
U5 :10

Q1:43
K30 :15

K30 :16
K30 :18
16 K37H:14

K20 :74

Q1:44

272 S26A :C
273 S27A :C
S15 :C
Q1:1

B2 :1

S3 :1
Q1:3
Q1:5

X20 :5

S3 :3
S32 :3
S32 :2

X1:2

U5 :7
U5 :8
U7 :7
U7 :8
S32 :6
S32 :5
S32 :7
X2 :4
1

11

31

181
211

241
PE
PE
PE

5
6
7

8
9
10

12
13

15

17
18
19
20
29
30

35
36
37

45

47
50
152
155
177
180

212
213

215

242

276

299
300
4

14

34

44

214
2A

7A

X1
DO NOT MODIFY MANUALLY

L1:
L+ :

L1:

L2 :
L3 :
L- :

N:

-:
+:
-:
+:
DRAWING BY CAD

H H
DATE 22.05.2023 LANGUAGE: PROJECT: =
EXEC. WAM MOTOR DRIVE UNIT EN +
VERIFIED SO SHEET 7
NO. MODIFICATION DATE NAME STANDARD ORIGIN. REPL. REPL.BY 10357962_00 7 SH.

1 2 3 4 5 6 7 8 9 10 11 12
Section 6. Bill of Material With Sub-Vendor List

NO Item Q’ty Specification Maker

- COT 1200-1000
TRENCH/
1 HV BUSHING 3 EA - 245kV, 1200kV BIL, 1000A
FRANCE
- Up to 1000meter

- COT 750-1000
TRENCH/
2 XV BUSHING 3 EA - 170kV, 750kV BIL, 1000A
FRANCE
- Up to 1000meter

- COT 170-1000
TRENCH/
3 NEUTRAL BUSHING 1 EA - 36kV, 170kV BIL, 1000A
FRANCE
- Up to 1000meter

- KMA3452000 KYEMYUNG/
4 TV BUSHING 2 EA - 34.5kV, 200kV BIL, 2000A KOREA
- Up to 1000meter
MR/
5 ON LOAD TAP CHANGER 1 EA - 3 X VM I 651-170/C-12 23 3W
GERMANY
WINDING TEMPERATURE - Compact type MESSKO /
6 2 EA
INDICATOR - Measuring range: 0~160°C GERMANY
OIL TEMPERATURE - Compact type MESSKO /
7 1 EA
INDICATOR - Measuring range: 0~160°C GERMANY
PRESSURE RELIEF - XPRD Type QUALITROL /
8 2 EA
- Operating pressure: 12 PSI USA
DEVICE FOR MAIN
PRESSURE RELIEF - XPRD Type QUALITROL /
9 3 EA
- Operating pressure: 20 PSI USA
DEVICE FOR OLTC
EMB/
10 BUCHHOLZ RELAY 1 EA - Double float type
GERMANY
TAIJIN /
11 FAN MOTOR 10 EA - 3PH 50HZ 380V
KOREA
SUDDEN PRESSURE RISE QUALITROL /
12 1 EA - 900 Type
RELAY USA
TAIJIN /
13 OIL LEVEL GAUGE 1 EA
KOREA
DEHYDRATING TAIJIN /
14 1 EA - Silica Gel Type
BREATHER KOREA

A.V.R 1 EA - 230PRO MR/


15
GERMANY

APAR /
16 INSULATION OIL -
INDIA
HV BUSHING
TECHNICAL DATASHEET 41431070 V1

Bushing Type OIL/AIR COT 1200-1000 L300

Connection type Cable

General specifications
Altitude 1300 m Mounting angle (from vertical) 30 °
Length under flange L1 984 mm Product information 44497672E
CT length L4 300 mm IEC 60137-2017
Standard
Temperature range -30 +40 °C -

Electrical specifications
Rated lightning impulse withstand voltage (BIL) 1200 kV Rated highest voltage for equipment (Um) 245 kV
Rated current (Ir) 1000 A Phase to earth voltage 142 kV
Dry switching impulse withstand voltage (SIL dry) 850 kV Power frequency withstand voltage (AC) dry 505 kV
wet 460 kV
Rated short-circuit current (Ith) 31,5 kA 3s Rated frequency 50/60 Hz

Routine tests (Up to 1000m)


Measurement of dielectric dissipation factor and capacitance at ambient temperature 182/300 kV
Measurement of partial discharge quantity # 10Pc 300 kV
Dry lightning impulse voltage withstand test 1260 kV
Dry power-frequency voltage withstand test 50 Hz 60s 505 kV
Test tap 2 kV
Voltage withstand test
Voltage tap - kV
Tightness test 1,5 barg
Top Terminal (air side)
Flat pad Aluminium 100x100 4xø14,5 / 44.5x44.5 Thickness 15 mm

Head
Oil level indicator type Optical

Insulator
Cantilever test load 500 daN
Insulator material Brown porcelain
Arcing distance AD 2400 mm
Creepage distance 9300 mm
USCD (IEC 60815) 53,7 mm/kV

Flange
Flange Round 12xø22 BCD 400 mm

Draw lead stud


Standard draw lead stud drilling ø8x35 Lemb 2750 (mm)

Other
Standard sparkgaps
XV BUSHING
TECHNICAL DATASHEET 41431268 V1

Bushing Type OIL/AIR COT 750-1000 L300

Connection type Fixed conductor

General specifications
Altitude 1300 m Mounting angle (from vertical) 30 °
Length under flange L1 720 mm Product information 44497653E
CT length L4 300 mm IEC 60137-2017
Standard
Temperature range -30 +40 °C -

Electrical specifications
Rated lightning impulse withstand voltage (BIL) 750 kV Rated highest voltage for equipment (Um) 170 kV
Rated current (Ir) 1000 A Phase to earth voltage 98 kV

Power frequency withstand voltage (AC) dry 355 kV


wet 325 kV
Rated short-circuit current (Ith) 31,5 kA 3s Rated frequency 50/60 Hz

Routine tests (Up to 1000m)


Measurement of dielectric dissipation factor and capacitance at ambient temperature 104/170 kV
Measurement of partial discharge quantity # 10Pc 170 kV
Dry lightning impulse voltage withstand test 788 kV
Dry power-frequency voltage withstand test 50 Hz 60s 355 kV
Test tap 2 kV
Voltage withstand test
Voltage tap - kV
Tightness test 1,5 barg
Top Terminal (air side)
Flat pad Aluminium 100x100 4xø14,5 / 44.5x44.5 Thickness 15 mm

Head
Oil level indicator type Optical

Insulator
Cantilever test load 400 daN
Insulator material Brown porcelain
Arcing distance AD 1460 mm
Creepage distance 5270 mm
USCD (IEC 60815) 53,7 mm/kV

Flange
Flange Round 12xø16 BCD 290 mm

Lower terminal (oil side)


Cylindrical flat spot Copper ø38x85 Thickness 20 2xø13 spacing 45 (mm)

Shield
Bayonet shield H195 ø240/160 (mm)
Type of coating : Epoxy

Other
Standard sparkgaps
NEUTRAL BUSHING
TECHNICAL DATASHEET 41431092 V2

Bushing Type OIL/AIR COT 170-1000 L300

Connection type Cable

General specifications
Altitude 3000 m Mounting angle (from vertical) 30 °
Length under flange L1 440 mm Product information 44497653E
CT length L4 300 mm IEC 60137-2017
Standard
Temperature range -30 +40 °C -

Electrical specifications
Rated lightning impulse withstand voltage (BIL) 170 kV Rated highest voltage for equipment (Um) 36 kV
Rated current (Ir) 1000 A Phase to earth voltage 21 kV

Power frequency withstand voltage (AC) dry 77 kV


wet 70 kV
Rated short-circuit current (Ith) 25 kA 3s Rated frequency 50/60 Hz

Routine tests (Up to 1000m)


Measurement of dielectric dissipation factor and capacitance at ambient temperature 22 kV
Measurement of partial discharge quantity # 10Pc 36 kV
Dry lightning impulse voltage withstand test - kV
Dry power-frequency voltage withstand test 50 Hz 60s 77 kV
Test tap 2 kV
Voltage withstand test
Voltage tap - kV
Tightness test 1,5 barg
Top Terminal (air side)
Flat pad Aluminium 100x100 4xø14,5 / 44.5x44.5 Thickness 15 mm

Head
Oil level indicator type Optical

Insulator
Cantilever test load 200 daN
Insulator material Brown porcelain
Arcing distance AD 340 mm
Creepage distance 1116 mm
USCD (IEC 60815) 53,7 mm/kV

Flange
Flange Round 4xø24 BCD 184 mm

Draw lead stud


Standard draw lead stud drilling ø8x35 Lemb 585 (mm)

Other
Standard sparkgaps
ON LOAD TAP CHANGER
A_TEMP
MASCHINENFABRIK REINHAUSEN GMBH COPYRIGHT RESERVED

gepr.
The reproduction, distribution and utilization of this document as well as the communication of its contents to others without explicid authorization is
prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or design.

gez. edv 01.01.01


Än. In Änd.-Nr. Tag Name

312
313

311
305

514
314

513

512

M DRIVE SIDE OF TAP


511

505

SELECTOR / SIDE OF
414

413

412
160

411

405

CHANGE-OVER SELECTOR
310 301 170

10
POLE A ( H1 )

308

300

510

90

500

501

508

80

410

DRIVE SHAFT ARRANGEMENT


130
POLE C ( H3 )

400

401

408

120

40

50
POLE B ( H2 )

Overview representation

10366418_200_00
1/5

DIN A1
0 DRIVE SHAFT ARRANGEMENT
10 Drive: TAPMOTION® ED100S
40 Drive shafts 1.990 mm , revolutions: 16,50
50 Gear CD6400, 2:1, A
prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or design.
The reproduction, distribution and utilization of this document as well as the communication of its contents to others without explicid authorization is
80 Drive shafts 1.851 mm , revolutions: 8,25
90 Gear OGST, 16,5:1, B
120 Drive shafts 1.846 mm , revolutions: 8,25
130 Gear OGST, 16,5:1, B
160 Drive shafts 1.851 mm , revolutions: 8,25
170 Gear OGST, 16,5:1, B
300 Tap-changer cover
301 Tap-changer head, head version 1
305 Safety bleeder valve
308 Tap-changer head, lower part in bell-type tank design
310 Inspection window
311 Pipe connection R (NO 140X82)
312 Pipe connection S (NE 140X82)
313 Cover Q
314 Cover E2
400 Tap-changer cover
COPYRIGHT RESERVED

401 Tap-changer head, head version 1


405 Safety bleeder valve
408 Tap-changer head, lower part in bell-type tank design
410 Inspection window
411 Pipe connection R (NO 140X82)
412 Pipe connection S (NE 140X82)
413 Cover Q
414 Cover E2
500 Tap-changer cover
501 Tap-changer head, head version 1
MASCHINENFABRIK REINHAUSEN GMBH

505 Safety bleeder valve


508 Tap-changer head, lower part in bell-type tank design
510 Inspection window
511 Pipe connection R (NO 140X82)
512 Pipe connection S (NE 140X82)
513 Cover Q
514 Cover E2
Name

2/5
Tag

DRIVE SHAFT ARRANGEMENT


Änd.-Nr.

10366418_200_00
Än. In

gez. edv 01.01.01


gepr.

DIN A1
MASCHINENFABRIK REINHAUSEN GMBH COPYRIGHT RESERVED

gepr.
The reproduction, distribution and utilization of this document as well as the communication of its contents to others without explicid authorization is
prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or design.

gez. edv 01.01.01


Än. In Änd.-Nr. Tag Name

2462

DRIVE SHAFT ARRANGEMENT


Front View

10366418_200_00
3/5

DIN A1