You are on page 1of 4

PRODUCT OVERVIEW

VENTURI VALVES (VV)


Venturi Valves are mechanically pressure independent control valves designed
specifically for room pressure and fume hood control applications. The highly
engineered internal plunger assembly ensures the valve will respond to
changes in duct static pressure in less than one second, while turndown
ratios reaching 20:1 serve to maximize energy savings in unoccupied or
minimum flow set-points.
Each valve is factory calibrated, then characterized by flow to valve position
using the latest N.I.S.T. traceable equipment to ensure dependable and
repeatable valve accuracy. Price venturi valves are accurate to +/-5% of
flow when operated within the designed pressure range. Valve accuracy is
unaffected by inlet conditions and does not require any minimum distance of
straight duct on the inlet or outlet of the valve.
Available in constant or variable air volume configurations, the venturi valve is able to control flow without the need for measuring
devices in the airstream, eliminating the possibility of lint or other airborne particulates interfering with the control or accuracy of
the valve. The valve provides electronic flow feedback using a precision potentiometer to output a VDC signal linearly proportional
to airflow.
Venturi valves are available with integrated silencers with full sound performance data tested as a complete assembly. Hot water
coils are AHRI 410 certified and electric coils are ETL certified to UL1995 as a complete assembly and/or HW or electric reheat
coils as AHRI certified assemblies. All silencers and reheat coils are manufactured in-house with designs optimized for close-
coupling with the valve.

SPECIFICATIONS

Construction Operation
∙∙ Valve Body: 14 Ga. Aluminum ∙∙ Temperature Rating: 32 - 120°F
∙∙ Cone: 16 Ga. Aluminum ∙∙ Humidity Rating: 10 - 95% RH non-condensing
∙∙ Shaft: Teflon-coated 316 Stainless Steel ∙∙ Low pressure: 0.3 – 3.0” w.c. measured across the valve
∙∙ Shaft Supports: 316 Stainless Steel ∙∙ Medium pressure: 0.6 – 3.0” w.c. measured across the valve
∙∙ Shaft Bearings: Wear-resistant Operational Flow Range
with Teflon Additive
SIZE LOW PRESSURE MEDIUM PRESSURE
∙∙ Internal Hardware: 316 Stainless Steel
8 35-500 CFM 35-700 CFM
10 50-550 CFM 50-1000 CFM
Options 12 90-1200 CFM 90-1500 CFM
∙∙ Anti-Corrosion Coatings: 14 200-1400 CFM 200-2500 CFM

∙∙ Heresite (P403) Dual Size 10 100-1100 CFM 100-2000 CFM


Dual Size 12 180-2400 CFM 180-3000 CFM
∙∙ Kynar (PVDF)
Dual Size 14 400-2800 CFM 400-5000 CFM
∙∙ Connection: Flanged, Slip
and Drawband Clamp Triple Size 12 270-3600 CFM 270-4500 CFM
Triple Size 14 600-4200 CFM 600-7500 CFM
∙∙ Actuator: High Speed or Standard Speed
Quad Size 12 360-4800 CFM 360-6000 CFM
∙∙ Fail safe: Last position, Open or Closed
Quad Size 14 800-5600 CFM 800-10000 CFM
∙∙ 0.75” External Foam Insulation
Specifications subject to change without notice

pricecriticalcontrols.com | 678.578.7495 | 2016-10-31 | v200 1 of 4


PRODUCT LABELS

www. pricecriticalcontrols.com

criticalcontrols@priceindustries.com
criticalcontrols@price-hvac.com

678-578-7495

CALIBRATION
AIRFLOW (VDC OUT) 2.0 10.0 VALVE PRESS (VDC OUT) 2.0 10.0
AIRFLOW (CFM) 50 1000 VALVE PRESS (" W.C.) 0.0 5.0

FLOW FEEDBACK SIGNAL (CFM) = 119 * (LM VDC) + -188


VALVE PRESSURE SIGNAL ("WC) = 0.63 * (SP VDC) - 1.25 LMX output equations
1200
Each LMX curve is tested LM
LMXFLOW
FLOWOUTPUT
OUTPUTSIGNAL
SIGNAL
1000
and verified before shipping ACTUATOR INPUT SIGNAL
800
FLOW (CFM)

600 Calibration is linearized into the LMX


400 output signal equation
200
0
0 2 4 6 8 10
SIGNAL (VDC)
CFM @ 70°F, 0 FT ELEV. - PLEASE REFER TO MANUAL FOR ELEV. CORRECTION

TAG: DATE: Calibration date

www. pricecriticalcontrols.com

criticalcontrols@price-hvac.com
criticalcontrols@priceindustries.com

678-578-7495

SPECIFICATIONS

PRICE ORDER NO:


JOB NAME: Job Information
UNIT TAG:
LINE:

SERIAL NO:
UNIT SIZE:
FLOW RANGE: Valve Information
PRESSURE RANGE:
ORIENTATION:

CFM @ 70°F, 0 FT ELEV. - PLEASE REFER TO MANUAL FOR ELEV. CORRECTION

Test and QA sign-off TESTED: QA: DATE:

*O 00000000000001A001*

Required airflow direction


and orientation
AIRFLOW
HORIZONTAL ORIENTATION ONLY

pricecriticalcontrols.com | 678.578.7495 | 2016-10-31 | v200 2 of 4


TYPICAL WIRING

PRODUCT CODE

VV-108-AL-P-I-H-M-FL-CV-S-FLP-LMX

Pressure Connection Actuator Feedback


Valve Size Construction Coating Insulation Orientation Control Type Fail safe
Range Type Type Signal
108 - Size 8 AL - Aluminum P - Phenolic IN - 3/4” Fiber H - Horizontal L - Low FL - Flange CV - Constant SSA - Standard FLP - Actuator LMX -
110 - Size 10 Construction Coating - P403 Free External Configuration Pressure Connection Volume Speed Fail Last Position Electronic Flow
112 - Size 12 Heresite Insulation VU - Vertical up (0.3-3.0``WC) SL - Slip VAV - Variable HSA - High FCP - Actuator Feedback with
114 - Size 14 K - PVDF Configuration M - Medium Connection Air Volume Speed Fail Closed Pressure Alarm
210 - Double Coating - Kynar VD - Vertical Pressure 2P - Two- Position FHC - Fume
Ganged Size 10 down (0.6-3.0``WC) Position FOP - Actuator Hood Controller
212 - Double configuration Fail Open Electronic Flow
Ganged Size 12 Position Feedback
214 - Double
Ganged Size 14
312 - Triple
Ganged Size 12
314 - Triple
Ganged Size 14
412 - Quad
Ganged Size 12
414 - Quad
Ganged Size 14

pricecriticalcontrols.com | 678.578.7495 | 2016-10-31 | v200 3 of 4


This document contains the most current product information as of this printing.
For the most up-to-date product information, please go to pricecriticalcontrols.com

© 10/31/16 Price Industries Limited. All rights reserved.