OWNER’S ENGINEER:
NATIONAL INSPECTION & TECHNICAL TESTING CO LTD
(FAHSS TUV NORD)
PROJECT:
CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
NAME DATE SIGN TITLE:
PREPARED AP 06.08.2021
SCADA I/O SIGNAL LIST
CHECKED SB 09.08.2021
APPROVED KCM 10.08.2021
20PKSA001-LNT-SPV-I-LST-1301 4 1 OF 80
CONTENTS
1 Equipment .......................................................................................................... 3
2 Location ............................................................................................................. 4
2.1 Climate and site conditions ........................................................................... 5
3 Attachment ......................................................................................................... 6
Description
Document File
T-Series (30 min) - SG-63941-1908-10-1_TSmin_15_REP.pdf
SolarGis SG-63941-1908-10-1_TSmin_15.csv
TMY ( P50, P75, P90) SA-Jed-TMY_P50_2018-07-10.xlsx
ALBEDO Data Albedo_CSPS_Jeddah_KSA.csv
Multi Function Meter (MFM) I/O Quantity Per Equipment 1. IDT station Auxiliary Panel (400V ACDB)
S.12
No. (Associated with Auxiliary
Equipment Name Panel (400V Signal Description Signal Type (20PKSA001-LNT-SPV-E-DSH-1265)
Reference
ACDB) at Inverter Duty Transformer DI DO AI MODBUS RS 485 Modbus TCP/IP
station 2. Annexure-8 – IDT Auxiliary Panel MFM Data sheet
Active Power Value to SCADA Measurement - - - 1 -
Apparent Power Value to SCADA Measurement - - - 1 -
Reactive power Value to SCADA Measurement - - - 1 -
Active import/ export energy Value to SCADA Measurement - - - 1 -
Reactive import/ export energy Value to SCADA Measurement - - - 1 -
All Inverters Power on setting (The data field can only be 0 for Annexure-11 – SmartLogger ModBus Interface Definitions
Command - - - - 1
poweringon all inverters.)
All Inverters Power off setting (The data field can only be 0 for powering
Command - - - - 1
off all inverters.)
Transfer trip (The device shuts down when it stops due to faults and
Command - - - - 1
does not respond to the startup request.)
Array reset Command - - - - 1
All Inverters Active adjustment Command - - - - 1
All Inverters Reactive adjustment Command - - - - 1
All Inverters Active power adjustment by percentage Command - - - - 1
All Inverters Power factor adjustment Command - - - - 1
Total input DC current of all inverters Measurement - - - - 1
Total input power of all inverters Measurement - - - - 1
Total CO2 reduction of all inverters Measurement - - - - 1
Total active output power of all inverters Measurement - - - - 1
Total power factor of all inverters Measurement - - - - 1
Total reactive output power of all inverters Measurement - - - - 1
Total CO2 reduction of all inverters (Maximum value) Measurement - - - - 1
Total input DC current of all inverters (Maximum value) Measurement - - - - 1
Total energy yield generatedby all inverters Measurement - - - - 1
Daily energy yield generated by all inverters Measurement - - - - 1
Duration of daily power generation Measurement - - - - 1
Sum of phase A currents of all inverters Measurement - - - - 1
Sum of phase B currents of all inverters Measurement - - - - 1
Sum of phase C currents of all inverters Measurement - - - - 1
Phase A-B Voltage Measurement - - - - 1
Phase B-C Voltage Measurement - - - - 1
Phase C-A Voltage Measurement - - - - 1
Max. reactive adjustment Measurement - - - - 1
Min. reactive adjustment Measurement - - - - 1
Max. active adjustment Measurement - - - - 1
System reset Indication - - - - 1
Fast device access Indication - - - - 1
Device operation Indication - - - - 1
Smart Array Controller (At Inverter Duty Device access status Indication - - - - 1
13
Transformer station) Active power control mode Indication - - - - 1
Active power scheduling target value Measurement - - - - 1
Reactive power control mode Indication - - - - 1
Reactive power scheduling curve mode Indication - - - - 1
Reactive power scheduling target value Measurement - - - - 1
Active scheduling percentage Measurement - - - - 1
Ups Battery Feedback - - - - 1 If UpsBattery is TRUE, UPS is the TBOX power supply
Wind Alarm Trigger Control - - - - 1 Signal to send all trackers a global wind alarm
Tracker - Plant control from plant Stop Alarm Trigger Control - - - - 1 Signal to send all trackers a global stop alarm
18 SCADA
(TBOX to SCADA RIO panel)
Manual Elevation Target Trigger Control - - - - 1 Signal to send all trackers a global manual setpoin
Set Auto Control Trigger Control - - - - 1 Signal to send all trackers a set to auto signal
Construction Trigger Control - - - - 1 Signal to send all trackers a set to construction position signa
Wind Alarm Trigger CONTROL - - - - 1 Flag signal to send all trackers a global wind alarm
Tracker - GENERAL BLOCK CONTROL Stop Alarm Trigger CONTROL - - - - 1 Flag signal to send all trackers a global stop alarm
21
(TBOX to SCADA RIO panel)
Manual Elevation Target Trigger CONTROL - - - - 1 Flag signal to send all trackers a global manual setpoint
Set Auto Control Trigger CONTROL - - - - 1 Flag signal to send all trackers a set to auto signal
Wind Speed 3s Feedback - - - - 1 Average numeric value of wind speed of the last 3 seconds
Wind Direction 3s Feedback - - - - 1 Average numeric value of wind direction of the last 3 seconds
Wind Speed 30s Feedback - - - - 1 Average numeric value of wind speed of the last 30 seconds
Wind Direction 30s Feedback - - - - 1 Average numeric value of wind direction of the last 30 seconds
Tracker - MBOX BLOCK X
22
(TBOX to SCADA RIO panel)
Battery Level Feedback - - - - 1 Battery level
Alarms:
Alarms Feedback - - - - 1 - Bit 0: Anemometer Fault
- Bit 1: Charger Fault
1 IDTS-01_36kV Breaker-1 10 2 -- -- --
4 IDTS-01_36kV EFI/FPI -- -- -- 4 --
9 IDTS-01_LT Panel-1 4 -- -- -- --
10 IDTS-01_LT Panel-2 4 -- -- -- --
11 IDTS-01_LT Panel-1_MFM -- -- -- 18 --
12 IDTS-01_LT Panel-2_MFM -- -- -- 18 --
14 IDTS-01_UPS -- -- -- 15 --
17 IDTS-01_String Inverter (Total 40 Number) -- -- -- -- 4880 14 Nos. of String per String Inverter
1 IDTS-02_36kV Breaker-1 10 2 -- -- --
4 IDTS-02_36kV EFI/FPI -- -- -- 4 --
10 IDTS-02_LT Panel-1 4 -- -- -- --
11 IDTS-02_LT Panel-2 4 -- -- -- --
12 IDTS-02_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-02_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-02_UPS -- -- -- 15 --
18 IDTS-02_String Inverter (Total 40 Number) -- -- -- -- 4880 14 Nos. of String per String Inverter
1 IDTS-03_36kV Breaker-1 10 2 -- -- --
4 IDTS-03_36kV EFI/FPI -- -- -- 4 --
10 IDTS-03_LT Panel-1 4 -- -- -- --
11 IDTS-03_LT Panel-2 4 -- -- -- --
12 IDTS-03_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-03_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-03_UPS -- -- -- 15 --
18 IDTS-03_String Inverter (Total 40 Number) -- -- -- -- 4880 14 Nos. of String per String Inverter
1 IDTS-04_36kV Breaker-1 10 2 -- -- --
2 IDTS-04_36kV Disconnector Break Switch-1 3 -- -- -- --
3 IDTS-04_36kV Numerical Relay-1 -- -- -- 6 --
4 IDTS-04_36kV EFI/FPI -- -- -- 4 --
5 IDTS-04_36kV Load Break Switch-1 3 -- -- -- --
6 IDTS-04_36kV Load Break Switch-2 3 -- -- -- --
7 IDTS-04_36kV Load Break Switch-3 3 -- -- -- --
8 IDTS-04_Inverter Duty Transformer-1 (From RMU) 12 -- -- -- --
9 IDTS-04_Inverter Duty Transformer-1 (Marshalling box) -- -- 5 -- --
10 IDTS-04_LT Panel-1 4 -- -- -- --
11 IDTS-04_LT Panel-2 4 -- -- -- --
12 IDTS-04_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-04_LT Panel-2_MFM -- -- -- 18 --
14 IDTS-04_Auxiliary Transformer Panel 1 -- -- -- --
15 IDTS-04_UPS -- -- -- 15 --
16 IDTS-04_Auxiliary Panel (400V ACDB)_MFM -- -- -- 13 --
17 IDTS-04_SACU -- -- -- -- 394 42 Nos. of String Inverter connected.
18 IDTS-04_String Inverter (Total 42 Number) -- -- -- -- 5124 14 Nos. of String per String Inverter
1 IDTS-05_36kV Breaker-1 10 2 -- -- --
2 IDTS-05_36kV Disconnector Break Switch-1 3 -- -- -- --
3 IDTS-05_36kV Numerical Relay-1 -- -- -- 6 --
4 IDTS-05_36kV EFI/FPI -- -- -- 4 --
5 IDTS-05_36kV Load Break Switch-1 3 -- -- -- --
6 IDTS-05_36kV Load Break Switch-2 3 -- -- -- --
7 IDTS-05_Inverter Duty Transformer-1 (From RMU) 12 -- -- -- --
8 IDTS-05_Inverter Duty Transformer-1 (Marshalling box) -- -- 5 -- --
9 IDTS-05_LT Panel-1 4 -- -- -- --
10 IDTS-05_LT Panel-2 4 -- -- -- --
11 IDTS-05_LT Panel-1_MFM -- -- -- 18 --
12 IDTS-05_LT Panel-2_MFM -- -- -- 18 --
13 IDTS-05_Auxiliary Transformer Panel 1 -- -- -- --
14 IDTS-05_UPS -- -- -- 15 --
15 IDTS-05_Auxiliary Panel (400V ACDB)_MFM -- -- -- 13 --
16 IDTS-05_SACU -- -- -- -- 378 40 Nos. of String Inverter connected.
17 IDTS-05_String Inverter (Total 40 Number) -- -- -- -- 4880 14 Nos. of String per String Inverter
1 IDTS-06_36kV Breaker-1 10 2 -- -- --
4 IDTS-06_36kV EFI/FPI -- -- -- 4 --
10 IDTS-06_LT Panel-1 4 -- -- -- --
11 IDTS-06_LT Panel-2 4 -- -- -- --
12 IDTS-06_LT Panel-1_MFM -- -- -- 18 --
15 IDTS-06_UPS -- -- -- 15 --
18 IDTS-06_String Inverter (Total 40 Number) -- -- -- -- 4880 14 Nos. of String per String Inverter
1 IDTS-07_36kV Breaker-1 10 2 -- -- --
4 IDTS-07_36kV EFI/FPI -- -- -- 4 --
10 IDTS-07_LT Panel-1 4 -- -- -- --
11 IDTS-07_LT Panel-2 4 -- -- -- --
12 IDTS-07_LT Panel-1_MFM -- -- -- 18 --
15 IDTS-07_UPS -- -- -- 15 --
18 IDTS-07_String Inverter (Total 40 Number) -- -- -- -- 4880 14 Nos. of String per String Inverter
1 IDTS-08_36kV Breaker-1 10 2 -- -- --
4 IDTS-08_36kV EFI/FPI -- -- -- 4 --
10 IDTS-08_LT Panel-1 4 -- -- -- --
11 IDTS-08_LT Panel-2 4 -- -- -- --
12 IDTS-08_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-08_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-08_UPS -- -- -- 15 --
18 IDTS-08_String Inverter (Total 42 Number) -- -- -- -- 5124 14 Nos. of String per String Inverter
1 IDTS-09_36kV Breaker-1 10 2 -- -- --
4 IDTS-09_36kV EFI/FPI -- -- -- 4 --
9 IDTS-09_LT Panel-1 4 -- -- -- --
10 IDTS-09_LT Panel-2 4 -- -- -- --
11 IDTS-09_LT Panel-1_MFM -- -- -- 18 --
12 IDTS-09_LT Panel-2_MFM -- -- -- 18 --
14 IDTS-09_UPS -- -- -- 15 --
17 IDTS-09_String Inverter (Total 40 Number) -- -- -- -- 4880 14 Nos. of String per String Inverter
1 IDTS-10_36kV Breaker-1 10 2 -- -- --
4 IDTS-10_36kV EFI/FPI -- -- -- 4 --
10 IDTS-10_LT Panel-1 4 -- -- -- --
11 IDTS-10_LT Panel-2 4 -- -- -- --
12 IDTS-10_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-10_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-10_UPS -- -- -- 15 --
18 IDTS-10_String Inverter (Total 40 Number) -- -- -- -- 4880 14 Nos. of String per String Inverter
1 IDTS-11_36kV Breaker-1 10 2 -- -- --
4 IDTS-11_36kV EFI/FPI -- -- -- 4 --
10 IDTS-11_LT Panel-1 4 -- -- -- --
11 IDTS-11_LT Panel-2 4 -- -- -- --
12 IDTS-11_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-11_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-11_UPS -- -- -- 15 --
18 IDTS-11_String Inverter (Total 40 Number) -- -- -- -- 4880 14 Nos. of String per String Inverter
1 IDTS-12_36kV Breaker-1 10 2 -- -- --
4 IDTS-12_36kV EFI/FPI -- -- -- 4 --
10 IDTS-12_LT Panel-1 4 -- -- -- --
11 IDTS-12_LT Panel-2 4 -- -- -- --
12 IDTS-12_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-12_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-12_UPS -- -- -- 15 --
18 IDTS-12_String Inverter (Total 42 Number) -- -- -- -- 5124 14 Nos. of String per String Inverter
1 IDTS-13_36kV Breaker-1 10 2 -- -- --
4 IDTS-13_36kV EFI/FPI -- -- -- 4 --
9 IDTS-13_LT Panel-1 4 -- -- -- --
10 IDTS-13_LT Panel-2 4 -- -- -- --
11 IDTS-13_LT Panel-1_MFM -- -- -- 18 --
12 IDTS-13_LT Panel-2_MFM -- -- -- 18 --
14 IDTS-13_UPS -- -- -- 15 --
17 IDTS-13_String Inverter (Total 15 Number) -- -- -- -- 1830 14 Nos. of String per String Inverter
18 IDTS-13_String Inverter (Total 25 Number) -- -- -- -- 3150 16 Nos. of String per String Inverter
1 IDTS-14_36kV Breaker-1 10 2 -- -- --
4 IDTS-14_36kV EFI/FPI -- -- -- 4 --
10 IDTS-14_LT Panel-1 4 -- -- -- --
11 IDTS-14_LT Panel-2 4 -- -- -- --
12 IDTS-14_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-14_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-14_UPS -- -- -- 15 --
18 IDTS-14_String Inverter (Total 40 Number) -- -- -- -- 5040 16 Nos. of String per String Inverter
1 IDTS-15_36kV Breaker-1 10 2 -- -- --
2 IDTS-15_36kV Disconnector Break Switch-1 3 -- -- -- --
3 IDTS-15_36kV Numerical Relay-1 -- -- -- 6 --
4 IDTS-15_36kV EFI/FPI -- -- -- 4 --
5 IDTS-15_36kV Load Break Switch-1 3 -- -- -- --
6 IDTS-15_36kV Load Break Switch-2 3 -- -- -- --
7 IDTS-15_36kV Load Break Switch-3 3 -- -- -- --
8 IDTS-15_Inverter Duty Transformer-1 (From RMU) 12 -- -- -- --
9 IDTS-15_Inverter Duty Transformer-1 (Marshalling box) -- -- 5 -- --
10 IDTS-15_LT Panel-1 4 -- -- -- --
11 IDTS-15_LT Panel-2 4 -- -- -- --
12 IDTS-15_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-15_LT Panel-2_MFM -- -- -- 18 --
14 IDTS-15_Auxiliary Transformer Panel 1 -- -- -- --
15 IDTS-15_UPS -- -- -- 15 --
16 IDTS-15_Auxiliary Panel (400V ACDB)_MFM -- -- -- 13 --
17 IDTS-15_SACU -- -- -- -- 378 40 Nos. of String Inverter connected.
18 IDTS-15_String Inverter (Total 40 Number) -- -- -- -- 5040 16 Nos. of String per String Inverter
1 IDTS-16_36kV Breaker-1 10 2 -- -- --
4 IDTS-16_36kV EFI/FPI -- -- -- 4 --
10 IDTS-16_LT Panel-1 4 -- -- -- --
11 IDTS-16_LT Panel-2 4 -- -- -- --
12 IDTS-16_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-16_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-16_UPS -- -- -- 15 --
18 IDTS-16_String Inverter (Total 42 Number) -- -- -- -- 5124 14 Nos. of String per String Inverter
1 IDTS-17_36kV Breaker-1 10 2 -- -- --
4 IDTS-17_36kV EFI/FPI -- -- -- 4 --
10 IDTS-17_LT Panel-1 4 -- -- -- --
11 IDTS-17_LT Panel-2 4 -- -- -- --
12 IDTS-17_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-17_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-17_UPS -- -- -- 15 --
18 IDTS-17_String Inverter (Total 40 Number) -- -- -- -- 5040 16 Nos. of String per String Inverter
1 IDTS-18_36kV Breaker-1 10 2 -- -- --
4 IDTS-18_36kV EFI/FPI -- -- -- 4 --
10 IDTS-18_LT Panel-1 4 -- -- -- --
11 IDTS-18_LT Panel-2 4 -- -- -- --
12 IDTS-18_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-18_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-18_UPS -- -- -- 15 --
18 IDTS-18_String Inverter (Total 40 Number) -- -- -- -- 5040 16 Nos. of String per String Inverter
1 IDTS-19_36kV Breaker-1 10 2 -- -- --
4 IDTS-19_36kV EFI/FPI -- -- -- 4 --
10 IDTS-19_LT Panel-1 4 -- -- -- --
11 IDTS-19_LT Panel-2 4 -- -- -- --
12 IDTS-19_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-19_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-19_UPS -- -- -- 15 --
18 IDTS-19_String Inverter (Total 42 Number) -- -- -- -- 5124 14 Nos. of String per String Inverter
1 IDTS-20_36kV Breaker-1 10 2 -- -- --
4 IDTS-20_36kV EFI/FPI -- -- -- 4 --
10 IDTS-20_LT Panel-1 4 -- -- -- --
11 IDTS-20_LT Panel-2 4 -- -- -- --
12 IDTS-20_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-20_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-20_UPS -- -- -- 15 --
18 IDTS-20_String Inverter (Total 42 Number) -- -- -- -- 5124 14 Nos. of String per String Inverter
1 IDTS-21_36kV Breaker-1 10 2 -- -- --
4 IDTS-21_36kV EFI/FPI -- -- -- 4 --
10 IDTS-21_LT Panel-1 4 -- -- -- --
11 IDTS-21_LT Panel-2 4 -- -- -- --
12 IDTS-21_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-21_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-21_UPS -- -- -- 15 --
18 IDTS-21_String Inverter (Total 42 Number) -- -- -- -- 5124 14 Nos. of String per String Inverter
1 IDTS-23_36kV Breaker-1 10 2 -- -- --
4 IDTS-23_36kV EFI/FPI -- -- -- 4 --
9 IDTS-23_LT Panel-1 4 -- -- -- --
10 IDTS-23_LT Panel-2 4 -- -- -- --
12 IDTS-23_LT Panel-2_MFM -- -- -- 18 --
14 IDTS-23_UPS -- -- -- 15 --
17 IDTS-23_String Inverter (Total 40 Number) -- -- -- -- 5040 16 Nos. of String per String Inverter
1 IDTS-24_36kV Breaker-1 10 2 -- -- --
4 IDTS-24_36kV EFI/FPI -- -- -- 4 --
10 IDTS-24_LT Panel-1 4 -- -- -- --
11 IDTS-24_LT Panel-2 4 -- -- -- --
13 IDTS-24_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-24_UPS -- -- -- 15 --
18 IDTS-24_String Inverter (Total 40 Number) -- -- -- -- 5040 16 Nos. of String per String Inverter
1 IDTS-25_36kV Breaker-1 10 2 -- -- --
4 IDTS-25_36kV EFI/FPI -- -- -- 4 --
18 IDTS-25_String Inverter (Total 40 Number) -- -- -- -- 5040 16 Nos. of String per String Inverter
1 IDTS-26_36kV Breaker-1 10 2 -- -- --
4 IDTS-26_36kV EFI/FPI -- -- -- 4 --
10 IDTS-26_LT Panel-1 4 -- -- -- --
11 IDTS-26_LT Panel-2 4 -- -- -- --
13 IDTS-26_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-26_UPS -- -- -- 15 --
18 IDTS-26_String Inverter (Total 40 Number) -- -- -- -- 5040 16 Nos. of String per String Inverter
1 IDTS-27_36kV Breaker-1 10 2 -- -- --
4 IDTS-27_36kV EFI/FPI -- -- -- 4 --
10 IDTS-27_LT Panel-1 4 -- -- -- --
11 IDTS-27_LT Panel-2 4 -- -- -- --
13 IDTS-27_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-27_UPS -- -- -- 15 --
18 IDTS-27_String Inverter (Total 40 Number) -- -- -- -- 5040 16 Nos. of String per String Inverter
1 IDTS-28_36kV Breaker-1 10 2 -- -- --
4 IDTS-28_36kV EFI/FPI -- -- -- 4 --
10 IDTS-28_LT Panel-1 4 -- -- -- --
11 IDTS-28_LT Panel-2 4 -- -- -- --
13 IDTS-28_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-28_UPS -- -- -- 15 --
18 IDTS-28_String Inverter (Total 40 Number) -- -- -- -- 5040 16 Nos. of String per String Inverter
1 IDTS-29_36kV Breaker-1 10 2 -- -- --
4 IDTS-29_36kV EFI/FPI -- -- -- 4 --
10 IDTS-29_LT Panel-1 4 -- -- -- --
11 IDTS-29_LT Panel-2 4 -- -- -- --
13 IDTS-29_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-29_UPS -- -- -- 15 --
18 IDTS-29_String Inverter (Total 42 Number) -- -- -- -- 5124 14 Nos. of String per String Inverter
1 IDTS-30_36kV Breaker-1 10 2 -- -- --
4 IDTS-30_36kV EFI/FPI -- -- -- 4 --
9 IDTS-30_LT Panel-1 4 -- -- -- --
10 IDTS-30_LT Panel-2 4 -- -- -- --
12 IDTS-30_LT Panel-2_MFM -- -- -- 18 --
14 IDTS-30_UPS -- -- -- 15 --
17 IDTS-30_String Inverter (Total 40 Number) -- -- -- -- 5040 16 Nos. of String per String Inverter
1 IDTS-31_36kV Breaker-1 10 2 -- -- --
2 IDTS-31_36kV Disconnector Break Switch-1 3 -- -- -- --
3 IDTS-31_36kV Numerical Relay-1 -- -- -- 6 --
4 IDTS-31_36kV EFI/FPI -- -- -- 4 --
5 IDTS-31_36kV Load Break Switch-1 3 -- -- -- --
6 IDTS-31_36kV Load Break Switch-2 3 -- -- -- --
7 IDTS-31_36kV Load Break Switch-3 3 -- -- -- --
8 IDTS-31_Inverter Duty Transformer-1 (From RMU) 12 -- -- -- --
9 IDTS-31_Inverter Duty Transformer-1 (Marshalling box) -- -- 5 -- --
10 IDTS-31_LT Panel-1 4 -- -- -- --
11 IDTS-31_LT Panel-2 4 -- -- -- --
12 IDTS-31_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-31_LT Panel-2_MFM -- -- -- 18 --
14 IDTS-31_Auxiliary Transformer Panel 1 -- -- -- --
1 IDTS-32_36kV Breaker-1 10 2 -- -- --
4 IDTS-32_36kV EFI/FPI -- -- -- 4 --
9 IDTS-32_LT Panel-1 4 -- -- -- --
11 IDTS-32_LT Panel-1_MFM -- -- -- 18 --
12 IDTS-32_LT Panel-2_MFM -- -- -- 18 --
14 IDTS-32_UPS -- -- -- 15 --
17 IDTS-32_String Inverter (Total 40 Number) -- -- -- -- 5040 16 Nos. of String per String Inverter
1 IDTS-33_36kV Breaker-1 10 2 -- -- --
4 IDTS-33_36kV EFI/FPI -- -- -- 4 --
11 IDTS-33_LT Panel-2 4 -- -- -- --
12 IDTS-33_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-33_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-33_UPS -- -- -- 15 --
18 IDTS-33_String Inverter (Total 40 Number) -- -- -- -- 5040 16 Nos. of String per String Inverter
1 IDTS-35_36kV Breaker-1 10 2 -- -- --
4 IDTS-35_36kV EFI/FPI -- -- -- 4 --
10 IDTS-35_LT Panel-1 4 -- -- -- --
11 IDTS-35_LT Panel-2 4 -- -- -- --
12 IDTS-35_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-35_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-35_UPS -- -- -- 15 --
18 IDTS-35_String Inverter (Total 42 Number) -- -- -- -- 5208 14 Nos. of String per String Inverter
1 IDTS-36_36kV Breaker-1 10 2 -- -- --
4 IDTS-36_36kV EFI/FPI -- -- -- 4 --
9 IDTS-36_LT Panel-1 4 -- -- -- --
10 IDTS-36_LT Panel-2 4 -- -- -- --
11 IDTS-36_LT Panel-1_MFM -- -- -- 18 --
12 IDTS-36_LT Panel-2_MFM -- -- -- 18 --
14 IDTS-36_UPS -- -- -- 15 --
17 IDTS-36_String Inverter (Total 40 Number) -- -- -- -- 5040 16 Nos. of String per String Inverter
1 IDTS-37_36kV Breaker-1 10 2 -- -- --
4 IDTS-37_36kV EFI/FPI -- -- -- 4 --
10 IDTS-37_LT Panel-1 4 -- -- -- --
11 IDTS-37_LT Panel-2 4 -- -- -- --
12 IDTS-37_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-37_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-37_UPS -- -- -- 15 --
18 IDTS-37_String Inverter (Total 40 Number) -- -- -- -- 5040 16 Nos. of String per String Inverter
1 IDTS-38_36kV Breaker-1 10 2 -- -- --
4 IDTS-38_36kV EFI/FPI -- -- -- 4 --
10 IDTS-38_LT Panel-1 4 -- -- -- --
11 IDTS-38_LT Panel-2 4 -- -- -- --
12 IDTS-38_LT Panel-1_MFM -- -- -- 18 --
13 IDTS-38_LT Panel-2_MFM -- -- -- 18 --
15 IDTS-38_UPS -- -- -- 15 --
18 IDTS-38_String Inverter (Total 42 Number) -- -- -- -- 5124 14 Nos. of String per String Inverter
1 IDTS-39_36kV Breaker-1 10 2 -- -- --
2 IDTS-39_36kV Disconnector Break Switch-1 3 -- -- -- --
3 IDTS-39_36kV Numerical Relay-1 -- -- -- 6 --
4 IDTS-39_36kV EFI/FPI -- -- -- 4 --
5 IDTS-39_36kV Load Break Switch-1 3 -- -- -- --
6 IDTS-39_36kV Load Break Switch-2 3 -- -- -- --
7 IDTS-39_36kV Load Break Switch-3 3 -- -- -- --
8 IDTS-39_Inverter Duty Transformer-1 (From RMU) 12 -- -- -- --
9 IDTS-39_Inverter Duty Transformer-1 (Marshalling box) -- -- 5 -- --
1 IDTS-40_36kV Breaker-1 10 2 -- -- --
4 IDTS-40_36kV EFI/FPI -- -- -- 4 --
9 IDTS-40_LT Panel-1 4 -- -- -- --
10 IDTS-40_LT Panel-2 4 -- -- -- --
11 IDTS-40_LT Panel-1_MFM -- -- -- 18 --
12 IDTS-40_LT Panel-2_MFM -- -- -- 18 --
14 IDTS-40_UPS -- -- -- 15 --
17 IDTS-40_String Inverter (Total 40 Number) -- -- -- -- 5040 16 Nos. of String per String Inverter
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Sensitivity: Unclassified
#
Page 1 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
L1 Phase Voltage Value to SCADA Measurement - - - 1 - - Annexure-10 – O&M Auxiliary Panel MFM Data
sheet
L2 Phase Voltage Value to SCADA Measurement - - - 1 - -
Fire Alarm Panel Manual fire alarm box activates trouble signal to SCADA Alarm 1 - - - - -
4
(O&M Building)
General Alarm Signal to SCADA Alarm 1 - - - - -
PV plant Active power set point command feedback value to SCADA Measurement - - - - 1 -
Ramp down rate set point command feedback value to SCADA Measurement - - - - 1 -
PV plant Reactive power set point command feedback value to SCADA Measurement - - - - 1 -
Sensitivity: Unclassified
#
Page 2 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Sensitivity: Unclassified
#
Page 3 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Sensitivity: Unclassified
#
Page 4 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Sensitivity: Unclassified
#
Page 5 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Sensitivity: Unclassified
#
Page 6 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Sensitivity: Unclassified
#
Page 7 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Sensitivity: Unclassified
#
PSS SAS system signals from PV Page 8 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Sensitivity: Unclassified
#
Page 9 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Sensitivity: Unclassified
#
Page 10 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Sensitivity: Unclassified
#
Page 11 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Sensitivity: Unclassified
#
Page 12 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Sensitivity: Unclassified
#
Page 13 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Sensitivity: Unclassified
#
Page 14 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Sensitivity: Unclassified
#
Page 15 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
Pooling Substation (PSS) signals from
16 PSS SAS system to PV SCADA Document Title L&T Document No. Rev. No.
33kV Indication
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Sensitivity: Unclassified
#
Page 16 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Sensitivity: Unclassified
#
Page 17 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Sensitivity: Unclassified
#
Page 18 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
Statcom-1 signals from PV SCADA to
19 AP SB KCM Annexure-12 – Statcom Modbus Interface list
14-Nov-22
PSS SAS
Sensitivity: Unclassified
#
Page 19 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Sensitivity: Unclassified
#
Page 20 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
Note: This I/O list shall be updated based on the vendor document of electrical equipment's in case of any change.
Sensitivity: Unclassified
#
Page 21 of 21
Project: CONTRACT NO: 0047390-0000108EU01:2000735990.16
REPDO ROUND 2 JEDDAH 300 MWAC PV SOLAR PROJECT AT JEDDAH, KSA
20PKSA001-LNT-SPV-I-LST-1301 4
SCADA I/O SIGNAL LIST AT O&M BUILDING Prepared Checked Approved Date
AP SB KCM 14-Nov-22
1 UPS -- -- -- 35 -- --
2 GPS 2 -- -- -- -- --
3 ACDB_MFM -- -- -- 14 --