This document provides a punch list of 25 items for a solar installation project. It details maintenance, repairs and replacements done at various facilities, including updating monitoring systems, replacing damaged components, adding protective covers, and checking connections. Photos were provided for some items.
This document provides a punch list of 25 items for a solar installation project. It details maintenance, repairs and replacements done at various facilities, including updating monitoring systems, replacing damaged components, adding protective covers, and checking connections. Photos were provided for some items.
This document provides a punch list of 25 items for a solar installation project. It details maintenance, repairs and replacements done at various facilities, including updating monitoring systems, replacing damaged components, adding protective covers, and checking connections. Photos were provided for some items.
been delivered to the managers of the facilities. please find the uploaded documents
2 GX GSM modem The installation was
done in the south, as for the north, it will be handed over to the UNOPS
3 connection bolts Grease added to all
connection bolts for all lots. please find the uploaded documents 4 Ventilation fans Power supplied and turned on/off switch in all lots. please find the uploaded documents
5 Drawings we did all drawing
inside all boxes (Combiner - MDB-etc).
please find the
uploaded documents
6 connection bolts we used Torque
wrench shell be used To check of all bolts. 7 Data sheets and O&M manuals All leaflets (Datasheets- Catalogs- O&M manuals....) Available in all rooms in lastic files. please find the uploaded documents
8 VRM Activation We activated all
monitoring systems in VRM web for both systems (victron and Outback) in all Lots.
9 Earthing And Lighting pits All earthing and
lightning pits measured resistance more than 5 Ohm it was reduce.
10 Fire extinguisher All fire extinguishers in
all facilities (All Lots) are carrying third party inspection label for date of inspection (and refilling if required). please find the uploaded documents
11 Outback Charge Controller All charge controller
checked they are inside of service.
12 Charge Controller (Outback) Ground fault fuses of
charger controllers replaced with same rating 1A-600VDC for all outback in all lots. 13 Shunt for battery motoring and All shunt and battery battery bus bar rack bus bar of the battery monitoring Protected by fiberglass in all sites. please find the uploaded documents
14 Entrance holes to battery rooms All cable tray entrance,
Air conditioning and ventilation fans holes are sealed and plugged against dust, water, and insects in all facilities for all lots. please find the uploaded documents
15 Photocell for Outdoor Lighting we replaced photocell
for outdoor lighting for AI-Khansa School, Haeel School. 14 October Hospital. AI-Zahra'a School. AI-Shahidah Eqbal School AI-Faroq-Rosod School, Salem Saleh School, AI- Waseti School, AI-Faroq-Sebah School, AI-Saeed School, Mousa Awadh School, Motherhood & Child Center -Qatabah and AI-Salam Hospital. Please find the uploaded documents. 16 Protection cover for Outback inverters All outback inverters bottom side covered by in all lots.
cover PV modules area and place to the highest point in facility rooftop in following ABU-MUSA SCHOOL, DHALMA H. AI-Wahdah School, Saeed Ali Hospital, AI- Khatwah school and Al-Ershad School. 19 Indoor Lighting We Completed indoor lighting installing in:- Dhebah Health center. Thee Ata Health center. AI-Ershad School. 20 Monitoring system firmware's update All monitoring system firmware updated for all site in all Lots. 21 AC SPD The activated AC SPD replaced in:- AI-Maidan Health Center. Dhebah HC. Thee Ata'a HC. Saeed Ali Hospital. Maryam School. Please find the uploaded documents. 22 Blocking Diode Burned blocking diode was replaced in Saeed Ali Hospital. AI-Mawaset Rural Hospital Ali Abdullah School Wa'lan HC. Please find the uploaded documents. 23 Smoke Detector We replaced all Smoke detector which was malfunctioned in:- AI-Khatwah School, AI- Jeel AI-Jadeed School. Zinab School, Sumaia School, Khadejah School, Hadhar HC. Dhebah HC. Asma School.
Please find the
uploaded documents. 24 Tagging and Labeling Tag of strings, PV modules, cables & chargers completed in:- Haifan Hospital & Da'an HC, AI-Jeel AI- Jadeed School, Saeed Ali Hospital, AI- Mawaset Rural Hospital. AI-Zahra'a School, AI- Saqaf School, Khadejah School, AI- Shahidah Eqbal School, Tur AI- Bahah Hospital. AL-ESHRAQSCHOOL, SOUQAI-RABUA H.C, Sumaia School Arwa AI-Fawz School 25 Batteries connection bolts Some batteries connection bolts changed in: AI-Jeel AI-Jadeed School, AI-Wahdah School, AI-Naser Adhalem School, AI-Shaheed AI- Eryani School, And Hadhar HC 26 Alternator operation and temperature The alternator control unit operation and temperature control unit pot are working in:- khadejah School 27 Sign Board relocation We Relocated signboard to the correct place Saeed Ali Hospital AI-Mawaset Rural Hospital 14 October Hospital, AI-Zahra'a School, Aisha School, Zinab School, Tur AI- Bahah Hospital.
28 Battery monitoring System (BMV) BMV is working in:-
-Tur AI-Bahah Hospital -DAR HABA H.C, AL-ESHRAQ SCHOOL -A I-Khatwah & AI-Ershad School.
Please find the
uploaded documents 29 BMV Shunt base The base of battery shunt replaced in:- AI-Khansa School, Khadejah School, Bait AI-Hojaini HC Please find the uploaded documents
30 Battery rack We fixed the Missing
parts of the battery rack and installed it in:- -Arwa AI-Fawz School. -Asma Schoof. 31 Mounting structure We fixed the Missing parts and bolt of the mounting structure and installed it :- AI-Naser Adhalem School Aisha School, Zainab School & Az-Zahra'a Schooi- Yafe'e 32 Concrete block grout Concrete block grouting completed in:- AI-Khatwah, AI- Tahreer & AI-Ershad School & Haifan Hospital. AI-Faroq-Rosod School, Salem Saleh School, AI- Waseti School, AI- Faroq-Sebah School, AI-Saeed School, Mousa Awadh School, Motherhood & Child Center -Qatabah and AI-Salam Hospital. Omar School. Please find the uploaded documents. 33 RCCB of Ac Coupling and MDB RCCB change and installed in: Haeel School, Khawlah School_ Asma School, AI-Khansa School, Omar School, AI-Dhahi Hospital. 34 MDB Neutral We fixed Only one neutral wire connected inside MDB:- - Jarf Esbeel HC. 35 Paint in PV Modules the paint Removed from PV modules in:- -Wa'lan HC, Masaood HC. -AI-Maidan - Health.Center. -AI-Adel School.
36 Datalink between Inverter or BMV2 Datalink between
and - CCGX. Inverter or BMV2 and CCGX is Working in:- - Thee Ata'a Health Center. - Az-Zahr'a' School- Yafe'e.
37 Main Circuit Breaker for MDB We changed main
circuit breaker for MDB to 3poles in: - AI-Hayfa Health center. - Dhebah HC.
38 PV module Fixing We fixed bolt and
Installed it for PV module in:- - Aisha School, Zainab School & Az-Zahra'a Schooi- Yafe'e 39 Charge Controller We installed Smart Solar Control Display in:- Al- zahra'a School- Yafe'e, Bait AI-Hojaini HC. 40 Ac Coupling We Installed MCCB in AC coupling at - AI- Wahdah School.