TEST REPORT

Product Name :Uninterruptible Power System

COMPACT 10KVA, COMPACT 15KVA,


COMPACT 20KVA, COMPACT 30KVA,
Model Number :COMPACT 40KVA
Battery bank:
COMPACT-BT BATTERY BANK SERIES
Prepared for : EnSmart Power Ltd.
Address : Kemp House 160 City Road, London, EC1V 2NX, United
Kingdom

Prepared by : EMTEK (SHENZHEN) CO., LTD.


Address : Bldg 69, Majialong Industry Zone, Nanshan District,
Shenzhen, Guangdong, China

Tel: (0755) 26954280


Fax: (0755) 26954282

Report Number : ES160322008S-11

$二维码$

TRF No.: IEC62040_1D Page 1 of 74 Report No. ES160322008S-11 Ver.1.0


TEST REPORT
IEC 62040-1
Uninterruptible power systems (UPS) –
Part 1: General and safety requirements for UPS

Report Number. .............................. : ES160322008S-11


Date of issue ................................... : June 16, 2020
Total number of pages ................... 74 pages

Applicant’s name ........................... : EnSmart Power Ltd.


Address ........................................... : Kemp House 160 City Road, London, EC1V 2NX, United
Kingdom
Test specification:
Standard.......................................... : IEC 62040-1:2008 (First Edition) + Am 1: 2013
EN 62040-1: 2008+A1: 2013
Test procedure ............................... : CE-LVD
Non-standard test method ............ : N/A
Test Report Form No. .................... : IEC62040_1D
Test Report Form(s) Originator .... : TÜV Rheinland Japan Ltd.
Master TRF ..................................... : Dated 2016-08
Copyright © 2016 IEC System of Conformity Assessment Schemes for Electrotechnical
Equipment and Components (IECEE System). All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the
IECEE is acknowledged as copyright owner and source of the material. IECEE takes no responsibility
for and will not assume liability for damages resulting from the reader's interpretation of the reproduced
material due to its placement and context.
If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the
CB Scheme procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory
and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
General disclaimer:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing CB Testing
Laboratory. The authenticity of this Test Report and its contents can be verified by contacting the NCB,
responsible for this Test Report.

TRF No.: IEC62040_1D Page 2 of 74 Report No. ES160322008S-11 Ver.1.0


Test item description ....................... : Uninterruptible Power Systems
Trade Mark ........................................ :

Manufacturer .................................... : EnSmart Power Supplies and Energy Storage Systems Ind.
Trade A.S
Halk Cad. No:8/A3, Atasehir, Istanbul 34752, Turkey
Model/Type reference ...................... : COMPACT 10KVA, COMPACT 15KVA, COMPACT 20KVA,
COMPACT 30KVA, COMPACT 40KVA
Battery bank: COMPACT-BT BATTERY BANK SERIES
Ratings .............................................. : See the rating labels.

TRF No.: IEC62040_1D Page 3 of 74 Report No. ES160322008S-11 Ver.1.0


Testing procedure and testing location:

CB Testing Laboratory: EMTEK (SHENZHEN) CO., LTD.


Testing location/ address ............................ : Bldg 69, Majialong Industry Zone, Nanshan District,
Shenzhen, Guangdong, China
Associated CB Testing Laboratory:
Testing location/ address ................................ :

Tested by (name + signature) ........................ : Gary Zhang/


Engineer
Approved by (name + signature) .................... : William Guo /
Manager

Testing procedure: TMP


Testing location/ address ................................ :

Tested by (name + signature) ........................ :


Approved by (name + signature) .................... :
Testing procedure: WMT
Testing location/ address ................................ :

Tested by (name + signature) ........................ :


Witnessed by (name + signature) ................... :
Approved by (name + signature) .................... :
Testing procedure: SMT
Testing location/ address ................................ :

Tested by (name + signature) ........................ :


Approved by (name + signature) .................... :
Supervised by (name + signature) ................. :
Testing procedure: RMT
Testing location/ address ................................ :

Tested by (name + signature) ........................ :


Approved by (name + signature) .................... :
Supervised by (name + signature) ................. :

TRF No.: IEC62040_1D Page 4 of 74 Report No. ES160322008S-11 Ver.1.0


List of Attachments (including a total number of pages in each attachment):
- IEC 62040-1 TRF (59 pages): Main report
- Appendix 1 (2 pages): European group differences and national differences
- Appendix 2 (11 pages): Product photo
Summary of testing:
Tests performed (name of test and test clause): Testing location:
 Tests performed on the bench EMTEK (SHENZHEN) CO., LTD.
 Maximum ambient temperature: +40°C Bldg 69, Majialong Industry Zone, Nanshan
 Tested for moderate conditions. District, Shenzhen, Guangdong, China
 EUT is designed for altitudes not exceeding
2000m.
 Installation category II is specified in
installation manual for this product.
 Pre-production sample without serial number.
 Test on model: COMPACT 40KVA can represent
other models. For model differences refer to page
6-7.
The EUTs pass the tests
Summary of compliance with National Differences:
List of countries addressed: Group differences and national differences for CENELEC countries
were checked.
The product fulfils the requirements of EN 62040-1: 2008+A1: 2013.

TRF No.: IEC62040_1D Page 5 of 74 Report No. ES160322008S-11 Ver.1.0


Copy of marking plate:
The artwork below may be only a draft. The use of certification marks on a product must be
authorized by the respective NCBs that own these marks.
Copy of rating label:

Uninterruptible Power System


Model: COMPACT 10KVA
AC INPUT: 220/230/240Vac, 29A Max.,1Φ+N+PE, 50/60Hz
BATT INPUT: ±96/108/120Vdc, 26/23/21A
OUTPUT: 220/230/240Vac,1Φ+N+PE, 50/60Hz
CAPACITY: 10kVA/9kW
Icc: 6kA

Uninterruptible Power System


Model: COMPACT 15KVA
AC Input: 380/400/415VAC, 3φ+N+PE, 50/60Hz, 32A Max.
Batt. Input: ±120Vdc, 66A.
AC output: 380/400/415VAC, 3φ+N+PE, 50/60Hz, 32A Max.
CAPACITY: 15KVA/13.5KW
Icc: 6kA

Uninterruptible Power System


Model: COMPACT 20KVA
AC Input: 380/400/415VAC, 3φ+N+PE, 50/60Hz, 40A Max.
Batt. Input: ±120Vdc, 88A.
AC output: 380/400/415VAC, 3φ+N+PE, 50/60Hz, 40A Max.
CAPACITY: 20KVA/18KW
Icc: 6kA

TRF No.: IEC62040_1D Page 6 of 74 Report No. ES160322008S-11 Ver.1.0


Uninterruptible Power System
Model: COMPACT 30KVA
AC Input: 380/400/415Vac;3Φ+N+PE; 63A Max; 50/60Hz
Batt. Input: ±120Vdc;143A
AC output: 380/400/415Vac;3Φ+N+PE; 63A Max;50/60Hz
CAPACITY: 30kVA/27kW
Icc:6kA

Uninterruptible Power System


Model: COMPACT 40KVA
AC Input: 380/400/415Vac;3Φ+N+PE; 80A Max; 50/60Hz
Batt. Input: ±192/204/216/228/240/Vdc;119/112/106/100/95A
AC output: 380/400/415Vac;3Φ+N+PE;80A Max;50/60Hz
CAPACITY: 40kVA/36KW
Icc:6kA

Copy of Manufacturer and importer mark

Manufacturer: EnSmart Power Supplies and Energy Storage Systems


Ind. Trade A.S
Address: Halk Cad. No:8/A3, Atasehir, Istanbul 34752, Turkey
Importer: XXX
Address: XXX

TRF No.: IEC62040_1D Page 7 of 74 Report No. ES160322008S-11 Ver.1.0


Copy of caution mark:

Caution:
 For operation read user manual including safety warnings
first!
 This unit may be opened by authorized technicians only!
 Lead acid battery in the inside of the enclosure!
 The battery may present a risk of electric shock and energy
hazards.
 Risk of explosion if battery replaced by an incorrect type. For
battery information, see user’s manual.
 For disposal instructions of the battery, see user’s manual.
 See installation instructions before connecting to the
supply.

Remark:
- The CE marking and WEEE symbol should be at least 5.0mm and 7.0mm respectively in height.
- The above marking are the minimum requirements required by the safety standard. For the final
production sample, the marking which do not give rise to misunderstanding may be add.

TRF No.: IEC62040_1D Page 8 of 74 Report No. ES160322008S-11 Ver.1.0


Test item particulars ..................................................:
Classification of installation and use ......................: [x] User
[] Service Personal
Supply Connection .....................................................: [x] pluggable equipment [x] type A [] type B
[] permanent connection
[x] detachable power supply cord
[] non-detachable power supply cord
Equipment mobility ....................................................: [x] movable [] transportable
[] stationary [] for building-in
Operation condition ...................................................: [x] continuous
[] rated operating / resting time:
Access location ..........................................................: [x] operator accessible
[] restricted access location
Over voltage category (OVC) ....................................: [] OVC I [x] OVC II [] OVC III [] OVC IV
Mains supply tolerance (%) or absolute mains +/-10% (declared by client)
supply values ..............................................................:
Tested for IT power systems.....................................: [] Yes [x] No
IT testing, phase-phase voltage (V) .........................:
Class of equipment ....................................................: [x] Class I [] Class II []Not classified
Considered current rating of protective device as 80A
part of the building installation (A) ..........................:
Pollution degree (PD) .................................................: [] PD 1 [x] PD 2 [] PD 3
IP protection class ......................................................: IP20
Elevation during operation (m) .................................: Up to 2000m
Elevation of test laboratory (m) ................................: Below 2000m
Mass of equipment (kg) .............................................: >67kg
Possible test case verdicts:
- test case does not apply to the test object ........... : N/A
- test object does meet the requirement ................. : P (Pass)
- test object does not meet the requirement ........... : F (Fail)
Testing ......................................................................... :
Date of receipt of test item ........................................ : N/A
Date (s) of performance of tests ............................... : N/A

General remarks:
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.

Throughout this report a comma / point is used as the decimal separator.

Manufacturer’s Declaration per sub-clause 4.2.5 of IECEE 02:

TRF No.: IEC62040_1D Page 9 of 74 Report No. ES160322008S-11 Ver.1.0


The application for obtaining a CB Test Certificate Yes
includes more than one factory location and a Not applicable
declaration from the Manufacturer stating that the
sample(s) submitted for evaluation is (are)
representative of the products from each factory has
been provided ................................................................:

When differences exist; they shall be identified in the General product information section.
Name and address of factory (ies) .......................... : None
General product information:
This report is amended from previous report ES160322008S, issued on March 30, 2016, due to below
amendments:
- Changed of Applicant and manufacturer
- Change of trade mark
- Changed of Type name to COMPACT 10KVA, COMPACT 15KVA, COMPACT 20KVA, COMPACT
30KVA and COMPACT 40KVA; Battery bank: COMPACT-BT BATTERY BANK SERIES, which is
identical to original model except for model name.
No any tests need be considered.

1. The equipment with models COMPACT 10KVA, COMPACT 15KVA, COMPACT 20KVA,
COMPACT 30KVA, COMPACT 40KVA are line interactive type uninterruptible power supply with
sinewave o/p in line mode and square waveform in battery mode for general supply of office
equipment.
2. The UPS is designed as "Primary" type: input and output circuits and battery circuits are
considered as primary circuits during line mode. Operator cannot replace the battery.
3. Double/reinforced insulation provided between primary circuits (during line mode) or hazardous
voltage secondary circuits (during battery mode) and external surface USB port and RS232 port by
application of sufficient clearances and creepage distances within the unit.
4. Model difference description:
All models have the same constructions, circuit diagram and PCB layout. Only model name, appearance
and the parameter of some parts are different. Unless otherwise stated, all tests were performed on model
COMPACT 40KVA which means the typical model.

TRF No.: IEC62040_1D Page 10 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

4 GENERAL CONDITIONS FOR TESTS P


4.5 Components P
Comply with IEC 62040-1 or relevant component Components, which were P
standard found to affect safety aspects,
comply with the requirements
of this standard or within the
safety aspects of the relevant
IEC component standards.
(see appended table 4.5)
1.5.2/RD Evaluation and testing of components Components, which are P
certified to IEC and/or national
standards, are applied
correctly within their ratings.
Components not covered by
IEC standards are tested
under the conditions present
in the equipment.
1.5.3/RD Thermal controls Thermal control not used N/A
1.5.4/RD Transformers Transformers used are P
suitable for their intended
application and comply with
the relevant requirements of
the standard and particularly
Annex C.
1.5.5/RD Interconnecting cables Not provided. N/A
1.5.6/RD Capacitors bridging insulation Between lines: X2 capacitor P
according to IEC 60384-14:
1993 with 21 days damp heat
test was used.
Between Line and PE: Y2
capacitors according to IEC
60384-14 with 21 days damp
heat test was used.
1.5.7/RD Resistors bridging insulation P
1.5.7.1/RD Resistors bridging functional, basic or N/A
supplementary insulation
1.5.7.2/RD Resistors bridging double or reinforced insulation No resistors bridging double N/A
between a.c. mains and other circuits or reinforced insulation.
1.5.7.3/RD Resistors bridging double or reinforced insulation N/A
between a.c. mains and antenna or coaxial cable
1.5.8/RD Components in equipment for IT power systems N/A
4.6 Power interface P
1.6.1/RD AC power distribution systems TN power system P

TRF No.: IEC62040_1D Page 11 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

1.6.2/RD Input current Highest normal load for this P


equipment is the charging of
empty battery and operation
with the maximum specified
output load (see appended
table 4.6)
4.6 Neutral conductor Basic insulation for rated P
1.6.4/RD voltage between earthed parts
and line and neutral
conductors.
O/p neutral is not isolated
from the i/p neutral.
4.7 Marking and instructions P
4.7.1 General P
4.7.2 Power rating All required markings are P
1.7.1/RD affixed on labels located on the
enclosure of UPS
Input rated voltage/range (V) ....................................: See page 4-8 for details P
Input rated current/range (A).....................................: See page 4-8 for details P
Input symbol for nature of supply (d.c.) ....................: AC input N/A
Input rated frequency/range (Hz) ..............................: 50/60 Hz P
Number of Input phases and neutral ........................: 3Ø+N+PE P
Output rated voltage/range (V) .................................: See page 4-8 for details P
Output rated current/range (A) ..................................: See page 4-8 for details P
Output rated power factor, if less than unity, or The active power and P
active power and apparent power or active power apparent power are marked on
and rated current .......................................................: rating label.
Number of output phases and neutral .....................: 3Φ+N+PE P
Output rated active power (W or kW) .......................: See page 4-8 for details P
Output rated apparent power (VA or kVA) ...............: See page 4-8 for details P
Output symbol for nature of supply (d.c.) .................: AC outlet provided. N/A
Output rated frequency/range (Hz) ...........................: See page 4-8 for details P
Ambient operating temperature range (C).............: 0-40C N/A
Rated short-time withstand current (Icw) or rated Icc: 10kA P
conditional short-circuit current (Icc)
Manufacturer’s name or trademark or identification See page 1 for details P
mark ............................................................................:
Type/model or type reference ...................................: See page 1 for details P
Symbol for Class II equipment only ..........................: Class I equipment N/A

TRF No.: IEC62040_1D Page 12 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

Other symbols ............................................................: Additional symbols or P


markings do not give rise to
misunderstanding.
Certification marks .....................................................: To be evaluated when P
subjected to national approval
Instructions for units with automatic Instruction provided. See copy P
bypass/maintenance bypass, additional input a.c. of marking plate
supply, or external batteries, having text "See
installation instructions before connecting to the
supply" ........................................................................:
4.7.3 Safety instructions See below P
4.7.3.1 General "User manual" with directions P
regarding the maximum
ambient temperature, electrical
ratings, operation, description
of interfaces, connection to the
mains.
Service personnel installable
and to be operated by laymen.
Appropriate statements
provided in the "User Manual".
4.7.3.2 Installation ..................................................................: Installation instructions are P
available to the user in User's
Manual.
Location in a restricted access location only ...........: Instruction manual provided. P
Not for restricted access
location.
Permanent connector UPS .......................................: P
Pluggable type A or Pluggable type B UPS .............: See above P
4.7.3.3 Operation ....................................................................: The suitable information list in P
the user manual when operate
the UPS. Not for restricted
access location.
4.7.3.4 Maintenance ...............................................................: The instruction of maintenance P
is only included in the service
manual.
4.7.3.5 Distribution related backfeed ....................................: Caution label provided P,.
4.7.4 Main voltage adjustment ...........................................: Single input voltage range N/A
1.7.4/RD
Methods and means of adjustment; reference to N/A
installation instructions ..............................................:
4.7.5 Power outlets .............................................................: Relevant information provided P
1.7.5/RD on the marking that is affixed
near the outlets.

TRF No.: IEC62040_1D Page 13 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

4.7.6 Fuse identification (marking, special fusing P


1.7.6/RD characteristics, cross-reference) ..............................:
4.7.7 Wiring terminals See below P
1.7.7/RD
1.7.7.1/RD Protective earthing and bonding terminals ..............: Only PE of "Normal AC P
supply" with symbol IEC
60417-5019 (DB: 2002-10),
others with symbol IEC 60417-
5017 (DB: 2002-10).
1.7.7.2/RD Terminals for a.c. mains supply conductors ............: Terminals provided. Capital P
letters L1, L2, L3 and N are
used to identify input and
output phase.
1.7.7.3/RD Terminals for d.c. mains supply conductors ............: AC main supplied N/A
4.7.8 Battery terminals ........................................................: The terminal of batteries is P
marked with standard symbol
(IEC 60417, No. 5005 and No.
5006).
4.7.9 Controls and indicators See below P
1.7.8/RD
1.7.8.1/RD Identification, location and marking ..........................: LCD display provided, located P
on the front panel for
functional purpose only.
1.7.8.2/RD Colours .......................................................................: See above. Colours are P
acceptable due to only used
for information (no safety
involved even if disregarded).
1.7.8.3/RD Symbols ......................................................................: N/A
1.7.8.4/RD Markings using figures ..............................................: Not used. N/A
4.7.10 Isolation of multiple power sources ..........................: Only one external supply of N/A
1.7.9/RD hazardous voltage or energy
(via AC plug).
4.7.11 IT power systems TN power system. N/A
1.7.2.4/RD
4.7.12 Protection in building installation Protection against electric P
shock does not rely on
residual current devices.
Rated short-time withstand current (Icw) .................: N/A
Rated conditional short circuit current (Icc) .............: Icc: 10kA P
a) If higher Icp stated ≤ 10 kA Icc: 10kA P
a) If higher Icp stated > 10 kA N/A

TRF No.: IEC62040_1D Page 14 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

4.7.13 High leakage current (mA) ........................................: Leakage current of the N/A
5.1/RD equipment does not exceed
3.5 mA.
However due to the
connected load has influence
on the overall earth leakage
current a corresponding
statement was provided in the
user’s manual.
4.7.14 Thermostats and other regulating devices Neither thermostats nor other N/A
1.7.10/RD regulating devices provided.
4.7.15 Language(s) ...............................................................: User Manual and markings —
1.7.2.1/RD are both in English.
and Local language versions will
1.7.8.1/RD be made available during
national approval.
4.7.16 Durability of markings The label was subjected to P
1.7.11/RD the permanence of marking
test. The label was rubbed
with cloth soaked with water
for 15 s and then again for 15
s with the cloth soaked with
petroleum spirit. After this test
there was no damage to the
label. The marking on the
label did not fade. There was
neither curling nor lifting of the
label edge.
4.7.17 Removable parts No required markings placed P
1.7.12/RD on removable parts.
4.7.18 Replaceable batteries The battery is not placed in an P
1.7.13/RD operator access area. The
required warning is in the
safety manual.
Language(s) ...............................................................: —
4.7.19 Operator access with a tool ......................................: All areas containing hazard(s) P
1.7.2.5/RD are inaccessible to the
operator.
4.7.20 Battery PS with integral batteries P
Clearly legible information .........................................: Warning label attached on the P
outside surface of External
battery pack. Information
clearly legible
Battery type (lead-acid, NiCd, etc.) and number of Lead-Acid P
blocks or cells.............................................................:

TRF No.: IEC62040_1D Page 15 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

Nominal voltage of total battery (V) ..........................: Stated on rating user’s P


manual.
Nominal capacity of total battery (optional) ..............: Stated on rating user’s P
manual.
Warning label .............................................................: Warning language with P
information:
Caution: Lead-acid battery
inside the enclosure, it may
cause chemical hazard. The
battery may presents a risk of
electric shock and energy
hazards. For disposal
instructions for the battery,
see user’s manual.
Instructions .................................................................: The sufficient information P
about the battery was given in
the user’s manual.
2.1.1.5/RD Protection against energy hazards No energy hazard in operator P
access area. Checked by
means of the test finger.
4.7.21 Installation instructions Detailed information regarding P
1.7.2.4/RD external interfaces (RS232
port) provided in the User’s
Manual.

5 FUNDAMENTAL DESIGN REQUIREMENTS P


5.1 Protection against electric shock and energy hazards P
5.1.1 Protection for UPS intended to be used in operator No hazardous voltage circuit P
2.1.1/RD access areas wiring can be accessed by
operator.
2.1.1.1/RD Access to energized parts There is adequate protection P
against operator contact with
bare parts at ELV or
hazardous voltage or parts
separated from these with
basic or functional insulation
only (except protective earth).
No hazardous voltages
exceeding 1000V a.c. or
1500V d.c. Checked by test
finger, test probe and test pin.
Test by inspection ......................................................: Complies P
Test with test finger (Figure 2A) ...............................: Complies P
Test with test pin (Figure 2B) ....................................: Complies P
Test with test probe (Figure 2C) ...............................: No TNV circuits N/A

TRF No.: IEC62040_1D Page 16 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

2.1.1.2/RD Battery compartments No TNV circuits exist inside N/A


battery compartments
2.1.1.3/RD Access to ELV wiring No ELV wiring in operator N/A
accessible area.
Working voltage (Vpeak or Vrms); minimum —
distance through insulation (mm)
2.1.1.4/RD Access to hazardous voltage circuit wiring No any hazardous voltage P
circuit wiring operator
accessible.
2.1.1.5/RD Energy hazards ..........................................................: No energy hazard at operator P
accessible area. No energy
hazard during battery
replacement for service
person due to shape of
battery terminals.
2.1.1.6/RD Manual controls No conductive controls or N/A
handles or alike provided.
2.1.1.7/RD Discharge of capacitors in equipment The capacitance of the input P
circuits>0.1uF, refer to list of
critical components.
Measured voltage (V); time-constant (s) ..................: (See appended table 5.1.1 —
and 2.1.1.7/RD)
2.1.1.8/RD Energy hazards – d.c. mains supply The equipment is not N/A
connected to d.c. mains
supply
a) Capacitor connected to the d.c. mains supply ....: N/A
b) Internal battery connected to the d.c. mains N/A
supply .........................................................................:
2.1.1.9/RD Audio amplifiers in information technology No such parts. N/A
equipment...................................................................:
5.1.2 Protection for UPS intended to be used in service Checked by inspection, N/A
2.1.1.5 c) access areas unintentional contact is
/RD unlikely during service
operations.
Hazardous energy level ............................................: N/A
5.1.3 Protection for UPS intended to be used in Not for restricted access area N/A
2.1.1.5 c) restricted access areas
/RD
Hazardous energy level ............................................: N/A
5.1.4 Backfeed protection N/A
Shock hazard after de-energization of a.c. input for N/A
UPS
Measured voltage (V); time-constant (s) ..................: —

TRF No.: IEC62040_1D Page 17 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

Description of the construction .................................: Backfeed protection such as N/A


contactor will be provided
external to the UPS in the
final installation which is also
specified in installation
manual.
Air gap is employed for backfeed protection N/A
5.1.5 Emergency switching (disconnect) device REPO dry contactor provided, P
which is used to shut down
the UPS in case of
emergency

5.2 Requirements for auxiliary circuits P


5.2.1 Safety extra low voltage circuit - SELV See below: P
2.2/RD
2.2.1/RD General requirements All SELV circuits within limits. P
2.2.2/RD Voltages under normal conditions (V) ......................: Within SELV limits. (See P
appended table 5.2.1)
2.2.3/RD Voltages under fault conditions (V) ..........................: Within SELV limits. (See P
appended table 5.2.1)
2.2.4/RD Connection of SELV circuits to other circuits ...........: SELV circuits are only P
connected to other SELV and
protective earth.
5.2.2 Telephone network voltage circuits - TNV No TNV circuits N/A
2.3/RD
2.3.1/RD Limits N/A
Type of TNV circuits ..................................................: —
2.3.2/RD Separation of TNV circuits from other circuits and N/A
from accessible parts
2.3.2.1/RD General requirements N/A
2.3.2.2/RD Protection by basic insulation N/A
2.3.2.3/RD Protection by earthing N/A
2.3.2.4/RD Protection by other constructions .............................: N/A
2.3.3/RD Separation from hazardous voltages N/A
Insulation employed ...................................................: —
2.3.4/RD Connection of TNV circuits to other circuits N/A
Insulation employed ...................................................: —
2.3.5/RD Test for operating voltages generated externally N/A
5.2.3 Limited current circuits No limited current circuits, cl. N/A
2.4/RD 2.4/RD.
2.4.1/RD General requirements N/A

TRF No.: IEC62040_1D Page 18 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

2.4.2/RD Limit values —


Frequency (Hz) ..........................................................: —
Measured current (mA) .............................................: —
Measured voltage (V) ................................................: —
Measured circuit capacitance (nF or µF) .................: —
2.4.3/RD Connection of limited current circuits to other N/A
circuits
5.2.4 External signaling circuits See only above regarding N/A
3.5/RD RS485 and USB ports.
3.5.1/RD General requirements N/A
3.5.2/RD Types of interconnection circuits ..............................: N/A
3.5.3/RD ELV circuits as interconnection circuits No ELV interconnections. N/A
3.5.4/RD Data ports for additional equipment N/A
5.2.5 Limited power source N/A
2.5/RD
a) Inherently limited output N/A
b) Impedance limited output N/A
c) Regulating network limited output under normal N/A
operating and single fault condition
d) Overcurrent protective device limited output N/A
Max. output voltage (V), max. output current (A), —
max. apparent power (VA) ........................................:
Current rating of overcurrent protective device (A) .: —
Use of integrated circuit (IC) current limiters —

5.3 Protective earthing and bonding P


5.3.1 General P
2.6/RD Provisions for earthing and bonding See below P
2.6.1/RD Protective earthing Reliable connection of P
relevant conductive parts to
the PE terminal (via
green/yellow insulated wires).
2.6.2/RD Functional earthing Functional earthing on PCB P
board is separated by basic
insulation from primary circuit.
2.6.3/RD Protective earthing conductors and protective See below P
bonding conductors
2.6.3.1/RD General See subclause 2.6.3.3/RD P
2.6.3.2/RD Size of protective earthing conductors (see appended table 4.5) P

TRF No.: IEC62040_1D Page 19 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

Rated current (A), cross-sectional area (mm 2), (see appended table 4.5) —
AWG ...........................................................................:
2.6.3.3/RD Size of protective bonding conductors Refer to 2.6.3.4/RD P
Rated current (A), cross-sectional area (mm 2), Refer to 2.6.3.4/RD —
AWG ...........................................................................:
Protective current rating (A), cross-sectional area Refer to 2.6.3.4/RD —
(mm2), AWG ...............................................................:
2.6.3.4/RD Resistance of earthing conductors and their (See appended table 5.3.1) P
terminations; resistance (), voltage drop (V), test
current (A), duration (min) .........................................:
2.6.3.5/RD Colour of insulation ....................................................: Green/yellow P
2.6.4/RD Terminals See above P
2.6.4.1/RD General P
2.6.4.2/RD Protective earthing and bonding terminals Adequate protective earth P
connection, see also Sub-
clause 2.6.3.4/RD and 3.3/RD
Rated current (A), type, nominal thread diameter Separate PE and protective —
(mm) ...........................................................................: bonding conductor used.
2.6.4.3/RD Separation of the protective earthing conductor Separate wire for each P
from protective bonding conductors bonding connection.
2.6.5/RD Integrity of protective earthing See below P
2.6.5.1/RD Interconnection of equipment This UPS has its own earthing P
connection. Any other units
connected via a signal cable
to the PC by RS485 port shall
provide SELV only.
Additionally the parallel
connection port only
connected to the same type
port of other UPS units which
was classified as primary
circuits in the product and
reinforced insulated signal
wire will be used. Connection
for outputs and battery supply
have their own earth
connections which are
mounted on the internal metal
enclosure.
2.6.5.2/RD Components in protective earthing conductors and There are no switches or P
protective bonding conductors overcurrent protective devices
in the protective earthing /
bonding conductors.
2.6.5.3/RD Disconnection of protective earth P
2.6.5.4/RD Parts that can be removed by an operator P

TRF No.: IEC62040_1D Page 20 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

2.6.5.5/RD Parts removed during servicing It is not necessary to P


disconnect earthing except for
the removal of the earthed
part itself.
2.6.5.6/RD Corrosion resistance All safety earthing P
connections in compliance
with Annex J.
2.6.5.7/RD Screws for protective bonding Protective bonding conductors P
connected to metal chassis
via ring-type lugs fixed to
metal bolts (ISO thread type
M4), with nut and star-washer
provided.
2.6.5.8/RD Reliance on telecommunication network or cable Protective earthing is not rely N/A
distribution system on cable distribution system.
5.3.2 Protective earthing Accessible conductive parts P
2.6.1/RD are reliably connected to
protective earth terminal
2.10/RD Clearances, creepage distances and distances See clause 5.7 P
through insulation
4.2/RD Mechanical strength See clause 7.3 P
5.2/RD Electric strength See clause 8.2 P
5.3.3 Protective bonding Refer also to 2.6.3.4/RD P

5.4 AC and d.c. power isolation P


5.4.1 General P
3.4/RD Disconnection from the mains supply Breaker used disconnect P
device.
3.4.1/RD General requirement P
3.4.2/RD Disconnect devices Breaker used disconnect P
device.
3.4.3/RD Permanently connected equipment No such connection N/A
3.4.4/RD Parts which remain energized Adequate protection provided N/A
to service personnel during
backup and maintenance
mode.
3.4.5/RD Switches in flexible cords None provided. N/A
3.4.6/RD Number of poles - single-phase and d.c. equipment Switch used disconnect P
device.
3.4.7/RD Number of poles - three-phase equipment Breaker used disconnect N/A
device.
3.4.8/RD Switches as disconnect devices N/A
3.4.9/RD Plugs as disconnect devices N/A

TRF No.: IEC62040_1D Page 21 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

3.4.10/RD Interconnected equipment SELV circuits connect only to P


SELV circuits and Hazardous
Voltage circuits to Hazardous
circuits.
3.4.11/RD Multiple power sources Single mains power source N/A
provided.
5.4.2 Disconnect devices P
5.5 Overcurrent and earth fault protection P
5.5.1 General P
2.7.3/RD Short-circuit backup protection Over current protection by P
built-in fuses in each of 3
phases. Permanently
Connected Equipment.
Building Installation is
providing short-circuit backup
protection.
2.7.4/RD Number and location of protective devices ..............: Over current protector P
provided in live conductor
2.7.5/RD Protection by several devices Three fuse in parallel P
protection device provided.
No protective device in
neutral.
2.7.6/RD Warning to service personnel ...................................: Only one protection device N/A
provided.
5.5.2 Basic requirements Equipment relies on fuse or P
circuit breaker of the wall
outlet protection of the
building installation in regard
to L to N short-circuit. Over
current protection is provided
by the built-in fuse.
5.5.3 Battery circuit protection Ungrounded battery inside the P
UPS. Required fuses against
- overcurrent: 1
- earth fault: 1
Protection against overcurrent
by DC fuse in the positive
pole of the battery. However
earth faults will be covered by
devices in the building
installation.
5.5.3.1 Overcurrent and earth fault protection See below. P

TRF No.: IEC62040_1D Page 22 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

5.5.3.2 Location of protective device The fuses are directly located P


behind the supply wire of the
battery. The charger circuit is
located in the battery circuit
before the fuses. For the
charger circuit there are no
hazardous conditions under
any simulated fault conditions.
See appended table.
5.5.3.3 Rating of protective device The rating of the fuses inside P
the UPS provides adequate
safety protection during
abnormal and/or fault
conditions.
5.3.1/RD Protection against overload and abnormal (see appended table 8.3) P
operation
5.5.4 Short-time withstand current Icc: 10kA N/A
5.5.4.1 General N/A
5.5.4.2 Modes of operation N/A
5.5.4.3 Test procedure N/A
5.5.4.3.1 General application N/A
Rated UPS output current/(r.m.s) (A) .......................: —
Prospective test current/(r.m.s) (A) ..........................: —
Typical power factor ..................................................: —
Initial asymmetric peak current ration (Ipk / Icw) .....: —
Minimum durating of prospective test current —
(cycles 50/60 Hz) .......................................................:
5.5.4.3.2 Exemption from testing Specified Icc/ Icw not exceed P
10kA, no test necessary.
5.6 Protection of personnel – Safety interlocks P
5.6.1 Operator protection No hazardous voltage levels P
in operator accessible areas.
2.8/RD General principles N/A
2.8.1/RD Protection requirements N/A
2.8.2/RD Inadvertent reactivation N/A
2.8.3/RD Fail-safe operation N/A
2.8.4/RD Protection against extreme hazard N/A
2.8.5/RD Moving parts N/A
2.8.6/RD Overriding N/A
2.8.7/RD Switches, relays and their related circuits N/A

TRF No.: IEC62040_1D Page 23 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

2.8.7.1/RD Separation distances for contact gaps and their N/A


related circuits ............................................................:
2.8.7.2/RD Overload test N/A
2.8.7.3/RD Endurance test N/A
2.8.7.4/RD Electric strength test (see appended table 8.2) N/A
2.8.8/RD Mechanical actuators N/A
5.6.2 Service person protection N/A
5.6.2.1 Introduction N/A
5.6.2.2 Covers N/A
5.6.2.3 Location and guarding of parts N/A
5.6.2.4 Parts on doors No such parts. N/A
5.6.2.5 Component access No hazard likely when access N/A
breakers
2.8.3/RD Fail-safe operation N/A
5.6.2.6 Moving parts N/A
5.6.2.7 Capacitor banks No means of discharge P
provided. The installation
manual states that the
enclosure shall not be opened
for 5 minutes after all supplies
have been disconnected.
5.6.2.8 Internal batteries N/A

5.7 Clearances, creepage distances and distances through insulation P


2.10/RD
2.10.1/RD General See 2.10.3/RD, 2.10.4/RD P
and 2.10.5/RD.
2.10.1.1/R Frequency ..................................................................: P
Considered.
D
2.10.1.2/R Pollution degrees .......................................................: P
II
D
2.10.1.3/R Reduced values for functional insulation The functional insulations N/A
D comply with 5.3.4/RD a) and
c)
2.10.1.4/R Intervening unconnected conductive parts N/A
Considered.
D
2.10.1.5/R Insulation with varying dimensions N/A
No such transformer used.
D
2.10.1.6/R Special separation requirements No TNV N/A
D

TRF No.: IEC62040_1D Page 24 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

2.10.1.7/R Insulation in circuits generating starting pulses No such circuit generating N/A
D starting pulses.
2.10.2/RD Determination of working voltage (See appended table 5.7) P
2.10.2.1/R General P
See below.
D
2.10.2.2/R RMS working voltage P
(See appended table 5.7)
D
2.10.2.3/R Peak working voltage P
(See appended table 5.7)
D
2.10.3/RD Clearances See below. Annex G/RD was P
not considered.
2.10.3.1/R General Annex F/RD and minimum P
D clearances considered.
2.10.3.2/R Mains transient voltages P
See below.
D
a) AC mains supply ...................................................: Equipment is Overvoltage P
Category II.
b) Earthed d.c. mains supplies .................................: Not intended for d.c. mains N/A
supplies
c) Unearthed d.c. mains supplies .............................: Not intended for d.c. mains N/A
supplies
d) Battery operation ...................................................: Dedicated battery used. P
2.10.3.3/R Clearances in primary circuits P
(see appended table 5.7)
D
2.10.3.4/R Clearances in secondary circuits P
Sub-clause 5.3.4 considered.
D
2.10.3.5/R Clearances in circuits having starting pulses No such circuit generating N/A
D starting pulses.
2.10.3.6/R Transients from a.c. mains supply ............................: Normal transient voltage N/A
D considered (overvoltage
category II for primary circuit).
2.10.3.7/R Transients from d.c. mains supply ............................: N/A
D
2.10.3.8/R Transients from telecommunication networks and N/A
D cable distribution systems .........................................:
2.10.3.9/R Measurement of transient voltage levels N/A
D
a) Transients from a mains supply N/A
For an a.c. mains supply ...........................................: N/A
For a d.c. mains supply .............................................: N/A
b) Transients from a telecommunication network ...: N/A

TRF No.: IEC62040_1D Page 25 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

2.10.4/RD Creepage distances (see appended table 5.7) P


2.10.4.1/R General P
See below.
D
2.10.4.2/R Material group and comparative tracking index P
Material IIIb is used.
D
CTI tests .....................................................................: CTI rating for all material of P
min. 100.
2.10.4.3/R Minimum creepage distances P
(see appended table 5.7)
D
2.10.5 /RD Solid insulation Solid or laminated insulating P
materials having adequate
thickness are provided.
2.10.5.1/R General P
See below.
D
2.10.5.2/R Distances through insulation (see appended table 5.7) P
D
2.10.5.3/R Insulating compound as solid insulation Approved opto-couplers, see P
D appended table 4.5
2.10.5.4/R Semiconductor devices Approved optocoupler with P
D dti≥0.4mm used.
2.10.5.5/R Cemented joints No such construction. N/A
D
2.10.5.6/R Thin sheet material – General P
D
2.10.5.7/R Separable thin sheet material P
D
Number of layers (pcs) ..............................................: —
2.10.5.8/R Non-separable thin sheet material N/A
D
2.10.5.9/R Thin sheet material – standard test procedure P
D
Electric strength test —
2.10.5.10 Thin sheet material – alternative test procedure N/A
/RD
Electric strength test —
2.10.5.11 Insulation in wound components See cl. 2.10.5.12/RD P
/RD
2.10.5.12 Wire in wound components N/A
/RD
Working voltage .........................................................: —
a) Basic insulation not under stress .........................: N/A

TRF No.: IEC62040_1D Page 26 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

b) Basic, supplementary, reinforced insulation ........: N/A


c) Compliance with Annex U .....................................: N/A
Two wires in contact inside wound component; N/A
angle between 45 and 90 .......................................:
2.10.5.13 Wire with solvent-based enamel in wound No such construction. N/A
/RD components
Electric strength test —
Routine test N/A
2.10.5.14 Additional insulation in wound components No such construction. N/A
/RD
Working voltage .........................................................: —
- Basic insulation not under stress ...........................: N/A
- Supplementary, reinforced insulation ....................: N/A
2.10.6/RD Construction of printed boards See below P
2.10.6.1/R Uncoated printed boards (See appended table 5.7) P
D
2.10.6.2/R Coated printed boards No coated printed boards. N/A
D
2.10.6.3/R Insulation between conductors on the same inner No multi-layer PCBs provided. N/A
D surface of a printed board
2.10.6.4/R Insulation between conductors on different layers No multi-layer PCBs provided. N/A
D of a printed board
Distance through insulation N/A
Number of insulation layers (pcs) .............................: Single layer PCB N/A
2.10.7/RD Component external terminations (See appended table 5.7) P
2.10.8/RD Tests on coated printed boards and coated No such boards and N/A
components components
2.10.8.1/R Sample preparation and preliminary inspection N/A
D
2.10.8.2/R Thermal conditioning N/A
D
2.10.8.3/R Electric strength test (see appended table 8.2) —
D
2.10.8.4/R Abrasion resistance test N/A
D
2.10.9/RD Thermal cycling N/A
2.10.10/R Test for Pollution Degree 1 environment and Approved opto-couplers, see P
D insulating compound appended table 4.5
2.10.11/R Tests for semiconductor devices and cemented N/A
D joints

TRF No.: IEC62040_1D Page 27 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

2.10.12/R Enclosed and sealed parts Approved opto-couplers, see P


D appended table 4.5

6 Wiring, connections and supply P


6.1 General P
6.1.1 Introduction P
3.1/RD General P
3.1.1/RD Current rating and overcurrent protection All internal wires are UL P
recognized wiring which is
PVC insulated. Rated VW-1,
600V, minimum 105°C.
Internal wiring gauge is
suitable for current intended
to be carried. Internal wiring
for primary power distribution
protected against overcurrent
by built-in input fuse.
3.1.2/RD Protection against mechanical damage Wires do not touch sharp P
edges which could damage
the insulation and cause
hazard.
3.1.3/RD Securing of internal wiring Internal wires are secured by P
solder pins, cable ties and
quick connect terminals so
that a loosening of the
terminal connection is
unlikely.
3.1.4/RD Insulation of conductors The insulation of the individual P
conductors is suitable for the
application and the working
voltage. For the insulation
material see subclause
3.1.1/RD.
3.1.5/RD Beads and ceramic insulators No beads or similar ceramic N/A
insulators on conductors.
3.1.6/RD Screws for electrical contact pressure Electrical and earthing P
connections screwed two or
more complete threads into
metal. No screws of insulating
material for electrical and
earthing connections, or
where supplementary or
reinforced insulation could be
impaired by a metal
replacement.

TRF No.: IEC62040_1D Page 28 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

3.1.7/RD Insulating materials in electrical connections All current carrying P


connections are metal to
metal.
3.1.8/RD Self-tapping and spaced thread screws Self-tapping screws provided P
in inverter circuit and earthing
bonding.
3.1.9/RD Termination of conductors All conductors are reliable P
secured.
10 N pull test Force of 10 N applied to the P
termination points of the
conductors.
3.1.10/RD Sleeving on wiring Heat shrinkable tube used on P
the wire connector point.
6.1.2 Dimensions and rating of busbars and insulated N/A
conductors

6.2 Connection to power P


6.2.1 General provisions for connection to power P
3.2.2/RD Multiple supply connections N/A
3.2.3/RD Permanently connected equipment For permanent connection P
type, terminals for permanent
connection to supply.
Number of conductors, diameter of cable and —
conduits (mm) ............................................................:
3.2.4/RD Appliance inlets N/A
3.2.5/RD Power supply cords N/A
3.2.5.1/RD AC power supply cords N/A
Type ............................................................................: —
Rated current (A), cross-sectional area (mm²), —
AWG ...........................................................................:
3.2.5.2/RD DC power supply cords Not connected to DC power N/A
supply cords.
3.2.6/RD Cord anchorages and strain relief N/A
Mass of equipment (kg), pull (N) ..............................: —
Longitudinal displacement (mm)...............................: —
3.2.7/RD Protection against mechanical damage N/A
3.2.8/RD Cord guards N/A
Diameter or minor dimension D (mm); test mass (g) —
....................................................................................:
Radius of curvature of cord (mm) .............................: —

TRF No.: IEC62040_1D Page 29 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

6.2.2 Means of connection .................................................: P


More than one supply connection.............................: AC mains and internal battery P
used. Connector for the
battery not compatible with
inlet for AC mains.

6.3 Wiring terminals for external power conductors P


3.3/RD Wiring terminals for connection of external P
conductors
3.3.1/RD Wiring terminals P
3.3.2/RD Connection of non-detachable power supply cords N/A
3.3.3/RD Screw terminals Screws and nuts conforming P
to ISO 261 or ISO 262 input
terminal.
3.3.4/RD Conductor sizes to be connected Conductor size will be P
connected according to
installation manual.
Rated current (A), cord/cable type, cross-sectional For Phase/Neutral/Battery/PE —
area (mm2) .................................................................: conductors.
See instruction manual for the
configuration for all models
3.3.5/RD Wiring terminal sizes N/A
Rated current (A), type, nominal thread diameter —
(mm) ...........................................................................:
3.3.6/RD Wiring terminal design N/A
3.3.7/RD Grouping of wiring terminals N/A
3.3.8/RD Stranded wire N/A

7 Physical requirements P
7.1 Enclosure The UPS does not overturn P
when:
-tilted to an angle of 10°
-use a constant downward
force of 800N
-a force of 20% of the weight
is applied from any direction.
7.2 Stability P
4.1/RD

TRF No.: IEC62040_1D Page 30 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

Angle of 10 The UPS does not overturn P


when:
tilted to an angle of 10°
use a constant downward
force of 800N
a force of 20% of the weight is
applied from any direction.
Test force (N) .............................................................: See above P

7.3 Mechanical strength P


4.2/RD
4.2.1/RD General Tests performed and passed. P
Results see below. After tests,
unit complied with the
requirements of sub-clauses
2.1.1/RD, 2.6.1/RD and
2.10/RD.
4.2.2/RD Steady force test, 10 N 10 N applied to all —
components other than
enclosure.
4.2.3/RD Steady force test, 30 N 30 N applied to parts inside P
the UPS.
4.2.4/RD Steady force test, 250 N 250 N applied to outer P
enclosure.
4.2.5/RD Impact test See below P
Fall test No hazard as result from steel P
ball fall test.
Swing test No hazard as result from steel P
ball swing test.
4.2.6/RD Drop test; height (mm) ...............................................: Not required for this N/A
equipment.
4.2.7/RD Stress relief test Tested at temperature of 70 —
C. No distortion of enclosure
observed and no hazards.
4.2.8/RD Cathode ray tubes No CRT in the unit. N/A
Picture tube separately certified ...............................: —
4.2.9/RD High pressure lamps No high pressure lamp N/A
provided.
4.2.10/RD Wall or ceiling mounted equipment; force (N) .........: Not wall mounted equipment. N/A

7.4 Construction details P


7.4.1 Introduction Considered. P

TRF No.: IEC62040_1D Page 31 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

4.3.1/RD Edges and corners Edges and corners of the P


enclosure are rounded.
4.3.2/RD Handles and manual controls; force (N) ..................: No handles or manual controls N/A
provided. No axial pull applied
to push-buttons.
4.3.3/RD Adjustable controls No hazardous adjustable N/A
controls.
4.3.4/RD Securing of parts No loosening of parts P
impairing creepage distances
or clearances is likely to
occur.
4.3.5/RD Connection by plugs and sockets No mismating of connectors, P
plugs or sockets possible.
4.3.7/RD Heating elements in earthed equipment No heating elements N/A
provided.
4.3.11/RD Containers for liquids or gases The equipment does not N/A
contain flammable liquids or
gases.
4.4/RD Protection against hazardous moving parts No moving parts. N/A
4.4.1/RD General DC fan located at primary P
circuit. The enclosure of the
unit provide as fan guard.
Test finger applied to
openings. No fan blade
accessible.
4.4.2/RD Protection in operator access areas .........................: See 4.4.1 P
4.4.3/RD Protection in restricted access locations ..................: Not for restricted access N/A
locations
4.4.4/RD Protection in service access areas See 4.4.1 P
4.4.5/RD Protection against moving fan blades Considered P
4.4.5.1/RD General See below. P
Not considered to cause pain or injury. a) ...............: N/A
Is considered to cause pain, not injury. b) ...............: N/A
Considered to cause injury. c) ...............: N/A
4.4.5.2 Protection for users P
Use of symbol or warning ..........................................: (See appended table 7.7) P
4.4.5.3 Protection for service persons P
Use of symbol or warning ..........................................: Instructed in the service P
instructions
4.5/RD Thermal requirements See clause 7.7 P

TRF No.: IEC62040_1D Page 32 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

4.5.1/RD General P
4.5.2/RD Temperature tests P
Normal load condition per Annex L ..........................: Equipment loaded with rated P
output power.
4.5.3/RD Temperature limits for materials (see appended table 7.7) P
4.5.4/RD Touch temperature limits (see appended table 7.7) P
4.5.5/RD Resistance to abnormal heat ....................................: (see appended table 7.4) P
7.4.2 Openings See appended table 7.4.2 P
7.4.3 Gas Concentration The ventilation by openings P
exceeds the required airflow.
Refer to Annex M.
7.4.4 Equipment movement N/A

7.5 Resistance to fire P


4.7/RD
4.7.1/RD Reducing the risk of ignition and spread of flame Use of materials with the P
required flammability classes
Method 1, selection and application of components Method 1 is used. No P
wiring and materials excessive temperatures. No
easily burning materials
employed. Safety relevant
components used within their
specified temperature limits.
Method 2, application of all of simulated fault N/A
condition tests
4.7.2/RD Conditions for a fire enclosure P
4.7.2.1/RD Parts requiring a fire enclosure With having the following P
components:
a) Components in primary
circuits
c) Insulated wiring
Semiconductor devices,
transistors, diodes, integrated
circuits
d) Resistors, capacitors,
inductors
The fire enclosure is required.
4.7.2.2/RD Parts not requiring a fire enclosure The fire enclosure is required N/A
to cover all parts.
4.7.3/RD Materials See below. P
4.7.3.1/RD General PCB rated V-0. See P
appended table.

TRF No.: IEC62040_1D Page 33 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

4.7.3.2/RD Materials for fire enclosures Metal enclosure. (See P


appended table 4.3)
4.7.3.3/RD Materials for components and other parts outside See sub-clause 4.7.2/RD N/A
fire enclosures
4.7.3.4/RD Materials for components and other parts inside fire Internal components except P
enclosures small parts are V-2, HF-2 or
better.
4.7.3.5/RD Materials for air filter assemblies No air filters in the equipment. N/A
4.7.3.6/RD Materials used in high-voltage components No parts exceeding 4kV. N/A

7.6 Battery location P


7.6.1 Battery location and installation Batteries are located inside N/A
the UPS enclosure.
7.6.2 Accessibility and maintainability Maintenance free battery. The P
battery is connected by quick
connect terminals (no
necessary tightening).
7.6.3 Distance The temperature of the P
electrolyte and the gas
emission are within the limits
of this standard (see
appropriate subclauses).
7.6.4 Case insulation No Ni-Cd battery used inside. N/A
7.6.5 Wiring The protection of connection P
wiring complies with
subclause 3/RD.
7.6.6 Electrolyte spillage Sealed maintenance free P
batteries provided with an
unlikely emission of
electrolyte (VRLA type).
7.6.7 Ventilation For the ventilation of the lead- P
acid battery refer to table M.
7.6.8 Charging voltage See appended table 8.3. P

7.7 Temperature rise P


4.5/RD Thermal requirements P
4.5.1/RD General P
4.5.2/RD Temperature tests (see appended table 7.7) P
Normal load condition per Annex L ..........................: P
4.5.3/RD Temperature limits for materials (see appended table 7.7) P
4.5.4/RD Touch temperature limits (see appended table 7.7) P

TRF No.: IEC62040_1D Page 34 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

4.5.5/RD Resistance to abnormal heat ....................................: (See appended table 7.4) P

8 Electrical requirements and simulated abnormal conditions P


8.1 General provisions for earth leakage P
5.1.1/RD General Test conducted in accordance P
with Sub-clause 8.1
5.1.7/RD Equipment with touch current exceeding 3.5 mA P

8.2 Electric strength P


5.2/RD
5.2.1/RD General (see appended table 8.2) P
5.2.2/RD Test procedure (see appended table 8.2) P

8.3 Abnormal operating and fault conditions P


8.3.1 General P
5.3.1/RD Protection against overload and abnormal (see appended table 8.3) P
operation
5.3.2/RD Motors No Motor used. N/A
5.3.3/RD Transformers (See appended Annex C) P
5.3.4/RD Functional insulation ..................................................: Complies with a) and c). P
5.3.5/RD Electromechanical components No electromechanical P
component (except for
approved relays) provided.
5.3.9/RD Compliance criteria for abnormal operating and No fire propagated beyond P
fault conditions the equipment. No molten
metal was emitted. Electric
strength tests from primary to
SELV and primary to PE were
passed.
5.3.9.1/RD During the tests P
5.3.9.2/RD After the tests P
8.3.2 Simulation of faults No fire or molten metal P
occurred and no deformation
of enclosure during the tests.
8.3.3 Conditions for tests No reduction of clearance and P
creepage distance. Electric
strength test is made on
basic, supplementary and
reinforced insulation after test.

TRF No.: IEC62040_1D Page 35 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

9 Connection to telecommunication networks N/A


6/RD
6.1/RD Protection of telecommunication network service persons, and users of other N/A
equipment connected to the network, from hazards in the equipment
6.1.1/RD Protection from hazardous voltages N/A
6.1.2/RD Separation of the telecommunication network from N/A
earth
6.1.2.1/RD Requirements N/A
Supply voltage (V) .....................................................: —
Current in the test circuit (mA) ................................: —
6.1.2.2/RD Exclusions ..................................................................: N/A

6.2/RD Protection of equipment users from overvoltages on telecommunication N/A


networks
6.2.1/RD Separation requirements N/A
6.2.2/RD Electric strength test procedure N/A
6.2.2.1/RD Impulse test N/A
6.2.2.2/RD Steady-state test N/A
6.2.2.3/RD Compliance criteria N/A
6.3/RD Protection of the telecommunication wiring N/A
system from overheating
Max. output current (A) ..............................................: —
3.5/RD Interconnection of equipment N/A
3.5.1/RD General requirements N/A
3.5.2/RD Types of interconnection circuits ..............................: N/A
3.5.3/RD ELV circuits as interconnection circuits N/A
3.5.4/RD Data ports for additional equipment N/A
2.1.3/RD Protection in restricted access locations N/A
2.3.1/RD Limits N/A
Type of TNV circuits ..................................................: —
2.3.2/RD Separation from other circuits and from accessible P
parts
2.3.2.1/RD General requirements P
2.3.2.2/RD Protection by basic insulation P
2.3.2.3/RD Protection by earthing N/A
2.3.2.4/RD Protection by other constructions .............................: N/A

TRF No.: IEC62040_1D Page 36 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

2.3.3/RD Separation from hazardous voltages N/A


Insulation employed ...................................................: —
2.3.4/RD Connection of TNV circuits to other circuits N/A
Insulation employed ...................................................: —
2.3.5/RD Test for operating voltages generated externally N/A
2.6.5.8/RD Reliance on telecommunication network or cable N/A
distribution system
2.10.3.3/R Clearances in primary circuits N/A
D
2.10.3.4/R Clearances in secondary circuits N/A
D
2.10.4/RD Creepage distances N/A
2.10.4.1/R General N/A
D
2.10.4.2/R Material group and comparative tracking index N/A
D
CTI tests .....................................................................: —
2.10.4.3/R Minimum creepage distances N/A
D
M/RD Annex M, CRITERIA FOR TELEPHONE RINGING SIGNALS (see 2.3.1/RD) N/A
M.1/RD Introduction N/A
M.2 /RD Method A N/A
M.3/RD Method B N/A
M.3.1/RD Ringing signal N/A
M.3.1.1/R Frequency (Hz) ..........................................................: —
D
M.3.1.2/R Voltage (V) .................................................................: —
D
M.3.1.3/R Cadence; time (s), voltage (V) ..................................: —
D
M.3.1.4/R Single fault current (mA) ...........................................: —
D
M.3.2/RD Tripping device and monitoring voltage ...................: N/A
M.3.2.1/R Conditions for use of a tripping device or a —
D monitoring voltage
M.3.2.2/R Tripping device N/A
D
M.3.2.3/R Monitoring voltage (V) ...............................................: N/A
D

TRF No.: IEC62040_1D Page 37 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

A/RD Annex A, Tests for resistance to heat and fire N/A


A.1/RD Flammability test for fire enclosures of movable equipment having a total N/A
mass exceeding 18 kg, and of stationary equipment (see 4.7.3.2/RD)
A.1.1/RD Samples......................................................................: —
Wall thickness (mm) ..................................................: —
A.1.2/RD Conditioning of samples; temperature (C)..............: N/A
A.1.3/RD Mounting of samples .................................................: N/A
A.1.4/RD Test flame (see IEC 60695-11-3) N/A
Flame A, B, C or D.....................................................: —
A.1.5/RD Test procedure N/A
A.1.6/RD Compliance criteria N/A
Sample 1 burning time (s) .........................................: —
Sample 2 burning time (s) .........................................: —
Sample 3 burning time (s) .........................................: —
A.2/RD Flammability test for fire enclosures of movable equipment having a total N/A
mass not exceeding 18 kg, and for material and components located inside
fire enclosures (see 4.7.3.2/RD and 4.7.3.4/RD)
A.2.1/RD Samples, material ......................................................: —
Wall thickness (mm) ..................................................: —
A.2.2/RD Conditioning of samples; temperature (°C)..............: N/A
A.2.3/RD Mounting of samples .................................................: N/A
A.2.4/RD Test flame (see IEC 60695-11-4) N/A
Flame A, B or C .........................................................: —
A.2.5/RD Test procedure N/A
A.2.6/RD Compliance criteria N/A
Sample 1 burning time (s) .........................................: —
Sample 2 burning time (s) .........................................: —
Sample 3 burning time (s) .........................................: —
A.2.7/RD Alternative test acc. to IEC 60695-11-5, cl. 5 and 9 N/A
Sample 1 burning time (s) .........................................: —
Sample 2 burning time (s) .........................................: —
Sample 3 burning time (s) .........................................: —
A.3/RD Hot flaming oil test (see 4.6.2/RD) N/A

TRF No.: IEC62040_1D Page 38 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

A.3.1/RD Mounting of samples N/A


A.3.2/RD Test procedure N/A
A.3.3/RD Compliance criterion N/A

B/RD Annex B, Motor tests under abnormal conditions (see 4.7.2.2/RD and P
5.3.2/RD)
B.1/RD General requirements Motor in secondary DC Fan P
Position .......................................................................: —
Manufacturer ..............................................................: —
Type ............................................................................: —
Rated values ..............................................................: —
B.2/RD Test conditions P
B.3/RD Maximum temperatures N/A
B.4/RD Running overload test N/A
B.5/RD Locked-rotor overload test N/A
Test duration (days) ...................................................: —
Electric strength test: test voltage (V) ......................: —
B.6/RD Running overload test for d.c. motors in N/A
secondary circuits
B.6.1/RD General N/A
B.6.2/RD Test procedure N/A
B.6.3/RD Alternative test procedure N/A
B.6.4/RD Electric strength test; test voltage (V) ......................: N/A
B.7/RD Locked-rotor overload test for d.c. motors in P
secondary circuits
B.7.1/RD General P
B.7.2/RD Test procedure N/A
B.7.3/RD Alternative test procedure P
B.7.4/RD Electric strength test; test voltage (V) ......................: N/A
B.8/RD Test for motors with capacitors N/A
B.9/RD Test for three-phase motors N/A
B.10/RD Test for series motors N/A
Operating voltage (V) ................................................: —

TRF No.: IEC62040_1D Page 39 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

C/RD Annex C, Transformers (see 1.5.4/RD and 5.3.3/RD) P


Position .......................................................................: T2 —
Manufacturer ..............................................................: See appended table 4.5 —
Type ............................................................................: See appended table 4.5 —
Rated values ..............................................................: Class B —
Method of protection ..................................................: Circuit design —
C.1/RD Overload test See appended table 7.5 and P
8.3
C.2/RD Insulation See appended table C.2 P
Protection from displacement of windings ...............: See appended table C.2 P

D/RD Annex D, Measuring instruments for touch current tests (see 5.1.4/RD) P
D.1/RD Measuring instrument Measuring instrument P
according to figure D.1 was
used.
D.2/RD Alternative measuring instrument N/A

E/RD Annex E, Temperature rise of a winding (see Annex E/RD) N/A

F/RD Annex F, Measurements of clearances and creepage distance (see 2.10/RD P


and Annex G/RD)

G/RD Annex G, Alternative method for determining minimum clearances N/A


G.1/RD Clearances N/A
G.1.1/RD General N/A
G.1.2/RD Summary of the procedure for determining minimum clearances N/A
G.2/RD Determination of mains transient voltage (V) N/A
G.2.1/RD AC mains supply ........................................................: N/A
G.2.2/RD Earthed d.c. mains supplies ......................................: N/A
G.2.3/RD Unearthed d.c. mains supplies .................................: N/A
G.2.4/RD Battery operation .......................................................: N/A
G.3/RD Determination of telecommunication network N/A
transient voltage (V) ................................................:
G.4/RD Determination of required withstand voltage (V) N/A

TRF No.: IEC62040_1D Page 40 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

G.4.1/RD Mains transients and internal repetitive peaks ........: N/A


G.4.2/RD Transients from telecommunication networks .........: N/A
G.4.3/RD Combination of transients N/A
G.4.4/RD Transients from cable distribution systems N/A
G.5/RD Measurement of transient voltages (V) N/A
a) Transients from a mains supply N/A
For an a.c. mains supply N/A
For a d.c. mains supply N/A
b) Transients from a telecommunication network N/A
G.6/RD Determination of minimum clearances ................: N/A

H Annex H, Guidance on protection against ingress of water and foreign N/A


objects
(see IEC 60529)

I Annex I, Backfeed protection test N/A


I.1 General N/A
I.2 Test for pluggable UPS N/A
I.3 Test for permanently connected UPS N/A
I.4 Load-induced change of reference potential N/A
I.5 Solid-state backfeed protection N/A
(see clause 7.1-7.5 of IEC 62040-2 and clause
7.1-7.2 of IEC 62040-3)

J/RD Annex J, Table of electrochemical potentials (see 2.6.5.6/RD) P


Metal(s) used .............................................................: Zn plated copper for all —
materials

K/RD Annex K, Thermal controls (see 1.5.3/RD and 5.3.8/RD) N/A


K.1/RD Making and breaking capacity N/A
K.2 /RD Thermostat reliability; operating voltage (V) ......: N/A
K.3/RD Thermostat endurance test; operating voltage N/A
(V) ...............................................................................:
K.4/RD Temperature limiter endurance; operating N/A
voltage (V) .................................................................:

TRF No.: IEC62040_1D Page 41 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

K.5/RD Thermal cut-out reliability N/A


K.6/RD Stability of operation N/A

L Annex L, Reference loads P


L.1 General P
L.2 Reference resistive load P
L.3 Reference inductive-resistive load —
L.4 Reference capacitive-resistive loads Worst case power factors as P
specified by the manufacturer
maintained during the relevant
tests.
L.5 Reference non-linear load P
L.5.1 General P
L.5.2 Test method P
L.5.3 Connection of the non-linear reference load —

M Annex M, Ventilation of battery compartments P


M.1 General P
M.2 Normal conditions See appended table M P
M.3 Blocked conditions P
M.4 Overcharge conditions P

N Annex N, Minimum and maximum cross-sections of copper conductors N/A


suitable for connection (see 6.3)

U/RD Annex U, Insulated winding wires for use without interleaved insulation N/A
(see 2.10.5.4/RD)

V/RD Annex V, AC POWER DISTRIBUTION SYSTEMS (see 1.6.1/RD) P


V.1/RD Introduction P
V.2/RD TN power distribution systems See sub-clause 1.6.1/RD. P
V.3/RD TT power distribution systems N/A
V.4/RD IT power distribution systems N/A

TRF No.: IEC62040_1D Page 42 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

4.6, TABLE: Electrical Data (in normal conditions) P


1.6.2/RD
fuse # I rated (A) U (V) P (W) I (A) I fuse (A) condition/status
Circuit -- 342V/50Hz 36100 70.2 70.2 Normal operation with empty
breaker battery charging

Circuit -- 342V/60Hz 36100 70.2 70.2


breaker
Circuit 80 380V/50Hz 35900 61.5 61.5
breaker
Circuit 80 380V/60Hz 35900 61.5 61.5
breaker
Circuit 80 415V/50Hz 36100 56.9 56.9
breaker
Circuit 80 415V/60Hz 36100 56.9 56.9
breaker
Circuit -- 439.9V/50 35900 53.7 53.7
breaker Hz
Circuit -- 439.9V/60 35900 53.7 53.7
breaker Hz
Circuit -- 456.5V/50 36100 52.1 52.1
breaker Hz
Circuit -- 456.5V/60 36100 52.1 52.1
breaker Hz
Supplementary information:

5.1.1 TABLE: Max. V, A, VA Test N/A


2.1.1.5/RD
Voltage (rated) Current (rated) Voltage (max.) (V) Current (max.) VA (max.)
(V) (A) (A) (VA)
-- -- -- -- --
Supplementary information:

5.1.1 TABLE: Stored Energy N/A


2.1.1.5/RD
Capacitance C (µF) Voltage U (V) Energy E (J)
-- -- --
Supplementary information:

TRF No.: IEC62040_1D Page 43 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

5.1.1 TABLE: discharge of capacitors in the primary circuit P


2.1.1.7/
RD
Condition  calculated  measured t u 0V Comments
(s) (s) (s)

Power switch on -- 0.92 1.32 Vi=395V, 37% of Vi=146.15V, No load


(A-N) applied
Supplementary information:

5.2.1 TABLE: Evaluation Of Voltage Limiting Components In SELV Circuits P


2.2/RD
Component (measured between) max. voltage (V) Voltage Limiting Components
(normal operation)
V peak V d.c.
T2(on CNTL PCB) Pin6– Pin7 32.7 -- --
T2(on CNTL PCB) Pin8– Pin10 35.5 -- --
Fault test performed on voltage limiting components Voltage measured (V) in SELV circuits
(V peak or V d.c.)
-- --
Supplementary information:

5.2.3 Table: Limited current circuit measurement N/A


2.4.2/RD
Location Voltage Current Freq. (kHz) Limit Comments
(mV) (mA) (mAp)
-- -- -- -- -- --
Supplementary information:

5.3.1 and Table: Resistance of earthing measurement P


2.6.3.4/RD
Location Resistance Voltage drop Comments
measured (m) measured (V)
I/P earth to O/P earth 17 -- 32A, 2 minutes
Supplementary information: Limit value: ≤0.1Ω
Earthing continuity is achieved by sufficient conductor size. See relevant clauses.

TRF No.: IEC62040_1D Page 44 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

5.5.4 Table: Short-time withstand current test N/A


Rated max. output current Announced withstand Test current Comments
current
-- -- -- --
Supplementary information: Specified Icc not exceeds 10kA, no test necessary.

5.2.5 TABLE: Limited Power Sources N/A


2.5/RD
Circuit output tested:
Note: Measured Uoc (V) with all load circuits disconnected:
Components Test condition Uoc (V) Isc (A) VA
(Single fault)
Meas. Limit Meas. Limit
-- -- -- -- -- -- --
Supplementary information:
Sc=Short circuit, Oc=Open circuit

5.7 Table: Working Voltage Measurement P


2.10.2/RD
Location RMS voltage (V) Peak voltage (V) Comments
Tested on CNTL
T2 Pin 1-6 224 332 Line mode and rated output load.
T2 Pin 1-7 212 320 Ditto
T2 Pin 1-8 218 318 Ditto
T2 PIN 1-9 219 324 Ditto
T2 Pin 1-10 222 332 Ditto
T2 Pin 2-6 214 316 Ditto
T2 Pin 2-7 216 392 Ditto
T2 Pin 2-8 210 324 Ditto
T2 PIN 2-9 206 346 Ditto
T2 Pin 2-10 218 376 Ditto
T2 Pin 3-6 200 306 Ditto
T2 Pin 3-7 208 348 Ditto
T2 Pin 3-8 206 312 Ditto

TRF No.: IEC62040_1D Page 45 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

T2 PIN 3-9 209 306 Ditto


T2 Pin 3-10 200 318 Ditto

T2 Pin 4-6 199 324 Ditto

T2 Pin 4-7 210 382 Ditto

T2 Pin 4-8 205 317 Ditto

T2 PIN 4-9 205 338 Ditto

T2 Pin 4-10 209 375 Ditto

U25 Pin 1-3 217 316 Ditto

U25 Pin 1-4 219 323 Ditto

U25 Pin 2-3 220 331 Ditto

U25 Pin 2-4 210 318 Ditto

U73 Pin 1-3 217 316 Ditto

U73 Pin 1-4 219 323 Ditto

U73 Pin 2-3 220 331 Ditto

U73 Pin 2-4 210 318 Ditto

U47 Pin 1-3 217 316 Ditto

U47 Pin 1-4 219 323 Ditto

U47 Pin 2-3 220 331 Ditto

U47 Pin 2-4 210 318 Ditto

U49 Pin 1-3 217 316 Ditto

U49 Pin 1-4 219 323 Ditto

U49 Pin 2-3 220 331 Ditto

U49 Pin 2-4 210 318 Ditto

U59 Pin 1-3 217 316 Ditto

U59 Pin 1-4 219 323 Ditto

U59 Pin 2-3 220 331 Ditto

U59 Pin 2-4 210 318 Ditto

Supplementary information:
No isolation components used, main voltage considered

5.7, TABLE: Clearance And Creepage Distance Measurements P


2.10.3/RD

TRF No.: IEC62040_1D Page 46 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

clearance cl and creepage Up U r.m.s. Required cl cl required dcr dcr


distance dcr at/of: (V) (V) (mm) (mm) (mm) (mm)
Whole unit
Metal enclosure to bare pin of 420 250 2.0 12.2 2.5 >12.2
battery terminal (FI)
Primary pin to earthed metal 420 250 2.0 5.1 2.5 >5.1
plate on Input EMI PCB (BI)
Primary pin to earthed metal 420 250 2.0 8.9 2.5 >8.9
enclosure on Output EMI PCB
(BI)
ON COMM BOARD
Primary trace to secondary 420 250 4.0 6.2 5.0 6.2
trace under (U73) (RI)
Primary trace to secondary 420 250 4.0 5.1 5.0 5.1
trace under T2 (RI)
Primary winding to secondary 420 250 4.0 5.0 5.0 5.0
winding of T2 (RI)
Primary winding to core of T2 420 250 2.0 2.5 2.5 2.5
(BI)
Secondary winding to core of 420 250 2.0 2.5 2.5 2.5
T2 (BI)
Supplementary information: *FI=Functional insulation, BI=Basic insulation, RI=Reinforced insulation.
Unless otherwise specified, the worst conditions of Cl. & Cr. In above mentioned locations have been
considered and listed.

5.7, TABLE: Distance Through Insulation Measurements P


2.10.5.2/
RD
Distance through insulation di at/of: U r.m.s. Test voltage Required di di
(V) (V) (mm) (mm)
Plastic enclosure 250 AC 3000 0.4 >0.4*
Supplementary information: *see information in table 4.5 for details.

7.4, TABLE: Ball Pressure Test of Thermoplastics N/A


4.5.5/RD
Allowed impression diameter (mm) ..................... : 
Object/ Part No./ Material Manufacturer/ Test temperature (C) Impression diameter (mm)
trademark

TRF No.: IEC62040_1D Page 47 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

-- -- -- --
Supplementary information: Phenolic material bobbin used in Transformer and Line Choke without test.

7.4.2 TABLE: Openings P


4.6/RD
Location Size (mm) Comments
Top None No openings
Bottom None No openings
Side None No openings
Front 3.0x12.5 mm 65 openings for ventilation
Rear Diameter=67mm 1 opening for DC fan ventilation protected by metal
fan guard.
Supplementary information:

7.5 TABLE: Resistance to fire P


4.7/RD
Part Manufacturer of Type of material Thickness Flammability Evidence
material (mm) class
-- -- -- -- -- --
Supplementary information: see appended table 4.5

7.7, TABLE: Heating Test P


4.5/RD
Test voltage (V) ........................................................ :See below 
Ambient (oC) ............................................................. :See below 
Thermocouple Locations Max. temperature measured, Max. temperature
(oC) limit,
(oC)
Test condition: a b c --
On EMI Board
C1 52.3 53.6 57.9 85
PCB near C4 53.1 55.4 62.1 130
C3 49.5 53.3 64.8 100
On INV Board

TRF No.: IEC62040_1D Page 48 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

X-cap C64 50.4 56.8 59.5 100


K1 coil 53.8 61.6 66.3 130
T3 50.1 54.1 59.1 110
K1 coil 53.0 54.8 66.0 130
C13 47.1 58.4 62.1 105
L5 59.2 60.8 64.0 130
L1 50.7 55.7 62.9 130
T2 coil 54.7 59.2 66.0 110
T2 core 52.5 58.1 65.3 110
C14 42.8 48.6 61.6 105
PCB near Q12 47.6 55.1 56.2 130
C34 43.3 49.7 58.1 105
On CNTL Board
U3 body 39.7 46.6 56.3 100
T2 coil 50.3 56.5 57.5 110
T2 core 49.9 55.5 57.4 110
On PFC INDUCTOR Board
L1 coil 55.8 57.4 60.6 110
L2 coil 47.3 52.3 59.5 110
L3 coil 51.3 55.8 62.6 110
PCB near L2 53.4 60.3 64.8 130
On PFC Board
C12 41.4 47.8 60.4 105
PCB near Q13 45.2 53.9 55.0 130
C16 42.9 48.7 56.9 105
On The Unit
Inlet 34.3 41.6 50.4 70
Outlet 36.5 43.7 50.1 70
Fan body 37.6 41.7 52.3 70
Input wire 38.3 44.9 54.6 80
Battery wire 35.5 39.9 54.7 80
Top enclosure 35.2 38.3 47.9 75

TRF No.: IEC62040_1D Page 49 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

Front panel 31.9 36.6 46.8 95


Ambient 25.0 24.8 25.1 --
Supplementary information:
a. Recharge mode, I/P: 342V/60Hz, O/P: with Rating load until battery is full and temperature stable.
b. Recharge mode, I/P: 456.5V/50Hz, O/P: with Rating load until battery is full and temperature stable.
c. Discharge mode with Rating load until unit shutdown.
1. The temperatures were measured under the worst case normal mode defined in 1.2.2.1/RD and as
described in sub-clause 4.6 at voltages as described above.
2. With a specified ambient temperature of 40°C. Temperature is calculated as follows:
Winding components providing safety isolation:
- Class B →Tmax = 120-10= 110°C
*Measured 3 times with the max. Value list above.

7.7, TABLE: Heating test, resistance method N/A


4.5/RD
Test voltage (V) ....................................................... : 
Ambient, t1 (C) ........................................................ : 
Ambient, t2 (C) ........................................................ : 
Temperature rise of winding R1 (Ω) R2 (Ω) ΔT (K) Max. dT (K) Insulation
class
-- -- -- -- -- --
Supplementary information:

8 TABLE: touch current measurement P


5.1/RD
Measured between: Measured Limit Comments/conditions
(mA) (mA)
Metal enclosure to terminal A 2.47/3.2 3.5 Switch ‘e’ open
(three phase balance)
Metal enclosure to terminal A 1.2/1.3 3.5 Switch ‘e’ open
under A-phase imbalance
Metal enclosure to terminal A 1.1/1.2 3.5 Switch ‘e’ open
under B-phase imbalance
Metal enclosure to terminal A 1.0/1.1 3.5 Switch ‘e’ open
under C-phase imbalance
Front panel (with foil) to 0.005 / 0.005 0.25 Switch ‘e’ closed
terminal A

TRF No.: IEC62040_1D Page 50 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

RS485 port to terminal A 0.01 / 0.01 0.25 Switch ‘e’ closed


USB port to terminal A 0.001 / 0.001 0.25 Switch ‘e’ closed
Supplementary information:

8.2 TABLE: Dielectric Strength P


5.2/RD
Test voltage applied between: Test potential applied Breakdown / flashover
(V) (Yes/No)
Primary to Secondary (mains input & output conductor 3000Va.c. No
to USB port and RS485 port)
Primary to USB port and RS485 port 3000Va.c. No
Primary to earth (mains input & output conductor to 1500Va.c. No
earth)
Primary winding to secondary winding of transformer T2 3000Va.c. No
on CNTL PCB
Primary winding to core of transformer T2 on CNTL 1500Va.c. No
PCB
Secondary winding to core of transformer T2 on CNTL 1500Va.c. No
PCB
1 layer insulation tape used in transformer T2 on CNTL 3000Va.c. No
PCB
Supplementary information:

8.3 TABLE: Fault condition tests P


5.3/RD
Ambient temperature (C) : See below 
Power source for EUT: Manufacturer, model/type, 
output rating :
Component Fault Supply Test Fuse # Fuse Observation
No. voltage time current
(V) (A)

TRF No.: IEC62040_1D Page 51 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

Output o-l 415 3 hour F1, -- Unit shut down, when load to
20mins F2,F3 40KVA. No hazardous.
Maximum temperature:
On PSDR Board:
K1 coil= 57.3℃
K1 coil= 55.5℃
CT1 winding= 52.9℃
CT2 winding = 52.4℃
On CNTL Board:
U73 body= 42.2℃
T2 coil = 53.4℃
Ambient= 25.2℃
Output o-l Battery 10 min F1, -- When add to 40KVA load, UPS
mode F2,F3 transfer to fault mode and shut
down immediately. No damage.
No hazard.
Output s-c 415 10 min F1, 0 UPS transfer to fault mode and
F2,F3 no output, no damage, no
hazards
Output s-c Battery 10 min F1, -- UPS transfer to fault mode and
mode F2,F3 no output, no damage, no
hazards.
Ventilation Block-ed 415 2 hours F1, -- Unit work continuously. No
openings 09mins F2,F3 abnormal. No hazardous.
Maximum temperature:
On PSDR Board:
K1 coil= 55.5℃
K1 coil= 54.7℃
CT1 winding= 54.6℃
CT2 winding = 53.9℃
On CNTL Board:
U73 body= 42.8℃
T2 coil = 53.9℃
Ambient= 25.5℃

TRF No.: IEC62040_1D Page 52 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

Ventilation Block-ed Battery 1 hour F1, -- Unit work continuously. No


openings mode 40mins F2,F3 abnormal. No hazardous.
Maximum temperature:
On PSDR Board:
K1 coil= 54.3℃
K1 coil= 52.9℃
CT1 winding= 52.9℃
CT2 winding = 51.6℃
On CNTL Board:
U73 body= 41.5℃
T2 coil = 57.8℃
Ambient= 25.3℃
Fan near locked 415 5mins F1, -- After 5 minutes, EUT alarm for
PSDR PCB F2,F3 fan and turn to by pass.
Recoverable after fault removed.
No hazard.
Fan near locked Battery 5mins F1, -- EUT alarm and EUT is protected
PSDR PCB mode F2,F3 by thermal control. No hazard.
PSDR PCB & INV PCB
Battery F1, UPS shutdown, F3 opens no
C13 s-c 1 sec. 0
mode F2,F3 hazard.
UPS transfer to fault mode and
Battery F1,
Q14 G-S s-c 10 min -- shutdown immediately, no
mode F2,F3
damaged. No hazardous.
UPS transfer to fault mode and
Battery F1,
Q14 G-D s-c 1 sec. -- shutdown immediately. No
mode F2,F3
hazardous.
UPS transfer to fault mode and
Battery F1,
Q14 D-S s-c 1 sec. -- shutdown immediately, No
mode F2,F3
hazardous.
UPS transfer to fault mode and
Battery F1,
Q16 G-S s-c 10 min -- shutdown immediately, no
mode F2,F3
damaged. No hazardous.
UPS transfer to fault mode and
Battery F1,
Q16 G-D s-c 1 sec. -- shutdown immediately, No
mode F2,F3
hazardous.
UPS transfer to fault mode and
Battery F1,
Q16 D-S s-c 1 sec. -- shutdown immediately, No
mode F2,F3
hazardous.

TRF No.: IEC62040_1D Page 53 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

UPS transfer to fault mode and


Battery F1,
Q13 G-S s-c 10 min -- shutdown immediately, no
mode F2,F3
damaged. No hazardous.
UPS transfer to fault mode and
Battery F1,
Q13 G-D s-c 1 sec. -- shutdown immediately, No
mode F2,F3
hazardous.
UPS transfer to fault mode and
Battery F1,
Q13 D-S s-c 1 sec. -- shutdown immediately, No
mode F2,F3
hazardous.
CNTL PCB
U47 pin1- F1, Normal operation, no hazardous.
s-c 415 10 min --
pin2 F2,F3
U47 pin3- F1, Normal operation, no hazardous.
s-c 415 10 min --
pin4 F2,F3
F1, Normal operation, no hazardous.
U47 pin1 o-c 415 10 min --
F2,F3
F1, Normal operation, no hazardous.
U47 pin3 o-c 415 10 min --
F2,F3
U25 pin1- F1, Normal operation, no hazardous.
s-c 415 10 min --
pin2 F2,F3
U25 pin3- F1, Normal operation, no hazardous.
s-c 415 10 min --
pin4 F2,F3
F1, Normal operation, no hazardous.
U25 pin1 o-c 415 10 min --
F2,F3
F1, Normal operation, no hazardous.
U25 pin3 o-c 415 10 min --
F2,F3
U73 pin1- F1, Normal operation, no hazardous.
s-c 415 10 min --
pin2 F2,F3
U73 F1, Normal operation, no hazardous.
s-c 415 10 min --
pin3-pin4 F2,F3

F1, Normal operation, no hazardous.


U73 pin1 o-c 415 10 min --
F2,F3
F1, Normal operation, no hazardous.
U73 pin3 o-c 415 10 min --
F2,F3
U49 pin1- F1, Normal operation, no hazardous.
s-c 415 10 min --
pin2 F2,F3
U49 F1, Normal operation, no hazardous.
s-c 415 10 min --
pin3-pin4 F2,F3

TRF No.: IEC62040_1D Page 54 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

F1, Normal operation, no hazardous.


U49 pin1 o-c 415 10 min --
F2,F3
F1, Normal operation, no hazardous.
U49 pin3 o-c 415 10 min --
F2,F3
U59 F1, Normal operation, no hazardous.
s-c 415 10 min --
pin1-pin2 F2,F3

U59 F1, Normal operation, no hazardous.


s-c 415 10 min --
pin3-pin4 F2,F3

F1, Normal operation, no hazardous.


U59 pin1 o-c 415 10 min --
F2,F3
F1, Normal operation, no hazardous.
U59 pin3 o-c 415 10 min --
F2,F3
Supplementary information:
s-c: short circuit, o-c: open circuit, o-l: over load
Transformer winding and core temperature limit is 164°C (175-10-(40-39))

C.2/RD TABLE: transformers P


Loc. Tested Working Working Required Required Required Required
insulation voltage voltage electric clearance creepage distance
peak / V rms / V strength / mm distance / thr. insul.
mm
(2.10.2) (2.10.2) (5.2) (2.10.3) (2.10.4) (2.10.5)
T2 Primary reinforced
winding/pin insulation
to 420 250 3000Vac 4.0 5.0 *
secondary
winding/pin
T2 Primary basic
winding/pin insulation 420 250 1500Vac 4.0 5.0 *
to core
T2 basic
Secondary insulation
420 250 1500Vac 4.0 5.0 *
winding/pin
to core
Loc. Tested Test Measured Measured Measured
insulation voltage/ V clearance creepage distance
/ mm dist./ mm thr. insul.
/ mm;
number
of layers
T2 Primary reinforced insulation 3000Vac 11.8 11.8 *
winding/pin

TRF No.: IEC62040_1D Page 55 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

to
secondary
winding/pin
T2 Primary
winding/pin reinforced insulation 1500Vac 2.8 3.3 *
to core
T2
Secondary
reinforced insulation 1500Vac 2.8 3.3 *
winding/pin
to core
Supplementary information:
* 2 or 3 layers .

C.2/RD TABLE: transformers N/A


Transformer

M Ventilation of battery compartments N/A


The required dimension for the ventilation openings will be calculated with the
following formula:
A ≥ Q/360 [m²]
with Q = 0.054 * n * I * C
where:
Q : airflow in m³/h
n : number of battery cells
I : constant factor (0.2A/100Ah for valve regulated lead acid
batteries)
C : is the battery nominal capacity in Ah at the 10h discharge
rate
With the specific data for the UPS the following dimension for the ventilation
openings is required:
n :

TRF No.: IEC62040_1D Page 56 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

C :
A ≥ (0.054 * n * 0.2 A/100 Ah * C)/360
A≥
Verdict
The size of ventilation openings in battery cabinet exceeds the required airflow by
far (as well as the UPS).

4.5 TABLE: Critical components information P


Object / part No. Manufacturer/ Type / model Technical data Standard Mark(s) of
trademark conformity1)
Whole unit
Fan DELTA FFB1224EHE 24Vdc/1.5A, UL 507 UL
ELECTRONICS XAG 4000RPM
INC
Alternate SHENZHEN YM2412PMZB 24Vdc/0.8A UL 507 UL
HUAXIA 1-1 4000RPM
HENGTAI
ELECTRONIC
CO LTD
Fan SHENZHEN DZ12038B24 24Vdc/1.47A UL 507 UL
HUAXIA UR 4500RPM
HENGTAI
ELECTRONIC
CO LTD
Alternate Minebea motor 4715VL-05W- 24Vdc/1.48A UL 507 UL
manufacturing B89 6400RPM
corporation 6.9m3/min
Breaker Nader NDMI-125C 63A/400Vac 10KA IEC 60947-2 VDE
(Classic 30K- 3P
TT(Std))
Breaker Nader NDG1-100 3P 63A/400Vac IEC60947-3 VDE
(Classic 30K-
TT(Std))
Breaker Nader NDMI-125C 80A/400Vac 10KA IEC 60947-2 VDE
(Classic 40K- 3P
TT(Std))
Switch Nader NDG1-100 3P 100A/400Vac IEC60947-3 VDE
(Classic 40K-
TT(Std))
EMI Board

TRF No.: IEC62040_1D Page 57 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

X2-capacitors FARAD PXK2A7W22K 2.2uF 275Vac IEC/EN 60384- VDE


(C2,C12,C22) ELECTRONICS 4
14
CO LTD
Alternate ZHENGZHOU CBB62B 2.2uF 275Vac IEC/EN 60384- VDE
WEIHUATRONIC
14
TECHNOLOGY
CO., LTD
X2-capacitors SHENZHEN CBB62B 275Vac, 1uF, 100 IEC/EN 60384- VDE
(C1,C7,C11,C1 JINGHAO ℃ 14
7,C21,C27) CAPACITOR CO
LTD
Y2-capacitors FARAD MKP63 0.1uF,300Vac 100 IEC/EN 60384- VDE
(C3,C3a,C3b,C ELECTRONICS ℃ 14
3C,C5,C6,C8,C CO LTD
8a,C8b,C13,C1
3a,C13b,C13c,
C15,C16,C18,C
18a,C18b,C23,
C23a,C23b,C23
c,C25,C26,C28,
C28a,C28b,C31
,C31a,C31b,C3
2,C32a,C32b,C
33,C34)
Y2-capacitors JYA-NAY CO JY 1nF, 250Vac, 125 IEC/EN 60384- VDE
(C9,C19,C29,C LTD ℃ 14
4,C14,C24,C10,
C20,C30)
INV power board
Fuse(F1) XC 5F F6.3A/250Vac EN 60127-1, VDE
ELECTRONICS EN 60127-3
(SHENZHEN)
CORP LTD
Y2- capacitors TDK CS 4.7nf, 250Vac, 125 IEC/EN 60384- VDE
(C45,C46,C47, CORPORATION ℃ 14
C48,C49,C50)
Relay (K1) SONG CHUAN 812H-1C-C 12Vdc, DIN VDE 0435 VDE
PRECISION CO 10A/277Vac EN 60255
LTD

Transformer JEPULS ER28 484uH,130℃


(T2) TECHNOLOGY
IEC 62040-1
Test in
(SHENZHEN) CO appliance
LTD
- Bobbin CHANG CHUN
PLASTICS CO T375J V-0, 150℃ UL94 UL
LTD

TRF No.: IEC62040_1D Page 58 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

- Primary 130℃
Various Various UL1446 UL
Winding Wire
TeamWork
-Triple insulated
International TIWW-B 130℃ IEC 60950 VDE
wire
Corporation
- Insulation JINGJIANG WF 130℃
Tape(Margin YAHUA
Tape) PRESSURE UL510 UL
SENSITIVE
GLUE CO LTD
- Teflon Tube CHANGYUAN TFL 200℃
ELECTRONICS UL 224 UL
GROUP CO LTD
- Varnish HANG CHEUNG 8562 150℃
PETROCHEMICA UL1446 UL
L LTD
Transformer CLICK BCK4201-967 360uH, 130℃
Test in
(T3) TECHNOLOGY IEC 62040-1
appliance
CO LTD
Film capacitors various various 0.22uF, 1000Vdc Test in
IEC 62040-1
(C1,C7,C13) appliance
Temperature co XC KSD301 10A/250Vac, 90℃ UL 873, UL
ntrolled switch ELECTRONICS UL 60730-1
(J5-HS3) (SHENZHEN)
CORP LTD
INV Inductor board
Fuse COOPER ET F100A/690Vac EN 60127-1, VDE
(F1,F2,F3) BUSSMANN LLC EN 60127-2
Alternate MERSEN URS 100A/690Vac EN 60127-1, VDE
FRANCE SB S A EN 60127-2
S
Mutual inductor various various 1.0H, 130℃ Test in
IEC 62040-1
(CT1,CT2,CT3) appliance
Inductance various various 300uH, 180℃ Test in
IEC 62040-1
(L1,L5,L9) appliance
Relay SONG CHUAN 897P-1AH-C 12Vdc 70A/14Vdc DIN VDE 0435 VDE
(RLY1,RLY2,K3 PRECISION CO EN 60255
) LTD

X2-capacitors SHENZHEN CBB62B 275Vac, 1.0uF, IEC/EN 60384- VDE


(C6,C15,C21) JINGHAO 110℃ 14
CAPACITOR CO
LTD

TRF No.: IEC62040_1D Page 59 of 74 Report No. ES160322008S-11 Ver.1.0


IEC 62040-1
Clause Requirement + Test Result - Remark Verdict

Alternate FARAD PXK2A7W10K 275Vac, 1.0uF, IEC/EN 60384- VDE


ELECTRONICS 5 100℃ 14
CO LTD
X2-capacitors ZHENGZHOU MKP62 0.22uF, 275Vac, IEC/EN 60384- VDE
(C7,C8,C9) WEIHUATRONIC 110℃ 14
TECHNOLOGY
CO., LTD
PFC power
board
Fuse (F3,F4) LITTELFUSE INC KLKD* F30A/600Vac EN 60127-1, VDE
EN 60127-2
Transformer CORMEX UU10.5 63mH, 130℃ -- VDE
(T1,T4) ELECTRONICS UL
IND CO LTD
PFC inductor board
X2-capacitors ZHENGZHOU MKP62 1.0uF, 275Vac, IEC/EN 60384- VDE
(C59,C60,C61) WEIHUATRONIC 110℃ 14
TECHNOLOGY
CO., LTD
alternative Xiamen C42P2105K9F 275Vac, 1.0uF, IEC/EN 60384- VDE
Faratronic Co. Ltd C000 100℃ 14
Relay SONG CHUAN 897P-1AH-C 12Vdc 70A/14Vdc DIN VDE 0435 VDE
(K1,K2,K3) PRECISION CO EN 60255
LTD

Inductance various various 1mH,180℃ Test in


IEC 62040-1
(L1,L2) appliance
Inductance various various 300uH, 180℃
Test in
(L3,L4,L5,L6,L7, IEC 62040-1
appliance
L9)
Control board
Opto-coupler various K1010-4C-1 5000Vrms IEC 60747-5-5 VDE

alternative various PS2501L-1 5000Vrms IEC 60747-5-5 VDE


Relay COPYRIGHT TQ2-5V 5Vdc 0.5A/125Vac DIN VDE 0435 VDE
(RE1,RE2,RE3) Panasonic EN 60255
Electric Works
Co., Ltd
Transformer CORMEX EEL16 510uH, 130℃ -- VDE
(T2) ELECTRONICS UL
IND CO LTD
Supplementary information:
1) Provided evidence ensures the agreed level of compliance. See OD-2039.

TRF No.: IEC62040_1D Page 60 of 74 Report No. ES160322008S-11 Ver.1.0


European group differences and national differences of EN 62040-1
Clause Requirement + Test Result - Remark Verdict

EN 62040-1, GROUP DIFFERENCES (CENELEC common modifications EN)


Clause Requirement + Test Result - Remark Verdict
Contents Add the following annexes: P
Annex ZA (normative) Normative references to international
publications with their
corresponding European publications
Annex ZB (normative) Special national conditions

ZA NORMATIVE REFERENCES TO INTERNATIONAL PUBLICATIONS WITH 


THEIR CORRESPONDING EUROPEAN PUBLICATIONS

The following referenced documents are indispensable for the application of this
document. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any
amendments) applies.
Note: When an international publication has been modified by common
modifications, indicated by (mod), the relevant EN/HD Applies.

TRF No.: IEC62040_1D Page 61 of 74 Report No. ES160322008S-11 Ver.1.0


European group differences and national differences of EN 62040-1
Clause Requirement + Test Result - Remark Verdict

ZB ANNEX (normative)

SPECIAL NATIONAL CONDITIONS (EN)

The FI, NO and SE - SNCs originate from IEC 60950-1 2nd Edition, which is the reference document (RD)
for IEC 62040-1. The national requirements are included in IEC 62040-1 through the following statement
in the scope of the standard:
“National requirements additional to those in IEC 60950-1 apply and are found as notes under relevant
clauses of the RD.”

The national requirements have not been specifically listed in the EN 62040-1:2008.
If demanded, CLC/TC 22X will be requested to take proper measures to complete EN 62040-1 with
Annexes ZB containing the SNCs as presented below.

EN 62040-1:2008 supersedes EN 62040-1-1:2003. As a reference, see also SNCs for Finland, Norway
and Sweden as included in the earlier EN 62040-1-1:2003
Clause Requirement + Test Result - Remark Verdict
4.7.3 In Finland, Norway and Sweden, when safety Permanent connection N/A
relies upon connection to the safety earth (see equipment
5.3), a pluggable equipment type A UPS shall
have a marking on the equipment, stating that the
UPS must be connected to an earthed mains
socket-outlet.

The marking text in the applicable countries shall be


as follows:

In Finland: "Laite on liitettävä suojakoskettimilla


varustettuun pistorasiaan"

In Norway: “Apparatet må tilkoples jordet


stikkontakt”

In Sweden: ”Apparaten skall anslutas till jordat uttag”


4.7.11 In Norway, because of a widely used IT power P
system, equipment shall be designed or modified
for connection to such a system and shall be
marked by a label with the following wording in
Norwegian:
“Apparatet er egnet for tilkopling til et IT
forsyningsnett”
9 In Finland, Norway and Sweden requirements of P
6.1.2.1 and 6.1.2.2 in Annex ZB of EN 60950-1:2001
apply.

TRF No.: IEC62040_1D Page 62 of 74 Report No. ES160322008S-11 Ver.1.0


Fig. 1 – Overview (I) of UPS

Fig. 2 – Overview (II) of UPS

TRF No.: IEC62040_1D Page 63 of 74 Report No. ES160322008S-11 Ver.1.0


Fig. 3 – Overview (III) of UPS

Fig. 4 –Overview (III) of UPS

TRF No.: IEC62040_1D Page 64 of 74 Report No. ES160322008S-11 Ver.1.0


Fig. 5 – Inside view I of UPS

Fig. 6 –Inside view II of UPS

TRF No.: IEC62040_1D Page 65 of 74 Report No. ES160322008S-11 Ver.1.0


Fig. 7 –Component side view of PCB

Fig. 8 –Trace side view of PCB

TRF No.: IEC62040_1D Page 66 of 74 Report No. ES160322008S-11 Ver.1.0


Fig. 9 –Component side view of PCB

Fig. 10 –Trace side view of PCB

TRF No.: IEC62040_1D Page 67 of 74 Report No. ES160322008S-11 Ver.1.0


Fig. 11 –Component side view of PCB

Fig. 12 –Trace side view of PCB

TRF No.: IEC62040_1D Page 68 of 74 Report No. ES160322008S-11 Ver.1.0


Fig. 13 –Component side view of PCB

Fig. 14 –Trace side view of PCB

TRF No.: IEC62040_1D Page 69 of 74 Report No. ES160322008S-11 Ver.1.0


Fig. 15 –Component side view of PCB

Fig. 16 –Trace side view of PCB

TRF No.: IEC62040_1D Page 70 of 74 Report No. ES160322008S-11 Ver.1.0


Fig. 17 –Component side view of PCB

Fig. 18 –Trace side view of PCB

TRF No.: IEC62040_1D Page 71 of 74 Report No. ES160322008S-11 Ver.1.0


Fig. 19 –Component side view of PCB

Fig. 20 –Trace side view of PCB

TRF No.: IEC62040_1D Page 72 of 74 Report No. ES160322008S-11 Ver.1.0


Fig. 21 –Component side view of PCB

Fig. 22 –Trace side view of PCB

*** End of Report ***

TRF No.: IEC62040_1D Page 73 of 74 Report No. ES160322008S-11 Ver.1.0


声明
Statement

1. 本报告无授权批准人签字及“检验报告专用章”无效;

This report will be void without authorized signature or special seal for testing report.

2. 未经许可本报告不得部分复制;

This report shall not be copied partly without authorization.

3. 本报告的检测结果仅对送测样品有效,委托方对样品的代表性和资料的真实性负责;

The test results or observations are applicable only to tested sample. Client shall be responsible for

representativeness of the sample and authenticity of the material.

4. 本检测报告中检测项目标注有特殊符号则该项目不在资质认定范围内,仅作为客户委托、科研、教学或内部质量

控制等目的使用;

The observations or tests with special mark fall outside the scope of accreditation, and are only used for

purpose of commission, research, training, internal quality control etc.

5. 本检测报告以实测值进行符合性判定,未考虑不确定度所带来的风险,本实验室不承担相关责任,特别约定、标

准或规范中有明确规定的除外;

The test results or observations are provided in accordance with measured value, without taking risks caused
by uncertainty into account. Without explicit stipulation in special agreements, standards or regulations,

EMTEK shall not assume any responsibility.

6. 对本检验报告若有异议,请于收到报告之日起 20 日内提出;

Objections shall be raised within 20 days from the date receiving the report.

TRF No.: IEC62040_1D Page 74 of 74 Report No. ES160322008S-11 Ver.1.0