Professional Documents
Culture Documents
IEC 62109-2
Safety of Power Converter for use in Photovoltaic Power Systems
Part 2: Particular requirements for inverters
Report Number. .............................. : 70.409.20.075.07-00 part 2 of 2
Date of issue................................... : 2021-06-04
Total number of pages…………….: 27
Name of testing laboratory TÜV SÜD Certification and Testing (China) Co., Ltd.
preparing the report…………….….: Guangzhou Branch
Applicant’s name ........................... : AISWEI New Energy Technology (Jiangsu) Co., Ltd.
Address ........................................... : Building 9, No.198 Xiangyang Road, 215011 Suzhou,
PEOPLE'S REPUBLIC OF CHINA
Test specification:
Standard ......................................... : IEC 62109-2:2011 (First Edition)
Test procedure ............................... : TUV mark
Non-standard test method……….: N/A
Test Report Form No. .................... : IEC62109_2B
Test Report Form(s) Originator .... : LCIE - Laboratoire Central des Industries Electriques
Master TRF ..................................... : Dated 2016-08
Copyright © 2016 IEC System of Conformity Assessment Schemes for Electrotechnical
Equipment and Components (IECEE System). All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as
copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting
from the reader's interpretation of the reproduced material due to its placement and context.
If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the
CB Scheme procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory
and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
General disclaimer:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing CB Testing
Laboratory. The authenticity of this Test Report and its contents can be verified by contacting the NCB,
responsible for this Test Report.
Responsible Testing Laboratory (as applicable), testing procedure and testing location(s):
Name of testing laboratory TÜV SÜD Certification and Testing (China) Co., Ltd.
preparing the report: Guangzhou Branch
Location/ address ......................................... : 5F, Communication Building, 163 Pingyun Rd, Huangpu
Ave. West, Guangzhou 510656, P. R. China
Associated Testing Laboratory: CQC - Trusted(Jiangsu) Testing Technology Co., Ltd.
Testing location/ address ............................ : No.99, Wenlan Road, Xianlin University Zone, Xianlin
Street, Qixia District, NanJing, China
Tested by (name, function, signature) ........ : Shan Huang
Summary of testing:
All the tests results are confirmed to the requirements of the standard.
Tests performed (name of test and test clause): Testing location:
All tests were conducted on ASW20K-LT-G2. All tests were CQC - Trusted(Jiangsu) Testing
conducted at test voltage: 3/N/PE~ 230/400V and test Technology Co., Ltd.
frequency: 50Hz if not specified.
No.99, Wenlan Road, Xianlin University
Fault-tolerance of residual current monitoring – clause Zone, Xianlin Street, Qixia District,
4.4.4.15.1; NanJing, China
Fault-tolerance of automatic disconnecting means –
clause 4.4.4.15.2;
Cooling system failure – Blanketing test – clause
4.4.4.17;
Array insulation resistance detection for inverters for
ungrounded and functionally grounded arrays – clause
4.8.2;
Array residual current detection – clause 4.8.3;
Inverter backfeed current onto the array – clause 9.3.4
as combined with clause 4.4 in IEC 62109-1(ed.1)/ EN
62109-1:2010;
General remarks:
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict
4.8.3.5.1 General P
Where required by Table 30, the inverter shall P
provide residual current monitoring that
functions whenever the inverter is connected
to the mains with the automatic disconnection
means closed.
The residual current monitoring means shall P
measure the total (both a.c. and d.c.
components) RMS current.
As indicated in Table 30 for different inverter P
types, array types, and inverter isolation
levels, detection may be required for
excessive continuous residual current,
excessive sudden changes in residual
current, or both, according to the following
limits:
a) Continuous residual current: The inverter shall disconnect within 0,3 s and P
indicate a fault in accordance with 13.9 if the continuous residual current exceeds:
- maximum 300 mA for inverters with 100mA@160ms P
continuous ouput power rating ≤30kV;
- maximum 10 mA per kVA of rated N/A
continuous output power for inverters with
continuous output power rating > 30 kVA.
The inverter may attempt to re-connect if the P
array insulation resistance meets the limit in
4.8.2.
b) Sudden changes in residual current: The P
inverter shall disconnect from the mains
within the time specified in Table 31
The inverter indicates a fault in accordance P
with 13.9, if a sudden increase in the RMS
residual current is detected exceeding the
value in the table.
- 30mA@0,3s 25mA@220ms P
- 60mA@0,15s 55mA@80ms P
- 150mA@0,04s 110mA@20ms P
The inverter may attempt to re-connect if the P
array insulation resistance meets the limit in
4.8.2.
4.8.3.5.2 Test for detection of excessive continuous See appended test table P
residual current: test repeated 5 times and 4.8.3.5.2 Test for detection of
time to disconnect shall not exceed 0,3 s. excessive continuous residual
current
4.8.3.5.3 Test for detection of sudden changes in See appended test table P
residual current repeated 5 times and each of 4.8.3.5.3 Test for detection of
the 5 results shall not exceed the time limit sudden changes in residual current
indicated in for each row (30mA, 60mA
and150mA) of Table 31.
4.8.3.6 Systems located in closed electrical operating Outdoor use, not limited to be N/A
areas located in closed electrical
operating areas.
The protection against shock hazard is not N/A
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict
IEC 62109-2
Clause Requirement + Test Result - Remark Verdict
13 PHYSICAL REQUIREMENTS P
13.9 Fault indication P
Where this Part 2 requires the inverter to indicate a fault, both of the following P
shall be provided:
a) a visible or audible indication, integral to Visible indication P
the inverter, and detectable from outside
the inverter, and
b) an electrical or electronic indication that RS485 port as communication P
can be remotely accessed and used. method for remote accessed and
used
The installation instructions shall include P
information regarding how to properly make
connections (where applicable) and use the
electrical or electronic means in b) above, in
accordance with 5.3.2.10.
Slave CPU, Short +3.3V MAINS:400 10min - - PV inverter shut down immediately.
U523 power supply PV: 800 DSP protect by itself for low
pin to GND voltage.No components damage,
no hazard. Inverter can be
restarted and operated normally
when the fault was removed.
Inverter ceases to operate,
indicates a fault in accordance with
13.9, disconnects from
Check that the residual current monitoring operates properly the mains, and does not re-
connect after any sequence of
removing and reconnecting PV
power, AC power, or both
Supplementary information:
Also see report 70.409.20.075.07-00 part 1 of 2.
Relay driver Open MAINS:400 10min - - PV inverter could not start. Red
R544 before PV: 800 fault LED light, The fault
start-up information” Relay check Fail”. No
components damage, no hazard.
Relay driver Short MAINS:400 10min - - PV inverter could not start. Red
Q504 before PV: 800 fault LED light, The fault
start-up information” Relay check Fail”. No
components damage, no hazard.
Relay driver Short MAINS:400 10min - - PV inverter could not start. Red
Q505 before PV: 800 fault LED light, The fault
start-up information” Relay check Fail”. No
components damage, no hazard.
The remaining relays gaps in
Check that the relays fulfil the basic insulation or simple separation
series provided basic clearance:
based on the PV circuit working voltage.
≥2 x 2.26 mm
Each active phase can be switched. (L1/L2/L3) Yes
Supplementary information:
Also see report 70.409.20.075.07-00 part 1 of 2.
4.8.2 TABLE: Array insulation resistance detection for inverters for ungrounded and P
functionally grounded arrays
4.8.2.1 Array insulation resistance detection for inverters for ungrounded arrays P
DC Voltage below DC Voltage for Resistance between Required Insulation Result
minimum operating inverter begin ground and PV resistance
voltage operation input terminal R = (VMAX PV /
(V) (V) (kΩ) 30mA)
(kΩ)
ISO setting=200kΩ
DC+(MPP tracker 1)
100 150 180 33.3 Insulation fault
100 150 180 33.3 Insulation fault
100 150 180 33.3 Insulation fault
100 150 180 33.3 Insulation fault
100 150 180 33.3 Insulation fault
100 150 220 33.3 Normal Operation
100 150 220 33.3 Normal Operation
100 150 220 33.3 Normal Operation
100 150 220 33.3 Normal Operation
Setting: 55mA@80ms
60 100.0 150
60 100.0 150
60 86.0 150
60 86.0 150
60 76.0 150
Setting: 110mA@20ms
150 28.0 40
150 28.0 40
150 28.0 40
150 32.0 40
150 36.0 40
PV2+ to N:
(MPP tracker 2)
UN
Limit (mA) Limit (ms)
Disconnection time (ms)
Setting: 25mA@220ms
30 242.0 300
30 224.0 300
30 238.0 300
30 238.0 300
30 222.0 300
Setting: 55mA@80ms
60 86.0 150
60 78.0 150
60 78.0 150
60 86.0 150
60 86.0 150
Setting: 110mA@20ms
150 38.0 40
150 38.0 40
150 22.0 40
150 34.0 40
150 28.0 40
PV- to N:
UN
Limit (mA) Limit (ms)
Disconnection time (ms)
Setting: 25mA@220ms
30 238.0 300
30 226.0 300
30 226.0 300
30 232.0 300
30 232.0 300
Setting: 55mA@80ms
60 98.0 150
60 94.0 150
60 94.0 150
60 88.0 150
60 88.0 150
Setting: 110mA@20ms
150 26.0 40
150 28.0 40
150 28.0 40
150 28.0 40
150 28.0 40
Note:
1.The capacitive current is risen until disconnection.
2.Test condition: Ic + 30/60/150mA <= Icmax. R1 is set that 30/60/150mA Flow and switch S is closed.
3. The inverter in designed to used common PV- for both MPP tracker 1 and tracker 2.