AlarmLine
Intrinsic Safety Barriers for Conventional and
Addressable AlarmLine™ Systems A UTC Fire & Security Company
K-73-10
FEATURES 24 barriers (see Ordering Information for part numbers).
• Permits AlarmLine installation in Classified Hazard- To determine if the need for an intrinsically safe circuit
ous Areas exists on a specific application, consult the National Elec-
• Compatible with Smart and Conventional control sys- tric Code and the local Authority Having Jurisdiction
tems (AHJ).
• 1-Channel Operation
REFERENCE DOCUMENTS
• Shunt-Diode Type
• Limits Energy • Kidde® Linear Heat Detection Color Brochure:
• Slim Packaging KF-0070
• UL Listed • Kidde Application Guide–Intelligent LHS™ Systems:
• FM Approved 73-100
• Kidde PEGAsys™ Data Sheet: 76-000
DESCRIPTION
• ARIES™ Data Sheet: 76-600
AlarmLine™ applications in classified hazardous areas
• Addressable AlarmLine Module Data Sheet: 73-02
with potentially explosive vapors, dust or fibers require
the use of Intrinsic Safety Barriers so as to limit the total • AlarmLine LHD-4 Data Sheet: 73-01
energy entering the hazard via the sensor wiring conduc-
tors.
1
Kidde P/N 73-117068-031 shunt-diode Safety Barriers
4
2
0.98 0.45
(as shown in Figures 1 and 2) are 1-channel devices that 0.56
2X M4 X 9
use intrinsically safe techniques to allow electrical signals 0.29 0.29
2 1
to be conveyed between non-hazardous (safe) and haz-
ardous areas. The Safety Barriers achieve this by limiting
the transfer of energy in one direction to a level that can-
2.42
not cause ignition of explosive atmospheres. 1.94
WIRING
Each barrier handles two conductors, so two barriers are 3.35
required for each sensor cable. As shown in Figures 3 3.68
and 4, two Intrinsic Safety Barriers are used for each Figure 1. Intrinsic Safety Barrier Dimensions (Inches)
AlarmLine Sensor which is then connected to either the
conventional hardwired LHD-4 module (P/N 73-117068-
3
To Control
Panel
Initiating
Circuit
NO NCCOM NO NC COM
17 18 19 20 21 22
FAULT FIRE
RELAY RELAY
Additional
Modules
TROUBLE/FAULT
OUTPUT
FIRE
CABLE LED
(-) (+) SENSOR (-) (+) (-) (+)
1 2 3 4 5 6 7 8 9 10 11 12
24VDC -
BLUE
WHITE
ORANGE
RED
SWITCHED +
POWER
1 2 3 4
ALARMLINE INTERFACE
MODULE TERMINAL STRIP
Intrinsic Safety GROUND
Terminal Strip
Barrier BUS
in Junction Box
6 AlarmLine
Sensor
Conductor 3 Conductor 3 Conductor 3 (Red Conductor)
5
3
1
WEATHERTIGHT
ENCLOSURE SAFE HAZARDOUS
AREA AREA
COPPER CONNECTION
CABLE
Kidde PEGAsys™
or ARIES™ Control Addressable AlarmLine
Panel Module
Intrinsic Safety
Barrier Ground Terminal Strip
in Junction Box
Bus
Conductor 1
Conductor 1 (Orange Conductor) Conductor 1 (Orange Conductor)
2 4 AlarmLine
Sensor
Conductor 2 (White Conductor) Conductor 2 Conductor 2 (White Conductor)
1 3
Conductor 3
SLC Loop Conductor 3 (Red Conductor)
1 4
Conductor 3 (Red Conductor)
Conductor 4
Conductor 4 (Blue Conductor) Conductor 4 (Blue Conductor)
2 3
Weathertight
Enclosure SAFE HAZARDOUS
AREA AREA
COPPER CONNECTION
CABLE
-2-
SPECIFICATION ORDERING INFORMATION
FM Approvals Class I, Division I, Groups A, B, C, D Part Number Description
Class II, Division 1, Groups E, F, G
Class III, Division 1 73-117068-031 Intrinsic Safety Barrier for AlarmLine (need 2
per sensor)
Operating Temper- -4° F (-20° C) to 140° F (60° C)
ature Range 73-117068-032 Intrinsic Safety Barrier Weathertight Enclo-
sure. Holds two Barriers.
Humidity 5 to 95% R.H.
73-117068-033 Intrinsic Safety Barrier Weathertight Enclo-
Terminals Will accept up to #12 AWG; sure. Holds up to five Barriers.
-3-
Kidde and SmartOne are registered trademarks of Kidde-Fenwal, Inc.
AEGIS, ARIES and AlarmLine are trademarks of Kidde-Fenwal, Inc.