USNS Big Horn July2022 (MSC)

Space Heater PTO#1 PTO#2


SG ok ok
SCM ok ok
RUM ok New RUM has
no Heater

Visual Inspection PTO#1 PTO#2


Cubical Fans ok ok
SG Fans ok ok
SCM Oil Pumps ok ok
SG Oil Pumps ok ok
SG Inside
SCM Inside ok
SCR Modules (Heat sink) ok

Aux. Test PTO#1 PTO#2


Cubical Fans ok ok
Run Up Motor Fan ok Kein ext. Fan
SG Lüfter ok ok

Excitation Test PTO#1 PTO#2


Simotras Status ok ok
Strom Soll- Istwert ok ok

Rotor Position Test PTO#1 PTO#2


Motor Position in °el und Excitation Istwert in Amps ok ok
+94° 14,0A +120° 14,0A

Converter SCR Pulsing Test PTO#1 PTO#2


SCR Gates Impulse mit Scopemeter kontrolieren ok ok
Beidseitige Impulszuführung prüfen (Ringleitung öffnen)

Alarm blocking während Test active ? ok ok

SCM Pumpen Failure vor PTO Start Up ?


S7 Power Back Up PTO#1 PTO#2
24Vdc 0k ok
24Vdc Floating ok ok
3,6Vdc Lithium Bat. Batt. missing Batt. missing

Failure Alarm Message History ? See details ok

SCM Start in Test Mode PTO#1 PTO#2


SCM Frequency (RUM rpm) mit Bus Frequency vergleichen
SCM Spannug mit Bus Spg. Vergleichen
RUM Main Fuses Hot Spot monitoring mit Thermo Camera

Megga Test PTO#1 PTO#2


SG + Converter + SCM
Run Up Motor
Fans, Pumpen
Excitation

Signale zwischen Main Switch Board und S7 PTO#1 PTO#2


Gen. and Motor Select Signal ok ok
Frequency Sollwert Ok EW54=54% Ok EW54=55%
Diesel Gen On Bus S7 I7.5 ok ok
Main Circuit Breaker ON Feedback
Preferential Trip
Stand By Diesel Start

AC an Control Cubical H11 PTO#1 PTO#2


Funktion ok ok
Temperature Setting

Software PTO#1 PTO#2


S7
Sinamics
Simotras
Extras PTO#1 PTO#2
Run Up Motor Power Relay Kontakt Abbrand
Warnings and Failure Test
Overvoltage Protection Varistor Fuses F184...186 ok
Overvoltage Protection Varistor Fuses F117...119 ok
Machine Side Converter voltage actual value
U-V-W checked in operation at F114...116
Line Side Converter voltage actual value
U-V-W checked in operation at Q805

Details:

PTO#1 Failure Alarm Message History:


*Failure 007 Blowing of Fuse LSC Power Cubicle
*Failure 013 Overload RUM (+H14-K242)
*Failure 010 Trip Fan SGM (+H14....)
*Failure 049 Busfailure Excitation SGM
*Failure 006 Trip MCB Puls Power Supply