Professional Documents
Culture Documents
GP-16!04!01 Grounding and Overvoltage Protection
GP-16!04!01 Grounding and Overvoltage Protection
Scope
1) [I] This Global Practice (GP) covers bonding, grounding, overvoltage protection, and lightning
protection facilities for electrical power systems and equipment, structures and buildings, and product
loading stations.
2) [I] This GP does not cover process instrumentation or cathodic protection systems. However, overall
grounding system design shall include requirements specified in other practices, e.g., instrumentation.
Contractor shall submit overall grounding design to the Owner's Engineer for approval.
Copyright Waiver
ExxonMobil Development Company and ExxonMobil Pipeline Company hereby license the use of ExxonMobil Engineering Practices System (EMEPS) Global Practices (GPs) for
use by any ExxonMobil division, subsidiary, or more-than-50%-owned affiliate. The GPs may be downloaded and modified as necessary for project and affiliate use. Written
permission from ExxonMobil Development Company or ExxonMobil Pipeline Company is not required. However, any modified GPs must be renumbered to a project-specific or
affiliate-specific number to distinguish them from the GPs on the EMEPS web site. ExxonMobil operated joint ventures may utilize GPs to create project-specific or location-specific
specifications. It is the responsibility of individual affiliate or joint venture to ensure that the use of GPs and their derivatives is limited to joint venture related business and not
disclosed or used outside the JV without appropriate EM management approval.
GP 16-04-01 Grounding and Overvoltage Protection January 2008
Table of Contents
1. Required References
This section lists the Practices, codes, standards, specifications, and publications that shall be used with
this document. Unless otherwise specified herein, use the latest edition.
2. Definitions
Term [I] Description
Acceptable and [A] Where this GP lists more than one type of equipment or method as
Preferred Practices acceptable, Contractor shall make the selection based on the installed
cost. Where one particular type of equipment or method is listed as
preferred, it shall be selected, provided: (1) it is lower or equivalent in
installed cost than other acceptable types or methods, and (2) it has
reduced maintenance and operating costs that provide sufficient cost
benefit to offset an initial added investment. Owner's Engineer shall
approve alternative choices.
Bonding Two or more objects are considered to be bonded if connected together
through a conducting path. Objects that are not inherently in contact
with each other through a conducting path may be bonded by connecting
them together with a bonding conductor. The conductor shall be sized to
safely conduct the current or dissipate the charge likely to be imposed.
Ground Return Path A metallic connection between the metal enclosure of electrical
equipment and the system neutral ground of the power supply to the
equipment. If the systems neutral is grounded through impedance, the
ground return path must connect on the ground side of the impedance.
The path is a low-impedance path from the equipment enclosure to the
neutral ground. It serves as the equipment grounding conductor in
grounded neutral systems.
Grounding An object is considered to be grounded when connected by a conducting
connection, either inherently, by a grounding conductor to the earth, or
to some conducting body that serves in place of the earth, such as where
rock or high resistivity soil is present.
Grounding Electrode Grounds are the Grounding Electrode System. The electrodes may be
System buried grounding conductors, underground metallic water piping, or
large underground metallic objects in intimate contact with earth, such
as metallic building frames, pile casings, driven rods, or concrete
encased electrodes consisting of reinforcing bars or copper conductors in
underground foundations or footings.
Lightning Arrester A protective device for limiting surge voltages on equipment by
(Surge Arrester) discharging or bypassing surge current. It prevents continued flow of
follow current to ground, and is capable of repeating these functions.
Use of arcing horns and or rod gaps is not an acceptable method of
suppressing electrical surges.
Liquids Classified as Liquids are Classified as Static Electrical Charge Accumulators if their
Static Electrical conductivity is 50 picomhos/meter (50 pS/m) or less. Distilled
Charge Accumulators petroleum products, including petroleum solvents, are generally
accumulators. Crude oil, residual fuel oil, asphalts (both penetration and
cutback), Bunker C, residual products with Conradson carbon above 1
percent, and water soluble products such as alcohol have high
conductivity and are classified as non-accumulators.
Switch Loading Loading a high flash product into a tank truck, tank car, or container
previously containing a low flash product, without cleaning or gas-
freeing the tank or container. The high flash product must be treated as
low flash during loading in such cases.
Zone of Lightning Space adjacent to a lightning protection system that is substantially
Protection immune to direct lightning flashes.
NFPA 780 Chapter 4, "Protection for Ordinary Structures," and
Chapter 7, "Protection for Structures Containing Flammable Vapors,
Flammable Gases or Liquids That Can Give Off Flammable Vapors,"
cover the cone and rolling sphere concepts for determining the zone
extent. Specific regional or national standards, while using the same
concepts, may have requirements that result in different extents of the
zone of protection.
3) [I] Ground return conductors located within cable assemblies may be uninsulated and shall be of the
same material and stranding as the cable line conductors. If insulated, color coding shall comply with
requirements of the applicable regulations.
4) [R] Grounding conductor burial depths shall be at least 18 in. (450 mm). Burial depths in switch or
transformer yards graded with stone shall be at least 12 in. (300 mm) below the stone.
5) [R] If the wiring method is buried cable, common grounding conductors run with the buried cable
shall be laid in the cable trenches as far as routing permits.
6) [R] If the wiring method is underground conduit, common grounding conductors run with the
conduits shall be laid along a formed side of the duct banks.
7) [I] Insulated copper conductors shall be provided in the following:
a) Corrosive environments (H 2 S, acids, caustics, etc.)
b) Highly corrosive soil conditions
c) Installations with close proximity to lead-covered power cables or extensive underground piping
systems
d) Installations with close proximity to buried metallic structures connected to cathodic protection
systems
8) [S] Grounding conductors leaving the ground at grade shall be protected as follows:
a) Conductors, except those used for lightning protection and lightning arrester grounding, shall be
protected by rigid metal, nonmetallic conduit, or pipe sleeves, where they extend above grade.
Lightning protection and arrester ground conductors shall be protected by nonmetallic conduit
sleeves.
b) Sleeves shall extend a minimum of 6 in. (150 mm) below grade and 10 in. (250 mm) above grade.
c) Metal sleeves shall be encased in concrete 3 in. (75 mm) thick all around.
d) Concrete encasement shall extend 6 in. (150 mm) above grade.
e) Nonmetallic sleeves shall be rigid, heavy-wall, polyvinyl chloride or high density, polyethylene
conduit.
f) Sleeves are not required within switch or transformer yards or under elevated substations.
made by brazing, welding, or with connectors that qualify as permanent grounding connections per
IEEE 837.
3.3. Grounds
1) [S] All Grounds shall have a resistance to earth not exceeding 5 ohms throughout the year,
considering seasonal variations in soil conditions. Grounds for low resistance grounded systems shall
not exceed 2 ohms.
2) [R] If permanently installed and located within a reasonable distance of the equipment or structure to
be grounded, the following may be used as grounding electrodes:
a) Buried grounding conductors at least 20 ft (6 m) long and buried to a depth of 30 in. (760 mm).
Minimum size shall be No. 2 AWG (35 mm2).
b) Underground metallic water piping, if buried portion is more than 10 ft (3 m) long.
c) Large underground metallic objects in intimate contact with earth, such as metallic building
frames, pile casings, or concrete encased electrodes consisting of reinforcing bars, or copper
conductors that are part of an underground foundation or footing. These electrodes shall provide
the conductive equivalent of at least 20 ft (6 m) of electrically conductive reinforcing bar, not less
than 1/ 2 in. (13 mm) diameter, or 20 ft (6 m) of No. 2 AWG (35 mm2) copper conductor. The
thickness of concrete encasement shall be not less than 2 in. (50 mm).
d) [A] Artificial made electrodes consisting of driven copper-clad steel rods or equivalent. Unless
specified otherwise, rods shall be copper-clad steel equivalent to Copperweld, with a minimum
diameter of 5/ 8 in. (16 mm) and a minimum length of 8 ft (2.5 m). The tops of rod and grounding
conductor connections shall be buried at least 18 in. (450 mm) below grade. A ground well shall
be provided for each rod and its connector, when specified. Where blocking obstructions are
encountered at depths less than 8 ft (2.5 m) that prevent vertical installation, trench burial may be
used as the placement method, with the approval by Owner's Engineer.
e) If more than one electrode is connected to a grounding system, the electrode spacing shall be at
least 10 ft (3 m) apart.
f) Electrodes of different systems shall be bonded together when in reasonable proximity.
3) [M] Electrode grounding conductors and connections shall comply with the following:
a) A grounding conductor shall connect the top of each electrode to an accessible aboveground
connection point. The minimum size shall be No. 2 AWG (35 mm2).
b) The connection point may be located on the structure or equipment to be grounded, or on a
nearby permanent structure, to serve as a tie-in point for other grounding conductors. At tie-in
points, conductors from electrodes shall be identified with corrosion resistant metal bands to
facilitate their removal for test purposes.
c) The grounding conductor shall be connected to the electrode by brazing or welding and to the
connection points by a bolted or screw-type solderless connector. In ground wells, the rod
connection may use bolted or screw type connectors.
2) [S] The design of grounding systems shall provide protection from step, touch, mesh, and transfer
potentials at the following areas:
a) Outdoor switchyards and main substations that are supplied by overhead lines at utility company
voltage
b) Substations adjacent to a utility-supplied switchyard or main substation
c) Generating stations
d) Gas-insulated substations (GIS)
e) [A] Grounding system design shall be evaluated using the guidelines presented in IEEE 80, or
equivalent regional or national standards. Grounding system design for these areas shall be
submitted for approval by Owner's Engineer.
c) For impedance grounded systems, the grounding conductor ampacity for the time allowed by the
lowest responsive relay shall be not less than the maximum current rating of the impedance and
the minimum size specified by the applicable regulations.
5. Enclosure Grounding
5.1. Wiring Systems
1) [S] Metal enclosures for wire and cable, such as conduits, cable trays, and raceways, shall be
grounded at their supply ends by connection to the switchgear or control center ground bus, when
such equipment is used; or by connection to the grounded metallic equipment enclosures when
switchracks are used. The wire and cable metal enclosures shall have metal connections to the
utilization equipment enclosures at their load end.
2) [S] The electrical continuity of metal enclosures, or wire and cable, shall be ensured between
terminals. Nonmetallic conduit sections or fittings shall not be used in metal conduit systems, unless
bonding is provided across such sections and fittings.
3) [S] Metallic armor, sheaths, and metallic insulation shielding of all cables shall be bonded together
and grounded at the cable's supply end by connection to the switchgear or control center ground bus,
when such equipment is used; or by connection to the grounded metal equipment enclosures when
switchracks are used. Exception: insulation shields of high-voltage motor feeders may be grounded
at only the motor end as a means of controlling switching surge voltages, provided that cable armor
and or conduit is grounded at both ends.
4) [S] Metallic armor and sheaths of multi-conductor cables shall be bonded and grounded in accordance
with the following:
a) Bonded together and grounded at each cable termination
b) Bonded together at each splice and bonded across each splice
c) Bonded together and to equipment metal enclosures at the load end
5) [R] Metallic insulation shielding in shielded multi-conductor cables shall be grounded at each
termination and shall be bonded to the cable metal sheath and armor (if any). If practicable, the
insulation shielding of cables with multiple splices shall also be grounded at each splice and bonded
to the cable metal sheath and armor (if any).
6) [R] Bonding and grounding methods for single-conductor cables having metallic armor, sheaths, or
insulation shielding must be engineered for the specific installation to avoid dangerous sheath, shield
voltages, or excessive heating due to circulating currents. Generally, single-conductor cables smaller
than 500 kCM (240 mm2) with all three phases in the same duct may be bonded and grounded the
same as multi-conductor cables. Armor, sheaths, and shielding of larger cables may require single-
point grounding with insulating joints between grounded sections.
5.2. Equipment
1) [S] Metal enclosures of fixed equipment operating above 1000 volts between conductors shall be
grounded by a connection to a ground in their immediate vicinity, in addition to the ground return
conductor.
2) [S] Metal enclosures of fixed equipment operating at 1000 volts or less between conductors and
supplied from ungrounded or high resistance grounded systems shall be grounded by one of the
conductor types specified in Section 6, Item (5).
3) [C] If supplied from solidly grounded systems, metal enclosures of fixed equipment operating at 1000
volts or less between conductors are considered grounded through their ground return path and do not
require further grounding.
4) [S] Main distribution equipment such as metal-clad and metal-enclosed switchgear, control centers,
and turnaround power centers shall be grounded by two separate connections from their ground
busses to grounds in the immediate vicinity. The metal enclosures of the individual devices on
switchracks shall be bonded to the switchrack frame, and the frame shall be grounded by two separate
connections to grounds in the immediate vicinity. Equipment grounds in substations of grounded
neutral systems shall be interconnected with the substation neutral ground.
5) [S] Metal enclosures of portable equipment shall be connected to a grounding conductor located
within the same cable assembly as the line conductors supplying the equipment as follows:
a) Grounding conductor shall be the same size as the line conductor.
b) Grounding conductor shall be connected to the receptacle enclosure through separate contacts in
the supply plug and receptacle, and shall be bonded to the plug enclosure.
c) Plug and receptacle shall be polarized and arranged so that the ground connection makes first and
breaks last.
Note: For enclosed or confined conductive work spaces, applicable regulations may place
specific restrictions on grounding and power supply for portable equipment used in these spaces.
6) [S] Metal enclosures such as fences, partitions, and grill work around equipment operating above
1000 volts between conductors shall be grounded by connections to grounds in their immediate
vicinity.
7) [S] Metal fences and grills enclosing the space under elevated substation buildings shall be grounded
by connections to ground in their immediate vicinity.
6. Ground Returns
1) [O] [R] A ground return path is required for each circuit in the following:
a) Solidly grounded systems
b) Impedance grounded systems
2) [O] [R] If switchgear or control centers are used, the supply ends of ground return paths shall
terminate at the switchgear or control center ground bus.
3) [O] [R] If switchracks are used, the supply ends of ground return paths shall terminate by connection
to the metal enclosure of the individual control devices.
4) [O] [R] The load ends of ground return paths shall terminate by connection to a ground bus, when
available, or to the metal enclosure of the equipment served by the ground path's circuit.
5) [I] Ground return paths shall be one of the following:
a) Rigid metal conduit
2) [*] [C] When specified, one or more conductors may serve as the common (main) ground return path
for a group of circuits in direct buried cable systems, in nonmetallic conduit duct banks, or above
ground cable raceways. In such cases, the following shall apply:
a) Main ground return conductors shall be run within the same cable trench or above ground cable
raceway as their line conductors.
b) Main ground return conductors shall be run within separate conduits in the duct bank.
c) It is preferred that common ground return conductors be tapped or connected to local ground bars
and individual conductors run to the equipment enclosures along the route of the circuit
conductors. Alternatively, the main ground return conductor may be looped and connected to
each equipment enclosure.
d) Main ground return conductors and their branch conductors shall be arranged to maintain
minimum spacing to their associated line conductors as much as possible.
e) If more than one main ground return conductor is used, the conductors may be bonded together
and a single conductor used for connection to equipment enclosures.
f) Main and branch ground return conductors shall be bare stranded, medium-hard-drawn copper,
with a minimum size of 2 AWG (35 mm2).
6) [S] Important structures that are not within a zone of protection (i.e., shielded) or are not inherently
self-protective shall be protected as follows:
7) [S] Lightning protection requirements for metallic structures shall be per Table 1.
b) If container filling is through a closed system, or if the filling nozzle is in electrical contact with
the container and will remain so throughout the filling operation
3) [S] Tank truck bonding conductors, when required, shall be provided at each loading or unloading
position as follows:
a) One end of the conductor shall be permanently connected directly to the fill stem or to other
points on the piping or steel loading rack that are electrically connected to the fill stem, (either
inherently or through bonding connections).
b) A battery type clip (or equivalent) shall be connected to the other end of the bonding conductor.
The conductor shall be long enough to permit attachment of the clip to the truck at a point that is
in metallic contact with the cargo tank being loaded or unloaded.
c) Bonding conductor shall be a 6 AWG (16 mm2) single conductor, rope-stranded, copper cable.
The cable shall have a thermosetting jacket for mechanical protection of the conductor.
4) [S] Tank car bonding, when required, shall be as follows:
a) Insulating rail joints shall be provided to isolate from the main track, the track section upon which
cars will stand while being loaded or unloaded. The purpose of these joints is to isolate stray
currents resulting from signal or power systems on the main track.
b) Joints shall be located to avoid being bridged by standing cars not loading or unloading.
c) Bond around all rail joints in the track section upon which cars will stand while being loaded or
unloaded.
d) Bond both rails of the track section upon which cars will stand while being loaded or unloaded to
the loading rack steel structure. If not inherently bonded together, the loading and unloading
piping shall be bonded to the loading rack steel structure.
5) [S] Container bonding, when required, shall keep the filling nozzle and container at the same
electrical potential to prevent a possible static spark in the area of a flammable mixture. Bonding
shall be as follows:
a) When the filling nozzle may not be or remain in electrical contact with the container, the
container shall rest on a metal base plate while being filled. This base plate shall be bonded to the
supply piping.
b) If the filling nozzle is inherently bonded to the supply piping, such as by the use of metallic hose
or pipe, no additional bonding to that specified in 5a) above is required.
c) If the filling nozzle is not inherently bonded to the supply piping, such as when a nonmetallic
hose or pipe is used, an additional bond shall be provided between the nozzle and supply piping.
d) All metallic parts of the fill assembly shall form a continuous electrically conductive path
downstream from the point of bonding on the supply piping.
b) Where marine loading arms or electrically bonded oil cargo hoses are used
c) For loading and unloading products having closed cup flash points below 100°F (37.8°C), or
which are at a temperature above or within 15°F (8°C) of their flash point
Record of Change
Version 1.0.0 Date: 01/02
Location Action Description
Initial Publish.