PROJECT : CLIENT : JOB NO.

: DATE : Mechanical Equipment Anchorage to Concrete Based on IBC 2000 INPUT DATA & DESIGN SUMMARY
KWIK BOLT-II DIAMETER ANCHOR DEPTH EDGE DISTANCE EQUIPMENT WEIGHT CENTER OF MASS ANCHORAGE LENGTH ANCHOR # ALONG L DIR ANCHOR SPACING ANCHORAGE WIDTH ANCHOR # ALONG B DIR ANCHOR SPACING hef c W H = = = = = 5 14 5.11 22 16 18 7.4 6 18 1/2 3 1/2 in. Per ICBO ER-4627 in. Per ICBO ER-4627 in kips ft, 2/3 total height ft per line in ft per line in

PAGE : DESIGN BY : REVIEW BY :

L = NL = SL = L / (NL - 1) = B = NB = SB = B / (NB - 1) =

[THE ANCHORAGE, KWIK BOLT-II, DESIGN IS ADEQUATE.]

ANALYSIS
ALLOWABLE TENSION & SHEAR VALUES (ICBO ER-4627) Pt Vt Scr Smin Mcr Mmin DESIGN LOADS FH = Fp = (KH) MAX{ 0.3SDSIpW , MIN[ 0.4apSDSIp(1+2z/h)/Rp W , 1.6SDSIpW ] } , (IBC 1621.1.4) = 1.3 MAX{ 0.50W , MIN[ 1.32W , 2.64W ]} = = 1.72 W , (SD) 1.23 W , (ASD) = 17.16 kips where SDS = Ip = ap = Rp = FV = KV Fp = 22.31 kips, up & down z= h= KH = KV = MAXIMUM OVERTURNING MOMENT AT ANCHOR EDGE MOT = Fp H = 87.63 ft-kips MRES = (0.9W - Fv ) (0.5B) = -35.92 ft-kips CHECK TENSION CAPACITY Ps = KDSA Kseismic Kedge-space [(FV -0.9 W) / A + MOT y / I ] = where A = 2(NL + NB) -4 = I = MIN(Xi2 , Yi2 ) = y = 0.5 B = KDSA = Kseismic = 0.8 40 (total bolts) in2-bolts 66238 1011 lbs / bolt (B direction governs) 1.1 1.5 1 1.5 h 36 1.3 1.3 (IBC 1621.1.6, page 377) (IBC Tab 1621.3, page 381) (IBC Tab 1621.3 & 1621.1.7(1)) ft ft (IBC 1621.1.7(2), page 377) = = = = = = 1625 2085 7 3 1/2 6 3/4 3 3/8 lbs lbs in in in, shear, in, shear, 3 3/8 2 1/4 in, tension in, tension

SPACING & EDGE REQUIREMENTS (ICBO ER-4627, Table 2)

<

MOT

,therefore design tension anchors.

<

Pt

[SATISFACTORY]

44.4 in (DSA adapted ICBO value) 4/3 (IBC 1605.3.2) 1.00 (ICBO ER-4627, Tab.2 footnotes)

Kedge-space = [0.8 + 0.2(c - Mmin)(Mcr - Mmin)] [0.7 + 0.3(S - Smin)(Scr - Smin)] = CHECK SHEAR CAPACITY Vs = KDSA Kseismic Kedge-space FH / A = where 458 lbs / bolt

<

Vt

[SATISFACTORY] 1.00 (ICBO ER-4627, Tab.2 footnotes)

Kedge-space = [0.5 + 0.5(c - Mmin)(Mcr - Mmin)] [0.7 + 0.3(S - Smin)(Scr - Smin)] =

CHECK COMBINED LOADING CAPACITY (ICBO ER-4627 Sec. 2.5.2) (Ps / Pt)5/3 + (Vs / Vt)5/3 = 0.533

<

1.00

[SATISFACTORY]