Version: Service-3
Status: actual
SDG-865-01-01
Author: bs Date: 05-02-18 Smart Digital Governor HUEGLI TECH LTD
Engine SWITZERLAND
Operation Manual
Service Version
Please read this manual before installing and commissioning the system. It
contains important information about safety, use and maintenance of the system.
For information about the engine or the Bosch VP44 pump please refer to the
related literature.
Content:
2. Configurable Parameters
Parameter Access Accessibility for Service Operator Access Description
Via Keypad via: see point:
Menu Key SmartView Keypad Keypad only
1)
Safety Parameters
Password for keypad - - - Not shown 6356 7.2
2)
Flywheel teeth 0 5 R+W R+W R 8.1
Overspeed limit 1 5 R+W R+W R 8.2
Fuel Injection Parameters
ME setpoint adjust 1 3 R R+W - 9.2
ME setpoint range - - R - -
PID-Parameters
Gain (8-point map) 0 1 R+W R+W R+W 9.1
Stability 0 2 R+W R+W R+W 8.13
Derivative 0 3 R+W R+W R+W 8.14
Start Parameters
Crank termination 2 7 R+W R+W R 8.3
Start fuel begin point 1 6 R+W R+W R+W 8.8
Start ramp 0 6 R+W R+W R+W 8.7
Speed Parameters
Fixed speed settings 0 4 R + W R + W R 8.5
Droop for fixed speeds 1 4 R + W R + W R + W 8.5, 8.10
Variable speed hi limit 0 7 R + W R + W R + W 8.6
Variable speed lo limit 1 7 R + W R + W R + W 8.6
Droop f. variable speed 1 4 R + W R + W R + W 8.6, 8.10
Speed ramp acceleration 0 9 R + W R + W R + W 8.9
Speed ramp deceleration 1 9 R + W R + W R + W 8.9
Information
Software version 3) R R R 7.2
SDG Serial number - - - - -
Software Built date - - - - -
Engine number 4) R - -
Run time hour counter - - R - -
Fault log read out 0 8 R R R 11.2
Fault log clear 1 8 yes yes no 11.2
Create report with - - no no no
password
Create report without - - yes no no
passw.
Factory Settings
Reset to default config. 1-2-3-4 yes yes yes 10.3
Notes:
R Read only permitted
R+W Read and write permitted
1) SmartView, Service version. GAC configuration and monitoring software.
2) Engine specific password, not published.
3) Software version is flashed out after entering correct password.
4) Engine number issued by MAN
3. Specifications
Physical:
Dimensions 96 x 141 x 37 mm
Weight 0.64kg
Mounting Direct engine frame mounting,
isolated via rubber elements,
vertical mounting preferred, or in panel.
Performance:
Isochronous Operation / Steady State Stability ±0.25% or better
Speed Range of Governor 400 – 8000 Hz
Speed Drift with Temperature ±1% maximum
Environmental:
Ambient Operating Temperature Range -40o to 85 oC
Relative Humidity up to 95%
Configuration Parameters:
Flywheel Teeth Range 50 – 250 teeth
Overspeed Setting 400 –10000 Hz *
Crank termination 50 – 1000 Hz *
Fixed Speed settings (all 3 speeds) 400 – 8000 Hz *
Variable Speed settings 400 – 8000 Hz *
Start Fuel Ramp 0 – 100%
Start Fuel Preset 0 – 100% (max fuel)
Droop Range 0 – 10% regulation
Speed Ramp up 0 – 100%
Speed Ramp down 0 – 100%
Reliability:
Vibration 7G @ 20-100Hz.
Testing (100%) Functionally tested
Password Protection:
Password 4-digit number
Notes: *) Speed values in RPM are based on the number of flywheel teeth.
RPM = Pickup frequency x 60 / flywheel teeth. (Max. frequency is 10'000 Hz.)
• Battery connections to terminals A and B cable is strictly required. Connect the shield
should be 2,5 mm2 , twisted or shielded. to terminal A.
• Battery positive (+) input, Terminal B should • The shields should be insulated to insure that
be fused for 10 Amps as illustrated in the no part of it comes in contact with engine
diagram. ground, otherwise, stray signals may be
• The governor should be mounted isolated introduced into the SDG causing erratic
from engine ground. operation.
• The Magnetic Speed Sensor cable to • For specific speed configuration using
terminals H and I MUST BE SHIELDED (or terminals J and K, please see table 1.
twisted) for its entire length. The shield
should only be connected to terminal A or N.
• The cables to the Variable Speed
Potentiometer can be of any reasonable
length up to 10 m. A shielded or twisted
Extra Ground connection for Wire Shields N DZG – Crankshaft speed Pulse W
The SDG865 allows an extra ground connection This is a signal required by the VP44 unit for
on the secondary terminal strip. This helps in the injection timing information. The VP44 will run
connection of extra grounds such as cable without this signal but engine performance may
shields and so forth. be poor.
7. Keypad Functions
7.1 Overview
RUN/SETUP LED
STABILITY LED Lit when SDG powered
Flashing Flashing in SETUP mode
- if no CAN communication.
Lit when
- STABILITY parameter
accessed in SETUP mode Diagnostics port
FAULT LED
DERIVATIVE LED A RUN / Lit when fault is detected before
Lit when GAIN
B
SETUP engine start.
- engine is cranking STABILITY FAULT Flashing when fault is detected
- DERIVATIVE parameter
C
DERIVATIVE when engine is running.
accessed in SETUP mode
D 10 1 2 3
9
E MENU button
8 4 5 6 for accessing:
LED BAR: indicating: F 7 - the menus in SETUP mode
- analogue (%) values 6 - GAIN point in GAIN map
- selected menu in SETUP G 5 7 8 9
- selected point in GAIN map
4
H MENU
flashing out 4-digit numbers 3 0 + SETUP button
I 2 SETUP for accessing SETUP mode
1 _ press and hold until RUN/SETUP
J ENTER
0 RUN
LED is flashing
K
L
RUN button
when exit SETUP mode and
save settings:
M N O P Q R S T U V W X Y
press and hold until RUN/SETUP
LED stops flashing
+ / - ARROW keys
for changing analogue (%) values
ENTER button
for activating 4-digit numbers Note: Do not press ENTER when
entered by the numeric keys changing values by the arrow
keys.
7.2 Accessing SETUP mode The Bar Graph display will indicate which
menu is active (0, 1 or 2).
a) To access the SETUP mode press and b) Next press the particular key to access its
hold the SETUP button until RUN/SETUP function.
LED flashes. For example, press [MENU] [MENU] [5] to
b) Now enter the 4-digit security code access overspeed.
followed by the ENTER key. Note:
Each time a key is pressed the
Bar Graph LEDs will flash.
7.4 Entering 4-digit Numbers
c) If the proper security code has been Settings defined as 4-digit numbers are modified
entered, the Bar Graph LEDs will begin by typing in a 4-digit number followed by the
to flash out the 4-digit software version enter key. These values are flashed out by the
number. If not, repeat step b. four digits on the bar graph. Note: a 3-digit
d) The RUN/SETUP LED will always be number has to be typed in with a 0 (125 =[0]
flashing while the SDG is in the SETUP [1] [2] [5] ).
mode. If you have problems during the
configuration always check to make sure 7.5 Entering %-Values
this LED is flashing indicating you are in
SETUP mode. Settings defined as %-values are modified by
pressing the arrow keys [+] or [-]. You may
7.3 Accessing Functions have to press the arrow key several times to
illuminate the next LED. To set a defined value of
a) Once in the SETUP mode, the functions for example 30% press the [+] key until the LED
listed under each key can be accessed by 3 is on. If only LED 0 is on, this indicates the
using the MENU button. Each time the MENU value is between 0 and 9 %.
button is pressed, the next menu will become
active. Press until the desired menu is active.
A
RUN /
GAIN
SETUP
B STABILITY FAULT
1 2 3
DERIVATIVE
C
D 10 1 2 3
9
E
8
GAIN STABILITY DERIVATIVE MENU 0 7
4 5 6
MENU 0
F
6
- - ME SET POINT MENU 1 G
H
5
4
7 8 9
MENU
3 0 +
- - - MENU 2 I 2
1
SETUP
_
J ENTER
0 RUN
4 5 6
FIXED SPEED FLYW.TEETH START RAMP MENU 0
DROOP OVERSPEED START FUEL MENU 1
- - - MENU 2
A
RUN /
GAIN
SETUP
B STABILITY FAULT
DERIVATIVE
7 8 9
C
D 10 1 2 3
9
E
8 4 5 6
VAR.SP.HI-LINIT FAULT RETRIEVE SP.RAMP ACCEL. MENU 0 7
MENU 1
F
6
G 5 7 8 9
VAR.SP.LO-LIMIT FAULT LOG CLEAR SP.RAMP DECEL. MENU 1 H
4
3 MENU
0 +
CRANK TERM. - - MENU 2 I 2
1
SETUP
ENTER
_
J 0 RUN
MENU
0 +
A
SETUP
RUN /
GAIN
SETUP
B STABILITY FAULT
DERIVATIVE
C
_
D 10 1 2 3
9
E
8 4 5 6
7
MENU 2
F
ENTER G
6
5
4
7 8 9
RUN
H MENU
3 0 +
I 2 SETUP
1 _
J ENTER
0 RUN
10
9
8
7 This indicates the value is
If only LED 0 is on, 6 between 50% and 59%.
the value is between
5
0% and 9%.
4
3
2
1
0
EXAMPLE 1 – Bar Graph displaying between 50% and 59%.
10 10 10 10 10 10
9 9 9 9 9 9
8 8 8 8 8 8
7 7 7 7 7 7
6 6 6 6 6 6
5 5 5 5 5 5
4 4 4 4 4 4
3 3 3 3 3 3
2 2 2 2 2 2
1 1 1 1 1 1
0 0 0 0 0 0
all 1 5 0 0 all
8.2 Overspeed
The overspeed set point is used for engine protection.
Entering menu 1, key 5, the set value is being flashed out.
MENU MENU 5
Typing in a 4-digit number followed by pressing the enter key will change the
setting.
Now the new value is being flashed out.
MENU MENU 4
Droop settings for the particular fixed speed are made similarly but here the values
are modified by using the arrow keys.
Low speed
Turn the potentiometer such that minimum voltage is present on terminal E.
Access menu 1, key 7. The min. voltage is verified by the bar graph display. This
MENU MENU 7
state also is recognized by the SDG as the potentiometers minimum position.
Typing in the 4-digit number followed by pressing the enter key will assign the
min. speed value (low idle) to this lowest potentiometer position.
This min. value is now flashed out with the bar graph LEDs.
Droop setting for variable speed is made with no connections on terminals J and K,
MENU MENU 4 the values are modified by using the arrow keys.
Droop no yes
Droop Droop 1 Droop 2 Droop 3
„variable“
Droop no no
Droop Droop 1 Droop 2 Droop 3
„variable“
Trim [rpm] 0 0 0 nvar,min
Table 1 - Speed Select Chart
Additionally, there is a group of parameters that do not necessarily need to be preset for basic engine
operation: Starting Fuel and Speed Ramping.
MENU MENU 9 DOWN: Provides deceleration ramping during RPM input changes.
8.12 GAIN
See point 9.1: Gain Points.
MENU 1
8.13 Stability
Increase STABILITY by pressing the + key until the engine becomes unstable, then
MENU 2 slowly reduce by tipping the –key until the engine returns to stable operation.
Continue to reduce for about 2 to 3 counts.
8.14 Derivative
In certain cases it can be necessary to adapt also the dead time compensation
MENU 6 (DERIVATIVE). If the engine oscillates fast, even if GAIN is low, reduce
DERIVATIVE by tipping the - key. If engine oscillates very slowly, increase
DERIVATIVE by tipping the + key .
9. Setting of Maps
Each time the Menu button is pressed, the next Gain point will be accessed. Note:
MENU
An LED on the Bar Graph will illuminate indicating which Gain Point is active. Also,
note the Gain Value represented by the Bar Graph is not illuminated until you push
the [+] or [-] buttons.
To exit this mode you must press and hold the [RUN] button. This saves the
values you have just entered and exits the setup mode.
100%
Gain
An example of individual Gain
settings for each of the 8 speed
ranges.
X X X
X Note: The speed ranges are fixed
X
X and only the Gain value is adjusted.
0% X
Gain X
If a fault is detected before starting the engine, the fault LED will be steady on. If it is a critical fault then
the engine will not be allowed to start. If a fault is detect while the engine is running, the fault LED will
be flashing. If it is a critical fault then the engine will be commanded to shut down by commanding zero
fuel and the MAB line is pulled high. Please note if the external shut down is enabled, the Engine will be
allowed to run even when a critical fault is detected (with the exception of Overspeed). If a Critical Fault
is detected while in this mode, the SDG865 checks to see if it is an overspeed or if the Remote Shutdown
(E-stop) is triggered. If not then Fault 31 is logged in the Fault log. If the engine is damaged and Fault 31
is logged then the engine operator failed to shut down the engine.
Remote shutdown will be logged any time it is triggered (Fault 203). If the Remote shutdown is enabled
during starting, the engine will not start.
a) Enter Setup
MENU MENU 8 b) Menu 1, Key 8.
c) SDG865 then flashes out 3-2-1-0 indicating fault log cleared.
d) Exit by pressing RUN or cycling power.
Suppressed fault 0012 Fault detected while in fault suppressed Shut down requested.
mode.
OCC: Occur, how many times the fault tripped.
ORD: Order, last order the fault tripped.
S: Engine shutdown
Battery and wiring Check battery voltage Too much voltage drop
while cranking. due to too small wiring or
Check wiring. weak battery.
1.2 LED FAULT on? SDG in FAULT condition Overspeed limit was Recheck flywheel teeth
exceeded? and overspeed settings.
Cycle power OFF-ON.
Try to restart
1.3 LED RUN/SETUP SDG in SETUP mode Cycle power OFF-ON.
blinking? Try to restart.
1.4 LED GAIN on? Crank termination setting Crank termination setting Cycle power OFF-ON
too low. should be min. 50 RPM Try to restart.
above firing speed. Readjust setting if needed
1.5 both LED GAIN and No speed signal from Measure voltage on Should be min. 1.0 VRMS
DERIVATIVE off? magnetic speed sensor. terminals H and I during during cranking
cranking
1.6 Actuator failure. Check wiring. See wiring diagram.
Measure voltage on Compare with actuator
terminals C and D. specifications.
Measure actuator current. Do not disconnect actuator
while energized!
1.7 Bar Graph flashing SDG configuration corrupt. Check configuration. Reload software or
when power applied reconfigure the unit.
to SDG
6 Engine unstable
6.1 Slow periodic Battery voltage too low Check battery and wiring Replace battery
instability should be min. 20V with Use appropriate wiring.
24V-systems
12. Dimensions
96 37
82.4 17.5
5
6.
Ø
A RUN /
GAIN
SETUP
B STABILITY FAULT
DERIVATIVE
C
D 10 1 2 3
9
E
8 4 5 6
7
127.4
F
141
6
G 5 7 8 9
4
H MENU
3 0 +
I 2 SETUP
1 _
J ENTER
0 RUN
M N O P Q R S T U V W X Y