PERSONAL SERVICE REPORT

Boiler Water Personal Service Report

PLANT OF : Hakkani Paper & Board Mills Ltd. DATE: 20/02/2022

ADDRESS : 2 D.T Road, Noth Pahartoli PLANT: BOLER

CITY : CHITTAGONG

Sub: Submit the Boiler Water Analysis result.


Dear Sir,
Thank you very much for your kind co-operation. It is your Boiler Blow down Water Test Analysis Result
Pls. kind attention.

Parameter Soft Water Tolerable Limit Boiler Blow Down Tolerable Limit
PH (Power of 7.90 5.5-7.5 Max. 12.50 9.0-12.5Max.
Hydrogen)
Total dissolved solids 198 500 Max. 2300 2000-3500
(TDS) Maximum
Total Hardness 05 10 Max. 60 20 Maximum
CaCO3
Iron (Fe) 00 0.0-5 Max. 00 0-0.5 Maximum
Silica SiO2 20 10-15 Max. 25 10-25 Max.
M-Alkalinity 123 150 Max. 690 250 Max.
P- Alkalinity 00 50 Max 650 150 Max
Conductivity 299 1000 Max. 4610 3000 Max.
Calcium Hardness 05 60 Max. 30 10 Max.
Magnesium Hardness 00 40 Max. 30 10 Max.
Chloride 20 50 Max. 150 200 Max.
Ortho phosphate N/A N/A N/A Min-1.5
(H3PO4)
COC (TDS) N/A N/A N/A 3.5 Max.
Turbidity N/A Max-1 N/A 10 Max.
RSI at 35 °C N/A N/A N/A 4.0-7.0
Salt 148 500ppm 1270 1000ppm
Remark: From lab analysis It is found that all the values of Boiler water please maintain the chemical
and also maintain the as per recommended dosage for safe & sound operation of your plant.

1. Maintain the Softener & also maintain the chemicals strictly as per recommendation for safe
and sound operation of your plant.
2. Maintain the Blow Down system strictly
Note: 1. All values in PPM except Ph.
Prepard By
___________________
Engr Md Ibrahim