Professional Documents
Culture Documents
Vet-MR Grande Site Planning Guide 141012800 Rev2 SW 3.1A (Feb2014)
Vet-MR Grande Site Planning Guide 141012800 Rev2 SW 3.1A (Feb2014)
Service Manual
Site Planning Guide
© ESAOTE 2014
The reproduction, transmission or
use of this document or its contents
is not permitted without express
written authority. Offenders will be
liable for damages. All rights,
including rights created by patent
grant or registration of a utility model
or design, are reserved.
Replaces: Ver.1 English
Doc. Gen.: Feb/2014
141012800 VER.2
Document revision level
The document corresponds to the version/revision level effective at the time
of system delivery. Revisions to hard copy documentation are not
automatically distributed.
Please contact your local ESAOTE office to order current revision levels.
This document has been compiled referring to the ESAOTE document code
9800020011 ST Rev.17.
Disclaimer
The installation and service of equipment described herein is to be performed
by qualified personnel who are employed by ESAOTE or one of its affiliates
or who are otherwise authorized by ESAOTE or one of its affiliates to provide
such services.
Assemblers and other persons who are not employed by or otherwise directly
affiliated with or authorized by ESAOTE or one of its affiliates are directed to
contact one of the local offices of ESAOTE or one of its affiliates before
attempting installation or service procedures.
Part 0 Table of Contents
Power Supply for Air-conditioning ................................. 25 Bearing Points & Service Area __________________ 35
Medical Tubing ....................................................................... 26
Connections _________________________________27 Heat Dissipation _____________________________ 36
Part 6 Annex 49
Annex 1 _____________________________________49
Annex 2 _____________________________________50
5
141012800 VER.2 Table of Contents
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
6
7
141012800 VER.2 Introduction - General
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
8
Fig. 1: System Components (Magnet - Equine Configuration) Fig. 1: System Components (Magnet - Pets Configuration)
Fig. 2: System Components (Operating Console) Fig. 1: System Components (Electronics Unit)
9
141012800 VER.2 Introduction - System Components
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
10
11
141012800 VER.2 Introduction - Patient Routine Monitoring
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
12
Safety Notes
The magnet installed in the scan room is always under field and
attracts magnetic material. The apparatus and instruments to be
carried into the pavilion should be non-magnetic. Gurneys, stretchers
or other large metallic objects, which may possibly be attracted to the
magnet, can be dangerous. It could be useful to differentiate these
objects from the standard furnishings through the use of color-coding.
Items must not be brought into the pavilion unless they are made of
non-magnetic material. In general, people must be prohibited from
entering the scan room. Local regulations require that warning signs
be posted with respect to possible malfunctioning of instruments or
pacemakers due to the fringe magnetic field. Preventive measures
must be taken with regard to this. A warning sign calling the attention
of the hospital workers and patients entering the scan room must be
posted (refer also to next figure). Carrying a watch, credit card, etc.,
into the pavilion may cause them to malfunction.
13
141012800 VER.2 Planning - Room
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
14
Fig. 3: Example of Minimum Space Required for Vet-MR Grande Fig. 4: Example of Minimum Space Required for Vet-MR Grande
Installation (Pets version) Installation (Equine version)
Overall System Floor Load Floor Leveling
The floor must be able to support the weight of the magnet unit, In order to allow the pavilion to be installed directly on the floor, the
electronics operating console and two people (approximately total floor must be leveled to within 5 mm / 3 m.
weight of 7000 kg). Therefore, the floor may have to be reinforced to
sustain a total load of 7000 kg (plus the Pavilion weight and animal).
Tab. 4: Floor Leveling Requirements
Please take in consideration the Magnet weight distribution area to
properly define floor load specification and reinforcements eventually
necessary.
Floor Leveling Requirements
5 mm / 3 m
Tab. 2: Overall System Floor Load
Overall System Floor Load NOTICE The floor leveling must be maintained very
carefully after system installation
7000 kg (plus the Pavilion weight and animal)
15
141012800 VER.2 Planning - Room
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
16
Environment
To achieve optimum performance from the installed system, it is
important to provide patients and operators with a comfortable
environment, as well as to meet the temperature, humidity and other
environmental conditions that each system component requires.
Environmental Requirements
Temperature range 21 - 24 °C / 69.8 - 75.2 °F
Temperature stability 3 °C/h / 5.4 °F/h
Humidity range 45 - 80% (condensate free)
Atmospheric Pressure 700 - 1060 hPa
Metric to Imperial
Centigrade = 0.56 x (Fahrenheit - 32)
Fahrenheit = (1.8 x Centigrade) + 32
RF & Magnetic Field Interference RF Noise
Because the optional Shielding Box has limited shielding capabilities
The surroundings of any MR-site must be examined very carefully. In (≥70 dB at a frequency of 10 MHz while -30 dB μV/m is the System
the case of System sites, it is imperative to check for external sensitivity), the external RF noise must be no more than 40 dB μV/m
magnetic and RF interference (EMI and EFI) at an early stage of the in at least 95% of the measurements.
project. This check is called a “site survey” and consists of a set of The RF measurements must be acquired at 10MHz. Set it while
measurements that must be performed by a site survey specialist. performing acquisition using the SMM kit.
These results are then compared to the corresponding specifications
shown in this chapter.
The first step is to complete the Preliminary Site Survey Report (refer Tab. 6: Maximum RF Noise
to Annex 2) during the sales phase of the project, and to return it to
your site survey specialist. This information is needed in order to
estimate installation costs, the costs associated with the Maximum RF Noise
measurement, and to determine whether or not a system can be 40 dB μV/m
installed at that particular location. However, the final decision on the
suitability of the site depends on the results of site measurements,
and not on the Preliminary Site Survey Report.
NOTICE IF THIS THRESHOLD IS EXCEEDED IN NO
MORE THAN 5% OF MEASUREMENTS
DURING THE USUAL WORK TIME FOR THAT
NOTICE Both RF noise and magnetic field fluctuations are MRI SYSTEM, THE INSTALLATION ROOM IS
determined during the site survey using specially ALSO TO BE CONSIDERED SUITABLE
designed measuring equipment (SMM, Site
Measurement Module).
17
141012800 VER.2 Planning - RF & Magnetic Field Interference
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
18
Magnetic Field Fluctuation In order to keep these values valid, no more than one source must be
present within the limit shown in the Maximum Values without EFI
The need for EFI compensation and the shielding method must be table. Particular restrictions apply for moving iron masses (see the
determined according to the quasi-static (DC, < 5 Hz) and next table). Moving iron masses must be further than the distance
slow-changing magnetic field fluctuation (AC, 16-20 Hz; AC, from the magnet center as defined in the following table.
50-60 Hz),
All the values below refer to peak/peak fluctuation in the proposed
position of the magnet center. Tab. 9: Iron Masses Weight
The DC values, measured by SMD, to be considered are the
peak/peak variations within a window of ten minutes. When
measuring Ac fluctuation you must consider if RMS of peak/peak Weight Moving Direction
values have been recorded. X (Front-Back), Y (Vertical) Z (Lateral)
50 kg 5m 4m
Tab. 7: Maximum Values without EFI 200 kg 7m 5m
900 kg 9m 6m
Maximum Values without EFI 4500 kg 15 m 10 m
20000 kg 25 m 20 m
DC (< 5 Hz) 30 nT pkpk (0.3 mG)
AC (16.7 Hz) 6 nT pkpk (0.06 mG)
Regarding AC sources, no cables must run in the ceiling or in the floor
AC (50-60 Hz) 20 nT pkpk (0.2 mG) of the installation room, especially if their path is not fixed and stable.
Maximum Values for DC with EFI Tab. 12: Static Magnetic Field
Underground lines or trams 4000 nT (40 mG)
further than 100 m
Fringe Magnetic Field of External MRI Equipment
In this case the transversal component must always be checked and 0.1 mT line (at maximum) on the
the values must be lower than the Maximum Values with EFI. external boundaries of the Pavilion
19
141012800 VER.2 Planning - RF & Magnetic Field Interference
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
20
Building Vibrations
Building vibrations or shocks affecting the magnet may degrade
image quality. Vibrational acceleration amax transferred through
building vibrations to the magnet must not exceed the values shown in
the following table in the vertical direction.
21
141012800 VER.2 Planning - Power, Mains and Grounding
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
22
Fig. 5: Time/Current Characteristic These breakers must be approved in according to the international
and/or national and/or federal and/or local standards in force and they
must be installed in a wall-mounted sheltered box near the unit.
Wiring between the system and the CB must be via the three-wire
cable supplied with the system itself. It must be cut to the appropriate
length and cable end sleeves must be inserted before inserting them
into the terminal connection. The equipment must be permanent
connected to the Mains (according to EN 60601-1); therefore the
cable can be removed only by means of a special tool (e.g. a
screwdriver)
System Grounding
The grounding conductor must be insulated and must not be
electrically connected to surrounding structures. To ensure that the
system is grounded properly, the modular shielding pavilion is
insulated from the floor via corresponding insulating sheeting.
Never perform double ground connections to avoid grounding loop.
System Power Distribution Scheme
The main power distribution diagram is shown in the next figure.
23
141012800 VER.2 Planning - System Power Distribution Scheme
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
24
25
141012800 VER.2 Planning - Lighting Equipment
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
26
Medical Tubing
The locations of medical tubing (oxygen and vacuum suction) will be
determined in accordance with customer requirements.
Electrically insulated tubing (nylon, polyethylene, Teflon, etc.) must be
used for applications that are routed through the RF-shielded walls.
Metal tubing should not be used for these types of applications since
the tubing acts as a RF antenna by introducing external noise into the
Pavilion.
Insulate the primary-side tubing from the RF-shielded room. An
insulated tube and a copper pipe must be connected using a joint that
is appropriate to both materials.
For the oxygen tube the dimensions are 10 - 12 mm (diameter) and
100 mm (length).
Connections Tab. 20: Maximum Distance Filter Panel - Magnet
Maximum System Cable Lengths Maximum distance Filter Panel - Magnet Unit
The cable ducts for the System wiring outside the ESAOTE Pavilion is 2,8 m (average cable lengths 3,8 m)
not part of the delivery.
The cable ducts for the System wiring inside a dedicated RF Cage is
not part of the delivery.
In case of dedicated RF Cage please contact the ESAOTE Network and DICOM
headquarter asking the availability of cables with different lengths
than the standard kit.
Network
The system includes an internal network card for LAN connection. An
Tab. 18: Maximum Distance PC Unit - Electronics Unit appropriate outlet should be provided to connect to the LAN. The
network connection cable is not provided with the system. The
network cable is not provided with the system
Maximum Distance PC Unit - Electronics Unit
18 m (cable length 20 m)
DICOM Connection
The system uses the internal network card for DICOM connection.
An appropriate outlet should be provided to connect to the LAN.
Tab. 19: Maximum Distance Electronics Unit - Filter Panel The system can be connected to a laser cameras via DICOM (LAN).
For further information download the DICOM Statement from the
ESAOTE Restricted Web Site. The network connection cable is not
Maximum distance Electronics Unit - Filter Panel provided with the system.
7,5 m (average cable lengths 8,5 m)
27
141012800 VER.2 Planning - Connections
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
28
Needed items
To allow DSL Connections the following items are needed:
● On Customer side, MRI System connected to internet via DSL
Connection (see below for technical details): CONNECTION TO
THE WWW.ESAOTE.COM WEBSITE REQUIRED
Part 3 Technical Data
29
141012800 VER.2 Technical Data - System Components
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
30
Fig. 9: Dimension of Magnet Unit and Patient Table Equine Version Fig. 10: Dimension of Magnet Unit and Patient Table Pets Version
Electronics Unit Fig. 11: Electronics Box Dimensions
31
141012800 VER.2 Technical Data - System Components
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
32
Filter Panel Fig. 13: Filter Panel Installation Dimensions (Pavilion Internal View)
The Filter Panel filters the signals present in the System Cables and
provides continuity to the Pavilion (or RF Cage) shielding capabilities.
It’s tested with the system and sent with it. In case of Dedicated RF
Cage installation use the following draw to allow the Filter Panel
installation (dimensions and hole positions).
* the first value refers to the Magnet joke side, the second value refers
to the Magnet open side
33
141012800 VER.2 Technical Data - Magnet Fringe Field
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
34
Fig. 15: Magnet Fringe Field Distribution (lateral view) Fig. 16: Magnet Fringe Field Distribution (top view)
Bearing Points & Service Area The Magnet gravity point is indicated by the “G” letter and its position
is shown in the previous figure.
The next figure shows the position of the bearing points respect to the
Fig. 17: Gravity Point and Bearing Points (Magnet base top view) complete System installed inside the ESAOTE Pavilion.
35
141012800 VER.2 Technical Data - Bearing Points & Service Area
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
36
37
141012800 VER.2 Transport & Storage -
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
38
39
141012800 VER.2 Transport & Storage - Crate Dimensions
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
40
The following data are referring to the ESAOTE Pavilion only and are NOTICE THE SIZE AND THE GROSS WEIGHT OF THE
provided as an example: real shipments can even be slightly different OTHER CRATES CONTAINING THE CONSOLE
according to material availability, shipment characteristics and UNIT, MONITOR, COILS, COVERS AND
requirements, cost reducing, etc. ACCESSORIES MAY DEPEND ON THE
MEANS OF TRANSPORT CHOSEN (BY AIR, BY
SEA, BY ROAD…), AND THE NUMBER OF
Tab. 27: Pavilion
UNITS
Crate Number Gross Size Net [kg] Gross [kg] Fig. 22: Crate Label
(LxWxH) [mm]
Crate N.1 2900 x 1000 x 500 485 650
Crate N.2 2700 x 1000 x 900 120 270
Crate N.3 3300 x 1000 x 900 70 220
Crate N.4 3000 x 1600 x 600 470 750
Crate N.5 1900 x 650 x 400 80 140
Recycling
If possible, the crates, the pallet and the metal support of the
Magnetic Unit, used for transportation, should be recycled for a
maximum of 10 times.
Transport & Storage Conditions Tab. 30: Temperature Range during Transport and Storage of the Magnet
Humidity
When transporting and storing the magnet unit, never exceed the Pressure Range During Transportation and Storage
humidity range specified in the following table. Otherwise, the magnet Minimum pressure 500 hPa
will be damaged. Maximum pressure 1060 hPa
Tab. 29: Humidity Range during Transport and Storage of the Magnet
Temperature
When transporting and storing the magnet unit, never exceed the
temperature range specified in the following table. Otherwise, the
magnet will be damaged.
41
141012800 VER.2 Transport & Storage - Transport & Storage Conditions
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
42
System Storage
NOTICE You must define and delimit the 0,5 mT area
according to the following figures and forbid its
Storage of Many Units access to not authorized personnel. Signs
In case of storage of many systems, please refer to the following indicating that a permanent magnet will be
figure for correct Magnet Units positioning. present must be used all around that area as well.
43
141012800 VER.2 Transport & Storage - Installation Tools
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
44
45
141012800 VER.2 Transport & Storage - Magnet, Pallet and Gravity Point
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
46
Minimum Passage Dimensions NOTICE THE CARTS USED TO DEFINE THE HEIGHT
DIMENSION ARE 10CM HEIGHT: IN CASE OF
DIFFERENT CART HEIGHT THE MAGNET
During System Installation the Minimum Passage must be guarantee
HEIGHT MUST BE RE-CALCULATED.
for the entire distance from the location where the System is unloaded
to the Installation Room.
To move the Magnet into the installation room, ESAOTE developed Fig. 31: System Minimum Dimension with Installation Carts
and tested two different aluminum bar types:
● the long aluminum bars that are 1500mm
● the short aluminum bars that are 1500mm as well but with two
removable extensions to decrease the bar quote to 1080mm
47
141012800 VER.2 Transport & Storage - Minimum Passage Dimensions
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
48
Annex 1 11. Check whether the power, grounding and lighting requirements
are met
12. Make sure that modem, network and camera connections are
Recommended Planning Actions available
This is a list of recommended actions to be taken while planning a 13. Find out whether convenience outlets (emergency lamp, smoke
system installation: sensor, medical tubing) are to be installed
1. Check the room size against the minimum space required for 14. Define the room layout (position of modular shielding pavilion,
siting a system doors and console). Allow at least 0.2 m distance against the wall
for the filter panel and remember that the console must be placed
2. Check all the passage dimensions in order to be able to move the
within a distance range of 4,5 m from the filter panel
Magnet inside the Installation room
3. Check whether the floor has to be reinforced to sustain the total
load of a system
4. Make sure that the building vibration requirements are met.
5. Check whether the fringe field of the magnet requires an external
room shielding
6. Ensure that the minimum passage dimension required for carrying
in the system as well as the minimum weight of the system
components do not represent a problem for doors, floors, elevator,
etc.
7. Fill in the Preliminary Site Survey Report and send it to your site
survey specialist
8. Arrange for a site measurement with your site survey specialist.
9. Check whether the floor leveling requirements are met
10. Check whether the air-conditioning system fulfills the room
temperature requirements
49
141012800 VER.2 Annex - Annex 1
5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
50
Annex 2 column with the lowest class number will determine the preliminary
site status:
– Class 1: Very critical site, installation probably impossible
Preliminary Site Survey – Class 2: Critical site, installation probably possible but additional
Preliminary Site Survey Report must be filled in during the sales shielding required
phase of the project and then returned to your site survey specialist. – Class 3: Normal site, installation possible but additional
shielding may be required
Situation Report – Class 4: Uncritical site, installation probably possible, additional
shielding not required
The Situation Report is a brief description of the location of the
proposed site. Check the rooms surrounding the location with respect
to all six directions and enter the results into the Tab: Distance check: Remarks
- Where are...?. Use this section to enter any comments you consider important
regarding installing the system at that location.
Sources of Interference
The Distance Check is a systematic analysis of existing sources of
magnetic interference and the distance between these sources and
the center of the magnet. Sources of magnetic interference may be
associated with one or more of the following:
a) AC 50 Hz or 60 Hz: high current cables, etc.
b) AC 50 Hz or 60 Hz: transformers, motors, etc.
c) AC 16.6 Hz or 25 Hz: power cables used for trains
d) Moving iron objects: cars, trucks, elevators, patient beds,
equipment, etc.
e) Switched DC: tram, subway, other MR-systems
f) RF noise: antennas, fans (even not magnetic), monitors, engines,
transformers, ups, phone switch boards, medical systems, etc.
51
141012800 VER.2 Annex - Annex 2
5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
52
General Information
Sales representative:
Project manager:
Sales status: sold: probable: possible:
Customer name:
City:
Report issued by:
Date and signature:
Situation Report
Remarks
53
141012800 VER.2 Annex - Annex 2
5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
54
Annex 3
Building Vibration Requirements
Planning summary -65 dB(g) (from 0 to 12 Hz and from 20 to 100 Hz)
amax
-75 dB(g) (from 12 to 20 Hz)
Power requirements AC 200/208/220/230/240 V ± 10% Vet-MR Grande - Equine 1000 1582 1780 6350
Frequency 50/60 Hz ±1Hz Vet-MR Grande - Pets 2210 1825 1780 6500
Power 0.4 kVA during stand by (Electronics unit off) Electronics 600 720 1650 341
1.1 kVA during stand by (Electronics unit on) Operating Table Standard 1080 800 740 30
2.0 kVA during acquisition or quick heating Operating Table High 1100 900 800 35
Current Protection Thermal cutout 25 A primary, 20 A secondary TFT Monitor 18" 399 404 404-504 8
Earthing 2
Via power cable 6 mm section PC Unit 260 440 430 15
Pavilion (aluminum) 3850 2900 2280 500
55
141012800 VER.2 Annex - Annex 3
5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
56
System Crates
Temperature range during transport and storage
Minimum temperature -20 °C
Content Gross Net weight Size (LxWxH)
Maximum temperature 60 °C weight [kg] [kg] [mm]
Covers 132 62 1930 x 1220 x 1140
Humidity Range During Transportation and Storage Equine Kit
137 65 1960 x 1160 x 1050
Humidity range 15 ÷ 85% (condensate free) (optional)
Small Animal Kit 180 95 1650 x 1400 x 640
Pressure Range During Transportation and Storage PC, Coils and
96 52 1200 x 1000 x 900
Filter Panel
Minimum pressure 500 hPa
Accessories 145 101 1200 x 1000 x 900
Maximum pressure 1060 hPa
Desk 81 54 1170 x 870 x 420
Electronics 397 341 960 x 1150 x 2040
Maximum Tilt During Transportation and Storage
Only for the on truck shipping
Maximum tilt 10°
Magnet Unit 6450 (Pallet) 6250 1700 x 1100 x 1800
57
141012800 VER.2 Index
6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
58
RF ............................................................................................... 17
RF Noise ..................................................................................... 17
Room Size .................................................................................. 13
S
Safety ......................................................................................... 12
Service Area ............................................................................... 36
Sources of Interference .............................................................. 50
Static Magnetic Field .................................................................. 19
System Components .............................................................. 7, 29
T
Table of Contents .......................................................................... 3
Transport humidity ...................................................................... 41
Transport maximum tilt ............................................................... 42
Transport pressure ...................................................................... 41
Transport summary ..................................................................... 55
Transport temperature ................................................................ 41
Transportation device ................................................................. 43
U
UPS ............................................................................................ 24
V
Vibrations .................................................................................... 20
0 Table of Contents
1 Introduction
2 Planning
3 Technical Data
4 Transport
5 Annex
6 Index
7 Tbd
8 Tbd
9 Tbd
10 Tbd
11 Tbd
12 Tbd
13 Tbd
14 Tbd