2 Specifications 1 Molded Case Circuit Breakers

NF-S (Standard class)


Frame (A) 250 250 400 400 600 630
Model NF250-SGV NF250-SEV NF400-SW NF400-SEW NF630-SW

Image

2
Rated current In (A) 125-160 140-200 250 300 Adjustable 200 225
80-160 125-250 500 600 630
Rated ambient temperture 40°C (45°C for marine use) 175-250 350 400 250 300 350 400
Number of poles 2 3 4 3 4 2 3 4 3 4 2 3 4 2 3 4
Rated insulation voltage Ui (V) 690 690 690 690 690 690
690V 8/8 8/8 10/10 10/10 10/10 10/10
Rated short-circuit breaking capacities (kA)

500V 30/30 30/30 30/30 30/30 30/30 30/30


440V 36/36 36/36 42/42 42/42 42/42 42/42
1 Detailed Specifications

IEC 60947-2 415V 36/36 36/36 45/45 50/50 50/50 50/50


AC
EN 60947-2 400V 36/36 36/36 45/45 50/50 50/50 50/50
(Icu/Ics) 380V 36/36 36/36 50/50 50/50 50/50 50/50
230V 85/85 85/85 85/85 85/85 85/85 85/85
200V 85/85 85/85 85/85 85/85 85/85 85/85
DC 250V 20/20 (300V) (*2) − 40/40 (*2) − 40/40 (*2) 40/40 (*2)
Rated impulse withstand voltage Uimp (kV) 8 8 8 8 8 8
Current AC/DC compatible AC AC/DC compatible AC AC/DC compatible AC/DC compatible
Suitability for isolation Compatible Compatible Compatible Compatible Compatible Compatible
Reverse connection Possible Possible Possible Possible Possible Possible
Number of Without current 25,000 25,000 6,000 6,000 6,000 6,000
operating cycles With current (440VAC) 10,000 10,000 1,000 1,000 1,000 1,000
Utilization category A A A B A A
Rated short time with stand current Icw (kA) at 0.25s − − − 5 − −
Pollution degree 3 3 3 3 3 3
EMC environment condition (environment A or B) N/A A N/A A N/A N/A
ca
a a 105 140 105 140 140 185 140 185 140 185 140 185
dimensions (mm)

c
b 165 165 257 257 257 257
Overall

b c 68 68 103 103 103 103


ca 92 92 155 155 155 155
Mass of front-face type (kg) 1.4 1.6 2.0 1.7 2.2 4.6 5.2 6.8 6.0 7.6 5.4 6.2 8.0 5.4 6.2 8.0
Front connection (F) Page dScrew terminal dScrew terminal dBusbar terminal dBusbar terminal dBusbar terminal dBusbar terminal
Cassette-type Installation and

d
connections

Solderless (BOX) terminal (SL) d d d − − − − − − − − − − −


Rear (B) 92 dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud
Plug-in (PM) d d d d d d d d d d d
Alarm switch (AL) d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d
accessories

Auxiliary switch (AX) d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d


102
Shunt trip (SHT) d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d
Undervoltage trip (UVT) d (*3) d d (*3) d d d d d d d d d
With lead-wire terminal block (SLT) 114 d d d d d d d d d d d
Pre-alarm (PAL) 116 − d − d (*5) − −
Closed (S) d − d − − − − −
Enclosure Dustproof (I) 130 d − d − d − d − d − d −
Waterproof (W) d − d − d − d − d − d −
Electrical operation device (NFM) 133 d d d (*6) d (*6) d (*6) d (*6)
External accessories

Mechanical Panel mounting d d d d d d d d d d d


129
interlock (MI) (*7) Breaker mounting d d − d − d − d − d −
LC d d − − − −
Handle lock
HL 127 d d d d d d
device
HL-S d d d d d d
External (F) d d d d d d
117
operating handle (V) d d d d d d
Terminal cover (TC-L, TC-S, TTC, BTC, PTC) 121 d d d d d d d d d d d
Rear stud (B-ST) d d d d d d d d d d d d
94
Plug-in (PM) d d d d d d d d d d d d d d
IEC 35mm rail mounting adapters 137 − − − − − −
CE marking Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration
CCC recognition Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process
Marine use approval (NK, LR, ABS, GL)  (LR, ABS, GL) −  (LR, ABS, GL) − q − q − q − q −
Automatic tripping device Thermal-magnetic Electronic (effective value detection) Thermal-magnetic Electronic (effective value detection) Thermal-magnetic Thermal-magnetic
Trip button Equipped Equipped Equipped Equipped Equipped Equipped
Page of Characteristics and dimensions 152 154 156 158 162
Notes: *1 The trip action characteristics differ between AC and DC for products that are compatible with both AC and DC.
*2 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. Line Line
If wired as shown on the right, three and four poles can be used for up to 400 and 500VDC, respectively.
*3 The cassette type design makes it easy for customer to install. Available for installation on side below 250A frame
(excluding UVT).
*4 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. Not
available for use with connection as shown on the right. Load
Load
*5 Solid state relay output is option. Please specify if other output is necessary. 3-pole 4-pole
(Standard type is thus SLT equipped) AS for flush plate type, an outline differs from a standard.
*6 Place an order of other models in conjunction with the circuit breaker.
*7 Not isolation compatible. excluding 400 to 800A frame.

18
Characteristics
7 and Dimensions 1 Molded Case Circuit Breakers

NF630-CW
Model NF630-CW NF630-SW
Rated current In (A) 500 600 630

NF630-SW
Number of poles 2 3 2 3 4
Rated insulation voltage Ui (V) 690 690
690V − 10/10

breaking capacity (kA)


Rated short-circuit
500V 18/9 30/30

IEC 60947-2 AC 440V 36/18 42/42


(Icu/Ics) 400V 36/18 50/50
230V 50/25 85/85
DC (*1) 250V 20/10 40/40
Front Mounting screw: M6×72 (4pcs)
connection Insulating barrier: (2P: 2pcs, 3P: 4pcs, 4P: 6pcs)
Standard attached parts
Rear
Mounting screw: M6×85 (4pcs)
connection
Note *1 When wired as shown at the bottom of page 14, 3-pole models can be used for up
to 400VDC, and 4-pole models for up to 500VDC.

NF630-SW

Operating Characteristics

4h 4h

2h 2h

1h Operating characteristics 1h Operating characteristics


NF630-CW NF630-SW
30min 30min
20min 20min
14min 14min
10min 10min
6min 6min
4min 4min

2min 2min

1min 1min
Max. Max.
30s 30s
Operating time

Operating time

20s 20s

10s 10s

5s 5s
Min. Min.

2s 2s

1s 1s
AC
0.5s 0.5s
DC

0.2s 0.2s
DC AC
0.1s Max.total 0.1s Max.total
interrupting time interrupting time
0.05s 0.05s

0.02s 0.02s
Time delay trip Instantaneous trip Time delay trip Instantaneous trip
0.01s 0.01s
100 125 200 300 400 500 600 700 1000 1500 2000 3000 4000 100 125 200 300 400 500 600 700 1000 1500 2000 3000 4000

% of rated current % of rated current

Internal Accessories Temperature Compensation Curve


Operating handle

7
Left-side Right-side Lead wire 130
AL AX SHT or UVT
Rated ambient

mounting mounting direction


temperature
Current rating (%)

120

110

(*1) 100
1 Characteristics and Dimensions

90

(*1) (*1) (*1) 80


0 10 20 30 40 50 60
Note *1 Right-side mounting is standard of SHT and UVT. Specify separately for left-side mounting.
Ambient temperature (°C)
Remark: 1. Refer to page 106.

External Accessories
Accessories Type name Reference page Accessories Type name Reference page
F F-4S 117 2, 3P TCL-4SW3
Operating handle Large TC-L
Terminal cover

V V-4S 119 4P TCL-4SW4


2, 3P MI-4SW3 2, 3P TTC-4SW3
Mechanical interlock MI 129 Skeleton TTC 121
4P MI-4SW4 4P TTC-4SW4
Auxiliary handle HT HT-4SW 128 2, 3P BTC-4SW3
Rear BTC
Note *1 Specify the operation method and voltage. Order in combination with 4P BTC-4SW4
the breaker unit. HL HL-4SW
Handle lock device 127
HL-S HLS-4SW
3P
Electrical operation device NFM (*1) 133
4P

162
7 Characteristics and Dimensions 1
Molded Case Circuit Breakers
NF630-CW · NF630-SW
Outline Drawing

Front connection

12
Insulating barrier
(removable) 94.5
CL Conductor 4-pole
thickness 44
28
t=10 max. 8 30 3-pole
f10.5
CL
110

Breaker

16
Conductor thickness t=10 max. CL
Conductor drilling

43
for direct connection

39
Mounting hole CL Breaker CL

R6
257
CL CL

102

92
59

f12.5
Trip button

f7
39
CL

194
Neutral pole 44 118

97
f14 1.0mm clearance on each
M12 bolt 56 103 side of handle.
M6 screw
51 44 or f7 44
168 5 107
Front-plate cutout
112 185 155 3-pole 4-pole
140 196

3-pole 4-pole Drilling plan

Boring dimensions for rear connection


Rear connection type barriers (3-pole)

4-pole
Line side
Mounting plate Stud can be Breaker Eddy-current
rotated 90° 3-pole heat-reducing slit 6-f35
CL CL

24 24
8
Connection M6 screw
allowance or f7 4-M6 tap
or f7
225
265

CL

194

225
225
194
CL
14

25 20 20
83
32

128

24 24
M6 breaker
mounting screw
44 f35 44
10 8 11 11
8-M4 screw
f13 Add these tapped
113 87 Insulating tube 87 43.5
M12 bolt 44 holes in 8 positions
attached to
130.5 3P:Center pole to standard boring.
130.5 87
4P:Center and
neutral poles
3-pole 4-pole Load side

Drilling plan
Note The bore dimensional drawing shows
the breaker viewed from the rear.

Plug-in

4-pole
Plug-in terminal block Mounting plate
3-pole
CL Breaker CL
CL
35

55

Connection allowance 7
225
280

CL M8 terminal block CL
163
135

25
mounting screw
25
10

93

55
28

160

f10
1 Characteristics and Dimensions
20

30 Stud attachable in
18 44 87
this direction only

121 136 181


110
f13 Insulating barrier
M12 bolt 165.5
3-pole 4-pole
Drilling plan

Remark: 1. 2-pole models are 3-pole models with the central pole removed.

163