Induction diffuser DISA-360
Contents
Description ........................................................................................................................................ 3
Advantages ........................................................................................................................................ 3
Function ............................................................................................................................................ 3
Description of the equipment ................................................................................................................... 4
Construction .............................................................................................................................................................................. 4
Model ......................................................................................................................................................................................... 4
Accessories ................................................................................................................................................................................ 4
Fastening ................................................................................................................................................................................... 4
Models and dimensions ......................................................................................................................... 5
Dimensions and weights ............................................................................................................................................................ 5
Accessories ................................................................................................................................................................................ 7
Figures ....................................................................................................................................................................................... 7
Technical data .................................................................................................................................... 8
Performance data ....................................................................................................................................................................... 8
Sound level .............................................................................................................................................................................. 16
Flow data ................................................................................................................................................................................. 17
Control units ..................................................................................................................................... 25
Valves ...................................................................................................................................................................................... 25
Actuators ................................................................................................................................................................................. 26
Control units ............................................................................................................................................................................ 27
Condensation monitor ............................................................................................................................................................. 29
Assembly ........................................................................................................................................ 30
Maintenance .................................................................................................................................... 30
Legend ........................................................................................................................................... 30
Order details .................................................................................................................................... 31
Specification text ............................................................................................................................... 32
1
The cold water supply temperature must be selected
such that it does not fall below the dew point,
which may make it necessary to install protective de- 3
vices (condensate monitors)
. 4
The register of the DISA-360 can be swivelled down-
wards if the flexible connecting hoses are long 2
1 Primary air
Advantages 2 Room air
3 Secondary air
- 4-way throw for optimum air distribution and excellent reduc- 4 Heat exchanger
tion in temperature
- High energy efficiency Schematic diagram of the jet path
- High performance (compensation of high thermal loads)
- Compact dimensions and low height
- Saving in energy by means of reduced primary air
- Low noise level
- low mounting and maintenance expenditure
Accessories
Rubber lip seal (-GD)
Flexible connection hoses
- 500 mm (-FA 500)
- 800 mm (-FA 800)
- 1200 mm (-FA1200)
External thread flat sealing (-WA 1/2)
Volumetric flow measuring tube (-MR)
Control units
- Valves
- Actuators
- Room temperature control
- Condensation detector
Fastening
Fixing lugs
- for easy suspension of the induction diffuser
ap-65
L P
C
Ø D
75
75
141
220
LG B
7
BxLG with perforated sheet grille (-SR/-SQ/-RE/-OB)
592x592 592x1192 597x597 597x1197 617x617 617x1242 622x622 622x1247
L (mm) 519 1119 524 1124 519 1144 524 1149
C (mm) 515 520 515 520
D (mm) 98 / 123
P (mm) 24 24 22 22 24 12 22 9 with louvre grid (-PA)
-FM (mm) 900x900 900x1500 900x900 900x1500 900x900 900x1500 900x900 900x1500
WS2
ØD
WeightsDISA-360 66 122
NL 600 1200
Weights (1) (kg) 14,5 28 Heating
(1) Standard unit: housing + slot + grille and heat exchanger (empty) Cooling
LG
with 2 connecting pieces (-AS2/AS3) E
L
1/4 1/2 1/4
B x LG
LG 592 592 597 597 617 617 622 622
x x x x x x x x
592 1192 597 1197 617 1242 622 1247
Vertical connection (-V) E -H 625 630 625 630
with 1 connecting piece (-AS4) -V 550 555 550 555
F 409 1009 414 1014 409 1034 414 1039
L
= =
Air deflection blades
LG
with 2 connecting pieces (-AS5/AS6)
L
1/4 1/2 1/4
LG
Perforated sheet grille- Design - Individually adjustable air deflection blades (-LE)
- Blockwise adjustable air deflection blades (-LB)
With blockwise adjustable blades, 5 blades can be adjusted si-
multaneously.
The adjusting angle of the air deflection blades must not be
more than ± 45°, in order to guarantee its function.
DISA-...-SR DISA-...-SQ DISA-...-RE DISA-...-OB
DISA-360-...-592-...-V-AS4
DISA-360-...-1192-...-V-AS5/6
Lp [dB(A)]
DISA-360-…-B DISA-360-...-C DISA-360-…-D DISA-360-…-E
L PS
1 x Ø123
2 x Ø123
1 x Ø123
2 x Ø123
1 x Ø123
2 x Ø123
1 x Ø123
2 x Ø123
(mm) (Pa)
1 x Ø98
2 x Ø98
1 x Ø98
2 x Ø98
1 x Ø98
2 x Ø98
1 x Ø98
2 x Ø98
50 15 15 15 15 15 15 15 15 23 16 15 15 31 26 23 19
75 15 15 15 15 18 15 15 15 28 22 21 16 36 31 27 23
600x600
100 15 15 15 15 22 19 15 15 32 27 25 19 39 35 30 26
125 19 16 15 15 25 23 18 15 35 30 28 22 42 38 33 29
150 21 19 16 15 28 25 21 18 37 33 30 24 44 41 35 31
175 24 21 18 17 30 28 23 20 39 35 32 26 45 43 36 33
50 15 15 15 15 26 18 15 15 37 29 26 19 45 39 36 28
75 15 15 15 15 31 23 21 20 42 34 32 25 50 44 42 34
600x1200
100 20 17 15 15 34 27 26 24 45 38 36 30 54 47 46 38
125 23 20 18 18 37 30 29 27 48 41 39 33 57 50 49 41
150 26 23 21 21 39 33 32 30 50 43 42 36 59 52 52 44
175 28 25 24 24 41 35 35 32 52 45 44 38 61 54 54 46
LP[dB (A)] <= 15 display 15
xkr (m)
x (m)
y (m)
vmax
xW (m)
xkr (m)
x (m)
y (m)
vmax
xW (m)
xkr (m)
x (m)
y (m)
vmax
xW (m)
xkr (m)
x (m)
y (m)
vmax
xW (m)
Valve data:
Numbers Valve
kvs
stroke
(m3/h)
(mm)
0 1.) 0 0
1 0,188 0,25
2 0,375 0,65
3 0,563 0,88
4 0,750 1,12
5 0,938 1,30
6 1,125 1,46
7 1,313 1,57
0 2.) 1,50 1,90
The presetting < 5 is not recommended because of too little stroke res-
olution.
V100 (m3/ = (Register) flow rate with fully opened valve Two revolutions are possible on the presetting ring. The
Δpv100 (kPa) = Consumer pressure loss (register)
values listed in the table (numbers 01)... 02)) define the
first revolution. Another revolution (numbers 02) ... 6) will
increase the stroke to 2.5 mm (completely open), but the
Operation:
kvs values will no longer change after 02) .
If Siemens valves VD115CLC are motorised with actuators
SSA61..., the preset flow rate must be fixed at a valve
AB→A 0...100% stroke of 1.5 mm (factory setting 02). At a valve stroke <
1.5 mm, self-calibration will not be possible, and the actu-
AB→B 70...0%
ator/valve combination will remain blocked.
SSA61: STA73
grey Y Actuator signal DC 0...10 V brown
G
blue AC/DC 24 V
black G0 System zero (-at DC 24 V) G0
Model STA63
SSA81:
- Actuating power 100 N
orange Y2 Actuator signal CLOSED (AC 24 V) - Simple installation
- Standard version including con-
violet Y1 Actuator signal OPEN (AC 24 V)
necting cables of 1 m (2, 5 or 7 m
optional).
red G System potential (AC 24 V)
- 270° visible position indicator
- 3-wire connection
- Voltage AC 24 V, DC 0...10 V posi-
tion signal
Connection diagrams:
Terminals:
Terminals:
SD Switching difference
Q... Relay contact output
Nozzle configuration
-B -C -D -E
Total width
-592 -597 -617 -622
Total length Total length Total length Total length
-592 -1192 -597 -1197 -617 -1242 -622 -1247
with 1 connecting piece with 2 connecting pieces with 1 connecting piece with 2 connecting pieces
-AS1 -AS2/AS3 -AS4 -AS5/AS6
Order example
DISA-360-H-OL-SR-B-592-592-WS1-H-AS1-123
Unless stated otherwise, the thick-frame model will be delivered!