Professional Documents
Culture Documents
ER-UP/G
ER-UPD
ER-UPB
ER 60
ER 100
Centro-M
Centro-E
Centro-H
Table of contents
2
Table of contents
3
Preface
4
1 Scope of delivery
5
3 Safety instructions
WARNING Risk to health from chemicals DANGER Danger of electric shock from
or aggressive gases/vapours. operating the unit when not fully mounted.
Chemicals or aggressive gases/vapours may Electric components are a potential source of
harm health, especially if they are distributed electric shock.
throughout the rooms by the unit. If the unit is open, all off the supply circuits must
Never use unit to distribute chemicals or aggress- be switched off (mains fuse off), secured against
ive gases/vapours. being accidentally switched back on and a visible
warning sign must be attached.
NOTICE Damage to unit due to grease and oil
Only operate the unit when it is completely in-
vapours from range hoods.
stalled.
Grease and oil vapours from range hoods may
contaminate the unit and air ducts and reduce ef-
DANGER Danger if the relevant regula-
ficiency.
tions for electrical installations are not ob-
Never use unit to convey these substances.
served.
NOTICE Damage to the unit when continu- Before removing the housing cover or removing
ously conveying steam-saturated air. the fan insert and before installing the electrics,
Never use unit to convey steam-saturated air switch off all supply circuits, switch of mains fuse
and secure it against being accidentally switched
NOTICE Damage to the unit due to imbalance
back on again. Attach a warning sign in a clearly
of the impeller when conveying solid
visible place.
particles.
Be sure to observe the relevant regulations for
Never use unit to convey solid particles that could
electrical installation; e.g. DIN EN 50110-1. In
adhere to the unit.
Germany, particularly observe VDE 0100, with
NOTICE Unit damage during the construction the corresponding sections.
phase, caused by soiling of the unit and air A mains isolation device with contact openings of
ducts. at least 3 mm at each pole is mandatory.
Unit operation is not permitted during the con- Only connect unit to permanently wired electrical
struction phase. installation and with NYM-O or NYM-J cables,
Do not operate unit during the construction depending on the unit variant, 3 x 1.5 mm² or 5 x
phase. 1.5 mm².
Units may only be operated using the voltage and
NOTICE Damage to unit in the event of mois- frequency shown on the rating plate.
ture ingress. Unit may be energized even when at a standstill
IP X5 (protection against water jets). and may switch on automatically due to sensors
Never use unit outdoors. (time delay, humidity etc.). Maintenance and fault
finding only permissible when carried out by qual-
3.2 Safety instructions regarding in- ified electricians.
stallation, operation, cleaning and The degree of protection stated on the rating
plate is only guaranteed if installation is under-
maintenance taken correctly and if the connecting cable is cor-
DANGER Risks for children and people rectly guided through the stepped grommet (The
with reduced physical, sensory or mental cap- grommet must completely enclose the cable
abilities or a lack of knowledge. sheathing). The fan insert must also be engaged
Unit may only be installed, commissioned, and the housing cover installed.
cleaned and maintained by persons who can
safely recognise and avoid the risks associated
with this work.
6
3 Safety instructions
DANGER Danger due to fire transmission WARNING Risk of injury when working at
if an incorrect connection duct is connected to the heights.
ER housing. Always use the correct duct material Use appropriate climbing aids (ladders).
for the respective ER housing. Stability should be ensured, if necessary have
if incorrect ceiling compound is used for exhaust the ladders steadied by a 2nd person.
air systems with an intermediate ceiling (PAM- Ensure that you are standing securely and can-
GLOBAL RML or ceiling barrier system). Ensure not lose your balance and that there is no one
that the gap remaining between the main duct under the unit.
and wall or ceiling is fully sealed with non-flam-
mable materials resistant to deformation, such as WARNING Risk of injury and risk to
concrete, cement mortar or plaster. health from parts which may affect the ventil-
if the seal with the brickwork or wall boards is in- ation system which are added or modified at a
correct. If used outside the shaft, ensure that the later date.
gap remaining between the connection duct and Parts (range hood, air-ventilated fireplace etc.)
brickwork/wall boards is fully sealed with non- which are added or modified at a later date may
flammable materials resistant to deformation, result in health risks and operation which is not
such as concrete, cement mortar or plaster and permitted. Parts may only be added or modified
for the wall boards, special fire protection filler. at a later date if system compatibility is estab-
if the metal exhaust socket is incorrectly connec- lished/ensured by a planning office. If using an
ted to the connection duct. 3 steel blind rivets are exhaust air range hood or air-ventilated fireplace,
prescribed for the connection with the exhaust this must be accepted by a regional master chim-
socket. These must not impair the shutter func- ney sweep.
tion. Before commissioning, ensure that the shut-
off shutter moves with ease. WARNING Risk of injury and health risk
if the metal shut-off shutter is not correctly inser- in the event of changes or modifications or if
ted and screwed down in the exhaust socket. components which are not permitted are
During installation, it is essential that the shut-off used.
shutter is correctly positioned and screwed down. The unit may only be operated with original com-
The soldered strut must be correctly inserted and ponents. Changes and modifications to the units
the shutter must move with ease. are not permitted and release the manufacturer
from any guarantee obligations and liability, e. g.
DANGER Risk of injury in case of dam- if the housing is drilled at a point which is not
aged unit. permitted.
Switch the unit off immediately if you discover
damage or faults that could endanger persons or CAUTION Risk to health if unit is not cor-
property. rectly cleaned.
Prevent from being switched back on until fully Clean the unit regularly, at least every 2 years.
repaired. This is the only way of ensuring that the unit is
running hygienically.
WARNING Risk to health if filters are not
replaced or if there are no air filters. CAUTION Exercise caution when hand-
Heavily soiled or moist air filters can accumulate ling packaging materials.
harmful substances (mould, germs, etc.). This Observe applicable safety and accident preven-
may also happen if the unit is shut down for an tion requirements.
extended period. If the air filter is missing, the Store packaging material out of the reach of chil-
unit and air ducts become soiled. dren (risk of suffocation).
Never operate the unit without air filters.
Only use original filters.
Regularly change air filter when a filter change is
indicated (LED or TimeStrip).
If the unit has not been used for a long time, al-
ways replace the air filters.
7
4 System and product information
8
4 System and product information
9
4 System and product information
The switching variants and functions suited to the Unit Circuit Start Over- speed Mains
circuit board type are described in these instruc- type board delay run con- cable
tions. Tolerance of all time details max. + 20 %. type [s] time trol- [mm”]
• Standard model [min] lable
• VZ model: with start delay and overrun time. ER 60 Stand- no 3 x 1.5
• VZ 15 model with start delay and overrun time. ard
board
• VZC model with adjustable start delay and ad-
justable overrun time. ER Stand- yes 3 x 1.5
• F model: Barrier-free. With light control for 100 ard
rooms without windows (min. switch-on bright- board
ness 30 lx, max. switch-off brightness on unit ER 60 VZ cir- 50 6 no 5 x 1.5
0.3 lx). With start delay (50 sec.) and overrun VZ, ER cuit
time (6 min.). 100 VZ board
• G model: With base load circuit. Continuous ER 60 VZ 15 50 15 no 5 x 1.5
operation at 35 m³/h, high speed (full load) can VZ 15, board
be switched with optional switch. ER
• GVZ model with base load circuit, start delay 100 VZ
and overrun time, continuous operation at 15
35 m³/h, high speed (full load) can be switched ER 60 VZ 24 0…150 1.5… no 5 x 1.5
with optional switch. VZC, C 24
• I model with interval control. For manual opera- ER board
tion with start delay and overrun time. Operat- 100
ing period can be set to between 0 and 15 VZC
hours with intervals of around 10 minutes. Inter- ER 60 F cir- 50 6 no 3 x 1.5
val control off if 0 hours is set (Ti setting screw F, ER cuit
in far left position). Interval control active if Ti 100 F board
setting screw is turned at least 1/4 of a turn to
ER 60 G no 5 x 1.5
the right from the far left position.
G, ER board
• H model: Barrier-free. With humidity control. 100 G
Overrun time controlled by program (min. 15
ER 60 G no 5 x 1.5
minutes at full load). Can also be operated
GVZ, board
manually with optional switch. Not suitable for
ER + VZ
second room ventilation.
100 board
• D model: In combination with three-step switch GVZ
with 3 power levels: 35, 60 or 100 m³/h. Can be
used in combination with supply air elements ER 60 VZI 10 50* 10* no 5 x 1.5
for controlled domestic ventilation. I, ER board
100 I
• RC model with radio electronics: Use in radio-
controlled ventilation system MAICO smart. ER 60 H 15 no 5 x 1.5
Based on EnOcean technology. Network-com- H, ER board
patible (master-slave) → separate ER 100 RC 100 H
operating instructions. On/Off using radio switch ER Stand- no 5 x 1.5
or radio control RLS RC. With 3 power levels 100 D ard
35, 60 or 100 m³/h. board
ER RC cir- 15** no 3 x 1.5
100 cuit
RC board
Tolerance of all time details max. + 20 %.
W factory setting
* Start delay and overrun time for manual opera-
tion, e.g. using light switch
10
5 Technical data
** Overrun time only if unit is used with single The unit may only be installed in residential units
switch, without room air control RLS RC. with air-ventilated fireplaces under the following
conditions:
5 Technical data • the evaluation criteria drawn up by the respons-
ible, regional master chimney sweep are met;
5.1 Environmental conditions and op-
• Parallel operation of air-ventilated fireplaces for
erating limits liquid or gaseous fuels and air-extracting equip-
• Permissible maximum temperature of air me- ment can be prevented using safety devices or
dium + 40 °C. • the extraction of exhaust gas from the air-ventil-
• The air supply to the home must be set up so ated fireplaces is monitored by special safety
that virtually no air can flow into the living areas devices. The ventilation system or the fire-
from the kitchen, bathroom or WC. places must be switched off if the equipment is
• A room from which the air is to be extracted triggered.
must be fitted with a non-closable, free supply
air cross section of at least 150 cm², e.g. with 5.3 Technical data table
Maico MLK door ventilation grille. Sound pressure level 30 to 49 dB(A), depend-
• ER-UP/Centro units have resistance to interfer- LWA7 ing on unit model
ence in line with EN 55014-2 (depending on
For more technical data → rating plate.
pulse type and an energy component of 1000 to
4000 V). These values can be exceeded when Für Kennlinien → www.maico-ventilatoren.com
operating with fluorescent tubes. In this case,
additional interference suppression measures 5.4 Storage
(L, C or RC modules, protection diodes, varis- Only store unit horizontally in a suitable, dry
tors) are required. room. Ambient temperature – 10 °C to + 60 °C.
• Take the risk of draughts into account when Maico accepts no liability for corrosion damage
planning by selecting a suitable installation loc- caused by improper storage, e.g. storage in a
ation. damp environment.
11
6 Mounting preparations
12
6 Mounting preparations
9 Suction duct for second room connection on non-flammable materials that are resistant to
ER-UP/G: Flexible aluminium duct AFR 75/ deformation (e.g. concrete, cement mortar, fire
AFR 80 protection filler).
ER-UPD: Flexible aluminium duct AFR 75/ NOTICE Damage to unit, malfunctioning in the
AFR 80 event of corrosion damage from mortar.
or steel folded spiral-seams duct DN75/DN80 Wrap ventilation ducts, connected to the unit,
ER-UPB: Steel folded spiral-seams duct with a suitable adhesive tape to protect against
DN75/DN80 corrosion inside the brickwork, e.g. using cold-
18 Main duct: Steel folded spiral-seams duct shrink tape.
19 Connection duct on Preparing the shaft
ER-UP/G: Flexible aluminium duct AFR 75/
1. Produce opening in shaft or alternatively pro-
AFR 80
duce a wall facing. Ensure a suitable, flat sur-
ER-UPD: Steel folded spiral-seams duct
face for the housing so that the fan insert can
DN75/DN80
be safely inserted in the housing later on.
ER-UPB: Flexible aluminium duct AFR 75/
AFR 80, 2. For a second room connection, produce an
permitted inside the shaft opening in the wall or shaft for the suction
duct. Note permissible housing installation po-
21 Power cable
sitions.
Installation information 3. Correctly attach main duct inside the shaft.
• Observe approval: Certificates of approval [} 8] 4. For fire protection systems, use ceiling com-
and Requirements in line with approval [} 11]. pound. To do this, encase the ceiling and pour
• Always use correct duct material for the hous- in the material from above.
ing. 5. Connect connection duct, suitable for the
• For fire protection systems, the gap remaining housing, to the main duct and seal for ventila-
between the connection duct and brickwork/wall tion.
boards/wall/ceiling must be fully sealed with
13
6 Mounting preparations
6. Cut connection duct to length, note a max- 8. Lay power cable in shaft and allow to protrude
imum duct length of 2 m. by around 30 cm above the shaft opening.
Cut connection duct to a length which al- 9. In the ceiling area, fit a spigot made from shaft
material F90 around the shaft.
lows it to be fitted on the exhaust socket
and also sealed for ventilation at the unit The spigot compensates for the length of
end. the shaft walls in the event of a fire.
7. Lay suction duct and seal gap remaining cor- 10.Lay power cable: Provide unit with electrical
rectly as described in previous installtion in- connection.
structions.
6.3 Ceiling installation preparations
9 Suction duct for second room connection on Be sure to note the approval and installa-
ER-UP/G: Flexible aluminium duct AFR 75/ tion information: Preparations for wall installa-
AFR 80 tion.
ER-UPD: Flexible aluminium duct AFR 75/
AFR 80 Preparing the shaft and suspended ceiling
or steel folded spiral-seams duct DN75/DN80 1. Make an opening in the suspended ceiling.
ER-UPB: Steel folded spiral-seams duct 2. Make an opening in the shaft for DN 75 or DN
DN75/DN80 80 connection duct.
18 Main duct: Steel folded spiral-seams duct 3. For a second room connection, produce the
opening in the wall or shaft for the suction
19 Connection duct on
duct. Observe installation positions for the
ER-UP/G: Flexible aluminium duct AFR 75/
second room connection.
AFR 80
ER-UPD: Steel folded spiral-seams duct
DN75/DN80
ER-UPB: Steel folded spiral-seams duct
DN75/DN80
20 Power cable
14
6 Mounting preparations
18 Main duct (steel folded spiral-seams Duct attachment with duct clamp, alternatively
duct) duct attachment with clamping band
19 ER GH connection duct: Flexible alu-
minium duct
21 Floor ceiling
22 Steel threaded rod / stair bolt
23 Duct attachment
24 Duct clamp / clamping band
25 Spigot
26 Ceiling compound
27 Shaft wall
28 Wall/board seal
29 Suspended ceiling
30 Steel screws or steel blind rivets (3 of
each) Ensure a spacing of max. 1.5 m between the
duct attachments.
31 Dowel
1. Correctly attach main duct inside the shaft.
31.1 Steel dowel or anchor bolt
2. For fire protection systems, use ceiling com-
31.2 Metal expansion dowel pound. To do this, encase the ceiling and pour
32 Retaining bolt with nut in the material from above.
33 Retaining bolt 3. Fit duct attachments to the ceiling. Only use
34 Steel clamping band permitted mounting material.
Be sure to note the approval and installa-
tion information: Preparations for wall installa-
tion.
15
6 Mounting preparations
16
7 Housing installation
If installing on the wall with air outlet direc- 3 Metal shut-off shutter with release mechan-
tion (exhaust socket) to the left or right, note ism and yoke spring [3.1]
the following. Install shutter turned 90° (Pos. 4 Soldered strut
[L] or [R]) so it closes fully sealed in the install- 5 Metal exhaust socket
ation position. * Shown without fire protection board
Preparing the plastic shutter for wall installa- NOTICE The fire protection shut-off device is
tion permanently closed if there is no soldered
Upwards air outlet direction "O" strut.
Do not carry out any modifications. The shutter is Air extraction is then no longer possible.
fitted correctly ex-factory. Check that the soldered strut is inserted correctly
before installation. The functionality of the re-
Air outlet direction to the right "R"
lease mechanism must be ensured so that the
1. Remove plastic backflow preventer. Simply shut-off shutter also opens in normal operation.
pull this down and out of the exhaust socket.
NOTICE Unpleasant smells from the main
2. Turn backflow preventer, pos. [R]. duct.
3. Insert backflow preventer in exhaust socket The fire protection shut-off device does not close
until stop is reached. fully sealed if incorrectly installed.
Air outlet direction to the left "L" Before installation, check and ensure that the in-
4. Remove plastic backflow preventer. Simply stallation position is correct and the release
pull this down and out of the exhaust socket. mechanism is fully functional.
5. Turn backflow preventer, pos. [L]. Preparing the metal shut-off device with up-
6. Insert backflow preventer in exhaust socket wards air outlet direction
until stop is reached. 1. Remove the fitted yoke spring. To do this, use
Preparing the plastic shutter for ceiling install- pliers to pull yoke spring out of exhaust socket
from above.
ation
As a rule use the standard installation position 2. Check and ensure that shut-off shutter is fully
with upwards air outlet direction "O" for ceiling in- functional.
stallation. The shutter is fitted correctly ex-factory. Preparing the metal shut-off device with air
6.5.2 Fire protection shut-off device - ER-UPD outlet direction to the right or left
and ER-UPB housing No modifications needed.
1. Check and ensure that shut-off shutter is fully
functional.
7 Housing installation
7.1 Installing ER-UP/G housing
The following are not permitted:
• Second room connection with an ER 60 fan in-
sert (all models).
• Second room connection in combination with
Centro exhaust air elements.
• Connecting a WC odour extraction unit in com-
bination with Centro exhaust elements.
• Use of an ER fan or Centro exhaust air element
in the bathroom or toilet room, if other rooms in
the apartment are to be vented with the same
unit at the same time.
17
7 Housing installation
7.2 Installation information for ER- The toilet seat air extraction unit must not
be connected to the second room connection
UP/ G housing
socket or the Centro exhaust air element.
(also Requirements in line with approval [} 11]
Use ER-MO expanded rubber for acoustic insula-
and approval) tion of thin ceilings capable of resonance (System
ER-UP/G are equipped with a plastic housing and accessory components).
without fire protection equipment. The ER-UP/G
housing may be installed in the following installa- 7.3 Important information about
tion positions:
plastering
• Wall installation With air outlet direction (ex-
haust socket) upwards, to the right, to the left or • Max. compensable plaster overshoot 7 mm.
to the rear. Installation with mounting support. • Max. protruding housing edge 20 mm, can be
• Ceiling installation and suspended ceiling: compensated for with spacing frame DR
Installation with mounting support. 60/100.
• Ceiling installation and non-suspended ceil- • Installation at a depth of 50 to 100 mm can be
ing: Mounting directly on the ceiling. compensated for with the two-part wall frame
ER-MR.
Suitable mounting material is to be provided by
the customer. • The gap remaining between the housing and
shaft must be fully sealed with non-flammable
The plastic shutter should be prepared ac-
materials that are resistant to deformation so
cording to these instructions so that it closes
that incorrect air is not drawn in.
fully sealed in the installation position.
The housing must be inserted without any dis- • Joints between the housing and wall can be
tortion. Failure to do so will mean that the fan in- covered with cover frame ER-AR.
sert cannot engage correctly in the housing and We recommend keeping these installation
the degree of protection stated on the rating plate and operating instructions until final installa-
is no longer ensured. tion in the housing.
Break open the housing segment [S] below to use
the ER-ZR second room connection set or the 7.4 ER-UP/G wall installation, single
ER-AS extraction socket. room
A toilet seat air extraction unit is connected to the
housing using the ER-AS extraction socket
(DN 75/80).
18
7 Housing installation
2. Cut the mounting support to the required 6. Connect connection duct to exhaust socket
length, bend it into shape and fix it to the sealed for ventilation, e.g. with cold-shrink
housing with the supplied fixing screws. tape.
3. Mark fixing holes for mounting support on rear 7. Provide unit with electrical connection: Elec-
shaft wall, produce holes and insert dowels. trically connecting the unit.
Suitable mounting material is to be provided 8. Insert the plaster protective cover in the hous-
by the customer. ing.
19
7 Housing installation
9. Plaster in housing flush with front edge, note 7.5 ER-UP/G ceiling installation,
tile thickness if necessary: Important informa-
tion about plastering. single room
20
7 Housing installation
6. Connect connection duct to exhaust socket 8. Insert the plaster protective cover in the hous-
sealed for ventilation, e.g. with cold-shrink ing.
tape. 9. Plaster in housing flush with front edge.
7. Provide unit with electrical connection: Elec-
trically connecting the unit. 7.6 ER-UP/G wall installation, second
room
21
7 Housing installation
22
7 Housing installation
23
7 Housing installation
9. Plaster in housing flush with front edge, note 7.12 ER-UP/D installation, second
tile thickness if necessary: Important informa-
tion about plastering. room
24
7 Housing installation
• Second room connection in combination with A second room connection is only permitted with
Centro exhaust air elements. ER-UPB/R, ER-UPB/L or ER-UPB/U.
• Connecting a WC odour extraction unit in com-
bination with Centro exhaust elements. 7.15 Important information about
• Use of an ER fan or Centro exhaust air element plastering
in the bathroom or toilet room, if other rooms in
the apartment are to be vented with the same DANGER Fire may spread if ER-UPB
unit at the same time. housing is incorrectly installed.
Any gap remaining between the housing and
7.14 Installation information for ER- shaft/tiles must be fully sealed with non-flam-
mable materials resistant to deformation.
UPB housing
• Minimum overlap required for the ventilation
(also Requirements in line with approval [} 11]
shaft (without tiles, etc.) in the area of the con-
and approval)
nection duct 10 mm.
ER-UPB are equipped with fire protection cover
• Max. compensable plaster overshoot 7 mm.
and metal shut-off shutter with release mechan-
ism. • Max. protruding housing edge 20 mm, can be
Wall installation is described below. Ceiling in- compensated for with spacing frame DR
stallation should be undertaken following the de- 60/100.
scription for wall installation. • Installation at a depth of 50 to 100 mm can be
Housings can be installed with an air outlet direc- compensated for with the two-part wall frame
tion (exhaust socket) upwards, to the right or left. ER-MR.
With an upwards air outlet direction, the yoke • The gap remaining between the housing and
spring should be removed from the shut-off shaft must be fully sealed with non-flammable
device. materials that are resistant to deformation so
Suitable mounting material is to be provided by that incorrect air is not drawn in.
the customer. To screw down the connection duct • Joints between the housing and wall can be
use steel screws, if screwing into brickwork/con- covered with cover frame ER-AR.
crete use steel dowels. We recommend keeping these installation
The metal shut-off device should be pre- and operating instructions until final installa-
pared according to these instructions. tion in the housing.
25
7 Housing installation
26
7 Housing installation
27
8 Electrical connection
5.1 Steel connection socket DN 75/80 for 3. Produce fixing holes for adapter and insert
second room extraction on ER-UPB dowels.
6 Protective grille 4. Connect adapter fully sealed to suction duct,
e.g. with cold-shrink tape.
7 Filter mat filter class G2
5. Secure adapter to the wall with screws.
8 Adapter
6. Insert filter mat and fit protective grille in the
9 9 Suction duct, second room connection:
correct position.
Steel folded spiral-seams duct DN 75/80
With second room extraction, keep regulat-
1. Install housing as described in these instruc-
ing plate somewhere safe for the final installa-
tions.
tion. This is needed to operate the ER 100 fan
2. Secure suction duct and steel socket with 3
insert and is inserted in the cover.
steel blind rivets or steel screws and connect
sealed for ventilation. 8 Electrical connection
28
9 Installation of fan insert and cover
29
9 Installation of fan insert and cover
11 Fan insert The ER fan insert / the Centro exhaust air ele-
ment is inserted into the flush-mounted housing
12 Electronic circuit board (control)
as follows.
13 Housing floor seal
1. Switch off mains fuse, secure and fit warning
38 Plaster protective cover sign.
42 Connection terminal 2. Remove plaster protective cover and clean
43 Optional fixing with screws (to be provided any dirt off the flush-mounted housing.
by the customer) 3. Ensure that the fan type ticked in the housing
44 Locking lever box matches the type to be fitted.
45 Stud 4. Check ease of movement of shut-off shutter/
backflow preventer.
30
9 Installation of fan insert and cover
31
10 Commissioning
7. Affix time strip (supplied with the cover) and Control model RC
push the activation button [A] all the way. In- Radio-controlled fan system with up to 3 ER 100
stallation location of time strip, e.g. near the RC fans. These are switched on and off via a ra-
cover. dio switch, room air control RLS RC or radio win-
dow contacts.
If the fan is switched on and off manually,
The red dye in the interior of the function in accordance with DIN 18017-3 is
bar [B] is released. The not always ensured.
bar indicator first fills
slightly. Within the In the event of thermal overload, the unit
next 6 months, the bar switches off automatically. Wait until the mo-
indicator [B] will rise to the
upper edge (indicator value 6). tor has cooled down. Cool-down time may be
up to 10 minutes. The unit switches back on
automatically after cooling down.
32
12 Cleaning, maintenance
33
13 ER-AS extraction socket for WC odour extraction
13 ER-AS extraction socket for NOTICE Damage to unit in the event of im-
proper installation position of the housing
WC odour extraction floor seal.
Degree of protection is not guaranteed.
Lift up the housing floor seal before inserting the
ER-AS extraction socket and then reposition it
correctly afterwards.
3. Install ER-UP/G or ER-UPD housing unit in
accordance with these instructions. Note the
descriptions relating to the second room con-
nection.
4. Connect connection duct to ER-AS extraction
socket and branch in the concealed cistern.
Make sure the connections between the con-
nection duct and the extraction socket and the
branch are tight.
5. Install fan insert and cover.
It is important that regulating plate and fil-
ter mat supplied with the ER-AS are inser-
ted. The cover must engage audibly when
locking.
6. Run function test.
14 Fault rectification
Fault finding and repairs only permissible
when carried out by qualified electricians.
34
15 Spare parts
35
16 Removal
36
18 Wiring diagrams
Standard switching:
The fan starts up approximately 50 seconds after
the room lighting is switched on. The fan has an
overrun time of approximately 6 minutes after
switching off. With VZ 15 units, the overrun time
is approximately 15 minutes.
Switching option
The fan starts up approx. 50 seconds after
switching on the room lighting (with switch S1 and
The fan starts up after switching on the room S2).
lighting (with switch S1). The fan also switches off
The fan has an overrun time of approximately 6
after the room lighting has been turned off.
minutes after switching off with switch S1. With
ER 100 with Main and Second room connec- VZ 15 units, the overrun time is approximately 15
tion minutes. In addition, the fan can be switched off
The fan starts up after switching on the room with switch S2 independent of the room lighting.
lighting (with switch S1). The fan also switches off ER 60 VZC, ER 100 VZC
after the room lighting has been turned off. The fan starts up after a start delay when the
ER 60 VZ, ER 60 VZ 15, ER 100 VZ, ER 100 VZ room lighting is switched on. This can be adjusted
15 continuously from 0 - 150 seconds. Depending on
the setting, the fan has an overrun time of
between 1.5 and 24 minutes after switching off.
The overrun time can be adjusted continuously
from 1.5 to 24 minutes.
ER 100 VZ and ER 100 VZ 15 with main and
second room connection
The fan starts up approx. 50 seconds after
switching on the room lighting (with a switch). The
fan has an overrun time of approximately 6
minutes after switching off with the last switch to
have been used. With VZ 15 units, the overrun
time is approximately 15 minutes.
37
18 Wiring diagrams
38
18 Wiring diagrams
The fan is running in base load operation. Humid- The fan is switched manually to base load with
ity control is active, see Standard Switching. switch “S1”. Humidity control is active, see Stand-
Switch "S1" is used to switch manually to full load ard Switching. If, after being manually switched
operation. After switching full load operation off with switch "S1", the fan is in:
with "S1", the fan continues in full load operation
• full load operation, i.e. humidity is present, the
for an overrun time of 6 minutes. If after this time,
fan continues to run until the humidity drops be-
the humidity as measured at the fan:
low the switch-off point. Only then does the fan
• is higher than the switch-off point, the fan con- switch off automatically.
tinues to run in full load operation until the hu-
• base load operation, the fan switches itself off
midity drops below the switch-off point. Only
automatically.
then does the fan switch automatically back to
base load operation. If switch S1 is open, the fan can start up automat-
ically as a result of high room humidity.
• is lower than the switch-off point, the fan imme-
Switching option 3: Manual full load operation
diately switches automatically back to base load
with pre-defined overrun time.
operation.
Switching option 2: Manual base load opera-
tion
39
18 Wiring diagrams
ER 60 G, ER 100 G
Standard switching:
Fan always runs at base load. When the room is
in use (S1=On), the fan switches automatically to
full load after approx. 50 seconds.
Switching option
40
18 Wiring diagrams
41
Maico Elektroapparate-Fabrik GmbH
Steinbeisstr. 20
78056 Villingen-Schwenningen
Deutschland
Service +49 7720 6940
info@maico.de
D07.21_EN_DSW-AV