Professional Documents
Culture Documents
A three-phase fault is a symmetrical fault. The other three fault types (line to ground,
line to line, and two- line to ground) are called unsymmetrical or asymmetrical faults.
Because symmetrical faults result in balanced conditions, they may be analyzed using
per-phase analysis.
Unsymmetrical Faults
three conductors fall on the ground or come in with the neutral conductor. It is
a symmetrical fault
phase of the system. This fault mainly occurs among the 3-phases as well as the
fault.
Province of Laguna
According to Electrical4U, Three line of the conductor short with each other.
According to Elprocus, These kinds of faults are balanced which means the system
remains balanced after the fault occurs. So this fault rarely occurs, although it is the
harsh kind of fault that holds the largest current. So this current is used to determine
Province of Laguna
Unsymmetrical Fault
Unsymmetrical faults are normal fault which means the three phase lines
phase system.) and they do not have the equal phase displacement each other’s.
The unbalance load occurs due to the presence of the short circuit or open
natural disturbances are heavy wind speed, ice loading on the lines, lightening
Province of Laguna
In single line-to-ground fault, one conductor comes in contact with the ground or the
neutral conductor. Single line to ground fault is the most frequently occurring fault (60
to 75% of occurrence)
According Elprocus, This single L – G fault mainly occurs once a single conductor falls
toward the ground terminal. So around 70 to 80 % of the fault within the power
Province of Laguna
A line-to-line fault occurs when two conductors are short circuited. This type of
This L– L fault mainly occurs once two conductors are short-circuited and also
due to heavy wind. So the line conductors can be moved because of heavy wind,
they may touch with each other and causes short-circuit. So, 15 – 20% of the
faults can occur approximately.
Province of Laguna
A double line-to-ground fault occurs when two conductors fall on the ground or
come in contact with the neutral conductor. This type of fault occurrence
In this kind of fault, both the two lines get in touch with each other through the
Province of Laguna
otherwise more conductors used in the power system. The open-circuit faults
diagram is shown below. This circuit is for 1-phase, 2- phases, and 3-phases
open condition.
chance or purposely.
Fuse
used instead because they are not destroyed during overload conditions.
Circuit Breaker
circuit from damage caused by an overcurrent or short circuit. Its basic function
is to interrupt current flow to protect equipment and to prevent the risk of fire
PROTECTIVE RELAYS
Types of
Protective Relays
The protective relay is the device that responds to signals from the transducers
possible.
A relay is said to pick up when it operates to open its normally closed (NC)
to produce a desired control action. The smallest value of the actuating quantity
normally closed (NC) or to open a closed contact that is normally open (NO).
The largest value of the actuating quantity for this to happen is called the reset
value.
During study of electrical protective relays, some special terms are frequently
used. For proper understanding, the functions of different protective relays, the
2. Current setting.
In all electrical relays, the moving contacts are not free to move. All the contacts
continuously. This force is called the controlling force of the relay. This controlling
force may be the gravitational force, may be a spring force, or may be a magnetic force.
The force applied to the relay’s moving parts for changing the normal position
Province of Laguna
of the contacts is called deflecting force. This deflecting force is always in opposition of
controlling force and is present always in the relay. Although the deflecting force is
always present in the relay directly connected to live line, as the magnitude of this
force is less than controlling force in normal condition, the relay does not operate. If
the actuating current in the relay coil increases gradually, the deflecting force in
electromechanical relay is also increased. Once, the deflecting force crosses the
controlling force, the moving parts of the relay initiate to move to change the position
of the contacts in the relay. The current for which the relay initiates its operation is
The minimum pick up value of the deflecting force of an electrical relay is constant.
The deflecting force of the coil is proportional to its number of turns and the current
Now, if we can change the number of active turns of any coil, the required
current to reach at minimum pick value of the deflecting force, in the coil also changes.
That means if active turns of the relay coil are reduced, then proportionately more
current is required to produce desired relay actuating force. Similarly, if active turns of
the relay coil are increased, then proportionately reduced current is required to
Practically same model relays may be used in different systems. As per these system
requirements, the pickup current of the relay is adjusted. This is known as the current
setting of the relay. This is achieved by providing the required number of tapping in
the coil. These taps are brought out to a plug bridge. The number of active turns in the
For example, suppose, you want that, an over current relay should operate
when the system current just crosses 125% of rated current. If the relay is rated
with 1A, the normal pick up current of the relay is 1A and it should be equal to
Then, the relay will be operated when the current of CT secondary becomes
Province of Laguna
As per definition,
setting is 150%.
The operating time of an electrical relay mainly depends upon two factors :
1. How long distance to be traveled by the moving parts of the relay for closing
2. How fast the moving parts of the relay cover this distance.
So far by adjusting relay operating time, both of the factors to be adjusted. The
multiplier of relay. The time setting dial is calibrated from 0 to 1 in steps of 0.05
sec.
By adjusting only time setting multiplier, we cannot set the actual time of
depends upon the speed of operation. The speed of moving parts of relay
depends upon the force due to the current in the relay coil. Hence, it is clear
that the speed of operation of an electrical relay depends upon the level of fault
current. In other words, the time of operation of the relay depends upon plug
setting multiplier. The relation between time of operation and plug setting
From this graph one can determine the total time taken by the moving parts of
PSM. In time setting multiplier, this total traveling distance is divided and
When the time setting is 0.1, the moving parts of the relay have to travel only
0.1 times of the total traveling distance, to close the contact of the relay. So, if
we get the total operating time of the relay for a particular PSM from time/PSM
graph and if we multiply that time with the time setting multiplier, we will get,
Province of Laguna
the actual time of operation of the relay for said PSM and TSM.
For calculating actual relay operating time, we need to know these following
operations.
1. Current setting.
5. Time setting
Overcurrent Relays
operate when the actuating quantity equals, or exceeds, its pickup value. An overcurrent
relay can be either of two types: instantaneous or time-delay type. Both relay types are
frequently provided in one relay case and are actuated by the same current; however, their
individual pickup values can be adjusted separately. The pickup values may be adjusted
Province of Laguna
Grounding Systems/Components
• Grounding is one of the most important, but least understood, considerations in designing
from wiring and electrical equipment to earth or ground. This connection can be a wire
connection to some other approved ground such as a metal cold-water pipe or metal
reinforcing bar projecting from a concrete foundation or footing. NEC 2002 requires that
two approved grounding methods be used, but warns against the use of metal gas pipe for
grounding.
dangerous or excessive voltages in the system. Under certain conditions, higher than
connected to the system. Proper grounding ensures that these overvoltages are channeled
to earth or ground.
Two Elements In Electrical System Grounding
2. Equipment grounding
- is the grounding of one of the wires of the electrical system, such as the neutral, to limit
with other circuits carrying higher voltages than the grounded circuit. In addition,
Province of Laguna
grounding one of the wires of the system limits maximum voltage to ground under normal
operating conditions. Also, a circuit with a grounded conductor can have an automatic
circuit-opening device installed if a potentially dangerous ground fault should occur on one
Equipment Grounding
- is the permanent and continuous bonding together of all metal parts of equipment
enclosures such as conduit, boxes, cabinets, motor frames, and lighting fixtures that are
not intended to carry current and their connection to a system grounding electrode. The
ISO 9001:2015 Certified
Province of Laguna
current flow while permitting enough current to flow to blow the fuses or open the circuit
breakers protecting the circuit. This permits the installation of GFCI circuits which open
automatically in the presence of a ground fault. They prevent the accidental conduction of
voltages by metal enclosures, which can present a possibly fatal shock hazard to personnel
Generally, all or any of the electrodes listed below, if they are available on the
• Concrete-encased electrode
• Plate electrodes
Metal cold-water pipe
The cold-water pipe is now considered the least acceptable electrode, and is the only one
that may never be used by itself as the sole electrode. It must always be supplemented by
at least one “additional” grounding electrode. Any one of the other electrodes listed below
Province of Laguna
- provided the frame is effectively grounded (embedded in earth and /or buried in concrete
if it is effectively grounded).
Concrete-encased electrode
- within and near the bottom of a concrete foundation or footing in direct contact with the
earth. The electrode must consist of at least 20 ft of one or more steel reinforcing bars or
rods of not less than 1 2-in. diameter, or at least 20 ft of bare copper conductor not
- 20 ft of bare No. 2 or larger copper conductor. (It is expected that the conductor will have
Province of Laguna
Plate electrodes - with surface areas of at least 2 ft2 made of iron or steel plates at least 1
4 in. thick. Electrodes of nonferrous metal at least 0.06 in. thick are also approved.
ISO 9001:2015 Certified
Province of Laguna
Ground Fault
SURGE ARRESTER
impulses and switching impulses. Electrical surge produces a large transient over voltage in
the electrical network and system. The shape of the transient over voltage has a steeply
rising front with slowly decaying tail as shown in the figure below. This steep voltage wave
travels through the electrical network and causes over voltage stresses on all the electrical
That is why all electrical equipment and insulators of power system must be
protected against electrical surges. The method of protecting system from surge is
Province of Laguna
The main equipment commonly used for this purpose is lightning arrester or surge
arrester.
There are two types of surges one comes externally from atmosphere such as atmospheric
lightning. Second type is originated from electrical system itself, such as switching surges.
When an electrically charged cloud comes nearby an electrical transmission line, the cloud
induces electrical charges in the line. When the charged cloud is suddenly discharged,
through lightning, the induced charge in the transmission line is no longer confined static.
It starts travelling and originate dynamic transient over voltage. This transient over voltage
Province of Laguna
line inductance and stray capacitance. This surge voltage travels with speed of light. At the
end of the transmission line, as the surge impedance changes, the surge voltage wave
reflected back. This forward and backward travelling of surge voltage wave continues until
the energy of the surge or impulse is attenuated by line resistance. This phenomenon
causes voltage stress on the transmission system many times greater than normal rated
voltage of the system. Hence, surge protection scheme must be provided to the electrical
power transmission system to make reliable and healthy system. Lightning arrester is one
Lightning Arrester
As we said earlier, that the electrical surge also can be generated from the system itself.
Actually, during switching operation there may be a chance of current chopping. If during
normal operation, if electrical isolator is opened on load. Sudden open circuit is occurred in
the system.
In addition to these, the basic arc-quenching techniques of SF6 circuit breaker and vacuum
circuit breaker may give rise to current chopping and multiple re-ignition sometimes. As we
know that sudden current chopping give rise to the di/dt. [di/dt = rate of change of current
L(di/dt) where L is the inductance of load of system. This voltage is induced across the
opening contacts, and travels towards load and reflects in similar manner of lightning
impulse. Lightning arrestor or surge arrester are provided at the end of the transmission
Generally, oil field electrical power transformer, electrical switchgear, cables, electrical
transmission lines, distribution lines are quite capable for withstanding these switching
impulse voltages, as their insulation level is quite high to withstand these over voltages.
But, generator, electric motor, dry type transformers and electric arc furnaces etc. can not
withstand large switching impulse voltages. As essentially this types of equipment do not
have very high level of insulation. To protect this equipment from surges, lightning arrester
is must.
In electrical sub-station, arresters are mainly used at the entrance of any feeders and also
they are used at both rides of electrical power transformers as transformer is also
In modern era, gap less ZnO or zinc oxide surge arresters are mainly used for surge
Province of Laguna
The Zinc Oxide Lightning Arrester comprises of numbers of solid zinc oxide disc. This discs
are arranged one by one to form a cylindrical stack. The number of zinc oxide discs used
per lightning arrester depends upon the voltage rating of the system. This stack is kept
inside a cylindrical housing of polymer or porcelain. Then the stack is placed inside the
housing and highly pressed by heavy spring load attached to end cap at top. The
equipment connection terminal for line is projected from top cap and connection terminal
arrester is subjected to normal system voltage only. The zinc oxide has highly non-uniform
current voltage (I-V) characteristics. This typical I-V characteristic makes zinc oxide very
suitable for designing gap less zinc oxide lightning arrester for surge protection. The
nonlinear resistance of the block is an inherent bulk property and consists of mainly zinc
oxide (90 to 95%) with relatively small amounts of several additives of other metal oxide (5
to 10%) like alumina, antimony tri-oxide, bismuth oxide, cobalt oxide, zirconium etc. On a
macroscopic scale the additives are almost homogeneously distributed throughout the
arrester blocks. But the microstructures of the metal oxide block represents a network of
series and parallel arrangements of highly doped zinc oxide (ZnO) grains separated by inter
characteristics of individual junctions. The current carrying capacity of the surge arrester
Where, Ir and Vr are the reference current and voltage respectively of the lightning
arrester or surge arrester block. The value of x is 30 to 40 in case of metal oxide block. For
Province of Laguna
current increases linearly, i.e. for increasing system voltage at this range, current is
micro ampere. But beyond a certain voltage level, leakage current voltage level, leakage
current starts increasing very rapidly it is of KA range. The voltage beyond which the
current through the LA becomes such high, is referred as reference voltage and the current
through lightning arrester just beyond reference voltage level, prevents the system from
transient over voltage stress. The voltage-current relation in a metal oxide block highly
depends upon temperature. Metal oxide block has negative temperature co-efficient. That
means with increase in temperature, resistance of the surge arrester decreases hence for
some system voltage, the leakage current through the instrument increases with increase
in temperature.
As we know that, there would be a continuous leakage current through the LA. This
leakage current generates heat. This generated heat should be dissipated properly
otherwise the temperature of the LA may rise which further increases the leakage current.
Because of this the proper thermal design of surge arrester housing plays an important
role. There is a critical temperature depending upon the voltage rating of the metal oxide
block beyond which joule heat generated in the block which joule heat generated in the
block can not be dissipated at required rate and which finally leads to thermal runaway of
lightning arrester. Now we can understand that the working principle of LA or surge
arrester used for surge protection fully depends upon nonlinear V-I characteristics of metal