Pump Head Calculation

This document summarizes the head calculation for a chilled water pump system with 14 sections. It provides the pipe size, length between take-offs, fittings used, and total and friction head for each section. The total friction head for the whole system is calculated to be approximately 8.631 feet of water.

Uploaded by

romeyleenjoseph
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
142 views3 pages

Pump Head Calculation

This document summarizes the head calculation for a chilled water pump system with 14 sections. It provides the pipe size, length between take-offs, fittings used, and total and friction head for each section. The total friction head for the whole system is calculated to be approximately 8.631 feet of water.

Uploaded by

romeyleenjoseph
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Projcet: Hili Mall

Chilled Water Pump


Pump Head Calculation
Length Frection Loss.
Length Fittings Total Friction
Water pipe size between (ft of water
Section between Fittings QTY Equivelent Equivelent Head (ft of
Flowrate(gpm) (inch) take-offs per 100 equiv
take-offs (ft) Length. (ft) Length. (ft) water)
(m) ft)
1-2 502 10 1 3.28 3.28 0.142 0.0046576
CHECK VALVE 1 100
DRV 1 145
ELBOW 90 1 25
FC 1 12
TEE 1 50
332 332 0.142 0.47144
2-CHILLER 2008 0
2008 10 65 213.25 213.25 1.9 4.05175
IV&MV 2 24
ST 1 190
ELBOW 90 7 175
FC 1 12
TEE 1 50
CHILLER 1 8.631
451 451 1.9 8.569

CCHILLER-3 2008 10 27 88.56 88.56 1.9 1.68264


DRV 1 145
FC 1 12
TEE 1 50
207 207.00 1.9 3.933

3-4 1831.187 10 11.2 36.736 36.74 1.594 0.58557184


ELBOW 2 50
TEE 1 50
100 100.00 1.594 1.594

4-5 568.709 6 6 19.68 19.68 2.14 0.421152


ELBOW 90 1 16
TEE 1 30
IV 1 7
53 53 2.14 1.1342

5-6 188.46 4 5 16.4 16.40 2.067 0.338988


REDUCER 1 12 12.00 2.067 0.24804

6-7 80.36 3 6 19.68 19.68 1.627 0.3201936


ELBOW 90 1 7.5
REDUCER 1 6.5
IV 1 3.2
17.2 17.20 1.627 0.279844

7-8 55 2 1/2 21 68.88 68.88 2.36 1.625568


TEE 2 24
REDUCER 1 5
29 29.00 2.36 0.6844

8-9 49.61 2 1/2 13 42.64 42.64 1.96 0.835744


TEE 1 12
12.00 1.96 0.2352

9-10 44.22 2 1/2 6.39 21 21.00 1.578 0.33138


TEE 1 12 12.00 1.578 0.18936

10-11 35.346 2 21 68.88 68.88 2.5 1.722


TEE 1 10 0
REDUCER 1 4 0
14 14.00 2.5 0.35

11-12 19.81 2 1.32 4.33 4.33 0.871 0.0377143


TEE 1 10 10.00 0.871 0.0871

12-13 12.046 1 1/4 11 36 36.00 2.53 0.9108


Chilled Water Pump
Pump Head Calculation
Length Frection Loss.
Length Fittings Total Friction
Water pipe size between (ft of water
Section between Fittings QTY Equivelent Equivelent Head (ft of
Flowrate(gpm) (inch) take-offs per 100 equiv
take-offs (ft) Length. (ft) Length. (ft) water)
(m) ft)
TEE 1 7
REDUCER 1 2.3
9.3 9.30 2.53 0.23529

13-14 6.65 1 1/4 16.5 54.12 54.12 0.873 0.4724676


TEE 1 7 7.00 0.873 0.06111

14-FCU-B-L.4 3.17 1 19 62.32 62.32 0.88 0.548416


IV 1 1 0
ST 1 5 0
FC 1 6 0
UNION 1 2 0
FCU 1 4.71
14 14.00 0.88 0.1232

FCU-B-L.4-15 3.17 1 19 62.32 62.32 0.88 0.548416


DRV 1 15
2Way Valve 1 1
UNION 1 2
FC 1 6
24 24.00 0.88 0.2112

15-16 6.65 1 1/4 16.5 54.12 54.12 0.873 0.4724676


TEE 1 7
EXPANDER 1 4.7
11.7 11.70 0.873 0.102141

16-17 12.046 1 1/4 11 36 36.00 2.53 0.9108


TEE 1 7
EXPANDER 1 4.7
11.7 11.70 2.53 0.29601

17-18 19.81 2 1.32 4.33 4.33 0.871 0.0377143


TEE 1 10 10.00 0.871 0.0871

18-19 35.346 2 21 68.88 68.88 2.5 1.722


TEE 1 10 0
EXPANDER 1 2 0
12 12.00 2.5 0.3

19-20 44.22 2 1/2 6.39 21 21.00 1.578 0.33138


TEE 1 12 12.00 1.578 0.18936

20-21 49.61 2 1/2 13 42.64 42.64 1.96 0.835744


TEE 1 12
12.00 1.96 0.2352

21-22 55 2 1/2 21 68.88 68.88 2.36 1.625568


TEE 2 24
EXPANDER 1 2.6
26.6 26.60 2.36 0.62776

22-23 80.36 3 6 19.68 19.68 1.627 0.3201936


ELBOW 90 1 7.5
EXPANDER 1 3.8
DRV 1 43
54.3 54.30 1.627 0.883461

23-24 188.46 4 5 16.4 16.40 2.067 0.338988


EXPANDER 1 3.8 3.80 2.067 0.078546

24-25 568.709 6 8 26.24 26.24 2.14 0.561536


ELBOW 90 1 16
TEE 1 30
DRV 1 88
134 134 2.14 2.8676

25-26 1494.368 10 6 19.68 19.68 1.08 0.212544


TEE 2 66 66 1.08 0.7128

26-27 1830.87 10 6 19.68 19.68 1.593 0.3135024


Chilled Water Pump
Pump Head Calculation
Length Frection Loss.
Length Fittings Total Friction
Water pipe size between (ft of water
Section between Fittings QTY Equivelent Equivelent Head (ft of
Flowrate(gpm) (inch) take-offs per 100 equiv
take-offs (ft) Length. (ft) Length. (ft) water)
(m) ft)
ELBOW 90 1 25 25 1.593 0.39825

27-28 1834.35 10 1 3.28 3.28 1.599 0.0524472


ELBOW 90 1 25 25 1.599 0.39975

28-29 2008 10 3 9.84 9.84 1.9 0.18696


TEE 1 50 0
IV 1 12 0
FC 1 12 0
Air Separator 1 1
74 74 1.9 1.406

Total 63.690666
20% Safety 12.7381332
Total 76.4287992

Proposed Pump Head : 100 ft@502GPM