SW version 4.0.0
1 General information 2
2 Changes in the version 4.0.0 3
3 Changes in the version 3.14.2 5
4 Changes in the version 3.14.1 6
5 Changes in the version 3.14.0 7
6 Changes in the version 3.13.0 8
7 Changes in the version 3.12.1 10
8 Changes in the version 3.12.0 11
9 Changes in the version 3.11.4 12
26 Notes 33
IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.
WARNING: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.
Example: This type of paragraph contains information that is used to illustrate how a specific function
works.
4.2 Repairs
Import configuration wizard:
Resolves issue with import of translated text where part of them was not saved properly
Fixed
ScreenEditor:
Resolves issue where AfterTreatment screens were not added when ECU module Cummins CM2350
was configured
Fixed
Modules:
Resolves issue where error message was displayed when user changed ECU parameters in archive
that was configured with older version of ESL file
Fixed
5.2 Repairs
Modules:
An image was missing In Configured VPIO extension modules with index 9-16
"Display As" setting was not saved correctly
Fixed
PLC Editor:
Missing name of binary outputs thrown an error message
PLC Setpoint parameters were reseted when the VPIO modules were added
Fixed
ScreenEditor:
“Invalid floating point” error messages were displayed when user had navigated to the screen in
InteliVision 12 tab and when the Windows version was 2004 and higher
Incorrect name of “Select binary communication object” dialog window was displayed
Generic modules screens had not been added after configuration
Fixed
6.2 Repairs
Modules:
It was not possible to configure Modules without defined communication speed
Fixed
I/O tab:
Cylinder Temperature Wizard – state of Protection was not saved properly
Fixed
User Sensor:
Width of right panel has been returning back to default size – values in column “Converted” were not
visible properly
Fixed
PLC Editor :
“Select input” dialog window had been loaded slowly
Name of inputs had not been displayed in hints
when refreshing ComObjects connected to LAI, the Dimensions and decimal number formatting
edited in PLC editor did not propagate correctly to other tabs
Error message was displayed when dialog window “Choose Output Type” was closed by "x"
Fixed
ScreenEditor:
Instrument Button Link – ECU modules screens were missing in Administration section and screens
were not linked correctly
7.2 Repairs
Modules - Incompatible modules and ECU are not allowed to configure
Fixed
I/O – cannot save configuration when was sensor added via Others sensor
Fixed
PLC Editor:
PLC Analog signal was shown as binary (Fixed)
PLC Sheet was rendered over the second opened PLC Sheet (Fixed)
Icon of ECU Consistency check was missing in toolbar
Fixed
Confusing ECU error/warnings messages modification
Fixed
About window update
Fixed
GenConfig remained running in the background
Fixed
8.2 Repairs
Active alarm Sd ECU despite the communication settings without protection (“no protection” was set and
alarm L2 stay active)
Fixed
Confusing ECU error/warning messages
Fixed
New parameters Counter and Checksum causes that ECU configuration failed
Fixed
PLCEditor – Input window in PLC Editor sometimes freezing for a while
Fixed (cursor setting to a waiting state was added)
PLCEditor – Incorrect display PLC sheets with setting Windows Scale and Layout 125 %
Fixed
PLCEditor – Wrong setpoint range in block CompTime
Fixed (parameter Delay has correct range 0-3000.0 s)
11.2 Repairs
Incorrect picture of AIO-GAS in Modules Tab
Fixed
Controller Help window not working in Modules Tab
Fixed
13.2 Repairs
When switching between two different firmware with separated firmware and configuration it is not
possible to overwrite configuration. Appears also when upgrading IS2GAS-1.2.0 to higher version (1.3.0)
Fixed
72 binary outputs
8 analog inputs
3 analog outputs
Type of CAN modules is limited only to modules with lower communication speed support. Group of
supported CAN modules can vary based on FW updates. Additional information is displayed in
Genconfigon Modules page.
Support of InteliVision 12T external display with screen definition v. 2
Compatibility check between FW and HW versions of InteliSys GAS controller
FW HW Programming
1.2.0 or higher 2.2 or higher Enabled
1.2.0 or higher lower than 2.2 Enabled
lower than1.2.0 2.2 or higher Disabled
lower than1.2.0 lower than 2.2 Enabled
Support of InteliSys GAS 1.2.0
New functionality ECU Fault Codes
Added new page in Genconfigwith definition of ECU fault codes. This function works only for DM1
protocol.
Supported functions:
Change default text - the user can change default text for specific error code
Add text - the user can add text for error codes when text is not defined and error is displayed by
numbers only
Hide selected error codes - the user can select error codes that will not be displayed
Support of 2x I-CB (generic) modules
This option must be supported in the controller. Currently supported in InteliSys GAS 1.2.0.
Support of new generic module AI32 (generic)
Changed default mode of Genconfig
After instalation, Genconfigis now in Advanced mode as default.
Screen Editor for InteliVision 12Touch is supported in following controller default archives:
NT
InteliGen and InteliSys BaseBox 3.8.0
NTC
InteliGen and InteliSys BaseBox 3.8.0
The older controller archives will not work properly with the InteliVision 12Touch 1.1.0
Aftertreatment support
minimal requirements for full Aftertreatment (Tier IV Final standard) support:
NT NTC
InteliGen and InteliSys BaseBox 3.8.0, InteliGen and InteliSys BaseBox 3.8.0
InteliVision 5 version 1.7.0, InteliVision 8 version 2.4.0, InteliVision 12Touch version 1.1.0
Genconfig 3.6.1
Graphic support
Screen Editor for InteliVision 12Touch can run on OpenGL 3.0 (or higher) and GLSL 1.30 (or higher).
In case of problems Graphics drivers upgrade is recommended.
Select color pair dialog allowing to define custom color pair for day and night skin variants
Screens structure
Metering screens, Status screen, Service screen, Status bars (bottom)
Aftertreatment support (InteliVision 5, InteliVision 8, InteliVision 12Touch)
New Aftertreatment instrument available in ScreenEditor
New Aftertreatment icons available
Automatically generated Aftertreatment screen (when ECU with aftertreatment support is configured)
Others
Zoom 75% added
Com. object bit mask dialog for InteliVision 12Touch allows selecting any bits (not just interval)
Better identification of settings in Pictograms category (colored bits)
Columns splitter in properties window
15.3 Repairs
Undo function can cause access violation error in some cases
Partly fixed
Screen Editor for InteliVision 12Touch is supported in following controller default archives:
The older controller archives will not work properly with the InteliVision 12Touch 1.1.0
IMPORTANT: If the older archive (with InteliVision 12Touch support) is opened in the
new ScreenEditor (GenConfig 3.6.0 and newer) the internal screen description
version is automatically increased to the new version. Then if this automatically
updated archive is saved (uploaded) to the controller using the new ScreenEditor
(GenConfig 3.6.0. and newer) the ONLY InteliVision 12Touch 1.1.0. firmware will work
with the controller. It is because of internal compatibility issue.
Aftertreatment
Tier IV Final standard is fully supported only in InteliGen and InteliSys NT BaseBox 3.8.0 and
InteliGen and InteliSys NTC BaseBox 3.8.0
IGS NT 3.8.0 firmware is fully compatible with InteliVision 5 version 1.7.0, InteliVision 8 version
2.4.0 and InteliVision 12Touch version 1.1.0
IMPORTANT: It is very recommended to upgrade both displays firmware and controllers
archives to the newest ones (as specified above) to support Tier IV Final standard.
The older controller firmwares will not work properly (as regards Tier IV Final standard) with
InteliVision 5 (1.7.0) and InteliVision 8 (2.4.0)
IMPORTANT: If the older archive is opened in GenConfig 3.6.0 (and newer) the
Aftertreatment meter is not supported in InteliVision 5 and InteliVision 8.
Select color pair dialog allowing to define custom color pair for day and night skin variants
Screens structure
Metering screens, Status screen, Service screen, Status bars (bottom)
Aftertreatment support (InteliVision 5, InteliVision 8, InteliVision 12T)
New Aftertreatment instrument available in ScreenEditor
New Aftertreatment icons available
Automatically generated Aftertreatment screen (when ECU with aftertreatment support is configured)
Others
Zoom 75% added
Com. object bit mask dialog for InteliVision 12T allows selecting any bits (not just interval)
Better identification of settings in Pictograms category (colored bits)
Columns splitter in properties window
16.3 Repairs
Undo function can cause access violation error in some cases
Partly fixed
17.2 Repairs
Error message when using Cylinder temperatures configuration wizzard
Fixed
Removed "Output type" option when configuring ECU analog output
Some problems when editing "Service screen" for InteliVision 5 in ScreenEditor.
Fixed
In case of import PLC sheet with PLC block Force Prot, the message inside block configuration is lost.
Fixed
19.2 Repairs
Access violation error messages displayed if in configuration is unknown ECU
Fixed
Added detection of free space in configuration. Configuration has limited space for particular information
like Setpoints, Values, protections etc. In this cases could be limitation applied:
Adding of modules like ECON, DETCON, I-STEP etc.
Adding PLC Setpoints in PLC Editor
Adding analog protections on I/O card
Adding universal analog protections on Protections card
In cases above could not be allowed to add new Yellow/Red setpoint limit for protection or protection itself
Added detection of free space for Evaluation period of protection (fast/standard type). Each type has
limited number of protections. If space for specific period is full, it is not possible to use this type, option is
unavailable.
On picture below are all free positions for Fast period already used:
20.2 Repairs
Bug in configuration of User MODBUS
Fixed
Missing cylinder temperature configuration wizard for ISGASXX
Fixed
Error message when trying to set up protection on analog input
Fixed
21.2 Repairs
Problem with saving/loading user MODBUS definition
Fixed.
"List index out of bounds (2)" error message during Export configuration
Fixed
Some PLC blocks have checkbox for inverting binary I/Os, but the checkbox does nothing.
This checkboxes has been hidden when invert function is not available for specific PLC block.
Wrong generation of InteliVision 8 screens for more modules SHBIN, SHBOUT
Fixed.
Abstract error message during configuration of protection on analog inputs
Fixed
22.2 Repairs
Unable to add ECU value to history
Unable to add some values from ECU to history.
Sometimes error when closing GenConfig
Fixed
23.2 Repairs
Save for lather cloning (controller and displays) – IV5
Solved problem when in saved configuration set was missing FW for InteliVision 5.
Use second level for more specific info when required
Use third level when lists of setpoints, values etc. are required
No refresh of PLC input name
When PLC sheet input is connected to PLC sheet output and output name is changed, sheet input
name is now displayed with new name automatically.
Error when copying more PLC blocks
Copying high number of PLC blocks at once caused error message.