Auxiliary System is essential for smooth running of generation units. At 525MW CCPP, there
are three auxiliary transformer having capacity of 20MVA each. These auxiliary transformer step
down the 15kV to 11kV. If any two gas turbine generator out of three or GTG-2 is running,
generator output (15kV) is step down to 11kV for auxiliary usage. If no GTG is running, for
auxiliary consumption is import by system by stepping down 132kV to 15kV that is further step
down to 11kV.

No of Auxiliary Transformers 03
Capacity of Auxiliary Transformers 20MVA
Voltage Ratio 15/11kV
Nomenclature of Auxiliary Transformers 1. GTG-1 Auxiliary T/F
2. GTG-2 Auxiliary T/F
3. GTG-3 Auxiliary T/F
No of Bus Bar of 11kV 02
Bus Bar Name of 11kV A
B
Aux. Transformer Attached to Bus Bar A for Normal Supply GTG-1 Auxiliary T/F
Aux. Transformer Attached to Bus Bar B for Normal Supply GTG-3 Auxiliary T/F
Aux. Transformer Attached to Bus Bar A for Standby Supply GTG-2 Auxiliary Transformer
Aux. Transformer Attached to Bus Bar B for Standby Supply GTG-2 Auxiliary Transformer
Type of Circuit Breaker for 11kV Vacuum Type
No. of Phase 3
Voltage Level 11kV