Professional Documents
Culture Documents
2 Manual en Ingles Apendix 1 - Activation of KM1R and KM111 in 3-Bed Radial Flow Converter
2 Manual en Ingles Apendix 1 - Activation of KM1R and KM111 in 3-Bed Radial Flow Converter
Activation of KM1R/KM111
catalysts in a three-bed
radial flow converter
Making optimal performance possible
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
1 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
Table of contents
1 Introduction 4
1.1 The manual 4
1.2 Purpose of manual 4
2 The catalysts 4
2.1 KM1R/KM111 4
2.2 Pre-reduced catalyst 4
2.3 Filling densities 4
3 Catalyst activation 5
3.1 Activation of iron oxide 5
3.2 Heat of reaction 5
3.3 Amount of water formed during the activation 5
3.4 Activation schedule 5
4 Purging 6
4.1 Oxygen removal 6
5 Gas composition 7
5.1 Reducing gas 7
5.2 H2/N2-ratio 7
5.3 Establishing make-up gas addition and purge 7
5.4 Early stage of the reaction 7
5.5 Ammonia concentration at the inlet of the converter 8
5.6 Water concentration at the inlet of the converter 8
5.7 Oxygen equivalents and other poisons 8
6 Cooling 9
6.1 Water/air cooler 9
6.2 Refrigeration chillers 9
6.2.1 Sampling of aqueous ammonia 10
6.2.2 Refrigeration compressor 10
7 Gas circulation 10
7.1 Circulation rate 11
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
2 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
9 Gas distribution 12
9.1 Main inlet 12
9.2 Pressure shell and converter outlet temperature limits 12
9.3 Cold shot and inter-bed heat exchanger (IHE) valve(s) 12
10 Loop pressure 13
12 Water formation 14
12.1 Analysis of water content 14
12.2 Methods for water determination 14
13 Activation procedure 15
13.1 Activation time frame and data collection 15
13.2 First period 16
13.2.1 Valve positions 16
13.2.2 Pressure 16
13.2.3 Cooling 16
13.2.4 Circulation rate 17
13.2.5 Start-up heater 17
13.2.6 Heating up rate 17
13.2.7 Heat recovery 17
13.2.8 Bi-hourly water analysis 17
13.3 Second period 17
13.3.1 Catalyst temperatures 18
13.3.2 Pressure 18
13.3.3 Circulation rate 18
13.3.4 Heating up rate 18
13.4 Third period 18
13.4.1 First signs of reaction 18
13.4.2 H2/N2-ratio 18
13.4.3 Analyses of ammonia 19
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
3 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
16 Contact 23
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
4 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
1 Introduction
1.1 The manual
This manual contains Topsoe’s recommendations for the activation of a combined charge of Topsoe
ammonia synthesis catalysts KM1R and KM111 in a radial flow converter.
Should any deviation from this procedure be necessary, we recommend discussing this with Haldor
Topsoe A/S before starting the activation.
2 The catalysts
2.1 KM1R/KM111
The catalysts installed in beds 1, 2, and 3 respectively are Topsoe ammonia synthesis catalysts
KM1R, KM 111, and KM 111. The standard size for both catalysts is 1.5–3.0 mm.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
5 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
3 Catalyst activation
This chapter gives Topsoe’s recommendations concerning certain operating parameters during the
activation and concludes with a chronological description of the activation process.
- First period: The catalyst is heated to a level where the activation of the pre-reduced catalyst
begins.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
6 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
- Second period: The pre-reduced catalyst has been activated and the first signs of ammonia
production are seen. Furthermore, the heating continues to a temperature where the
activation of the unreduced catalyst in the second bed starts.
- Third period: The unreduced catalyst in the second bed is activated and ammonia synthesis
reaction is seen across the bed. At the same time, the activation of the unreduced catalyst in
the third bed has commenced.
- Fourth period: The catalyst in the third bed is active to an extent that no external heat source
is needed to keep the temperature high.
- Fifth period: The start-up heater can be taken out of service and the converter can slowly be
brought into normal operation.
The following sections present Haldor Topsoe’s detailed activation procedure as well as
recommendations concerning certain operating parameters during the activation.
4 Purging
4.1 Oxygen removal
In order to remove oxygen after loading of the catalyst and closing of the converter, it is very
important that the synthesis loop is purged thoroughly with nitrogen.
The purging of the loop is done with nitrogen by pressurizing and depressurizing three to five times.
Particular attention should be paid to the converter as the loaded catalyst may contain some pockets
of air that might be difficult to remove.
Any leftover of oxygen will react with the pre-reduced catalyst when the temperature of the catalyst
approaches 100°C (212°F). Thus, if relatively large amounts of oxygen are present, the activation
will be prolonged unnecessarily.
The oxygen level should preferably be kept below 1,000 ppmv in the loop near atmospheric
pressure.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
7 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
5 Gas composition
5.1 Reducing gas
Basically, the activation of the ammonia synthesis catalysts KM1R and KM111 could be carried out
with pure hydrogen. However, it is strongly recommended that the catalysts are activated in
synthesis gas of normal composition, i.e. with a H2/N2 ratio close to 3, as this will give a smooth
transition from activation to normal operation. Furthermore, it is recommended that the activation is
carried out in circulating gas.
5.2 H2/N2-ratio
Throughout the activation, the H2/N2 ratio should be maintained at 3. This allows the reaction to start
as soon as part of the catalyst has been activated. This will further prevent abrupt changes in the
catalyst temperatures and thus diminish the risk of affecting the catalyst and equipment adversely.
1. The heat produced allows for increasing the circulation rate above what can be supported by
the start-up heater alone. This ensures that the last part of the activation is carried out faster
than would otherwise be the case. At the same time, a gradual transition from activation to
normal operation is obtained.
2. The co-condensation of the produced ammonia and activation water results in a more
efficient removal of water from the synthesis gas before the gas is recycled to the converter.
This is highly important as water is poisonous to the catalyst.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
8 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
The ammonia content in the inlet and outlet gases of the converter should be initiated when
significant signs of ammonia synthesis reaction are seen at temperatures near 380–400°C (740–
780°F).
1. The equilibrium pressure of water vapor above the liquid phase consisting of ammonia and
water is lower than that above a liquid phase consisting of pure water
2. The freezing point of the mixed liquid phase is lower than that of pure water and allows for
the application of a lower condensation temperature.
Low water content further ensures that the highest activity is obtained and enhances the
temperature increment due to a higher degree of ammonia formation.
In the very unlikely event that some catalyst has become unstable and starts heating, the catalyst in
the drum or lifting hopper in question should be discarded.
Example: For a make-up gas with a concentration of 1.0 ppmv of CO and 2.5 ppm of CO2, the
oxygen equivalents are:
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
9 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
It should be emphasized that the gas should be free from catalyst poisons such as halogens, sulfur,
phosphorous, and arsenic.
6 Cooling
As described in section 5, low water and ammonia contents at the converter inlet is beneficial. This
can be obtained by cooling the gas to the lowest possible level without violating other restrictions, cf.
description of chiller(s) below.
If available, ammonia injection should also be considered part of the start-up procedure. In this case,
the loop chiller(s) may be started almost immediately.
The refrigeration chiller(s) should be taken into service when the condensate collected in the
ammonia separator downstream the chiller(s) constantly exhibits an ammonia concentration high
enough to prevent freezing, even if the temperature in the chiller(s) drops lower than intended.
The condensate can freeze in the chiller tubes even though the gas temperature outlet the chiller(s)
is above 0°C (32°F), since the surface of the cooling coils or tubes submerged in liquid ammonia is
colder than the gas and might be cold enough to cause freezing.
Particularly for this reason, working with a large safety margin is advisable. When the ammonia
separator condensate has a concentration of about 190 grams ammonia per liter of water (1.6 lbs.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
10 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
ammonia per gallon), its freezing point is below the boiling point of pure liquid ammonia at
atmospheric pressure.
Furthermore, when analyses of the ammonia water mixture condensed in the separator downstream
the chiller(s) show that the freezing point is sufficiently low, i.e. 25% by weight ammonia or more, a
temperature down to the normal temperature at the outlet of the chiller(s) is allowed.
Nevertheless, the chiller(s) is (are) not commissioned before the catalyst has gained substantial
activity and the ammonia concentration at the inlet of the converter is close to the chemical
equilibrium concentration. In this case, the chiller(s) should be commissioned slowly in order to avoid
a drastic drop in ammonia inlet concentration, which would result in a fast increase of reaction rate
and an uncontrollable development in the catalyst temperatures.
7 Gas circulation
It is recommended that the activation is carried out in circulating gas from the beginning, as this
allows a better control of the development in catalyst temperatures. When the pre-reduced catalyst
in the first bed starts becoming active, it may gain activity very quickly. Therefore, it will be necessary
to have the circulator in service in order to have proper temperature control. The circulation rate
should be as high as possible, keeping the required heating up rate in mind.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
11 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
A high circulation rate leads to the highest catalyst activity. It also helps to keep the water content of
the synthesis gas at a low level. The water concentration in the gas should not exceed 3,000 ppmv.
- 150°C (270°F) with respect to the highest temperature in the catalyst section, i.e. typically the
inlet to the first bed and
- 200°C (360°F) with respect to the converter outlet.
The gas flow through the start-up heater should be fairly large. The heating up rate is controlled by
increasing the energy input to the start-up heater.
At this time, the circulation rate should correspond to a space velocity of at least 1,000 Nm3/h per m3
(1,000 SCFH per ft3), preferably 1,500 Nm3/h per m3 (1,500 SCFH per ft3) of catalyst or even higher.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
12 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
9 Gas distribution
For better understanding of this section, we advise to study the sketches of the control principles for
Topsoe’s three-bed converters (S-300) in Appendices 1–3.
The gas stream passing through the main inlet is combined with the hot gas from the start-up heater
introduced through the cold-shot pipe. After the conditions in the start-up heater have stabilized, the
temperature at the inlet of the first bed is controlled by adjusting the circulation rate, using either the
circulator by-pass and/or the main inlet valve.
The inter-bed heat exchanger (IHE) valve is present in Topsoe’s three-bed converters (S-300 and
revamped S-200 converters) with a lower heat exchanger. Thus, the following section only applies to
these types of converters.
The IHE valve for quench gas, i.e. the gas to be introduced via the second inter-bed heat exchanger,
has to be fully closed at the beginning of the catalyst heating and activation. It is, however,
recommended that the IHE valve is cracked open to avoid thermal shock when quench gas is
introduced later on. This is due to the fact that when the catalyst in the first bed gains activity, the
inlet temperature to the second bed has to be controlled by introducing gas to the tube side of the
inter-bed heat exchanger. Changes in the flow rate through the IHE valve will imply changes of the
main gas flow rate in order to keep the first bed inlet temperature unchanged.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
13 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
10 Loop pressure
During the heating period, an operating pressure of 85 kg/cm2g (1210 psig) is recommended, if it is
possible with regard to the recirculation compressor.
Even though the exact value is not critical, it is important that the pressure is maintained constant to
facilitate temperature control. It is important to bear in mind that:
- in order to keep the gas velocity in the beds high, it is advisable not to operate at pressures
above 100 kg/cm2g (1,422 psig)
- at pressures much below 85 kg/cm2g (1,210 psig) water removal in the separators is less
efficient; which has an adverse effect on the final catalyst activity
A pressure of 85 kg/cm2g (1,210 psig) should be maintained until the activation of the second bed is
in progress under stable conditions. The pressure can be then increased to 100 kg/cm2g (1,422 psig)
within a couple of hours. Later on, during the activation of the third bed, the pressure should be
increased to 120 kg/cm2g (1,707 psig).
When the catalyst has gained some activity and the reaction has started, the pressure is maintained
constant by increasing the make-up gas into the loop and by adjusting the purge. The loop pressure
can be raised as the chiller(s) are brought in operation and the heat released from the ammonia
synthesis reaction allows an increment in the circulation rate.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
14 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
probably due to an asymmetrical activation of the catalyst. This will happen when the ammonia
synthesis takes place faster in one part of the bed than in another.
The problem is unlikely to occur, but the appropriate corrective measures are stated anyway.
12 Water formation
Most of the water formed during the activation is separated in the loop separators as aqueous
ammonia. The remainder will be found as a small impurity in the ammonia product during the first
days of operation.
A water analysis should be made at least every two hours, preferably every hour. The water
concentration in the gas leaving the converter should not exceed 3,000 ppmv when the catalyst
temperature is above 250°C (480°F).
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
15 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
A fourth and much simpler method is also presented in Appendix 5. This is an approximation that
should only be used if, for some reason, a more accurate method cannot be applied.
13 Activation procedure
This section contains a chronological description of the activation procedure which can be
considered as guidelines.
The expected duration of the activation will be in the order of 95 hours divided among five periods as
specified in the tables below:
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
16 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
- isolation valves on the piping to the start-up heater should be fully open
- cold-shot valve should be fully closed, cf. section 9
- IHE valve(s), if present, should be cracked open, cf. section 9
- main inlet valve should be open to an extent that does not apply any restrictions in the flow
going to the converter
13.2.2 Pressure
The loop pressure should be around 85 kg/cm2g (1,210 psig) and kept at this level throughout the
heating up period.
13.2.3 Cooling
The water/air coolers should be in operation from the beginning.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
17 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
18 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
13.3.2 Pressure
The loop pressure must be kept unchanged at 85 kg/cm2g (1,210 psig) in this period.
Heating up rate must always be subordinated to the water content at the converter outlet, which
should not be allowed to exceed 3,000 ppmv.
13.4.2 H2/N2-ratio
During this period, the catalyst might have gained sufficient activity to start synthesizing ammonia. It
is thus important to maintain the H2/N2-ratio around 3 in order to get a stable operation without
rapidly increasing or decreasing catalyst bed temperatures. Purging well and keeping the H2/N2-ratio
of the make-up gas at 3 can ensure this.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
19 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
If no sign of reaction is observed in form of an increasing bed outlet temperature, the second bed
inlet temperature may be raised to 430°C (800°F) in small steps.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
20 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
It should be kept in mind that when changing the valve positions the gas going to the converter is
diverted differently. This means that adjusting the heating up rate in one bed may also affect the
heating up rate in the other beds.
For Topsoe’s three-bed converters that are reusing the existing pressure shell from the S-200
converters, the inlet temperature to the second and third beds cannot be controlled independently,
cf. Appendices 2 and 3. In this case, one should aim at controlling the inlet temperature to the
second bed, but the inlet temperature to the third bed should not exceed 420°C (790°F).
13.4.8 Pressure
The pressure is slowly increased towards 120 kg/cm2g (1,707 psig). The pressure should be
increased stepwise by 5 kg/cm2 (71 psi). After each increase in the pressure, the operating
parameters should be allowed to stabilize. The pressure should not be increased by more than 5
kg/cm2 (71 psi) every half an hour.
For Topsoe three-bed converters that are reusing the existing pressure shell from the S-200
converters, one should aim at controlling the inlet temperature to the third bed while being careful not
to lose the reaction in the second bed. This could happen when the inlet temperature to this bed has
dropped too much.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
21 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
13.5.2 Pressure
The pressure is slowly increased towards design pressure. The pressure should not be increased by
more than 5 kg/cm2 (71 psi) every half an hour.
The circulation rate will be close to the maximum, the pressure about that of normal operation and
the production rate approximately 25% or more of design rate.
When taking the start-up heater out of service the temperature variations should be kept at a
minimum
The following measures may be taken to compensate for the reduction of the start-up heater load:
- raise the first bed inlet temperature slightly in order not to lose reaction
- reduce the circulation flow slightly by just opening the circulator bypass valve
- change the gas distribution at the inlet of the converter, namely in direction of more flow
through the main inlet and less flow through the start-up heater
- increase the load on the refrigeration if not already done.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
22 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
If the activation has to be interrupted and flow cannot be maintained, it is necessary to lower the
temperature by 50°C (100°F) below the level reached before discontinuing the circulation. This will
cause the activation rate to slow down to a very low level so that the circulation can be stopped
without jeopardizing the catalyst activity.
If a sudden fall out of the circulation causes interruption of the flow through the converter before
temperatures have been lowered by 50°C (100°F), the synthesis should be bled off gas downstream
the converter by purging. This will create a small flow through the catalyst in the normal flow
direction, and the activation water will be carried away from the already activated part of the catalyst.
15.2 Liability
The recommendations are given without any liability on the part of Haldor Topsoe for upset or
damage to the customers’ plants or personnel. Nothing herein is to be construed as recommending
any practice or any product in violation of any patent, law or regulation.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
23 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
15.3 Advisors
Haldor Topsoe representatives present at site are solely to be considered as advisors, who are in no
way responsible for the operations manager’s duties or responsible for operating customer’s facility
in a careful and safe manner. These responsibilities remain with the customer.
We wish to underline the importance of the operating recommendations issued by Haldor Topsoe
being carefully reviewed by the plant personnel before their adoption.
16 Contact
For contact information, please visit our website on www.topsoe.com.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
24 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
The above Control Principle is based on an S-300 converter in which it is possible to control the inlet
temperature to the first and second beds independently.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
25 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
1st bed
TIC
2nd bed
3rd bed
TIC
The above Control Principle is based on an S-200 to S-300 revamp reusing the existing pressure
shell. It is not possible to control the inlet temperature to the second and third beds independently.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
26 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
1st bed
TIC
2nd bed
3rd bed
LHE
The above Control Principle is based on an S-200 to S-300 revamp reusing the existing pressure
shell. It is not possible to control the inlet temperature to the second and third beds independently.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
27 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
28 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
Below a gas chromatographic method for determining the concentration of water vapor at the
converter outlet is described. The method is suitable for sampling and analyzing in the water
concentration range 100-10,000 ppmv in synthesis gas. The detection limit is approximately 100
ppmv of water vapor.
In Appendix 1 the Ascarite absorption method is described, which is applicable for determination of
500-5,000 ppm water vapor in a gas containing 0-25 mol % NH3.
Principle
The analysis for water vapor in gas mixtures is difficult when ammonia is present in significant
concentrations (percent). Usually columns exhibit severe tailing of ammonia, thus preventing
analysis of water in the ppm range.
This method is based on the use of Chromosorb 103 porous polymer (Johns-Manville). The unique
feature of this material is its ability to separate amines and ammonia without tailing. Since the
retention of water is greater than that of ammonia, slight tailing of water is permissible.
Apparatus
a) Sample Container: Stainless steel cylinder of a minimum volume of 500 ml (30.5 in3). Cylinders
of this type are available with a pressure range of 125 kg/cm2 g (1778 psig). The cylinder must
have two axially directed valves to facilitate flushing
b) Gas Chromatograph, using the following conditions:
Column: Chromosorb 103, 80/100 mesh, packed in 2 m long 1/8" OD, stainless
steel tubing. The column is packed with Chromosorb 103 and conditioned
at 250°C (480°F) for 8 hours with a helium flow of 18 ml/min. The column
is then carefully vibrated as the packing shrinks by the conditioning, and
the empty space is filled with Chromosorb 103. After 1 hour at 250°C
(480°F) the column is ready for use.
Carrier gas: Helium, flow 18 ml/min
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
29 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
Procedure
Preparation
Before sampling, the cylinder must be entirely free from condensed water which would be very
difficult to remove by a mere flushing.
Initially, the cylinder is dried by heating it to 60-80°C (140-176°F) and evacuating (oil vacuum pump)
or flushing it with a dry gas for one hour at this temperature level. The cylinder can be checked for
dryness by analyzing a dry gas by the present method.
During use, as long as no water condenses in the cylinder, no further drying out is necessary. If the
sample gas contains a maximum of 3,000-5,000 ppmv of water vapor, there will be no risk of
condensation in the cylinder down to around 20°C at the normally used sampling pressure (up to
around 3.5 kg/cm2 g [498psig]).
If higher water concentrations than the above are found, if gas has been sampled at higher
pressures and/or lower temperatures than the above, or if humid air has entered the cylinder, a
recheck for dryness must be made and, if necessary, the drying process must be repeated.
Sampling Procedure
The analysis method comprises the following steps:
1. Flush the cylinder with sample gas at a high flow rate for several minutes
2. Pressurize with sample gas to around 3.5 kg/cm2 g (498 psig)
3. Disconnect the cylinder and take it to the laboratory
4. Transfer the sample gas to the gas chromatograph via heated tubing
5. Analyze by gas chromatography
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
30 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
Precaution:
Always check the cylinder for dryness before use or if condensation of water is suspected, by
analyzing a dry gas.
Calibration
For sufficient accuracy of the analyses made during the activation of ammonia synthesis catalyst, the
calibration is done by means of nitrogen saturated with water vapor at a temperature of 0°C (32°F).
The calibration gas is prepared by bubbling nitrogen through a gas wash bottle containing water at
ambient temperature and thereafter passing the gas through a spiral wound glass condenser kept in
an ice bath at 0°C (32°F) before directing the calibration gas to the gas chromatograph. If a
condenser is not available, a narrow gas wash bottle may be used instead. The gas outlet from the
condenser is coupled directly to the gas chromatograph via heated tubing. A suitable flow rate of the
calibration gas is 25 ml/min (0.85 oz/min) and the pressure at which the saturation takes place can
be considered atmospheric
Note: The water vapor percent should be independent of the nitrogen gas flow in the range 10-50
ml/min (0.34 - 1.70oz/min), if not then the condenser is insufficient. A long and narrow bottle
completely immersed in ice is necessary.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
31 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
Figure 1 GC plot for 7% mol NH3 and 1000 ppmv H2O in H2/N2
Below a method for determining the concentration of water vapor at the converter outlet is described.
The method is applicable for determination of 500-5000 ppm water vapor in a gas containing 0-25
mol% NH3.
Principle
The determination is made by passing a certain volume of the gas over a water absorbing agent
which is strongly alkaline and does not absorb ammonia and then weighing the amount of water
absorbed.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
32 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
Apparatus
1. Two glass U-tubes with stopcocks (see Figure 2).
Reagents
1. Ascarite-II (8-20 mesh); sodium hydroxide coated silica. It is manufactured by The Arthur H.
Thomas Company, Philadelphia, Pa., USA. An alternative reagent is Carbosorp AS (6-12
mesh), BDH Laboratory Supplies, Poole, BH15 1TD, England.
2. Paraffin oil (or any non-reactive oil, e.g. silicone oil).
3. Sulfuric acid, 2 mol/l H2SO4.
Sampling
The sample point should be placed immediately after the converter. It is important to try to keep the
sample line hot enough to prevent condensation of water vapor in it. The temperature of the gas inlet
sampling tubes should, however, not exceed 40°C (104°F).
On Figure 2 is shown a set-up for the absorption procedure. Gas from the sample connection is
passed through a rubber or polymer hose to a series of two U-tubes containing Ascarite as water
absorbing agent. The second U-tube is inserted to control the efficiency of the first U-tube. Between
the sample point and the U-tubes a line is branched off and inserted into 25-50 cm (10-20in) of
paraffin oil (this arrangement serving as a pressure controller) or the branch-off line may end in a
rubber hose clip for control of the flow. The latter arrangement, where a large by-pass flow can be
taken, is to be preferred, especially if the sample line under pressure is long and it is difficult to keep
it hot.
The gas flow is measured downstream of the U-tubes. For the protection of the gas flow meter, an
ammonia absorption bottle with 1 liter (33.8oz) 2mol/l sulfuric acid may be inserted.
Procedure
Fill the two glass U-tubes with 10-15ml (0.34-0.51oz) of Ascarite. The tubes should be equipped with
stopcocks and cleaned and dried before use. Place a layer of glass wool over the Ascarite surface to
avoid that dust is carried out of the tubes. Grease and close the stopcocks. Keep outside of tubes
absolutely clean.
Purge the line from the sample point to the U-tube connection point effectively so that a
representative gas mixture is found in the line. Retain flow and connect the two U-tubes. This will
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
33 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
cause gas to go through the branch line and bubble up through the liquid. Open stopcocks. The four
stopcocks should always be opened from upstream and closed in the opposite order. Tubes are now
being purged.
Continue purging for about 10 minutes. The valve of the sample connection should be opened so
that a gas stream is going out through the pressure controller while gas is passed through the tubes,
whether this is done for purging or for absorption. The branch line should be inserted into the liquid
so as to give a flow through the U-tubes of about 2 l/min (67.6oz/min).
Then close stopcocks. Disconnect and separate the tubes. Keep flow through the sample line.
Weigh the tubes. Tubes are now ready for absorption. Purging of the tubes before weighing is done
in order to have gas of the same density in the tubes when weighing before and after absorption.
Again connect tubes to sample line. Open stopcocks. Pass gas through tubes for about 30 minutes,
corresponding to about 60 liters (2029 oz) of gas. If the gas flow rate is not high enough, increase
level in the pressure controller (4). The exact amount of gas passed through the tubes should be
measured and converted to standard conditions.
The tubes can be used a number of times without changing the Ascarite. When the amount of water
absorbed in the second tube becomes 20% or more of that absorbed in the first tube, the Ascarite
should be renewed.
If the tubes exhibit a weight loss instead of gain the Ascarite may be too humid to be used. In some
cases purging of the tubes for several hours with a dry gas re-stores the absorption properties.
As a rule the Ascarite should be procured in small packages and kept unopened until use. The
absence of color change is no indication of low humidity of the Ascarite, the color changes when
CO2 is absorbed. If, however, CO2 is absorbed, the Ascarite is definitely unfit for use.
Expression of results
The increase in weight gives directly the amount of water absorbed. Convert the amount of water
into mol water vapor and calculate the mol% of water in the gas.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
34 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
m 2 - m1
c= 18.02 × 100 mole %
B × (V2 - V1 ) m 2 - m1
+
83.14 × (273 + T ) 18.02
Where
c water vapor (mol% wet) (NH3 free basis)
m1,m2 total weight of the two U-tubes before (m1) and after (m2) the absorption (g)
B barometric pressure (mbar abs)
V1,V2 gas meter reading before and after the absorption (l)
T mean temp of the sample gas outlet the gas meter during the absorption (°C)
18.02 molecular weight of water
83.14 gas constant (mbar · l · mol-1 · K-1)
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
35 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
Principle
Calcium carbide reacts with water and produces acetylene and heat. This reaction has been the
basis for several analytical applications as e.g. determination of moisture in concrete, CRD 154-77
(pressure of acetylene measured) and trace moisture in liquid ammonia, ISO 7104 (acetylene is
measured by gas chromatography).
298
CaC2 + 2 H2O(l) ¾® C2H2(g)+ Ca(OH)2 DH = – 128.4 kJ/mol
298
CaC2 + H2O(l) ¾® C2H2(g)+ CaO DH = – 62.5 kJ/mol
In this method the heat of reaction is basis for estimation of water content.
Apparatus
1. Glass U-tube, as shown in figure 1
2. 2 thermometers 0-50°C (0-122°F), 0.1°C (1.8°F) graduation
3. Insulated box for U-tube
4. Flowmeter calibrated for synthesis gas.
Sampling procedure
The sample is taken from a high-pressure regulation valve close to the converter outlet. The
temperature of the valve must be sufficiently high to prevent condensation of water during expansion
of the gas for analysis. The gas then passes a cooler for conditioning to a temperature of 15-40°C
(59-104°F). After the cooler, plastic tube is used to connect to the U-tube via a flowmeter. In order to
have a quick response it is advantageous to split the gas stream before the flowmeter in a main
stream to vent and a smaller (1/10) stream to the flowmeter and analyzer.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
36 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
Procedure
1. Approximately 30 ml (1oz) of calcium carbide is added to the reaction chamber of the U-tube.
2. The two thermometers are mounted on the U-tube and the assembly placed in the insulated
box (protected from rain and direct sunlight).
3. A gas flow from the converter of 300 l/h (10145oz/h) equivalent to 5 l/min (169oz/min) is
directed through the U-tube in the direction as shown in figure 1.
4. The temperatures of the two thermometers are monitored and after 20 minutes the
temperature difference should be stable. Note: The input temperature must be below 40°C
(104°F) and appropriate cooling of the gas may be necessary.
5. The water content is calculated from the temperature difference of the thermometers, see
paragraph 7.1.
6. The carbide will change color to white when it reacts with water. Furthermore the granules
will disintegrate. The calcium carbide will last for approximately 8 hours at 3000 ppm water
content and longer at lower levels.
Expression of Results
Method of Calculation
The water content is calculated form the temperature difference:
The factor 300 is empirical and depends on heat balance between the produced heat and the heat
removed by the gas and to the surroundings.
Precision
The accuracy and precision is not known as it depends on several factors in the design of the U-tube
and insulation.
Bibliography
BASF: Determination of steam content in ammonia containing gases.
ISO 7104: Liquefied anhydrous ammonia for industrial use - Determination of water content - Gas
chromatographic method.
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
37 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
Specifications:
- Height 17cm (6.7 in)
- Diameter of reaction chamber 4 cm (1.6 in)
- Support of CaC2 layer: glass filter porosity 0
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.
Haldor Topsoe A/S | Haldor Topsøes Allé 1 | 2800 Kgs. Lyngby | Denmark
38 / 38
Manual – Activation of KM1R/KM111 in three-bed radial flow converters
www.topsoe.com
æ XH2O ö
YH2O, out = ç ÷ * (YNH3, out - YNH3, in ) , where
è XNH3 ø
Information contained herein is confidential; it may not be used for any purpose other
than for which it has been issued, and may not be used by or disclosed to third parties
without written approval of Haldor Topsoe A/S.