SUBSTATION INSULATORS QUIZ

©Stephen Brooks BEng CEng MIET


SUBSTATION INSULATORS
QUESTION 1 : IDENTIFY THESE TYPES OF INSULATORS

___________ ___________ ___________ ___________


___________ ___________ ___________ __________
SUBSTATION INSULATORS
QUESTION 2 : We want to use the following post insulator on a 132kV
substation. Calculate the creepage distance for a cat 2 environment.

Degree of MINIMUM CREEPAGE


Category Examples
Contamination DISTANCE mm/kV
1 Slight Rural areas without industry and far from the sea 16
2 Moderate Urban areas 20
3 Severe Industrial areas with pollution 25
4 Very severe Areas with heavy industry and susceptible to dust, fog and sea air 31
SUBSTATION INSULATORS

QUESTION 3 : FILL IN THE BLANKS

____ CONNECTION
__________

__________

______ CONNECTION
_________
SUBSTATION INSULATORS
QUESTION 4 : FILL IN THE BLANKS

The horizontal spacing between the


post insulators depends on
_______________________________

The phase to phase spacing between the


post insulators depends on
__________________________________
SUBSTATION INSULATORS
ANSWER 1

POST SUPPORT CAP & PIN BUSHINGS


INSULATORS INSULATORS INSULATORS
SUBSTATION INSULATORS
ANSWER 2

From the table, cat 2 creepage distance = 20mm / kV

The line voltage = 132kV. Phase voltage = 132kV / 1.73 = 76.3kV

Therefore creepage distance required = 76.3kV * 20mm = 1,526mm


SUBSTATION INSULATORS

ANSWER 3

FLAT CONNECTION
PALM

INSULATOR

SPIGOT CONNECTION
BASE
SUBSTATION INSULATORS
ANSWER 4

The horizontal spacing between the


post insulators depends on the type of
conductor being used

The phase to phase spacing between the


post insulators depends on the electrical
clearances between the busbars.
THANK YOU!!