UNIVERSITY OF TIKRIT

COLLEGE OF ENGINEERING
ELECTRICAL DEPARTMENT

ELECTRICAL
mohammed POWER
hameed ibrahim
‫القدرة الكهربائية‬

Done0 by:
Mohammed Hameed Ibrahim
Chapter one: power stations

 Contents
2
Steam power station 2

Hydro-electric power station 3

Nuclear power station 3

Diesel power station 4

Gas power station 4

Chapter two: variable load on power station 7


Tutorial problems 14

Chapter three: electrical design of transmission line 16


Resistance of transmission line 16

Inductance of transmission line 17

Capacitance of transmission line 20

Tutorial problems 22

Chapter four: performance of overhead lines 24


Short transmission line 24

Tutorial problems 28

Medium transmission line 29

Tutorial problems 35

Long transmission line 36

Connection of transmission line 36

Chapter five: mechanical design of overhead lines 37


Corona 37

Tutorial problems 41

Insulators 41

Tutorial problems 49

Sag in overhead lines 50

Tutorial problems 55

Chapter six: underground cables 56


Laying of underground cable 61

Insulation resistance & capacitance of a single core cable 62

Tutorial problems 64

Grading of cable 64

Tutorial problems 68

Capacitance of 3-core cable 68

Tutorial problems 69

1
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫‪1- Steam power station‬‬


‫محطة تعتمد في تشغيلها على حرق الوقود (الفحم) حيث‬
‫تستغل الطاقة الحرارية الناتجة في تسخين الماء وانتاج‬
‫بخار عند ضغط مرتفع ودرجة حرارة عالية ثم يستغل‬
‫هذا البخار في ادارة توربين بخاري بسرعة عالية قد تصل‬
‫الى ‪ 0033‬لفة في الدقيقة والتي بدورها تقوم بإدارة المولد‬
‫إلنتاج الكهرباء‬
‫وتكون كفاءتها واطئة بحدود ‪%03‬‬
‫االجزاء الرئيسية‬
‫‪1-‬‬ ‫‪steam generating equipment‬‬
‫‪2-‬‬ ‫‪condenser‬‬
‫‪3-‬‬ ‫‪prime mover‬‬
‫‪4-‬‬ ‫‪water treatment plant‬‬
‫‪5-‬‬ ‫‪electrical equipment‬‬
‫اختيار موقع المحطة‬
‫عند انشاء المحطة يجب االخذ بنظر االعتبار االمور‬
‫‪POWER‬‬ ‫التالية‬
‫‪ -1‬توفر كميات وافرة من المياه الباردة لغرض التبريد‬
‫‪ -2‬توفر وسائل نقل منخفضة الكلفة لجلب الوقود‬
‫‪STATIONS‬‬ ‫والمتطلبات االخرى الى المحطة‬
‫‪ -0‬يكون الموقع بعيدا عن المدن لتجنب التلوث‬

‫‪1-‬‬ ‫‪Thermal power station‬‬ ‫محاسن المحطة‬


‫‪2-‬‬ ‫‪Hydro-electric power station‬‬ ‫قدرتها عالية مقارنة مع المحطة الغازية ومحطات‬ ‫‪-1‬‬
‫‪3-‬‬ ‫‪Nuclear power station‬‬ ‫الديزل‬
‫‪4-‬‬ ‫‪Diesel power station‬‬ ‫امكانية تشغيلها لفترات طويلة دون توقف‬ ‫‪-2‬‬
‫‪5-‬‬ ‫‪Gas power station‬‬ ‫كلفة تشغيلية وانشائية واطئة مقارنة مع بقية‬ ‫‪-3‬‬
‫المحطات‬
‫تكاليف الصيانة قليلة‬ ‫‪-4‬‬
‫امكانية استخدام المحطة ألغراض اخرى كتحلية‬ ‫‪-5‬‬
‫المياه‬
‫مساوئ المحطة‬
‫تسبب تلوث الجو إلنتاجها كميات كبيرة من الدخان‬ ‫‪.1‬‬
‫واالبخرة‬
‫كفاءتها واطئة بسبب المفاقيد الكبيرة في اجزائها‬ ‫‪.2‬‬
‫يجب بناء المحطة بعيدا عن التجمعات السكانية‬ ‫‪.0‬‬
‫تحتاج الى كميات كبيرة من مياه التبريد‬ ‫‪.4‬‬

‫‪2‬‬
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫‪2-Hydro-electric power‬‬ ‫‪3-Nuclear power‬‬


‫‪station‬‬ ‫‪station‬‬
‫تعمل على تحويل الطاقة الناتجة من التفاعالت النووية‬
‫محطة طاقة تعمل على تحويل الطاقة الكامنة للماء الى‬
‫الى طاقة كهربائية‬
‫طاقة كهربائية‬
‫االجزاء الرئيسية‬
‫االجزاء الرئيسية‬
‫‪1- Nuclear reactor‬‬
‫‪1- Hydraulic structure‬‬
‫‪2- Heat exchanger‬‬
‫‪2- Water turbine‬‬
‫‪3- Steam turbine‬‬
‫‪3- Electrical equipment‬‬
‫‪4- alternator‬‬
‫اختيار موقع المحطة‬
‫اختيار موقع المحطة‬
‫‪ -1‬يجب ان تتوفر كمية كبيرة من الماء‬
‫‪ -1‬يجب ان تتوفر كميات كافية من الماء‬
‫‪ -2‬يجب ان يتوفر ارتفاع عمود الماء كافي‬
‫‪ -2‬البعد عن المناطق المأهولة بالسكان‬
‫‪ -0‬يجب مراعاة المسافة بين نقطة المحطة ومركز‬
‫‪ -0‬توفر نظام نقل من والى المحطة‬
‫الحمل الكهربائي‬
‫‪ -4‬يجب توفر نظام نقل من والى المحطة‬ ‫المحاسن‬
‫تصنيفها‬ ‫‪ -1‬كميات الوقود قليلة لذلك فان مشاكل التخزين ُمتجنبة‬
‫‪ -2‬مساحتها قليلة‬
‫حسب كمية الماء المتوفرة‬ ‫‪)1‬‬
‫‪ -0‬ال تعتمد على العوامل الجغرافية‬
‫محطة النهر الجاري‬ ‫‪)a‬‬
‫محطة ذات الخزين‬ ‫‪)b‬‬ ‫المساوئ‬
‫حسب ارتفاع الماء‬ ‫‪)2‬‬
‫االرتفاع الواطئ‪ :‬عندما ال يتجاوز ارتفاع الماء ‪03‬‬ ‫‪)a‬‬ ‫غير مناسبة لألحمال المتغيرة‬ ‫‪-1‬‬
‫متر‬ ‫الوقود عالي الثمن وصعب االستخراج‬ ‫‪-2‬‬
‫االرتفاع المتوسط‪ :‬عندما يتراوح ارتفاع الماء (‪-03‬‬ ‫‪)b‬‬ ‫كلفة انشائية كبيرة‬ ‫‪-0‬‬
‫‪ )033‬متر‬ ‫نصبها وتركيبها يتطلب خبرة عالية‬ ‫‪-4‬‬
‫االرتفاع العالي‪ :‬عندما يكون ارتفاع الماء أكثر من‬ ‫‪)c‬‬ ‫كلفة الصيانة ورواتب العاملين فيها عالية جدا‬ ‫‪-5‬‬
‫‪ 033‬متر‬
‫حسب الحمل‬ ‫‪)0‬‬
‫‪ ‬ذروة الحمل‬
‫‪ ‬الحمل االعتيادي‬
‫المحاسن‬
‫كلفة تشغيلية واطئة جدا ألنها تستخدم الماء كوقود‬ ‫‪-1‬‬
‫تحتاج الى زمن اقل في بداية التشغيل‬ ‫‪-2‬‬
‫نظيفة ال تلوث الجو‬ ‫‪-0‬‬
‫تتميز بالمتانة وعمرها طويل وتتطلب صيانة اقل‬ ‫‪-4‬‬
‫كمحطة فيها فوائد اخرى كخزن الماء‬ ‫‪-5‬‬
‫المساوئ‬
‫كلفة انشاء عالية‬ ‫‪.1‬‬
‫قد ال تتوفر كميات كافية من الماء للمحطة‬ ‫‪.2‬‬
‫تتطلب اشخاص ماهرين وذوي خبرة عالية إلنشاء‬ ‫‪.0‬‬
‫المحطة‬
‫كلفة نقل الطاقة عالية‬ ‫‪.4‬‬
‫اختالف كمية الكهرباء المتولدة من وقت الى اخر‬ ‫‪.5‬‬

‫‪3‬‬
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫‪4-Diesel power station‬‬ ‫‪5-Gas power station‬‬


‫تعتمد محطات الديزل على االت االحتراق الداخلي‬ ‫في هذه المحطة يتم تحويل طاقة الوقود الكيميائية الى‬
‫لتحويل الطاقة الحرارية الى طاقة حركية دوارة يحولها‬ ‫طاقة حرارية لتسخين الغازات التي يتم ادخالها الى‬
‫المولد بدوره الى قدرة كهربائية‬ ‫توربينات غازية تحول تلك الطاقة الى طاقة حركية تحرك‬
‫التوربين والذي بدوره يدور المولد الكهربائي وينتج طاقة‬
‫االجزاء الرئيسية‬ ‫كهربائية‬
‫‪1-‬‬ ‫‪Fuel supply system‬‬
‫االجزاء الرئيسية‬
‫‪2-‬‬ ‫‪Air intake system‬‬
‫‪3-‬‬ ‫‪Exhaust system‬‬ ‫‪1-‬‬ ‫‪Compressor‬‬
‫‪4-‬‬ ‫‪Cooling system‬‬ ‫‪2-‬‬ ‫‪Regenerator‬‬
‫‪5-‬‬ ‫‪Lubricating system‬‬ ‫‪3-‬‬ ‫‪Combustion chamber‬‬
‫‪6-‬‬ ‫‪Engine starting system‬‬ ‫‪4-‬‬ ‫‪Gas turbine‬‬
‫‪5-‬‬ ‫‪Alternator‬‬
‫المحاسن‬ ‫‪6-‬‬ ‫‪Starting motor‬‬
‫سهلة التصميم والتخطيط واالنشاء‬ ‫‪-1‬‬
‫المحاسن‬
‫كلفة انشائية واطئة‬ ‫‪-2‬‬
‫نسبة المفاقيد اقل مقارنة بالمحطة البخارية‬ ‫‪-0‬‬ ‫بسيطة التصميم وصغيرة الحجم‬ ‫‪-1‬‬
‫تتطلب مساحة اقل وعدد اقل من العمال والوحدات‬ ‫‪-4‬‬ ‫كلفة انشائية وتشغيلية واطئة‬ ‫‪-2‬‬
‫المساعدة‬ ‫كلفة الصيانة واطئة‬ ‫‪-0‬‬
‫تتطلب كميات قليلة من الماء للتبريد‬ ‫‪-5‬‬ ‫تتطلب كمية قليلة من الماء لذلك من الممكن انشائها‬ ‫‪-4‬‬
‫في المناطق الصحراوية‬
‫المساوئ‬
‫المساوئ‬
‫كلفة تشغيلية عالية الن كلفة الوقود عالية‬ ‫‪-1‬‬
‫غير مناسبة مع الحمل المفرد‬ ‫‪-2‬‬ ‫‪ -1‬الكفاءة الكلية قليلة ‪%23‬‬
‫كلفة الصيانة عالية‬ ‫‪-0‬‬ ‫‪ -2‬عمرها قصير بسبب درجات الحرارة العالية‬
‫تولد قدرة صغيرة نسبيا‬ ‫‪-4‬‬ ‫‪ -0‬تعطي قدرات ليست عالية‬
‫تعمل جزئيا فقط ولفترة قصيرة مقارنة ببقية‬ ‫‪-5‬‬
‫المحطات‬

‫‪4‬‬
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

5
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

6
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫القوانين المهمة‬
‫𝑒𝑣𝑟𝑢𝑐 𝑟𝑒𝑑𝑛𝑢 𝑎𝑒𝑟𝑎 = 𝑦𝑎𝑑 𝑟𝑒𝑝 𝑑𝑒𝑡𝑎𝑟𝑒𝑛𝑒𝑔 𝑠𝑡𝑖𝑛𝑢‬

‫𝑒𝑣𝑟𝑢𝑐 𝑟𝑒𝑑𝑛𝑢 𝑎𝑒𝑟𝑎‬


‫= 𝑑𝑎𝑜𝑙 𝑒𝑔𝑎𝑟𝑒𝑣𝑎‬
‫𝑠𝑟𝑢𝑜‪24 ℎ‬‬

‫𝑑𝑎𝑜𝑙 𝑒𝑔𝑎𝑟𝑒𝑣𝑎‬
‫= )𝐹 ‪𝑙𝑜𝑎𝑑 𝑓𝑎𝑐𝑡𝑜𝑟 (𝐿.‬‬
‫𝑑𝑛𝑎𝑚𝑒𝑑 𝑚𝑢𝑚𝑖𝑥𝑎𝑚‬

‫‪𝑢𝑛𝑖𝑡𝑠 𝑔𝑒𝑛𝑒𝑟𝑎𝑡𝑒𝑑 𝑖𝑛 𝑚𝑜𝑛𝑡ℎ‬‬


‫= 𝑑𝑎𝑜𝑙 ‪𝑚𝑜𝑛𝑡ℎ𝑙𝑦 𝑎𝑣.‬‬
‫𝑠𝑟𝑢𝑜‪720 ℎ‬‬

‫𝑟𝑎𝑒𝑦 𝑛𝑖 𝑑𝑒𝑡𝑎𝑟𝑒𝑛𝑒𝑔 𝑠𝑡𝑖𝑛𝑢‬


‫= 𝑑𝑎𝑜𝑙 ‪𝑦𝑒𝑎𝑟𝑙𝑦 𝑎𝑣.‬‬
‫𝑠𝑟𝑢𝑜‪8760 ℎ‬‬

‫𝑑𝑛𝑎𝑚𝑒𝑑 ‪𝑠𝑢𝑚 𝑜𝑓 𝑖𝑛𝑑𝑖𝑣𝑖𝑑𝑢𝑎𝑙 𝑚𝑎𝑥.‬‬


‫= 𝑟𝑜𝑡𝑐𝑎𝑓 𝑦𝑡𝑖𝑠𝑟𝑒𝑣𝑖𝑑‬
‫𝑆 ‪𝑚𝑎𝑥. 𝑑𝑒𝑚𝑎𝑛𝑑 𝑜𝑛 𝑃.‬‬

‫𝑑𝑎𝑜𝑙 𝑒𝑔𝑎𝑟𝑒𝑣𝑎‬
‫= 𝑟𝑜𝑡𝑐𝑎𝑓 𝑦𝑡𝑖𝑐𝑎𝑝𝑎𝑐 𝑡𝑛𝑎𝑙𝑝‬
‫𝑦𝑡𝑖𝑐𝑎𝑝𝑎𝑐 𝑡𝑛𝑎𝑙𝑝‬

‫𝑑𝑛𝑎𝑚𝑒𝑑 ‪𝑟𝑒𝑠𝑒𝑟𝑣𝑒 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦 = 𝑝𝑙𝑎𝑛𝑡 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦 − 𝑚𝑎𝑥.‬‬

‫‪𝑠𝑡𝑎𝑡𝑖𝑜𝑛 𝑜𝑢𝑡𝑝𝑢𝑡 𝑖𝑛 𝐾𝑊ℎ‬‬


‫= 𝑟𝑜𝑡𝑐𝑎𝑓 𝑒𝑠𝑢 𝑡𝑛𝑎𝑙𝑝‬
‫𝑒𝑠𝑢 𝑓𝑜 𝑠𝑟𝑢𝑜‪𝑝𝑙𝑎𝑛𝑡 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦 ∗ ℎ‬‬

‫‪VARIABLE LOAD‬‬ ‫‪𝑢𝑛𝑖𝑡𝑠 𝑔𝑒𝑛𝑒𝑟𝑎𝑡𝑒𝑑 𝑖𝑛 𝑦𝑒𝑎𝑟 = 𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑙𝑜𝑎𝑑 ∗ 8760‬‬


‫‪= 𝑚𝑎𝑥. 𝑑𝑒𝑚𝑎𝑛𝑑 ∗ 𝐿. 𝐹 ∗ 8760‬‬
‫‪ON POWER‬‬ ‫𝑑𝑛𝑎𝑚𝑒𝑑 ‪𝑚𝑎𝑥.‬‬
‫= 𝑟𝑜𝑡𝑐𝑎𝑓 𝑑𝑛𝑎𝑚𝑒𝑑‬
‫𝑑𝑎𝑜𝑙 𝑑𝑒𝑡𝑐𝑒𝑛𝑛𝑜𝑐‬
‫‪STATION‬‬

‫مالحظة‪- :‬‬
‫‪Types of load curve‬‬
‫‪0 < L.F < 1 ‬‬
‫‪1-Daily load curve 24 h‬‬ ‫‪ Connected load ‬تشمل جميع االجهزة‬
‫‪2-Monthly load curve 720 h‬‬ ‫المربوطة على المحطة الشغالة وغير الشغالة‬
‫‪3-Yearly load curve 8760 h‬‬ ‫وفائدته هي لمعرفة سعة االجهزة المربوطة‬
‫الى المحطة‬
‫فوائد منحني الحمل اليومي‬
‫‪ -1‬يبين لنا تغير الحمل مع الوقت‬
‫‪ -2‬المساحة تحت المنحني = عدد‬
‫الوحدات المتولدة في اليوم‬
‫‪ -0‬اعلى نقطة في المنحني تمثل الطلب‬
‫االعظم ‪max, demand‬‬
‫‪ -4‬النسبة بين المساحة تحت المنحني‬
‫والمساحة الكلية للمستطيل تعطينا‬
‫عامل الحمل ‪L.F‬‬
‫‪ -5‬منحني الحمل يساعد في اختيار‬
‫احجام واعداد وحدات التوليد‬

‫‪7‬‬
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 1:-A power station deliver a EXAMPLE 3:- A generated station has a
two consumers (A , B) as follow connected load of 43 MW and a maximum
Consumer A Consumer B demand of
(MW) (MW) 20 MW the units generated being
2 AM - 6 AM 5 10 61.5*106 per annum calculate
6 AM – 10 AM 10 10 a) Demand factor
10 AM – 2 PM 15 5 b) Load factor
2 PM – 6 PM 10 10 SOLUTION:
6 PM – 2 AM 5 15 a)
Plot the load curve then calculate the load 𝑑𝑒𝑚𝑎𝑛𝑑 𝑓𝑎𝑐𝑡𝑜𝑟 𝑖𝑠
factor of each load then find the load factor 𝑚𝑎𝑥. 𝑑𝑒𝑚𝑎𝑛𝑑
and diversity factor of station =
𝑐𝑜𝑛𝑛𝑒𝑐𝑡𝑒𝑑 𝑙𝑜𝑎𝑑
20 ∗ 103
= = 0.465
SOLUTION: 43 ∗ 103
b)
A+B 𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑑𝑒𝑚𝑎𝑛𝑑 𝑖𝑠
25 𝑢𝑛𝑖𝑡𝑠 𝑔𝑒𝑛𝑒𝑟𝑎𝑡𝑒𝑑 𝑖𝑛 𝑦𝑒𝑎𝑟
=
20 8760 ℎ
A+B (MW

15 61.5 ∗ 106
10 = = 7020 𝐾𝑊
8760 ℎ
5 𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑙𝑜𝑎𝑑
0 𝐿. 𝐹 =
𝑚𝑎𝑥. 𝑑𝑒𝑚𝑎𝑛𝑑
0 2 4 6 8 10 12 14 16 18 20 22 24 7020
TIME = = 0.351
20 ∗ 103
EXAMPLE 4:- A 100 MW power station
delivers 100 MW for 2 hours , 50 MW for
6 hours and is shut down for the rest of
𝑢𝑛𝑖𝑡𝑠 𝑔𝑒𝑛. 𝑝𝑒𝑟 𝑑𝑎𝑦 each day , it's also shut down for
𝐿. 𝐹 (𝐴) = maintenance for 45 days each year ,
24 ℎ ∗ 𝑚𝑎𝑥. 𝑑𝑒𝑚𝑎𝑛𝑑
calculate its annual L.F
5 ∗ 4 + 10 ∗ 4 + 15 ∗ 4 + 10 ∗ 4 + 5 ∗ 8
= SOLUTION:
24 ∗ 15
= 0.55 Energy supplied for each day
𝐿. 𝐹 (𝐵) = 0.72
=100*2+50*6=500 MWh
𝐿. 𝐹 𝑎𝑡 𝑡ℎ𝑒 𝑠𝑡𝑎𝑡𝑖𝑜𝑛 𝑖𝑠
2 ∗ 20 + 15 ∗ 4 + 20 ∗ 18 Station operates for=365-45=320 day
24 ∗ 20
= 0.958 Energy supplied in year is
=500*320=160000 MWh
EXAMPLE 2:- The max. Demand on
power station is 100 MW if the annual 𝑀𝑊ℎ 𝑠𝑢𝑝𝑝𝑙𝑖𝑒𝑑 𝑖𝑛 𝑦𝑒𝑎𝑟
L.Fyear=𝑚𝑎𝑥.𝑑𝑒𝑚𝑎𝑛𝑑∗𝑤𝑜𝑟𝑘𝑖𝑛𝑔 ℎ𝑜𝑢𝑟𝑠
load factor is 40% calculate the total
energy generated per year 160000
= 100∗320∗24 = 0.208
SOLUTION:
Units generated per year is
=max.demand*L.F*8760
=100*103*0.4*8760
=350.4 MW

8
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 5:Agenerating station has a EXAMPLE 6:-


maximum demand of 25 MW L.F=60% a A diesel station supplies the following
plant capacity factor = 50% and plant use loads to various consumers
factor =72% find Industrial consumer=1500 KW
a) The reserve capacity of the plant Commercial establishment=750 KW
b) The daily energy produced Domestic power =100 KW
c) Maximum energy that could Domestic light =450 KW
produce daily if the plant while If the maximum demand on the station is
running as per schedule were fully 2500 KW and the number of KWh
loaded generated per year is 45*105 determine
SOLUTION:- a) The diversity factor
b) Annual load factor
𝑎)
SOLUTION:
𝑎𝑣. 𝑑𝑒𝑚𝑎𝑛𝑑 = 𝑚𝑎𝑥. 𝑑𝑒𝑚𝑎𝑛𝑑 ∗ 𝐿. 𝐹 a)
3
= 25 ∗ 10 ∗ 0.6 = 15000𝐾𝑊 𝑡ℎ𝑒 𝑑𝑖𝑣𝑒𝑟𝑠𝑖𝑡𝑦 𝑓𝑎𝑐𝑡𝑜𝑟 𝑖𝑠
𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑑𝑒𝑚𝑎𝑛𝑑 𝑠𝑢𝑚 𝑜𝑓 𝑖𝑛𝑑𝑖𝑣𝑖𝑑𝑢𝑎𝑙 𝑚𝑎𝑥. 𝑑𝑒𝑚𝑎𝑛𝑑
𝑝𝑙𝑎𝑛𝑡 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦 = =
𝑝𝑙𝑎𝑛𝑡 𝑐𝑎𝑝. 𝑓𝑎𝑐𝑡𝑜𝑟 𝑚𝑎𝑥. 𝑑𝑒𝑚𝑎𝑛𝑑 𝑜𝑛 𝑝𝑜𝑤𝑒𝑟 𝑠𝑡𝑎𝑡𝑖𝑜𝑛
15𝑀𝑊 1500 + 750 + 100 + 450
= = 30 𝑀𝑊 = = 1.12
0.6 2500
𝑟𝑒𝑠𝑒𝑟𝑣𝑒 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦 𝑖𝑠 𝑏)
= 𝑝𝑙𝑎𝑛𝑡 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦 − 𝑚𝑎𝑥. 𝑑𝑒𝑚𝑎𝑛𝑑 𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑙𝑜𝑎𝑑 𝑝𝑒𝑟 𝑦𝑒𝑎𝑟 𝑖𝑠
= 30 − 25 = 5 𝑀𝑊 45 ∗ 105
= = 513.7 𝐾𝑊
𝑏) 8760

𝑑𝑎𝑖𝑙𝑦 𝑒𝑛𝑒𝑟𝑔𝑦 𝑝𝑟𝑜𝑑𝑢𝑐𝑒𝑑 𝑖𝑠 𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑙𝑜𝑎𝑑 513.7


𝐿. 𝐹 = =
𝑚𝑎𝑥𝑖𝑚𝑢𝑚 𝑑𝑒𝑚𝑎𝑛𝑑 2500
= 𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑑𝑒𝑚𝑎𝑛𝑑 ∗ 24
= 0.205
= 15 ∗ 24 = 360 𝑀𝑊
EXAMPLE 7:-A power station has
𝑐) maximum demand of 15000 KW, the
annual load factor is 50% and the plant
𝑚𝑎𝑥𝑖. 𝑑𝑒𝑚𝑎𝑛𝑑 𝑐𝑜𝑢𝑙𝑑 𝑏𝑒 𝑝𝑟𝑜𝑑𝑢𝑐𝑒𝑑 𝑖𝑠
capacity factor is 40% determine the
𝑎𝑐𝑡𝑢𝑎𝑙 𝑒𝑛𝑒𝑟𝑔𝑦 𝑝𝑟𝑜𝑑𝑢𝑐𝑒𝑑 reserve capacity of the plant
=
𝑝𝑙𝑎𝑛𝑡 𝑢𝑠𝑒 𝑓𝑎𝑐𝑡𝑜𝑟 SOLUTION:-
360 𝑀𝑊ℎ
= = 500 Units generated per year is
0.72 𝑑𝑎𝑦
=maximum demand*L.F*8760
=65.7*106 KWh
𝑢𝑛𝑖𝑡𝑠 𝑔𝑒𝑛𝑒𝑟𝑎𝑡𝑒𝑑 𝑖𝑛 𝑦𝑒𝑎𝑟
Plant capacity=𝑝𝑙𝑎𝑛𝑡 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦 𝑓𝑎𝑐𝑡𝑜𝑟∗8760

65.7 ∗ 106
= = 18750 𝐾𝑊ℎ
0.4 ∗ 8760
𝑟𝑒𝑠𝑒𝑣𝑒 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦 𝑖𝑠

9
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

= 𝑝𝑙𝑎𝑛𝑡 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦 − 𝑚𝑎𝑥. 𝑑𝑒𝑚𝑎𝑛𝑑 EXAMPLE 9 :At the end distribution


system a certain feeder supplies three
= 18750 − 15000 = 3750 𝐾𝑊 distribution transformers, each one
EXAMPLE 8 :- A power supply is having supplying a group of consumer whose
the following loads connected loads are

Type of load Maximum Diversity Demand transformer Load Demand Diversity


demand of group factor (KW) factor of group
(KW) Transformer 1 10 0.65 1.5
domestic 1500 1.2 0.8 Transformer 2 12 0.6 3.5
Commercial 2000 1.1 0.9 Transformer 3 15 0.7 1.5
industrial 10000 1.25 1 If the diversity factor among the
The overall diversity factor is 1.35, find transformers is 1.3 , find the maximum load
on the feeder
a) The maximum demand
b) Connected load of each type SOLUTION:-
SOLUTION:-
Sum of maximum demand of costumer on
a) The sum of maximum demands of
transformer = connected load*demand F
Loads is=1500+2000+10000
=10*0.65=6.5 KW
=13500KW
Maximum demand on transformer 1 is
13500
𝑚𝑎𝑥. 𝑑𝑒𝑚𝑎𝑛𝑑 = = 10000
1.35 =6.5/1.5=4.33 KW
b) 𝑐𝑜𝑛𝑛𝑒𝑐𝑡𝑒𝑑 𝑙𝑜𝑎𝑑 𝑖𝑠
Maximum demand on transformer 2 is
𝑚𝑎𝑥.𝑑𝑒𝑚𝑎𝑛𝑑∗𝑑𝑖𝑣𝑒𝑟𝑠𝑖𝑡𝑦 𝑓𝑎𝑐𝑡𝑜𝑟
= 𝑑𝑒𝑚𝑎𝑛𝑑 𝑓𝑎𝑐𝑡𝑜𝑟 =13*0.6 / 3.5=2.057 KW
1800 Maximum demand on transformer 3 is
𝑐𝑜𝑛𝑛𝑒𝑐𝑡𝑒𝑑 𝑙𝑜𝑎𝑑 (𝑑𝑜𝑚𝑒𝑠𝑡𝑖𝑐) =
0.8
=15*0.7 / 1.5 = 7 KW
= 2250 𝐾𝑊
Maximum demand on feeder is
𝑐𝑜𝑛𝑛𝑒𝑐𝑡𝑒𝑑 𝑐𝑜𝑚𝑚𝑒𝑟𝑐𝑖𝑎𝑙 𝑙𝑜𝑎𝑑 𝑖𝑠
1.1 𝑠𝑢𝑚 𝑜𝑓 𝑚𝑎𝑥𝑖𝑚𝑢𝑚 𝑑𝑒𝑚𝑎𝑛𝑑 𝑜𝑓 𝑡𝑟𝑎𝑛𝑠𝑓𝑜𝑟𝑚𝑒𝑟𝑠
2000 ∗ . 9 = 𝑑𝑖𝑣𝑒𝑟𝑠𝑖𝑡𝑦 𝑓𝑎𝑐𝑡𝑜𝑟 𝑎𝑚𝑜𝑛𝑔 𝑡𝑟𝑎𝑛𝑠𝑓𝑜𝑟𝑚𝑒𝑟𝑠
= = 2444 𝐾𝑊
0.9
4.33 + 2.057 + 7
𝑐𝑜𝑛𝑛𝑒𝑐𝑡𝑒𝑑 𝑖𝑛𝑑𝑢𝑠𝑡𝑟𝑖𝑎𝑙 𝑙𝑜𝑎𝑑 𝑖𝑠 = = 10.3 𝐾𝑊
1.3
10000 ∗ 1.25
= = 12500 𝐾𝑊
1

10
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 10:A generating station has EXAMPLE 11: A power station has to
the following daily load cycle meet the following demand
Time (hours) Load (MW) Group A : 200 KW 8 A.M – 6 P.M
0-6 40
6-10 50 Group B : 100 KW 6 A.M – 10 A.M
10-12 60 Group C : 50 KW 6 A.M – 10 A.M
12-16 50
16-20 70 Group D : 100 KW 10 A.M – 6 P.M
20-24 40
And 6 P.M – 6 A.M
Draw the load curve and find
Plot the daily load curve then find; the
a) Maximum demand
diversity factor, units generated per day
b) Units generated per day
and load factor
c) Average load
d) Load factor SOLUTION:-;
SOLUTION:- Time A B C D
‫نرسم منحني الحمل اعتماداً على القيم المعطاة في‬ (hours) (KW) (KW) (KW) (KW)
‫السؤال‬ 0-6 - - - 100
6-8 - 100 50 -
8-10 200 100 50 -
load curve 10-18 200 - - 100
80 18-24 - - - 100

60

40 load curve
20 400
load (KW

300
0 200
0 2 6 8 10 12 14 16 18 20 22 24 100
0
‫من الرسم يتضح لنا ان الطلب االعظم (اعلى نقطة في‬ 0 2 4 6 8 10 12 14 16 18 20 22 24
70 MW ‫الرسم) هو‬ time

‫عدد الوحدات المتولدة خالل اليوم تساوي المساحة تحت‬


‫المنحني حيث يتم تقسيم الرسم الى مستطيالت وحساب‬ Maximum demand = 350 KW
‫مساحتها وبذلك فان‬
Sum of individual maximum demand of
units generated in day is groups is = 200+100+50+100

=40*10+50*8+60*2+70*4 =450 KW

= 1200 MWh Diversity factor =450/350=1.286

Average load = units gen. in day/24hours Units generated in day is

=1200MWh/24h =50000 KW =100*6+150*2+350*2+300*8+100*6

L.F=average load / maximum demand =4600 KWh

=50000/70*103 =0.714 Average load=4600/24=191.7 KW


L.F=191.7/350=0.5477=54.77%

11
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 12:The daily demands of three = 0.167


consumers are given below
200 ∗ 6 + 1200 ∗ 2 + 200 ∗ 2
𝐿. 𝐹 3 =
Time Consumer Consumer Consumer 1200 ∗ 24
(hours) 1 (W) 2 (W) 3 (W) = 0.138
0-8 - 200 -
8-14 600 - 200 Sum of the maximum demand of 3
14-16 200 1000 1200 consumers=800+1000+1200=3000W
16-22 800 - - 𝑠𝑢𝑚 𝑜𝑓 𝑚𝑎𝑥.𝑑𝑒𝑚𝑎𝑛𝑑
Diversity factor=
22-24 - 200 200 𝑚𝑎𝑥.𝑑𝑒𝑚𝑎𝑛𝑑 𝑜𝑛 𝑠𝑡𝑎𝑡.
Plot the load curve and find 3000
= = 1.25
a) Maximum demand of individual 2400
consumers 𝑡𝑜𝑡𝑎𝑙 𝑒𝑛𝑒𝑟𝑔𝑦 𝑐𝑜𝑛𝑠𝑢𝑚𝑒𝑑 𝑖𝑛 𝑑𝑎𝑦
b) Load factor of individual 𝐿. 𝐹 =
𝑚𝑎𝑥. 𝑑𝑒𝑚𝑎𝑛𝑑 ∗ 24
consumers
c) Diversity factor 200 ∗ 8 + 800 ∗ 6 + 2400 ∗ 2 + 800 ∗ 6 + 400 ∗ 2
=
d) Load factor of the station 2400 ∗ 24
SOLUTION:- = 0.291 = 29.1%
EXAMPLE 13 :A power station has a
LOAD CURVE daily load cycle under: 250 MW for 6
hours, 200 MW for 8 hours, 160 MW for 4
2600
2400 hours, 100 MW for 6 hours, if the power
2200 station is equipped with 4 sets of 75 MW
2000
1800 each, calculate
1600
1400 a) Daily load factor
1200 b) Plant capacity factor
1000
800 c) Daily requirement
600 SOLUTION:-
400
200
0 Max demand = 260*103
0 2 6 8 10 12 14 16 18 20 22 24
Units generated per day is
TIME
=260*6+200*8+160*4+100*6

max. demand for consumer 1 is 800 W =4400 MWh

max demand for consumer2 is 1000 W 𝑢𝑛𝑖𝑡𝑠 𝑔𝑒𝑛𝑒𝑟𝑎𝑡𝑒𝑑 𝑝𝑒𝑟 𝑑𝑎𝑦


𝐿. 𝐹 =
𝑚𝑎𝑥. 𝑑𝑒𝑚𝑎𝑛𝑑 ∗ 24
max demand for consumer 3 is 1200 W
4400 𝑀𝑊
= = 0.705
260 ∗ 103 ∗ 24
𝑒𝑛𝑒𝑟𝑔𝑦 𝑐𝑜𝑛𝑠𝑢𝑚𝑒𝑑 𝑖𝑛 𝑑𝑎𝑦 𝑝𝑙𝑎𝑛𝑡 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦 = 75𝑀𝑊 ∗ 4 = 300𝑀𝑊
𝐿. 𝐹 1 =
𝑚𝑎𝑥. 𝑑𝑒𝑚𝑎𝑛𝑑 ∗ 24
𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑑𝑒𝑚𝑎𝑛𝑑
600 ∗ 6 + 200 ∗ 2 + 800 ∗ 6
= 𝑢𝑛𝑖𝑡𝑠 𝑔𝑒𝑛𝑒𝑟𝑎𝑡𝑒𝑑 𝑖𝑛 𝑑𝑎𝑦
800 ∗ 24 = = 183.33𝑀𝑊
24 ℎ𝑜𝑢𝑟𝑠
= 0.458
𝑎𝑣. 𝑑𝑒𝑚𝑎𝑛𝑑
200 ∗ 8 + 1000 ∗ 2 + 200 ∗ 2 𝑝𝑙𝑎𝑛𝑡 𝑐𝑎𝑝. 𝑓𝑎𝑐𝑡𝑜𝑟 =
𝐿. 𝐹 2 = 𝑝𝑙𝑎𝑛𝑡 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦
1000 ∗ 24
183.33𝑀𝑊
= = 0.611
300𝑀𝑊

12
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 14:Power station has the


following daily load cycle 25
load duration curve
Time (hours) Load (MW) 20

load MW
6–8 20 15
8 – 12 40
10
12 – 16 60
16 – 20 20 5
20 – 24 50 0
24 - 6 20 0 time hours 8760
Plot the load curve and load duration
curve also calculate the energy generated 1
𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑑𝑒𝑚𝑎𝑛𝑑 = ∗ (20 + 4)
per day 2
= 12𝑀𝑊
SOLUTION:-
Plant capacity factor is

80 LOAD CURVE 𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑑𝑒𝑚𝑎𝑛𝑑 12


= = = 0.48
𝑝𝑙𝑎𝑛𝑡 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦 25
load (MW

60
40 𝑢𝑛𝑖𝑡𝑠 𝑔𝑒𝑛𝑒𝑟𝑎𝑡𝑒𝑑 𝑖𝑛 𝑦𝑒𝑎𝑟 𝑖𝑠
20
1
0 = 4 ∗ 8760 + ∗ (16 ∗ 8760)
0 2 4 6 8 10 12 14 16 18 20 22 24 2
time (hours = 105120 𝑀𝑊
𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑑𝑒𝑚𝑎𝑛𝑑 12
Units gen. in day=area under curve 𝐿. 𝐹 = = = 0.6
𝑚𝑎𝑥𝑖𝑚𝑢𝑚 𝑑𝑒𝑚𝑎𝑛𝑑 20
max . 𝑑𝑒𝑚𝑎𝑛𝑑
80
load duration curve 𝑢𝑡𝑖𝑙𝑖𝑧𝑎𝑡𝑖𝑜𝑛 𝑓𝑎𝑐𝑡𝑜𝑟 =
𝑝𝑙𝑎𝑛𝑡 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦

60 20
= = 0.8
25
load (MW

40 EXAMPLE 16 :A generating station is to


supply four regions of load whose peak
20 load are
10 MW , 5 MW , 8 MW , 7 MW , the
0 diversity factor of the station is 1.5 and the
average annual load factor =60% , find
EXAMPLE 15:The load duration curve a
certain power station can be considered as a) The maximum demand on the station
a straight line from 20 MW to 4 MW , the b) Annual energy supplied by the station
plant capacity is 25 MW determine SOLUTION:-
a) 𝑚𝑎𝑥𝑖𝑚𝑢𝑚 𝑑𝑒𝑚𝑎𝑛𝑑 𝑜𝑛 𝑡ℎ𝑒 𝑠𝑡𝑎𝑡𝑖𝑜𝑛 𝑖𝑠
a) Plant capacity factor
b) Units generated per year 𝑠𝑢𝑚 𝑜𝑓 𝑖𝑛𝑑𝑖𝑣𝑖𝑑𝑢𝑎𝑙 max 𝑑𝑒𝑚𝑎𝑛𝑑
=
c) Load factor 𝑑𝑖𝑣𝑒𝑟𝑠𝑖𝑡𝑦 𝑓𝑎𝑐𝑡𝑜𝑟
d) Utilization factor 10 + 5 + 8 + 7
SOLUTION:- = = 20 𝑀𝑊
1.5
𝑏) 𝑢𝑛𝑖𝑡𝑠 𝑔𝑒𝑛𝑒𝑟𝑎𝑡𝑒𝑑 𝑖𝑛 𝑦𝑒𝑎𝑟 𝑖𝑠

13
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

= 𝑚𝑎𝑥. 𝑑𝑒𝑚𝑎𝑛𝑑 ∗ 𝐿. 𝐹 ∗ 8760 Load duration curve

= 20 ∗ 0.6 ∗ 8760 Maximum demand = 3040 KW


= 105.12 ∗ 106 𝐾𝑊ℎ
Average load per week is
EXAMPLE 17;The weekly load cycle for 𝑠𝑢𝑚 𝑜𝑓 𝑑𝑎𝑖𝑙𝑦 𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑙𝑜𝑎𝑑
generating station is given below = 7 𝑑𝑎𝑦

15487 𝐾𝑊
Load(MW)
Time(hours)
load

time

load
time

load

time
= = 2212 𝐾𝑊
7
day
𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑑𝑒𝑚𝑎𝑛𝑑 2210
𝐿. 𝐹 = =
𝑚𝑎𝑥𝑖𝑚𝑢𝑚 𝑑𝑒𝑚𝑎𝑛𝑑 3040
= 0.727
Sun. 4 4 5 1 3 8 2 11
Mon. 3 9 4 6 2 7 0.25 2 TUTORIAL PROBLEMS
Tue. 1 4 4 7 5 1 3 12
Wed. 4 2 3 10 2 8 1 4 1- A consumer has the following load
Thur. 3 4 2 5 0.25 2 1 6 cycle for a day
Fri. 2 7 3 6 1 6 0.5 5 Load (W) Time (hours)
Sat. 1 8 2 4 3 7 0.5 5 200 0-6
Construct the weekly duration curve and 3000 6-12
calculate L.F 100 12-13
SOLUTION:- 4000 13-16
2000 16-21
𝑢𝑛𝑖𝑡𝑠 𝑔𝑒𝑛𝑒𝑟𝑎𝑡𝑒𝑑 𝑖𝑛 𝑑𝑎𝑦 1000 21-24
𝑎𝑣. 𝑙𝑜𝑎𝑑 =
24 ℎ Find the load factor
4 ∗ 4 + 5 ∗ 1 + 3 ∗ 8 + 2 ∗ 11 [0.461]
𝑠𝑢𝑛. =
24
2- a generating station has a connected
= 2800 𝐾𝑊 load of 43 MW and a maximum demand
of 20 MW the units generated being
𝑚𝑜𝑛𝑑𝑎𝑦 = 2770 𝐾𝑊
61500000 for the year , calculate the
Tuesday=3040 KW load factor and demand factor
Wednesday =2416 KW [0.351 , 0.465]
Thursday = 1180 KW 3- a 100 MW power station delivers 100
MW for 2 hours , 50 MW for 6 hours
Friday = 1680 KW
and is shut down for the rest of each
Saturday = 1640 KW day , its also shut down for
maintenance for 45 days each year ,
calculate the annual L.F
3500
[0.208]
3000
2500 4- a generating station has a connected
2000
load of 40 MW and a maximum demand
of 20 MW , the units generated being
1500
60*106 , calculate the demand factor
1000
and the load factor
500
0 [0.5 , 0.3425]
tue sun mon wed fri sat ther

14
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

5- a generating station has a maximum [(i)35 MW (ii)560*103 (iii)23333 KW


load for the year of 18 MW and a load (iv)66.67% ]
factor of 0.305 and the maximum loads
10- a power station has to meet the
on the sub stations were 7500 , 5000 ,
following load demand
3400 , 4600 and 2800 KW , calculate
the units generated of the year and the Load A 50 KW 10 A.M – 6 P.M
diversity factor[48.09*106 , 1.3]
6- a power station is to supply 4 regions Load B 30 KW 6 P.M – 10 P.M
of load whose peak value are 10000 , Load C 20 KW 4 P.M – 10 A.M
5000 , 8000 , and 7000 KW , the
diversity factor of the load at the Plot the daily load curve and determine
station is 1.5 and the average annual (i) diversity factor (ii) units generated
load factor is 60% , calculate the per day (iii) load factor
maximum demand on the station and
[(i)1.43 (ii) 880 KWh (iii) 52.38 %]
annual energy supplied from the
station [20 MW , 105.12*106 KW] 11- a substation supplies power by four
7- a generating station supplies the feeders to its consumers , feeder 1
following loads 15000 , 12000 , 8500 , supplies six consumers whose
6000 , and 450 KW the station has a individual daily maximum demands are
maximum demand of 22000 KW , the 70 , 90 , 20 , 50 , 10 , 20 KW while the
annual load factor of the station is 48% maximum demand on the feeder is 200
, calculate (i)units generated per year KW , feeder 2 supplies four consumers
(ii)diversity factor (iii)demand factor whose daily maximum demands are 60
[(i)925*105 KWh (ii)52.4% (iii)1.9] , 40 , 70 , 30 KW while the maximum
8- a generating station has a maximum demand on the feeder is 160 KW ,
demand of 20 MW a load factor of 60% feeder 3 and 4 have a daily maximum
a plant capacity factor of 48% and a demand of 150 KW and 200 KW
plant use factor of 80% find (i) the daily respectively while the maximum
energy produced demand on the station is 600 KW ,
(ii) the reserve capacity of the plant determine the diversity factors for
(iii) the maximum energy that could be feeder 1 and feeder 2 and for the four
produced daily if the plant was running all feeders [1.3 , 1.25 , 1.183]
the time 12- a central station is supplying energy to
[(i)288*103 KWh (ii)0 (iii)4.8*103 a community through two substations ,
KWh] each substation feeds four feeders , the
9- a generating station has the daily load maximum daily recorded demands are
cycle
Load (MW) Time (hours) Power station =12000 KW
0-6 20 Sub- sub-
6-10 25 stationA=6000KW stationB=9000KW
10-12 30 F1=1700 KW F1= 2820 KW
12-16 25 F2=1800 KW F2=1500 KW
16-20 35 F2=2800 KW F3=4000 KW
20-24 20 F4=600 KW F4=2900 KW
Draw the load curve and find
i) Maximum demand Calculate the diversity factor between
(ii) Units generated per day (i)sub-stations (ii)feeders on the sub-
station A (iii)feeders on sub-station B
(iii) Average load
[(i)1.25 (ii)1.15 (iii)1.24]
(iv) Load factor

15
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

1- Resistance of T.L
𝝆𝒍
𝑅𝒅𝒄 = 𝒂
Ω

‫ يجب ضربها بمعامل معين يسمى‬Rac ‫لتحويلها الى‬


skin effect ‫بـ‬
Rac= 1.02*Rdc
‫هي ظاهرة تركز التيار على السطح‬:Skin effect
‫الخارجي للموصل ويعتمد على‬
‫نوع المادة‬ -1
‫نصف قطر السلك‬ -2
‫التردد‬ -0
‫شكل السلك‬ -4
‫كذلك تتأثر المقاومة بدرجة الحرارة حسب العالقة التالية‬

𝑅2 = 𝑅1 ∗ [1 + 𝛼(𝑇2 − 𝑇1 )]
𝑅1 1 + 𝛼1 𝑇1
=
𝑅2 1 + 𝛼0 𝑇0

ELECTRICAL
DESIGN OF
TRANSMISSION
LINE

Constant of transmission line is


1- Resistance Ω
2- Inductance H
3- Capacitance F
4- Conductance ʊ

16
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫‪2- Inductance of T.L‬‬ ‫للحصول على فولتيات متساوية في نهاية الخط نقوم‬
‫بعملية تبديل المواقع‬
‫‪Transposition‬‬
‫‪1- Inductance of single conductor‬‬
‫نتيجة لمرور التيار في الموصل ينشأ فيض مغناطيسي‬
‫بعضه داخل الموصل وبعضه خارجه (على سطح‬
‫الموصل)‬
‫تستخدم هذه العملية للحصول على معدل محاثة على خط‬
‫*المحاثة في دوائر الـ ‪ dc‬تساوي صفر اما‬ ‫واحد يساوي معدل محاثة الخط االخر (معدل محاثة‬
‫في دوائر الـ ‪ ac‬فعند مرور التيار في سلك‬ ‫متساوي في االطوار الثالثة) وبالتالي نحصل على‬
‫ينشا فيض مغناطيسي ومن هذا الفيض تنشا‬ ‫فولتية متزنة في نهاية الخط‬
‫المحاثة‬
‫𝐷‬ ‫اما اذا لم نستخدم هذه العملية فستكون فولتية نهاية الخط‬
‫‪𝐿 = 2 ∗ 10−7 ∗ 𝑙𝑛 ′‬‬ ‫غير متزنة‬
‫𝑟‬
‫‪r’=0.7788 r‬‬ ‫‪5- Double circuit three phase T.L‬‬
‫‪2- Inductance for single phase T.L‬‬
‫𝑚𝐷‬
‫‪two wire system‬‬ ‫‪La=2*10-7ln‬‬
‫𝑠𝐷‬
‫𝐷‬
‫‪La=2*10-7 ln‬‬ ‫‪Dm:‬‬
‫‪𝑟′‬‬
‫𝐷‬ ‫‪geometrical‬‬
‫‪Lb=2*10-7 ln 𝑟′‬‬ ‫‪means distance‬‬
‫𝐷‬
‫‪Lt=4*10-7ln 𝑟′‬‬ ‫𝑚‪𝐻/‬‬ ‫‪Ds: geometrical‬‬
‫‪mean radius‬‬
‫‪3- Inductance of symmetrical three‬‬
‫‪phase T.L‬‬ ‫‪Ds= 3√𝐷𝑠1 𝐷𝑠2 𝐷𝑠3‬‬
‫‪D‬‬ ‫‪Ds1= 4√𝐷𝑎𝑎 𝐷𝑎𝑎′ 𝐷𝑎′𝑎 𝐷𝑎′𝑎′‬‬
‫‪La=Lb=Lc=2*10-7ln r′‬‬

‫يسمى الخط ثالثي الطور‬ ‫‪Ds2= 4√𝐷𝑏𝑏 𝐷𝑏𝑏′ 𝐷𝑏′ 𝑏 𝐷𝑏′ 𝑏′‬‬
‫متماثال اذا وضعت‬
‫الموصالت الثالثة على‬ ‫‪Ds3= 4√𝐷𝑐𝑐 𝐷𝑐𝑐 ′ 𝐷𝑐 ′ 𝑐 𝐷𝑐 ′ 𝑐 ′‬‬
‫رؤوس مثلث متساوي‬
‫𝐴𝐶𝐷 𝐶𝐵𝐷 𝐵𝐴𝐷√‪Dm= 3‬‬
‫االضالع‬
‫‪DAB= 4√𝐷𝑎𝑏 𝐷𝑎𝑏′ 𝐷𝑎′ 𝑏 𝐷𝑎′ 𝑏′‬‬

‫‪4- Inductance of unsymmetrical‬‬ ‫‪DBC= 4√𝐷𝑏𝑐 𝐷𝑏𝑐 ′ 𝐷𝑏′ 𝑐 𝐷𝑏′ 𝑐 ′‬‬


‫‪three phase T.L transposed‬‬
‫‪DCA= 4√𝐷𝑐𝑎 𝐷𝑐𝑎′ 𝐷𝑐 ′ 𝑎 𝐷𝑐 ′ 𝑎′‬‬
‫عندما تكون االسالك‬
‫موضوعة بشكل افقي او‬
‫بشكل عمودي وتكون‬
‫المسافات بينها غير متساوية‬
‫او تكون موضوعة على‬
‫رؤوس مثلث متساوي‬
‫الساقين‬
‫𝐷‬
‫𝑞𝑒‪La=Lb=Lc=2*10-7 ln 𝑟′‬‬ ‫‪H/m‬‬

‫𝑎𝑐𝐷 𝑐𝑏𝐷 𝑏𝑎𝐷√‪Deq= 3‬‬

‫‪17‬‬
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 1 :Find L/phase Km of double Dm=4.94 m


circuit three phase overhead line, the phase 4.94
sequence ABC the line is completely La=2*10-7 ln
0.275
transposed , r=1.3 cm
=57*10-7 H/m
SOLUTION:-
EXAMPLE 2 :A single-phase line has two
parallel conductors 2 m a part, the
diameter of each conductor is 1.2 cm,
calculate the loop inductance per km of
the line
SOLUTION:-
D = 2 m = 200 cm
r= 0.6 cm r’=0.7788*0.6=0.4672

𝐷 L=4*10-7 ln D/r’=4*10-7 ln 200/0.4672


La=2*10 -7
ln 𝐷𝑚
𝑠
=2.423*10-6 H/m]*1000=2.423 mH/km
3
Ds= √𝐷𝑠1 𝐷𝑠2 𝐷𝑠3
EXAMPLE 3 :Find the inductance per km
Ds1= 4√𝐷𝑎𝑎 𝐷𝑎𝑎′ 𝐷𝑎′ 𝑎 𝐷𝑎′ 𝑎′ of three phase T.L using 1.24 cm diameter
conductors when these are placed at the
Daa=Da’a’=Dbb=Db’b’=Dcc=Dc’c’ corners of an equilateral triangle of each
side 2 m
=0.7788*1.3*10-2
SOLUTION:-
4 2
Ds1= √(0.7788 ∗ 1.3 ∗ 10−2 )2 ∗ √62 +62 D = 2 m = 2 cm
=0.292 m r= 0.62 cm

Ds2= 4√𝐷𝑏𝑏 𝐷𝑏𝑏′ 𝐷𝑏′ 𝑏 𝐷𝑏′ 𝑏′ r’ = 0.4828 cm

4 L=2*10-7 ln D/r’
=√(0.7788 ∗ 1.3 ∗ 10−2 )2 ∗ 62
=2*10-7 ln 200/0.4828=1.2*10-6 H/m
=0.275 m
L=1.2*10-6*1000=1.2 mH/km
Ds3=Ds1=0.292 m
EXAMPLE 4:The three conductors of
Ds=0.275 m
three phase T.L are arranged at the
Dm= 3√𝐷𝐴𝐵 𝐷𝐵𝐶 𝐷𝐶𝐴 corners of a triangle of sides 2m,2.5m and
4.5m , calculate the inductance per km of
𝐷𝐴𝐵 = 4√𝐷𝑎𝑏 𝐷𝑎𝑏′ 𝐷𝑎′𝑏 𝐷𝑎′ 𝑏′ the line when the conductors are regularly
transposed , the diameter of each
4 2 conductor is 1.24 cm
= √32 ∗ (√32 + 62 )
SOLUTION:-
= 4.48 𝑚
r= 0.62 cm
DBC=4.48 m
r’ = 0.62*0.7788=0.4828 cm
4
𝐷𝐶𝐴 = √𝐷𝑐𝑎 𝐷 𝑐𝑎 ′ 𝐷 𝑐′𝑎 𝐷
𝑐 ′ 𝑎′
D12=2 m=200 cm
4
= √63 ∗3 =6 D23=2.5 m =250 cm

18
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

D31=4.5 m = 450 cm Ds= 4√𝐷𝑎𝑎 𝐷𝑎𝑎′ 𝐷𝑎′𝑎 𝐷𝑎′ 𝑎′


Deq= 3√𝐷12 𝐷23 𝐷31 = 282.31 cm 4
=√1002 ∗ 0.3892 = 6.23 𝑐𝑚
𝐷𝑒𝑞
L=2*10-7 ln L=2*10-7 ln 50.76/6.23 = 0.42*10-6 H/m
𝑟′

=2*10-7 ln 282.31/0.4828 EXAMPLE 7:

=1.274*10-6
L=1.272*10-6*100 = 1.272 mH/km
EXAMPLE 5 :Calculate the inductance of
each conductors in three phase 3 wires
system when the conductors are arranged
in horizontal such that :D31 =4 m
D12=D23=2m , the conductors are
transposed and have a diameter of 2.5 cm
Find the inductance per phase per km the
SOLUTION:- conductor are transposed and are of radius
0.75 cm each, the phase sequence is ABC
Deq = 3√𝐷12 𝐷23 𝐷31
SOLUTION:-
3
= √4 ∗ 2 ∗ 2 = 2.52 𝑚 = 252 𝑐𝑚
r’ = 0.75*0.7788=0.584 cm

𝑟 = 1.25 𝑐𝑚 𝑟 = 0.9735 2
Dab=√0.752 + 32 =3.1 m
𝐷𝑒𝑞
L=2*10-7 ln 𝑟′ H/m
Dab’=√32 + 4.752 =5.62 m
L=2*10-7 ln 252/0.9735=1.11*10-6 H/m
Daa’=√62 + 42 =7.21 m
-6
L=1.11*10 *1000=1.11 mH/km
Ds= 3√𝐷𝑠1 𝐷𝑠2 𝐷𝑠3
EXAMPLE 6 :Two conductors single
phase line each of 1 cm diameter , are Ds1= 4√𝐷𝑎𝑎 𝐷𝑎𝑎′ 𝐷𝑎′ 𝑎 𝐷𝑎′ 𝑎′
arranged in vertical plant which one
4
conductor mounted 1 m above the other a =√(0.584 ∗ 10−2 )2 ∗ 7.212=0.205 m
second identical line is mounted at the same
Ds3=Ds1=0.205 m
height as the first and spaced horizontally
0.25 m apart from it, the two upper and two Ds2= 4√𝐷𝑏𝑏 𝐷𝑏𝑏′ 𝐷𝑏′ 𝑏 𝐷𝑏′ 𝑏′
lower conductors are connected in parallel
4
, determine the inductance per km of the =√(0.584 ∗ 10−2 )2 ∗ 5.52 = 0.18 𝑚
resulting double circuit line
3
Ds=√0.18 ∗ 0.205 ∗ 0.205 = 0.195 𝑚
SOLUTION:-
Dm= 3√𝐷𝐴𝐵 𝐷𝐵𝐶 𝐷𝐶𝐴
r = 0.5 cm
r’ = 0.389 cm DAB= 4√𝐷𝑎𝑏 𝐷𝑎𝑏′ 𝐷𝑎′ 𝑏 𝐷𝑎′ 𝑏′
4
L=2*10-7 ln Dm/Ds =√3.1 ∗ 5.62 ∗ 3.1 ∗ 5.62 = 4.17 𝑚
DBC=DAB=4.17 m
Dm= 4√𝐷𝑎𝑏 𝐷𝑎𝑏′ 𝐷𝑎′ 𝑏 𝐷𝑎′ 𝑏′
DCA= 4√𝐷𝑐𝑎 𝐷𝑐𝑎′ 𝐷𝑐 ′ 𝑎 𝐷𝑐 ′ 𝑎′
4 2
= √252 ∗ (√252 + 1002 ) =50.76 cm 4
=√6 ∗ 6 ∗ 4 ∗ 4=4.9 m

19
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

3
Dm=√4.9 ∗ 4.17 ∗ 4.17=4.4 m 3- Capacitance of T.L
-7
L=2*10 ln Dm/Ds 1- Capacitance of single phase T.L
4.4
L=2*10-7 ln 0.195
n
=0.623*10-6 mH/m
L=0.623*10-6*1000 =0.623 mH/km
EXAMPLE 8 :Calculate the inductance QA+QB=0
per phase per meter for a three phase QA=-QB
double circuit line whose phase conductor
𝑞 𝐷
have a radius of 5.3 cm with the horizontal Vab=𝜋𝜀 ln 𝑟 V
0
conductor arrangement
𝜋𝜀0
SOLUTION:- Cab= 𝐷 F/m
ln
𝑟

‫ هي القيمة الحقيقية لنصف القطر‬r


Van=0.5 Vab V
r’ = 5.3*0.7788=0.0413 Can=2 Cab F/m
3
Ds= √𝐷𝑠1 𝐷𝑠2 𝐷𝑠3 2- Capacitance of symmetrical three
phase T.L
Ds1= 4√𝐷𝑎𝑎 𝐷𝑎𝑎′ 𝐷𝑎′ 𝑎 𝐷𝑎′ 𝑎′
Qa+Qb+Qc=0
4
=√0.0413 ∗ 0.0413 ∗ 24 ∗ 24=0.995 m
𝑞 𝐷
Va=Vb=Vc=2𝜋𝜀 ln 𝑟 𝑉
Ds2=Ds3=Ds1=0.995 m 0

0 2𝜋𝜀
Ds=0.995 Ca=Cb=Cc=ln 𝐷/𝑟 F/m

Dm= 3√𝐷𝐴𝐵 𝐷𝐵𝐶 𝐷𝐶𝐴 3- Capacitance of unsymmetrical


three phase system but
DAB= 4√𝐷𝑎𝑏 𝐷𝑎𝑏′ 𝐷𝑎′ 𝑏 𝐷𝑎′ 𝑏′ transposed
4
=√8 ∗ 32 ∗ 16 ∗ 18 =13.45 m =DBC Deq= 3√𝐷1 𝐷2 𝐷3
DCA= 4√𝐷𝑐𝑎 𝐷𝑐𝑎′ 𝐷𝑐′𝑎 𝐷𝑐′𝑎′ 𝑞 𝐷𝑒𝑞
Va=Vb=Vc=2𝜋𝜀 ln 𝑟
0
4
=√16 ∗ 8 ∗ 40 ∗ 16 =16.917 m 2𝜋𝜀0
Ca=Cb=Cc= 𝐷𝑒𝑞
3 ln
Dm=√13.45 ∗ 13.45 ∗ 16.917 𝑟

=14.518 m
14.518 ‫ نتيجة لوجود المتسعة ينشأ تيار الشحن‬:‫مالحظة مهمة‬
L=2*10-7 ln 0.995 charging current
=5.36*10-7 H/m Ic=jWCVph
‫ هي ظاهرة زيادة فولتية االستالم‬: ‫ظاهرة فيرانتي‬
‫نتيجة لوجود متسعات الشحن للخطوط الغير محملة‬

20
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 1:A single phase T.L has two r = 1.25/2=0.625 cm


parallel conductors 3 m apart, radius of
2𝜋𝜀0 2𝜋∗8.85∗10−12 𝐹
each conductor being 1 cm , calculate the a) C= 𝐷𝑒𝑞 = 282
𝑚
ln ln
𝑟 0.625
capacitance of the line per km
=0.0091*10-9 F/m
SOLUTION:-
= 0.0091*10-6 F/km
r = 1 cm , D=3 m = 300 cm
𝜋𝜀 𝜋∗8.85∗10−12
=0.0091 μF/km
0
C=ln 𝐷/𝑟 𝐹/𝑚 = ln 300/1
F/m
C100km=0.0091*100 = 0.91 μF
-11
= 0.4875*10 F/m
C=0.4875*10-12*1000= 0.4875*10-8 F/km
b) Charging current per phase is
EXAMPLE 2:A 3-phase overhead T.L has
IC=Vph / Xc
its conductors arranged at the corners of an
equilateral triangle of 2 m side, calculate 66000
IC= ∗ 2𝜋𝑓𝐶
√3
the capacitance of each line conductor per
km , given that diameter of each conductor =38105.11*2π*50*0.91*10-6=10.9 A
is 1.25 cm
SOLUTION:-
r= 1.25/2 = 0.625 cm
D=2 m=200 cm
EXAMPLE 4;Calculate the capacitance of
2𝜋𝜀0 𝐹 2𝜋∗8.85∗10−12 𝐹 a 100 km long 3-phase , 50 Hz overhead T.L
C= 𝐷 𝑚
= 200
𝑚
ln ln
𝑟 0.625 consisting of 3 conductors , each of
diameter 2 cm and spaced 2.5 m at the
= 0.0096*10-9 F/m
corners of an equilateral triangle
= 0.0096*10-9*1000 F/km
SOLUTION:-
= 0.0096 μF/km
D=2.5 m = 250 cm
EXAMPLE 3 :A 3-phase, 50 Hz , 66 KV
r = 2/2 = 1 cm
overhead T.L conductors are placed in a
horizontal plane as shown in fig. below , the 2𝜋𝜀0 𝐹
C= 𝐷
𝑚
conductor diameter is 1.25 cm , if the line ln
𝑟
length is 100 km , calculate
2𝜋∗8.85∗10−12 𝐹
= 250
𝑚
a) Capacitance per phase ln
1
b) Charging current per phase
= 10.075*10-12 F/m
Assuming complete transposition of line
=10.075*10-9 F/km
C100km=10.075*10-9*100
= 1.0075*10-6 F = 1.0075 μF/phase

SOLUTION:-
3
Deq= 3√𝐷12 𝐷23 𝐷31 = √2 ∗ 2.5 ∗ 4.5

= 2.82 m = 282 cm

21
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 5 :A 3-phase , 50Hz ,132 kV TUTORIAL PROBLEMS


overhead line has conductor placed in a
1- A single phase line has two parallel
horizontal plane 4 m apart , conductor
conductors 1 m apart , the radius of
diameter is 2 cm , if the line length is 100
each conductor is 0.5 cm , calculate
km , calculate the charging current per
the loop inductance per km of the line
phase assuming complete transposition
[2.22 mH]
SOLUTION:- 2- find the inductance per km per phase
of a 3-phase T.L using 2 cm diameter
conductor when these are placed at
the corners of an equilateral triangle
of side 4 m
r = 2/2=1 cm = 1*10-2 m [1.25 mH]
3- a 20 km single phase line has two
3
Deq= 3√𝐷12 𝐷23 𝐷31 = √4 ∗ 4 ∗ 8 =5.04 m parallel conductors separated by 1.5
2𝜋𝜀0 2𝜋∗8.85∗10−12 𝐹
m , the diameter of each conductor is
C= 𝐷𝑒𝑞 = 5.04 0.823 cm , if the conductor has a
ln ln 𝑚
𝑟 0.01
resistance of 0.311 Ω/km , find the
= 0.00885*10-6 F/km loop impedance of this line at 50 Hz
C100km=0.00885*10-6*100=0.885*10-6 F [19.86 Ω]
4- the 3 conductor of a 3-phase line are
132∗103
Vph= = 76210 𝑉 arranged at the corners of a triangle of
√3
sides 4,5 and 6 m , calculate inductance
IC= WCVph =2π*50*0.885*10-6*76210 per km of the each conductor when
= 21.18 A conductors are regularly transposed ,
the diameter of each line conductor is
2 cm
[1.285 mH]
5- the 3 conductor of a 3-phase T.L are
arranged in a horizontal plane with a
spacing of 4 m between adjacent
conductors, the diameter of each
conductor is 2 cm , determine the
inductance per km per phase of the line
, assuming that the lines are transposed
[1.3 mH]
6- determine the inductance per km of a3-
phase T.L using 20 mm diameter
conductors are at the corners of
atringle with spacing 4,5 and 6 m ,
conductors are regularly transposed
[1.29 mH/km/phase]
7- determine the inductance of a 3-phase
symmetrical line whose conductors are
placed at the corners of an equilateral
triangle of side 1 m , the diameter of
each conductor is 20 mm
[0.971 mH/phase/km

22
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

8- a single phase T.L has two parallel


conductors 1.5 m apart , the
diameter of each conductor being
0.5 cm , calculate the line to
neutral capacitance for a line 80
km long [3.48 μF]
9- a 200 km , 3-phase T.L has its
conductors placed at the corners of
an equilateral triangle of 2.5 m
side , the radius of each conductor
is 1 cm , calculate (i)line to neutral
capacitance of the line
(ii)charging current per phase if
the line is maintained at 66 KV , 50
Hz
[(i)2.02 μF (ii)24.2 A]
10- the three conductor A,B and C of a
3-phase line are arranged in a
horizontal plane with DAB=2 m ,
DBC= 2.5 m , find line to neutral
capacitance per km if diameter of
each conductor is 1.24 cm , the
conductor are transposed at
regular intervals
[0.0091 μF]
11- the three conductor of a 3-phase
line are arranged at the corners of
a right angled isosceles triangle , if
each equal side of this triangle is 2
m ,find line to neutral capacitance
per km , take the diameter of each
conductors as 1.24 cm , the
conductors are transposed at
regular intervals [0.0094
μF/km]
12- a 3-phase , 50 Hz , 132 KV , T.L has
conductor placed in a horizontal
plane 4.56m apart , conductor
diameter is 22.4mm , if the line
length is 100 km , find the charging
current per phase , assuming
complete transposition [21.345 A]
13- three conductors of a 3-phase T.L
are arranged in a horizontal plane
6 m apart , the diameter of each
conductor is 1.24 cm , find the
capacitance of each conductor to
neutral per 100 km of the line
[0.785 μF]

23
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

1- Short transmission line

Vs=sending voltage
VR = receiving voltage
Is=sending current = IL =IR
R=total resistance of T.L
XL=total reactance of T.L

Performance of
Is =IR ………………………….….1
Overhead Lines Vs=VR+IR Z
VS=VR+(R+J XL )IR ………….....2
4 ‫ و‬3 ‫ مع المعادلتين‬2 ‫ و‬1 ‫بمقارنة المعادلتين‬
VS=AVR+BIR ……………………3
‫الغاية من دراسة خطوط النقل هي لمعرفة هبوط الجهد‬ IS=CVR+DIR …………………….4
‫والخسائر وكفاءة الخط‬
‫نستنتج ما يلي‬
‫وعلى اساسه تم تصنيف خطوط النقل الى ثالث اصناف‬
A=1 , B=Z , C=0 , D=1
‫ خط النقل القصير‬-1
AD – CB = 1
kV 23 ‫ كم ويعمل على‬03-53
Voltage Regulation
‫ خط النقل المتوسط‬-2
𝑉𝑆 −𝑉𝑅
V.R%= ∗ 100%
kV 102-23 ‫ كم ويعمل على‬023-03 𝑉𝑅

𝐼 𝑅 𝐶𝑜𝑠𝜃𝑅 +𝐼𝑅 𝑋𝐿 𝑆𝑖𝑛𝜃𝑅


‫ خط النقل الطويل‬-0 V.R%= 𝑅 ∗ 100%
𝑉𝑅
‫ فأكثر‬KV 102 ‫ كم فأكثر ويعمل على‬023
If V.R is +ve that means lagging p.f
If V.R is -ve that means leading p.f
𝑜𝑢𝑡𝑝𝑢𝑡 𝑝𝑜𝑤𝑒𝑟
Efficiency = 𝑖𝑛𝑝𝑢𝑡 𝑝𝑜𝑤𝑒𝑟
∗ 100%

𝑜𝑢𝑡𝑝𝑢𝑡 𝑝𝑜𝑤𝑒𝑟
=𝑜𝑢𝑡𝑝𝑢𝑡 𝑝𝑜𝑤𝑒𝑟+𝑙𝑜𝑠𝑠𝑒𝑠 ∗ 100%

24
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

=33708.3+j250 V

‫׀‬Vs‫(√=׀‬33708.3)2 + (250)2

=33709 V
Phasor diagram for laggin p.f b) Line losses=I2R
=(41.67)2*10=17.364 KW
Output power delivered=1100 KW
Power sent=1100+17.364=1117.364 KW
𝑝𝑜𝑤𝑒𝑟 𝑑𝑒𝑙𝑖𝑣𝑒𝑟𝑒𝑑
Phasor diagram for unity p.f Efficiency = 𝑝𝑜𝑤𝑒𝑟 𝑠𝑒𝑛𝑡
∗ 100%

1100
=1117.364 ∗ 100%

=98.44%
EXAMPLE 2 :What is the maximum length
in km for a single phase T.L having copper
Phasor diagram for leading p.f conductor of 0.775 cm2 crass section over
which 200 KW at unity power factor and at
3300 V are to be delivered, the efficiency if
T.L is 90% , take specific resistance as
EXAMPLE 1 :A single phase overhead T.L 1.725 μΩ cm
delivers 1100 KW at 33 KV at 0.8 p.f SOLUTION:-
lagging , the total resistance and inductive
reactance of the line are 10 Ω and 15 Ω Receiving end power = 200 KW
respectively , determine
Efficiency =0.9
a) Sending end voltage
Sending end power=200/0.9 = 222.22 KW
b) Sending end p.f
c) Transmission efficiency Line losses = 22.22 KW
SOLUTION:-
200∗103
Line current = 3300∗1
= 60.6 𝐴
Zt =R+jXL=10+j15
VR=33000 V Line losses=2I2R

𝑝𝑜𝑤𝑒𝑟 1100∗103 22.22 KW=2(60.6)2 R


I=𝑉 = 33000∗0.8 = 41.67 𝐴
𝑅 𝐶𝑂𝑆𝜃𝑅 222222
R=2∗(60.6)2 = 3.025 Ω
CosϴR=0.8 SinϴR=0.6
𝜌𝑙
I’=I(cosөr-jsinөr) R=
𝐴
𝑅𝐴 3.025∗0.775
=41.67(0.8-j0.6)=33.33-j25 l= 𝜌
= 1.725∗10−6
a) Sending end voltage
=1.35*106 cm
Vs=VR+IZ
=13.6 km
=3300+(33.33-j25)(10+j15)
=33000+333.3-j250+j500+375

25
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 3:A 3-phase T.L delivers 5000 EXAMPLE 4 : Estimate the distance over
KW at 22 KV at p.f=0.8 lagging, the which a load of 15000 KW at p.f=0.8
resistance and reactance of each conductor lagging can be delivered by a 3-phase T.L
is 4Ω and 6Ω respectively, determine having conductor each of resistance 1 Ω
per km the voltage at the receiving end is to
a) Sending end voltage
be 132 KV and the losses in the line is to be
b) Percentage regulation
5% PR
c) Transmission efficiency
SOLUTION:- SOLUTION:-
Receiving end voltage per phase 15000
I= = 82 𝐴
√3∗132∗103 ∗0.8
22000
VR= = 12700 𝑉 Line losses=0.05*15000 = 750 KW
√3

Z=4+j6 Line losses=3I2R


5000∗103 750*103=3(82)2R
I= = 164 𝐴
3∗12700∗0.8
R=37.18 Ω
cosөR=0.8 sinөR=0.6
Resistance of each conductor per km is
VR=12700 V
1 Ω (given)
I’=I(cosөR –jsinөR)
Length of line = 37.18 km
=164(0.8-j0.6)=131.2-j98.4
EXAMPLE 5:A 3-phase T.L delivers 3600
a)
KW at p.f=0.8 lagging to a load, if the
Vs=VR+IZ sending end voltage is 33 KV , find

=12700+(131.2-j98.4)(4+j6) a) Receiving end voltage


b) Line current
=13815.2+j393.6 c) Transmission efficiency
/Vs/=√(13815.2)2 + (393.6)2 Z=5.31+j5.54
=13820.8 V SOLUTION:-
33000
Line value of Vs=√3 ∗ 13820.8 Vs= = 19052 𝑉
√3
= 23938 𝑉 3600 150∗105
I=3𝑉 =
𝑉𝑆 −𝑉𝑅 𝑅 ∗0.8 𝑉𝑅
b) V.R%= 𝑉𝑅
∗ 100%
a)Vs=VR+IRcosөR+IXlsinөR
13820.8−12700
= ∗ 100% 15∗105
12700 19052=VR+ ∗ 5.31 ∗ 0.8
𝑉𝑅
=8.825%
15 ∗ 105
c) Line losses=3I R 2 + ∗ 5.54 ∗ 0.6
𝑉𝑅
=3*(164)2*4=322752 W VR=18435 V
Transmission efficiency
5000 𝐾𝑊 VR line=√3 ∗ 18435 = 31.93 𝐾𝑉
=(5000+322.752) 𝐾𝑊 ∗ 100% =93.94 %
15∗105 15∗1015
b)I= = = 81.36 𝐴
𝑉𝑅 18435

line losses=3I2R

26
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

=3(81.36)2*5.31=105.447 KW VS=6351+262.43*1.5*0.8+262.43*4*0.6
3600 = 7295.8 V
Efficiency=3600+105.447 ∗ 100%
𝑉𝑆 −𝑉𝑅
= 97.15% V.R%= 𝑉𝑆
∗ 100%

EXAMPLE 6:A short 3-phase T.L with an 7295.8 − 6351


impedance of 6+j8 Ω per phase has = ∗ 100%
6351
sending end and receiving end voltage of
120 KV and 110 KV respectively for = 14.88 %
some receiving end load at p.f=0.9 lagging Line losses=3I2R
,find
=3*(262.43)2*1.5
a) Output power
b) Sending end p.f =310*103 W
SOLUTION:-
Output power = √3VLILCosө
110∗103
VR= = 63508 𝑉 =√3*1100*262.43*0.8
√3

120∗103 =4000 KW
VS= = 69282 𝑉
√3
I/p power=o/p power+losses
VS=VR+IRcosөR+IXLsin өR
=4000+310=4310 KW
69282=63508+I*6*0.9+I*8*0.435
5774
Transmission efficiency=4000/4310
I= 8.88 = 650.2 𝐴
=0.928=92.8 %
3𝑉 ∗𝐼∗𝑐𝑜𝑠𝜃𝑅
a) o/p power= 𝑅 𝐾𝑊 EXAMPLE 8:A 3-phase, 50 Hz , 16 km
1000
3∗63508∗650.2∗0.9
long overhead line supplies 1000 KW at
= 1000 11 KV , 0.8 p.f lagging ,the line resistance
is 0.03Ω per phase per km and line
= 111490 𝐾𝑊 inductance is 0.7Ω per phase per km ,
𝑉𝑅 𝑐𝑜𝑠𝜃𝑅 +𝐼𝑅 calculate The sending end voltage, voltage
p.fS=cosөS= 𝑉𝑆 regulation and efficiency of T.L
63508∗0.9+650.2∗6
= 69282
= 0.88 𝑙𝑎𝑔𝑔𝑖𝑛𝑔 SOLUTION:-
11 𝐾𝑉
EXAMPLE 7 : An 11 KV 3-phase T.L has VR= = 6351 𝑉
√3
a resistance of 1.5 Ω and reactance of 4 Ω
1000
per phase , calculate the percentage I=3∗11000∗0.8 = 65.6 𝐴
regulation and efficiency of the line when a
total load of 5000 KVA at 0.8 lagging p.f is R=0.03*16 = 0.48 Ω
supplied at 11 KV at the distant end XL=2πf l *16=2π*50*0.7*103*16
SOLUTION:- =3.52 Ω
11∗103
VR= 3 = 6351 𝑉 VS = VR + I R cosөR + I XL sinөR

CosөR=0.8 SinөR=0.6 VS=6351+65.5*0.48*0.8+65.5*3.52*0.6


5000 𝐾𝑉𝐴 = 6515 V
I= 3∗6351
= 262.43 𝐴
6515−6351
V.R%= ∗ 100% = 2.58%
VS=VR+IRCosөR+IXLsinөR 6351

27
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

Line losses=3I2R 20 km long , the resistance and


reactance of each conductor are (0.25
=3*(65.5)2*0.48=6.2 KW
and 0.28)Ω/km , if the receiving end
I/P power = O/P power+line losses line voltage is maintained at 11 KV
,find (i)sending end line voltage
=1000+6.2 = 1006.2 KW (ii)percentage regulation
Transmission efficiency is (iii)transmission efficiency
[(i)11.84 KV (ii)7.61%
1000
= 1006.2*100% =99.2% (iii)94.32%]
6- estimate the distance over which a
TUTORIAL PROBLEMS load of 15000 KW at 0.85 p.f can be
delivered by a 3-phase T.L having
1- a single-phase T.L delivers 1100 KW
conductors of steel-cored aluminum
at 33 KV at 0.8 p.f lagging , the total
each of resistance 0.905Ω/phase per
resistance of the line is 10 Ω and the
km the voltage at the receiving end is
total inductive reactance is 15 Ω
to be 132 KV and the loss in
determine (i)sending end voltage
transmission is to be 7.5% of the load
(ii)sending end p.f
[69.55]
(iii)transmission efficiency
7- a 3-phase line 3 km long delivers
[(i)33.71 KV (ii)0.795 lag (iii)98.5%] 3000KW at a p.f 0.8 lagging to a load ,
the resistance and reactance per km of
2- an industrial load consisting of a group each conductor are (0.4 and 0.3) Ω
of induction motors which aggregate respectively , if the voltage at the
500KW at 0.6 p.f lagging is supplied by supply end is maintained at 11 KV ,find
a distribution feeder having an (i)receiving end voltage line to line
equivalent impedance of (0.15+j0.6)Ω (ii)line current (iii)transmission
, the voltage at the load end of the efficiency [(i)10.46 KV (ii)207A
feeder is 2300 V, find (i)load current (iii)95%]
(iii)sending end voltage 8- a short 3-phase T.L with an impedance
[(i)209A (ii)2.42 KV] of (5+j20) Ω/phase has sending end
and receiving end voltages of 46.85 KV
3- a single phase T.L delivers 4000 KW at respectively for some receiving end
11 KV at 0.8 p.f lagging , if resistance load at a p.f of 0.8 lagging , determine
and reactance/conductor are 0.15and (i)power output (ii)sending end p.f
0.02Ω respectively (i)percentage [(i)22.86 KW (ii)0.657 lag]
regulation (ii)sending end p.f (iii)line 9- a short 3-phase T.L connected to a
losses 33KV , 50 Hz generating station at the
sending end is required to supply a
[(i)19.83% (ii)0.77 lag (iii)620 kW]
load of 10 MW at 0.8 p.f lagging at
4- a single phase 11 KV line with a length 30KV at the receiving end , if the
of 15 km is to transmit 500 KVA ,the minimum transmission efficiency is to
resistance and inductive reactance of be limited to 96% , estimate the per
the line is (0.5 and 0.3)Ω/km phase value of resistance and
respectively , calculate the efficiency inductance of the line [2.4 Ω,0.028H]
and regulation of the line for 0.8 p.f 10- a single phase T.L is delivering
lagging 500KVA load at 2 KV , its resistance is
0.2 Ω and inductive reactance is 0.4 Ω
[97.74% , 3.34%] , determine the voltage regulation if the
5- a load of 1000 kW at 0.8 p.f lagging load power factor is (i)0.707 lagging
received at the end of a 3-phase line (ii)0.707 leading [(i)5.3% (ii)-1.655]

28
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

2- Medium T.L 𝑌𝑍
𝐴=𝐷 =1+
2
‫ طرق لتمثيل خط النقل المتوسط‬0 ‫هناك‬
𝑌𝑍 2
𝐵 = (𝑍 + )
a) T-nominal method 4
b) Π-nominal method
c) End condenser method 𝐶=𝑌
AD-BC=1

a) T-nominal method
EXAMPLE 1:3-phase , 50 Hz , T.L , 100
km long has the following constants
R/km/phase=0.1 Ω
XL /km/phase=0.2 Ω
Equivalent circuit for T-nominal method Capacitance susceptance /km/phase
=0.04*10-4 S
Determine a) sending end current
b) Sending end voltage
c) Sending end p.f
d) Transmission efficiency
Phasor diagram for T-nominal method
When supplying a balanced load of
lagging p.f
10000KW at 66 KV p.f=0.8 lagging
𝐼𝑆′ = 𝐼𝐶′ + 𝐼𝑅′
SOLUTION:-
𝑍
𝑉𝐶′ = 𝑉𝑅′ + 𝐼𝑅
2
𝑍
𝑉𝑆′ = 𝑉𝐶′ + 𝐼𝑆
2
𝑍 𝑍
𝑉𝑆′ = 𝑉𝑅′ + 𝐼𝑅 + 𝐼𝑆
2 2 Rt=0.1*100=10 Ω
𝐼𝑆′ = 𝑌𝑉𝐶′ + 𝐼𝑅′ XLt=0.2*100=20 Ω
𝑍 Y=0.04*10-4*100=4*10-4 S
= 𝑌 (𝑉𝑅′ + 𝐼𝑅 ) 𝐼𝑅′
2 66000
VR= = 38105 𝑉
𝑍 √3
= 𝑌𝑉𝑅′ + (1 + 𝑌 ) 𝐼𝑅′
2 10000∗103
IR= = 109 𝐴
√3∗66∗103 ∗0.8
𝑍 𝑍 𝑍
𝑉𝑆′ = 𝑉𝑅′ + 𝐼𝑅′ + [𝑌𝑉𝑅′ + (1 + 𝑌 ) 𝐼𝑅′ ]
2 2 2 Cosөr=0.8 sinөr=0.6
𝑌𝑍 𝑍2 Z=R+jXL=10+j20
𝑉𝑆′ = 𝑉𝑅′ (1 + ) + (𝑍 + 𝑌 ) 𝐼𝑅′
2 4
VR=VR+j0=38105 V
𝑍
𝐼𝑆′ = 𝑌𝑉𝑅′ + (1 + 𝑌 ) 𝐼𝑅′ IR=IR(cosθR – jsinθR)
2
=109(0.8-j0.6)=87.2-j65.4

29
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

=39195+j545 XLt=0.4*100=40 Ω

IC=jYV1 Y=2.5*10-6*100=2.5*10-4 S

=j4*10-4(39195+j545) Z=20+j40
110∗103
=-0.218+j15.6 V R= = 63508 𝑉
√3

IS=IR+IC 20∗106
I R= = 116.6 𝐴
√3∗110∗103 ∗0.9
=(87.2-j65.4)+(-0.218+j15.6)
CosθR=0.9 SineθR=0.435
=87-j49.8=100∟-29.47o
VR=VR+j0=63508 V
IS=100 A
IR=IR(cosθR-jsinθR)
VS=V1+IS Z/2 =116.6(0.9-j0.435)=105-j50.7 A
=(39195+j545)+(87-j49.8)(5+j10) V1=VR+IR Z/2
=40128+j1170 =63508+(105-j50.7)(10+j20)
=40145 ∟1.4o =65572+j1593

VS line to line=√3 ∗ 40145 = 69.533 𝐾𝑉 IC=j Y V1

Sending end power=3 VS IS cosθS =j2.5*10-4(65572+j1593)

ΘS=1.4o+29.47o=31.27o =-0.4+j16.4

IS=IR+IC
Cosθs=0.853
=105-j50.7-0.4+j16.4=104.6-j34.3 A
Sending end power is
IS=110∟-18.9 A
=3*40145*100*0.853
VS=V1+IS Z/2
=10273.105 KW
=(65572+j1593)+(104.6-j34.3)(10+j20)
Transmission efficiency is
=67304+j3342
1000
=10273.105*100% /VS/=67387
=97.34 % VS line =67387*√3=116.717 KV
EXAMPLE 2 :3-phase, 50 Hz , T.L 100 km Total line losses for the three phase is
long deliver 20 MW at 0.9 p.f lagging and at 110
KV , the resistance and reactance of the line per =3(IS)2 R/2 + 3(IR)2 R/2
phase per km are 0.2Ω and 0.4Ω while =3*1102*10+3*116.62*10
capacitance admittance is 2.5*10-6S/km/phase
calculate a) VS & IS b) efficiency of T.L =0.778*106 W = 0.77 MW
20
SOLUTION:- Transmission efficiency= = 0.9629
20+0.77

Rt=0.2*100=20 Ω

30
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

b) Π-nominal method EXAMPLE 1 :3-phase , 50 Hz , 150 km line


has a resistance , inductive reactance and
capacitance shunt admittance of 0.1Ω 0.5Ω
and 3*10-6 S per km per phase , if the line
delivers 50 MW at 110 KV and 0.8 p.f
lagging , determine the sending end voltage
and current

Equivalent circuit for π-nominal method SOLUTION:-

R=0.1*150 = 15 Ω
Phasor diagram for π method lagging p.f XL=0.5*150=75 Ω
𝑉𝑆′ = 𝑉𝑅′ + 𝐼𝐿′ 𝑍 Y=3*10-6*150=45*10-5 S
𝑌 110∗103
𝐼𝐿′ = 𝐼𝐶1

+ 𝐼𝑅𝐼 𝐼𝐶1 = 𝑉𝑅 VR= = 63508 𝑉
2 √3

𝑌 𝑌 50∗106
𝐼𝐿′ = 𝑉𝑅′ + 𝐼𝑅′ 𝐼𝐶2 = 𝑉𝑆 IR= = 328 𝐴
√3∗110∗103 ∗0.8
2 2
𝑌 CosθR=0.8 sinθR=0.6
𝑉𝑆′ = 𝑉𝑅′ + (𝑉𝑅′ + 𝐼𝑅′ ) 𝑍
2 IR=IR(cosθR-jsinθR)
𝑌𝑍 ′
𝑉𝑆′ = (1 + ) 𝑉 + 𝑍𝐼𝑅′ … … … .1 =328(0.8-j0.6)=262.4-j196.8
2 𝑅
IC1=jVR Y/2
𝐼𝑆 = 𝐼𝐿 + 𝐼𝐶2
45∗10−5
𝑌 𝑌 IC1=63508*j = 𝑗14.3
𝐼𝑆′ = 𝑉𝑅′ + 𝐼𝑅′ + 𝑉𝑆′ … … … … . .2 2
2 2
IL=IC1+IR
2‫ في م‬1‫ من م‬VS ‫بتعويض قيمة‬
=(262.4-j196.8)+j14.3
𝑌 𝑌𝑍 𝑌
𝐼𝑆 = 𝑉𝑅 + 𝐼𝑅 + [(1 + ) 𝑉𝑅 + 𝑍𝐼𝑅 ] =262.4-j182.5 A
2 2 2
𝑌2𝑍 𝑌𝑍 VS=VR+IL Z
𝐼𝑆 = [𝑌 + ] 𝑉𝑅 + [1 + ] 𝐼𝑅
4 2 =63508+(262.4-j182.5)(15+j75)
=81131+j16942.5 V
𝑌𝑍 /Vs/=82881 V
𝐴=𝐷 =1+
2
Line to line sending end voltage
𝐵=𝑍
=82881*√3=143.55 KV
𝑌2𝑍
𝐶=𝑌+
2 IC2=jVS Y/2

31
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

45∗10−5 VS=VR+IL Z
=(81131+j16942.5)*j 2
=38105+(176-j66)(10+j50)
=-3.81+j18.25 A
=43165+j8140=43925∟10.65o
IS=IL+IC2
/VS/=43925 V
=(262.4-j182.5)+(-3.81+j18.25)
VS line to line =√3 ∗ 43925 = 76 𝐾𝑉
=258.6-j164.25
IC2=jVS Y/2
/IS/=306.4
10∗10−4
EXAMPLE 2: 100 km long, 3-phase T.L =(43165+j8140)* j 2
has the following line constants
=-4+j21.6 A
R/phase/km = 0.1 Ω
IS=IL+IC2=(176-j66)+(-4+j21.6)
XL/phase/km =0.5 Ω
=172-j44.4
Suspectance/phase/km =10*10-6 S
/IS/=177.6∟-14.5o A
If the line supplies load of 20MW at 0.9 p.f
lagging at 66 KV at the receiving end, ΘS=10.65o+14.5o=25.15o
calculate by nominal π method Sending end p.f = cosθS =0.905 lag
a) Sending end power factor 𝑉𝑠 −𝑉𝑅
V.R%= 𝑉𝑅
∗ 100%
b) Voltage regulation
c) Transmission efficiency 43925−38105
SOLUTION:- = ∗ 100% = 15.27 %
38105

Sending end power=3 VS IS cosθS


=3*43925*177.6*0.905=21.18 MW
Transmission efficiency=20/21.18=0.94
Transmission efficiency %= 94 %

R=0.1*100=10 Ω
XL=0.5*100 = 50 Ω
Y=10*10-6*100=10*10-4 S
66∗103
VR= = 38105 𝑉
√3

20∗106
IR= = 195 𝐴
√3∗66∗103 ∗0.9

SinθR=0.435
IR=IR(cosθR-jsinθR)
=195(0.9-j0.435)=176-j85
IC1=jVR Y/2
10∗10−4
=38105*j 2
= 𝑗19 𝐴

IL=IR+IC1=(176-j85)+j19=176-j66 A

32
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

c) End condenser method EXAMPLE 1 :A medium single-phase T.L


100 km long has the following constants
R/km =0.25 Ω , XL/km=0.8 Ω
Susceptance/km=14*10-6 km
VR=66 KV , assuming that the total
capacitance of the line is located at the
receiving end alone , determine
a) The sending end current
Equivalent circuit for end condenser b) The sending end voltage
method c) Voltage regulation
d) Supply power factor
The line delivering 15000 KW at 0.8 p.f
lagging, draw the phasor diagram to
illustrate your calculation
SOLUTION:-

Phasor diagram for end condenser method


lagging p.f
IS=IC+IR
IS=Y VR + IR
VS=VR+ISZ
R=0.25*100=25 Ω
VS=VR+(YVR+IR)Z
XL=0.8*100=80 Ω
=VR+YZVR+ZIR
Y=14*10-6*100=14*10-4 S
=(1+YZ)VR+ZIR …………….1
15000∗103
IL=66∗103 ∗0.8 = 284 𝐴
IS=YVR+IR ……………………2
4 ‫ و م‬0 ‫بالمقارنة مع م‬ VR=VR+j0=66000 V

VS=AVR+BIR ………………..3 IR=IR(cosθR – jsinθR)

IS=CVR+DIR ………………...4 = 284 (0.8-j0.6)=227-j170 A


IC= j Y VR=j14*10-4*66000

A=(1+YZ) B=Z = j 92 A

C=Y D=1 a)

AD - BC=1 IS=IR+IC=(227-j170)+j90
= 227-j78
/IS/=240 A

33
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

b)
Home works
drop voltage=ISZ=IS(R+jXL)
1- Draw the phasor diagram of the
=(227-j78)(25+j80)
medium T.L T-nominal method for
=11915+j16210 V (i)unity power factor (ii) leading
power factor
VS=VR+ISZ=66000+11915+j16210 2- Draw the phasor diagram of the
= 77915+j16210 V medium T.L π-nominal method for
(i)unity power factor (ii) leading
/VS/=79583 V power factor
3- Draw the phasos diagram of the
c)
medium T.L end condenser method
𝑉𝑆 −𝑉𝑅 for (i)unity power factor
V.R%= 𝑉𝑅
∗ 100% = 20.58 %
(ii)leading power factor
d)
−78
θ1=tan−1 =-18.96oR
227
16210
θ2=tan−1 77915 =11.5o

θS=18.96o+11.5o=30.46
supply p.f =cos 𝜃𝑠 = cos 30.46
=0.86 lag

‫قوانين الخسائر الخاصة بخط النقل المتوسط‬


T-method π-method End condenser
method
Single phase 𝑅 𝑅 𝐼𝑙2 𝑅 𝐼𝑆2 𝑅
𝐼𝑅2 + 𝐼𝑆2
2 2
𝑅 𝑅
Three phase 3 (𝐼𝑅2 + 𝐼𝑆2 ) 3 𝐼𝑙2 𝑅 3 𝐼𝑆2 𝑅
2 2

34
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

TUTORIAL PROBLEMS 4- A 3-phase , 50Hz, 100 km T.L has the


following constants ………..
1- A medium single phase T.L 100 km long
Resistance/phase/km = 0.1 Ω
has the following constants
Reactance/phase/km = 0.5 Ω
Resistance/km/phase =0.15 Ω Inductive
Susceptance/phase/km = 10-5 S If
reactance/km/ph=0.377 Ω Capacitive
the line supplies a load of 20 MW at 0.9
react./km/phase=31.87 Ω Receiving end
p.f lagging at 66 KV at the receiving
line voltage=132KV assuming that the
end , calculate by using nominal π
total capacitance of the line is localized
method:(i)sending end current (ii)line
at the receiving end alone , determine
value of sending end voltage
(i)sending end current (ii)line value of
(iii)sending end p.f (iv)regulation
sending end voltage (iii)regulation
[(i)177.6 A (ii)76KV (iii)0.905 KV
(iv)sending end p.f the line is delivering
(iv)15.15%]
72 MW at 0.8 p.f lagging [(i)377.3
5- A 3-phase overhead transmission line
A (ii)155.7 KV (iii)17.9%
has the following constants :
(iv)0.774 lag]
Resistance/phase = 10 Ω Inductive
2- A 3-phase ,50 Hz T.L has the
reactance/phase=35 Ω Capacitive
following constants -4
admittance/phase=3*10 if the line
Resistance/phase = 9.6 Ω
supplied a balanced load of 40000 KVA
Inductance/phase=0.097 mH
at 110 KV and 0.8 p.f lagging ,
Capacitance/phase=0.765μF if
calculate : (i)sending end p.f
the line is supplying a balanced load
(ii)percentage regulation
of 24000 KVA 0.8 p.f lagging at 66 KV
(iii)transmission efficiency
,calculate (i) sending end current
[(i)0.798 lag (ii)10% (iii)96.38 %]
(ii)line value of sending end voltage
6- A 3-phase , 50 Hz transmission line
(iii)sending end p.f (iv)percentage
,100 km long ,110 KV between the line
regulation (v)transmission efficiency
at the receiving end has the following
[(i)204 A (ii)75 KV (iii)0.814 lag
constants : ……………
(iv)13.63% (v)93.7%]
Resistance/km/phase = 0.153 Ω
3- A3-phase,50Hz T.L delivers 10MW at
Inductance/km/phase = 1.21 Ω
0.8 p.f lagging at 66 KV , the resistance
Capacitance/km/phase=0.00958 μF The
and inductive reactance of the line per
line supplies a 20000 KW load at 0.9
phase are (10 and20) Ω respectively
p.f lagging , calculate using nominal π
while capacitance admittance is 4*10-4
method representation , the sending
S ,calculate (i)sending end current
end voltage , current , p.f , regulation
(ii)sending end voltage(line to line)
and the efficiency of the line
(iii)sending end power factor
[(i)115.645 KV ; 109 A ; 0.923 lag ;
(iv)transmission efficiency
5.13% ; 97.21% ]
[(i)100A (ii)69.8KV (iii)0.852 (iv)97.5
%]

35
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

3- Long transmission line Connection of T.L


1- Series connection

‫طريقة التحليل المعتمدة لتحليل واخراج قيم الثوابت في‬ To find the overall constants of two T.L
Rigorous method ‫خط النقل الطويل تسمى بـ‬ connected in series
𝑉𝑆 𝐴 𝐵1 𝐴2 𝐵2 𝑉𝑅
=[ 1 ][ ]
𝐼𝑆 𝐶1 𝐷1 𝐶2 𝐷2 𝐼𝑅
A=A1A2+B1C2
B=A1B2+B1D2
C=C1A1+D1C2
𝑍
VS=VR cosh√𝑍 𝑌+IR√𝑌 𝑠𝑖𝑛ℎ√𝑍 𝑌 D=C1B2+D1D2
‫إذا كان الخطين متماثلين‬
𝑌
𝐼𝑆 = 𝑉𝑅 √ sinh √𝑍 𝑌 + 𝐼𝑅 cosh √𝑍 𝑌 A1=A2=A A=A2+BC
𝑍
B1=B2=B B=AB+BD
𝑍
A=cosh√𝑍 𝑌 , 𝐵= √ sinh √𝑍 𝑌 C1=C2=C C=CA+DC
𝑌

D1=D2=D D=CB+D2
𝑌
𝐶 = √ 𝑠𝑖𝑛ℎ√𝑍 𝑌 , 𝐷 = cosh √𝑍 𝑌 2- Parallel connection
𝑍

𝐴𝐷 − 𝐵𝐶 = 1

IS=IS1+IS2 VS=VS1=VS2
IR=IR1+IR2 VR=VR1=VR2
𝑉𝑆1 𝐴 𝐵1 𝑉𝑅
=[ 1 ]
𝐼𝑆1 𝐶1 𝐷1 𝐼𝑅
𝑉𝑆2 𝐴 𝐵2 𝑉𝑅2
=[ 2 ]
𝐼𝑆2 𝐶2 𝐷2 𝐼𝑅2
𝐴1 𝐵1 +𝐴2 𝐵2 𝐵1 𝐵2
𝐴= , B=
𝐵1 +𝐵2 𝐵1 +𝐵2

(A1 − A2 )(D1 − D2 )
C = (C1 + C2 ) −
B1 + B2
𝐵1 𝐷2 + 𝐵2 𝐷1
𝐷=
𝐵1 + 𝐵2

36
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫‪Corona‬‬
‫وهي ظاهرة ظهور وهج شاحب اللون حول الموصل عند‬
‫الفولتيات العالية ويمكن رؤيته في الظالم‬
‫إذا كان البعد بين موصلين أكثر من ‪ 15‬مرة من نصف‬
‫قطر الموصل فان زيادة الجهد عن قيمة فولتية القطع وهي‬
‫الفولتية التي تؤدي الى حدوث ظاهرة الهالة تؤدي الى‬
‫حدوث قفز وميض وشرارة الى جميع مناطق الفراغ‬
‫الواصل بين الموصلين‬
‫اما إذا كان البعد بين الموصلين اقل من ‪ 15‬مرة من نصف‬
‫قطر الموصل فان قفز الوميض او الشرارة تحدث قبل‬
‫ظهور الهالة المرئية‬
‫هناك عدة ظواهر تصاحب هذه الظاهرة‬
‫تأين الهواء المحيط بالموصل‬ ‫‪-1‬‬
‫ظهور ضوء بنفسجي يحيط بالموصل‬ ‫‪-2‬‬
‫ضوضاء وازيز يصاحب الظاهرة‬ ‫‪-0‬‬
‫انبعاث غاز االوزون‬ ‫‪-4‬‬
‫العوامل المؤثرة على ظاهرة الهالة‬
‫الجو المحيط بالموصل‪ :‬إذا كان الجو عاصف او‬ ‫‪-1‬‬
‫ممطر تحدث الهالة بفولتية اقل منها من الجو‬
‫الطبيعي‬
‫‪MECHANICAL‬‬ ‫سطح الموصل‪ :‬إذا كان املسا تكون اقل حدوثا وإذا‬ ‫‪-2‬‬
‫‪DESIGN OF‬‬ ‫كان خشنا يحتوي على نتوءات يكون حدوث هذه‬
‫الظاهرة بنسبة أكبر‬
‫‪OVERHEAD T.L‬‬ ‫نصف قطر الموصل‪ :‬يقل حدوث هذه الظاهرة‬ ‫‪-0‬‬
‫بزيادة نصف القطر‬
‫المسافة بين الموصالت‪ :‬يقل حدوث هذه الظاهرة‬ ‫‪-4‬‬
‫بزيادة المسافة بين الموصالت‬
‫الفولتية العاملة‪ :‬كلما ارتفعت فولتية الخط ازداد‬ ‫‪-5‬‬
‫حدوث ظاهرة الهالة‬
‫االجزاء الرئيسية لخط النقل هي‬
‫طرق تجنب ظاهرة الهالة‬
‫‪1.‬‬ ‫‪Conductors‬‬
‫‪2.‬‬ ‫‪Insulators‬‬ ‫‪ -1‬زيادة قطر السلك او استخدام الموصالت المجوفة‬
‫‪3.‬‬ ‫‪Cross arm‬‬ ‫‪ -2‬زيادة المسافة بين الموصالت‬
‫‪4.‬‬ ‫‪Tower‬‬ ‫محاسن ظاهرة الهالة‬
‫‪ -1‬تأين الهواء المحيط بالموصل حيث تكثر به عدد‬
‫االيونات كأنما قطر الموصل الفعلي يزداد فتقل‬
‫المقاومة‬
‫‪ -2‬تقلل من االجهادات الساكنة الكهربائية التي تعمل‬
‫على سطح الموصل‬
‫‪ -0‬تقلل من ‪– serge voltages‬وهي فولتيات اعلى‬
‫من الفولتية العادية – حيث تصل الفولتية الى قيم‬
‫عالية جدا خالل فترة زمنية قليلة وعادة ما تحدث‬
‫نتيجة للبرق او فتح وغلق قواطع الدورة‬

‫‪37‬‬
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫المساوئ‬ ‫‪Power loss due to corona‬‬


‫‪ -1‬خسائر في القدرة وبذلك تقل كفاءة الخط‬ ‫لدينا قانونين لحساب الفقد المصاحب للهالة‬
‫‪ -2‬يتأكسد السطح الخارجي للموصل بسبب تولد‬
‫غازاالوزون‬ ‫‪1- Peek formula‬‬
‫‪ -0‬التيار المسبب للهالة غير جيبي وهبوط الفولتية غير‬ ‫‪242.2‬‬ ‫𝑟‬
‫جيبي مما يؤدي الى تأثر خطوط النقل المجاورة‬ ‫=‪P‬‬ ‫𝛿‬
‫𝑓(‬ ‫‪+ 25)√𝐷 (𝑉 − 𝑉𝐶 )2 *10-5‬‬

‫وحدة قياس ‪ p‬هي ‪kW/km/phase‬‬


‫‪Disruptive critical voltage‬فولتية القطع الحرجة‪:‬‬ ‫تستخدم ‪ Vc‬اذا كانت الهالة غير مرئية اما اذا كانت‬
‫اقل فولتية طورية تحدث عندها ظاهرة الهالة وتقاس بـ‬ ‫مرئية فنستخدم ‪Vv‬‬
‫‪KV‬‬
‫القدرة الضائعة ‪P :‬‬
‫‪ Visual critical voltage:‬اقل فولتية طورية تكون‬
‫عندها الهالة مرئية‬ ‫التردد ‪f :‬‬
‫فولتية الخط ‪V :‬‬
‫‪2- Peterson formula‬‬
‫‪Vc= E r δ m ln D/r‬‬
‫تستخدم هذه المعادلة اذا تحقق الشرط التالي‬
‫‪0.3‬‬
‫‪Vv= E r δ mv (1+‬‬ ‫‪)ln D/r‬‬
‫𝛿 𝑟√‬ ‫‪V/Vc <1.8‬‬
‫𝑏 ‪3.92‬‬ ‫‪21.2 ∗ 𝑓 ∗ 𝑉 2 ∗ 10−6‬‬
‫=‪δ‬‬ ‫=𝑝‬ ‫𝐹‬
‫𝑡‪273+‬‬ ‫‪𝐷 2‬‬
‫) 𝑟 ‪(ln‬‬
‫الفولتية التي تحدث عندها الهالة ‪Vc :‬‬
‫هي قيمة تستخرج من الجدول التالي‪F‬‬
‫الفولتية التي تكون عندها الهالة مرئية‪Vv :‬‬
‫إذا كانت قيمة ‪V/Vc‬‬ ‫‪V/VC‬‬ ‫‪F‬‬
‫شدة المجال الكهربائي ‪E :‬‬ ‫‪0.6‬‬ ‫‪0.012‬‬
‫غير موجودة في الجدول‬
‫نصف قطر الموصل ‪r :‬‬ ‫يجب ان ترسم منحني‬ ‫‪0.8‬‬ ‫‪0.018‬‬
‫ونسقط القيمة اليجاد قيمة‬ ‫‪1‬‬ ‫‪0.05‬‬
‫المسافة بين الموصالت‪D :‬‬ ‫‪F‬‬ ‫‪1.2‬‬ ‫‪0.08‬‬
‫‪1.4‬‬ ‫‪0.3‬‬
‫كثافة الهواء ‪δ :‬‬ ‫‪1.6‬‬ ‫‪1‬‬
‫الضغط الجوي ‪b :‬‬ ‫‪1.8‬‬ ‫‪3‬‬
‫‪2‬‬ ‫‪6‬‬
‫درجة الحرارة ‪t :‬‬ ‫‪2.2‬‬ ‫‪8‬‬
‫عامل انتظام الشكل ‪m :‬‬
‫مالحظات‬
‫‪ ‬عند الظروف القياسية يكون (‪ )δ=1‬اما إذا لم‬
‫تكن قياسية فتكون القيمة اقل من ‪1‬‬
‫‪ ‬إذا كان السطح الخارجي للموصل املسا فان ‪m=1‬‬ ‫‪Total power losses = 3 p l‬‬
‫اما إذا لم يكن املسا فان القيمة اقل من ‪ 1‬وغالبا ما‬
‫تكون قيمتها محصورة بين ‪ 3..2‬و ‪3.0‬‬ ‫حيث ان ‪ l‬هو طول الخط‬
‫‪ ‬إذا كان الجو عاصف يستخدم القانون االتي‬
‫‪Vc = ( E r δ m ln D/r ) * 0.8‬‬
‫‪ ‬دائما ما تكون قيمة ‪E = 21.2 KV/cm‬‬

‫‪38‬‬
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 1 :Find the corona By using Peterson formula for fair weather
characteristic of a 110 KV , 50 Hz , 3-phase 21.1 𝑓 𝑉 2 ∗10−6
T.L 175 km long consisting of three 1cm PC= 𝐷 𝐹 KW/phase/km
(ln )2
𝑟
diameter stranded copper conductors
spaced in 3 m delta arrangement , V/VC=63.5/55.6 = 1.142
temperature 26o C and barometric pressure F= 0.0713
is 74 cm , m=0.85 mv for local
corona=0.72 and mv for general corona = 21.1∗50∗(63.5)3 ∗10−6
PC= 300 2 *0.0713
0.82 (ln )
0.5

SOLUTION:- = 0.3903 KW/phase/km

Vc=E r δ m ln D/r KV/phase Total power loss = 3*0.3903*175 = 204.5 KW

3.92 𝑏 3.92∗74 For stormy weather


δ=273+𝑡 = 273+26 = 0.97
V/0.8VC=63.5/(0.8*55.6)=1.427 → F=0.3945
r=1/2 = 0.5 cm D=300 cm
21.1∗50∗(63.5)3 ∗10−6
PC= 𝐷 ∗ 0.3945
Vc=21.1*0.97*0.85*0.5 ln 300/0.5 (ln )2
𝑟

=55.6 KV =2.165 KW/phase/km

We given mv=0.72 for local corona & Total power loss=3*2.165*175 = 1138 KW
mv=0.82 for general corona EXAMPLE 2:A certain 3-phase , 220 KV
0.3 𝐷 ,50Hz T.L consist of 1.5 cm radius
Vv=E r δ m ( 1+ ) ln 𝑟
√𝑟 𝛿 conductor spaced 2 m apart in equilateral
0.3 300 triangle if the irregularity factor is 0.85 ,
𝑉𝑣 = 21.1 ∗ 0.97 ∗ 0.72 ∗ 0.5 (1 + ) ln
√0.5 ∗ 0.97 0.5 the temperature is 40o C and atmospheric
pressure is 76 cm calculate the corona
= 67.5 KV
losses per km
0.3 300
Vv=21.1*0.97*0.82*0.5(1+ ) ln 0.5 SOLUTION:-
√0.5∗0.97

= 76.9 KV 3.92 𝑏 3.92 ∗ 76


𝛿= = = 0.95
110 273 + 𝑡 273 + 40
V= = 63.5 𝐾𝑉
√3
Vc=21.1 m δ r ln D/r
By using peek formula fair weather
=21.1*0.85*0.95*1.5 ln 200/1.5
242.2 𝑟
𝑃𝑐 = (𝑓 + 25)√ (𝑉 − 𝑉𝐶 )2 ∗ 10−5 = 125 KV/km
𝛿 𝐷
220
242.2 0.5 Vph= = 127 𝐾𝑉
Pc= (50 + 25)√ (63.5 − 55.6)2 ∗ 10−5 √3
0.97 300

By using peek formula


= 0.481 KW/phase/km
242.2 𝑟
Total power loss=3*0.481*175 = 252.5 KW P= 𝛿
(𝑓 + 25)√𝐷 (𝑉 − 𝑉𝑐 )2 ∗ 10−5
For stormy conditions (VC*0.8)
242.2 1.5
VC=0.8*55.6=44.48 KV P= (50 + 25)√ (127 − 125)2 ∗ 10−5
0.95 200

242.2 0.5 = 0.066 KV


PC= (50 + 25)√ (63.5 − 44.48)2 ∗ 10−5
0.97 300
Total power loss = 0.066 *3=0.198 KW
= 2.79 KW/phase/km

Total power loss=3*2.79*175=1464 KW

39
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 3 : A 3-phase , 50 Hz , 220 KV T.L VC=210/√3=121.25 KV


consists of conductors of 1.2 cm radius spaced
2 m at the corners of an equilateral triangle , Assuming m=1 and δ=1
calculate the corona power loss per km of the
line at temperature of 20o C and barometric VC=E m r δ ln D/r
pressure of 72.2 cm , take the surface factors of
121.25=21.2*1*0.978*1 ln D/0.978
the conductor as 0.96
ln D/0.978 = 5.848
SOLUTION:-
3.92∗72.2 D/0.978=𝑒 5.848
𝛿= 273+20
= 0.966
D/0.978=348.8
VC=21.1 r m δ ln D/r
D=341 cm
=21.1*1.2*0.96*0.966 ln 200/1.2

= 120.66 KV/phase
EXAMPLE 6:A 3-phase ,220 KV ,50Hz
T.L consists of 1.5 cm radius conductor
220
V= = 127 KV/phase spaced 2 m apart in equilateral triangle
√3
formation , if the temperature is 40o C and
242.2 𝑟 atmospheric pressure is 76 cm , calculate
P= (𝑓 + 25)√ (𝑉 − 𝑉𝐶 )2 ∗ 10−5
𝛿 𝐷
the corona loss per km of the line, take
m=0.85
242.2 1.2
= ∗ 75√ (127 − 120.66)2 ∗ 10−5 SOLUTION:-
0.966 200
3.92 𝑏 3.92 ∗ 76
= 0.579 KW/km/phase 𝛿= = = 0.952
273 + 𝑡 273 + 40
Total power losses=3*0.579 = 1.737 KW/km
VC= E r m δ ln D/r
EXAMPLE 4 :A 3-phase line has
conductors 2 cm in diameter spaced =21.2*1.5*0.85*0.952*ln200/1.5
equilaterally 1 m apart , if E=21.2 kV/cm , = 125.9 KV
find the disruptive critical voltage for the
220
line , take air density factor 0.952 and V= = 127 𝐾𝑉
√3
irregularity factor m=0.9
242.2 𝑟
SOLUTION:- P= 𝛿
(𝑓 + 25)√𝐷 (𝑉 − 𝑉𝐶 )2 ∗ 10−5

VC=E r m δ ln D/r
242.2 1.5
P = 0.952 ∗ 75√200 (127 − 125.9)2 ∗ 10−5
=21.2*1*0.9*0.952*ln100/1
= 0.019999 KW/km/phase
=83.64 KV/phase]*√3 =144.8 KV
Total power loss=3*0.019999=0.05998 KW
EXAMPLE 5 :A 132 KV line with 1.956 cm
diameter, conductors is built so that corona
takes place if the line voltage exceeds 210
KV (r.m.s) , if the value of potential
gradient at which ionization occurs can be
taken as 30 KV/cm , find the spacing
between conductors
SOLUTION:-
r= 1.956/2 = 0.978 cm
E=21.2 KV/cm

40
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫‪TUTORIAL PROBLEMS‬‬
‫العوازل‬
‫‪1- Estimate the corona loss for a 3-phase ,‬‬
‫‪110 KV , 50 Hz ,150 km long T.L consisting‬‬ ‫من المعلوم ان موص الالالالالالت خطوط النقل المعلقة عارية‬
‫‪of three conductors each of 10 mm‬‬ ‫وليسالالت معزولة ولذلك فان الوظيفة االولى التي تسالالتخدم‬
‫‪diameter and spaced 2.5 m apart in an‬‬ ‫العوازل من اجلها هي عزل الموص الالالالالالت عن بعض الالالالالها‬
‫‪equilateral triangle formation , the‬‬ ‫البعض وعن ج سم البرج تحت اق صى الجهود وفي ا سوأ‬
‫‪temperature of air is 30o C and the‬‬ ‫الظروف الجوية المتوقعة ‪ ,‬اما الوظيفة الثانية فهي اسناد‬
‫‪atmospheric pressure is 750 mm of‬‬ ‫او حمل الموصالت تحت اسوأ االجهادات الميكانيكية‬
‫‪mercury , take irregularity factor as 0.85 ,‬‬
‫‪ionization of air may be assumed to take‬‬ ‫المواد المستخدمة في صناعة العازل‬
‫‪place , take the dielectric strength of air as‬‬
‫الخزف ((‪porcelain‬‬ ‫‪.1‬‬
‫‪30 KV/cm‬‬ ‫]‪[316.8 KW‬‬
‫الزجاج المقوى (‪)toughened-glass‬‬ ‫‪.2‬‬
‫‪2- Taking the dielectric strength of air to be‬‬
‫‪30 KV/cm , calculate the disruptive critical‬‬ ‫تمتاز العوازل الزجاجية عن الخزفية بما يلي‬
‫‪voltage for a 3-phase line with conductors‬‬
‫‪of 1 cm radius and spaced symmetrically‬‬ ‫في العوازل الزجاجية من الممكن رؤية عدم التجانس‬ ‫‪.1‬‬
‫‪4 m apart‬‬ ‫]‪[220 KV line voltage‬‬ ‫من خالل الفقاعات او غيرها‬
‫‪3- A 3-phase ,220 KV ,50 Hz T.L consists of‬‬ ‫من المزايا العملية للعوازل الزجاجية هو انه عند‬ ‫‪.2‬‬
‫‪1.2 cm radius conductors spaced 2 m at the‬‬ ‫تعرض العازل للضغط نتيجة للجهود العالية او إلي‬
‫‪corners of an equilateral triangle ,‬‬ ‫سبب ميكانيكي خارجي فان ذلك يؤدي الى تكسر‬
‫‪calculate the corona loss per km of the line‬‬ ‫الزجاج الى شظايا صغيرة يمكن رؤيتها على االرض‬
‫‪, the condition of the wire is smoothly‬‬ ‫وبذلك يمكن تمييز العازل المتضرر عن غيره ‪ ,‬اما في‬
‫‪weathered and the weather is fair with‬‬ ‫حالة العوازل الخزفية فان تمييز العازل المتضرر ال يتم‬
‫‪temperature of 20o C and barometric‬‬ ‫بسهولة إذ ان الخزف يتشقق او يتفطر عند تعرضه‬
‫‪pressure of 72.2 cm of Hg‬‬ ‫لالنهيار الكهربائي‬
‫معامل التمدد الحراري للزجاج اقل من معامل التمدد‬ ‫‪.0‬‬
‫الحراري للخزف وهذا يجعل االجهاد الذي يسببه تغير‬
‫درجة الحرارة المحيط قليال في حالة العوازل الزجاجية‬
‫ان تسخين العازل نتيجة تعرضه ألشعة الشمس يكون‬ ‫‪.4‬‬
‫اقل في حالة العازل الزجاجي الن معظم اشعة الحرارة‬
‫تخترق الزجاج بدال من امتصاصها‬

‫العوامل المؤثرة على تصميم العازل‬

‫االجهادات الكهربائية والميكانيكية‪ :‬يجب ان يكون العازل‬ ‫‪-1‬‬


‫قادرا على تحمل االجهادات الكهربائية والميكانيكية التي‬
‫يتعرض لها‬
‫المسار السطحي للتسرب‪ :‬يجب ان يكون المسار‬ ‫‪-2‬‬
‫السطحي للتسرب ذا مقاومة عالية تكفي لمنع أي تيار ذو‬
‫قيمة محسوسة من السريان الى االرض‬
‫سمك العازل‪ :‬يجب ان يكون العازل ذو سمك يكفي لمنع‬ ‫‪-0‬‬
‫حدوث ثقب او اختراق بسبب التعرض الى ارتفاع في‬
‫الجهد‬
‫معامل االمان‪ :‬يجب ان تكون النسبة بين قيمة الجهد الذي‬ ‫‪-4‬‬
‫يحدث عنده الثقب او االختراق وقيمة الجهد الذي يحدث‬
‫عنده قفز الوميض والذي يسمى بمعامل االمان للعازل‬
‫ضد االختراق اذ يجب ان تكون هذه النسبة عالية (أكبر‬
‫من واحد) وذلك لحماية العازل من الفشل التام في تأدية‬
‫عمله‬
‫العوامل الجوية‪ :‬يجب تصميم العازل بحيث يتمكن من‬ ‫‪-5‬‬
‫مقاومة التغيرات الكبيرة والمفاجئة في درجة الحرارة‬
‫وتحمل تأثيرات البرد واالمطار والغبار والدخان‬
‫والضباب واالبخرة الكيمياوية دون تلفها نتيجة تفاعل‬
‫كيميائي‬

‫‪41‬‬
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫انواع العوازل المستخدمة في خطوط النقل‬ ‫‪ ‬عوازل العمود‬

‫‪ ‬عوازل المسمار‬ ‫مزايا عوازل العمود‬

‫مزايا عوازل المسمار‬ ‫لها مضالت متماثلة ذات اقطار متساوية وتبعد عن‬ ‫‪-1‬‬
‫بعضها البعض بمسافات متساوية مما يجعل مسار‬
‫يتكون عازل المسمار من قطعة واحدة او أكثر من‬ ‫‪-1‬‬ ‫التسرب منتظما‬
‫الخزف او الزجاج المقسى وتسمى كل قطعة بالمظلة‬ ‫لها متسعة كهربائية واطئة وتدرج جهد واطئ عن‬ ‫‪-2‬‬
‫تكون المظالت مسارا مناسبا للتسرب بين الموصل‬ ‫‪-2‬‬ ‫الموصالت الحية (المكهربة)‬
‫واالرض‬ ‫يكون الجهد الذي تتكون عنده الهالة عاليا‬ ‫‪-0‬‬
‫يصمم السطح الخارجي للمظالت بحيث ينطبق على‬ ‫‪-0‬‬ ‫اجزاء تثبيت العازل تكون خارج مادة العازل وهذا‬ ‫‪-4‬‬
‫الخطوط المتساوية الجهد للمجال الكهربائي الذي‬ ‫يمنع حدوث اجهادات تسبب انفجار العازل‬
‫تسببه منظومة الموصالت والمسند وبذلك تكون‬ ‫تكسر المظالت نتيجة الجهد الكهربائي او ضرر‬ ‫‪-5‬‬
‫جميع نقاط هذه السطوح متساوية الجهد مما يؤدي‬ ‫ميكانيكي خارجي ال يؤثر في قيمة جهد قفز الوميض‬
‫الى منع سريان تيار التسرب عبر هذه السطوح في‬ ‫يمكن تصميم العازل بحيث يكون محور العازل‬ ‫‪-0‬‬
‫الظروف االعتيادية‬ ‫بوضع افقي دون الحاجة الى استخدام ذراع المسند‬
‫تكون المظالت عادة متباعدة عن بعضها البعض‬ ‫‪-4‬‬
‫وذلك للحصول على أكبر فائدة ممكنة من عملية‬
‫التنظيف التي تسببها االمطار‬ ‫مساوئ عوازل العمود‬
‫تستعمل عوازل المسمار ذات المظلة الواحدة عندما‬ ‫‪-5‬‬
‫يكون جهد الخط ‪ 00‬كيلو فولت او اقل‬ ‫‪ -1‬يستخدم لغاية جهد ‪ 00‬كيلو فولت‬
‫تستخدم عوازل المسمار المتعددة المظالت عندما‬ ‫‪-0‬‬ ‫‪ -2‬صعوبة تجفيف وتحميص الخزف لعازل العمود ذي‬
‫يكون جهد الخط ‪ 22-00‬كيلو فولت‬ ‫القلب الصلد عندما يزداد قطره‬
‫يتم تثبيت عازل المسمار الى ذراع المسند بواسطة‬ ‫‪-.‬‬
‫مسمار محوري فوالذي يتصل من الناحية الثانية‬
‫بحلقة معدنية مسننة من االخل ومثبتة بواسطة‬
‫االسمنت في تجويف داخل العازل‬
‫عوازل المسمار يمكن ان تقارن من حيث السلوك‬ ‫‪-0‬‬ ‫‪ ‬عوازل التعليق‬
‫الكهربائي بمجموعة معقدة من المتسعات‬ ‫مزايا عوازل التعليق‬
‫والمقاومات المربوطة على التوالي حيث تشكل‬
‫المظالت والفسحات الفاصلة بينها متسعات‬ ‫تكون الكلفة االولية لسلسلة عوازل التعليق اقل من‬ ‫‪-1‬‬
‫المنظومة كما يمكن تمثيل مسارات التسرب على‬ ‫الكلفة االولية لعازل مسمار مكافئ لها من حيث‬
‫سطح العازل وعبر العازل نفسه بمقاومات‬ ‫مقدار الجهد‬
‫صنع عوازل التعليق من مادة عازلة متجانسة أسهل‬ ‫‪-2‬‬
‫مما هي عليه في عوازل المسمار الكبيرة الحجم‬
‫مساوئ عوازل المسمار‬ ‫مرونة سلسلة عوازل التعليق تؤدي الى تقليل‬ ‫‪-0‬‬
‫االجهادات الميكانيكية والى تعادل التوتر بين‬
‫‪ -1‬تكون الهالة‬ ‫الموصالت على جهتي المسند‬
‫‪ -2‬زيادة الكلفة االولية عند استخدامه في الفولتيات‬ ‫من الممكن استخدام سلسلة عوازل التعليق مع‬ ‫‪-4‬‬
‫العالية‬ ‫خطوط نقل ذات جهود مختلفة وذلك بتغيير عدد‬
‫العوازل في السلسلة حسب متطلبات خط النقل‬
‫في حالة حصول عطب في أحد عوازل السلسلة‬ ‫‪-5‬‬
‫يستبدل ذلك العازل دون الحاجة الى استبدال السلسلة‬
‫بكاملها‬
‫عندما يكون الحمل الميكانيكي على خط النقل عاليا‬ ‫‪-0‬‬
‫يمكن استعمال سلسلتين او أكثر من عوازل التعليق‬
‫على التوازي‬

‫‪42‬‬
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫مساوئ عوازل التعليق‬


‫‪ -1‬لغاية جهد ‪ 53‬كيلو فولت تكون كلفة عوازل التعليق‬
‫عالية‬
‫‪ -2‬مرونة عوازل التعليق تسمح لموصالت خط النقل‬
‫بان تتأرجح بازاحات كبيرة ولذا يجب ان تكون‬
‫االبعاد بين موصالت الخط في حالة استخدام عوازل‬
‫التعليق اعلى مما هي عليه في حالة استعمال عوازل‬
‫المسمار وهذا يتطلب ان تكون أذرع المسند اكبر‬
‫وبذلك تكون اذرع المسند‬

‫عازل مسمار متعدد المظالت من النوع العادي‬

‫عازل عمود‬
‫مجوف‬
‫عازل مسمار متعدد المضالت من النوع المضاد‬
‫للضباب‬

‫عازل تعليق‬

‫‪43‬‬
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫اختبارات عوازل خطوط النقل‬ ‫‪ -.‬اختبار المسامية‪ :‬هذا االختبار هو اختبار للطالء‬
‫على العوازل الخزفية ‪ ,‬في هذا االختبار يوزن‬
‫اختبار قفز الوميض الجاف‪ :‬يركب العازل وهو‬ ‫‪-1‬‬ ‫العازل وبعد ذلك يغطس لمدة ‪ 24‬ساعة في ماء‬
‫نظيف في الوضع الذي يكون عليه اثناء االستعمال‬ ‫مضغوط وبعدها يوزن مرة ثانية فاذا لوحظت زيادة‬
‫ويسلط عليه جهد ذو تردد ‪ 53‬هرتز وتزداد قيمة هذا‬ ‫في وزن العازل فانه يدل على ان العازل فشل في‬
‫الجهد تدريجيا حتى تصل الى قيمة صغرى محددة‬ ‫اختبار المسامية‬
‫تعتمد على نوع وحجم العازل ويجب ان يتحمل‬ ‫‪ -0‬اختبار النبض ‪ :‬ان انهيار العازل او عدم انهياره ال‬
‫العازل هذه القيمة من الجهد لفترة ال تقل عن ‪03‬‬ ‫يعتمد على الفولتية المسلطة فقط بل يعتمد كذلك على‬
‫ثانية دون حدوث قفز الوميض‬ ‫النسبة التي يزداد فيها هذا الجهد ‪ ,‬بما ان العوازل‬
‫اختبار قفز الوميض الرطب‪ :‬ان هذا االختبار مماثل‬ ‫‪-2‬‬ ‫يجب ان تتحمل الصواعق وتحويرات الفتح والغلق‬
‫لالختبار السابق اال انه يجري بعد تسليط مطر‬ ‫اللتين لهما موجات ذات جبهات حادة االنحدار فيجب‬
‫اصطناعي نظيف ذي مقاومة ودرجة حرارة‬ ‫تصميم العازل بحيث تكون قيمة جهد قفز الوميض‬
‫محددتين وتحدد كذلك نسبة سقوط المطر والزاوية‬ ‫ذي الموجة النبضية ذات الجبهة الحادة االنحدار‬
‫التي يسقط فيها ‪ ,‬يجب ان يتحمل العازل اثناء هذا‬ ‫اعلى من قيمة جهد قفز الوميض ذي الموجة الجيبية‬
‫االختبار قيمة صغرى محددة للجهد اقل من القيمة‬ ‫التي ترددها ‪ 53‬هرتز ‪ ,‬ان النسبة النبضية تتراوح‬
‫المحددة في االختبار االول وذلك لمدة ‪ 03‬ثانية على‬ ‫بين ‪ 1.2‬و ‪ 1.0‬بالنسبة لعوازل التعليق وبين ‪1.0‬‬
‫االقل دون حدوث قفز الوميض‬ ‫و ‪ 2.0‬بالنسبة لعوازل المسمار ‪ ,‬يمكن اجراء هذا‬
‫اختبار قفز وميض التلوث‪ :‬ان هذا االختبار مماثل‬ ‫‪-0‬‬ ‫االختبار للتوصيل الى قيمة جهد قفز الوميض‬
‫لالختبار الثاني ولكنه يجري بعد تسليط ضباب‬ ‫النبضي بتسليط نبضات ذات شكل موجة كما في‬
‫وزخات ملحية ودخان وغبار وبعض الكيمياويات ‪,‬‬ ‫الشكل ادناه‬
‫ان القيمة الصغرى للجهد الذي يجب ان يتحمله‬
‫العازل لمدة ‪ 03‬ثانية دون حدوث قفز الوميض في‬ ‫‪120‬‬
‫هذا االختبار هي نصف القيمة المحدد لالختبار‬
‫‪100‬‬
‫الثاني‬
‫انهيار الثقب ‪ :‬يحدث الثقب عندما تنهار مادة العازل‬ ‫‪-4‬‬ ‫‪80‬‬
‫وتسمح لسريان التيار داخل العازل بين الموصل‬
‫‪60‬‬
‫وذراع المسند ‪ ,‬يتمكن العازل من البقاء صالحا‬
‫لالستعمال بعد حدوث قفز الوميض اما في حالة‬ ‫‪40‬‬
‫حدوث الثقب فيجب استبداله وعلى ذلك يجب تصميم‬
‫‪20‬‬
‫العازل بحيث تكون قيمة الجهد التي يحدث فيها‬
‫الثقب اعلى من تلك التي يحدث فيها قفز الوميض ‪,‬‬ ‫‪0‬‬
‫في هذا االختبار يغطس العازل في زيت عازل‬ ‫‪0‬‬ ‫‪10‬‬ ‫‪20‬‬ ‫‪30‬‬ ‫‪40‬‬ ‫‪50‬‬
‫نظيف لمنع حدوث قفز الوميض ويزداد الجهد‬
‫المسلط عليه تدريجيا ويجب ان يتحمل العازل في‬
‫هذه الحالة قيمة جهد مقدارها ‪ 1.0‬مرة بقدر قيمة‬
‫الجهد التي يحدث فيها قفز الوميض الجاف دون‬
‫حدوث ثقب في العازل‬
‫االختبار الميكانيكي‪ :‬تعرض عوازل التعليق الى‬ ‫‪-5‬‬
‫توتر مقداره ‪ 1.2‬مرة بقدر اعظم حمل ميكانيكي‬
‫تتعرض له اثناء استعمالها اما عوازل المسمار‬
‫فتتعرض الى عزم انحناء يعادل ‪ 2.5‬مرة ألعظم‬
‫حمل ميكانيكي تتعرض له اثناء االستعمال وبعدئذ‬
‫يعاد االختبار االول‬
‫اختبار درجة الحرارة‪ :‬يغطس العازل في حوض‬ ‫‪-0‬‬
‫ماء بدرجة حرارة ‪ .‬مئوية لمدة ساعة وبعدها‬
‫يوضع في حوض ماء درجة حرارته ‪ .3‬مئوية لمدة‬
‫ساعة ايضا وتكرر هاتان العمليتان ‪ 0‬مرات‬
‫تستغرق كل منها فترة ساعة وبعدها يجفف العازل‬
‫ويعاد عليه االختبار االول‬

‫‪44‬‬
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫الدائرة المكافئة للعوازل‬ ‫‪Voltage distribution on a string‬‬


‫الفولتية المسلطة توزع على اقراص السلسلة وتكون‬ ‫‪of insulator‬‬
‫فولتية طورية وتكون الفولتية على القرص االول كبيرة‬ ‫‪ -1‬إذا كانت السلسلة بدون حلقة حارسة‬
‫تمثل السلسلة كهربائيا بمجموعة من المتسعات‬ ‫‪C1 = k C‬‬
‫‪V2 = ( k+1) V1‬‬
‫‪V3 = ( k2+3k+1) V1‬‬
‫‪V=V1+V2+V3‬‬
‫𝑉‬
‫‪Ƞ = 3𝑉 ∗ 100%‬‬
‫‪3‬‬

‫اذا كانت السلسلة مكونة من ‪ 4‬اقراص‬


‫‪C : self-capacitance‬‬
‫‪V4=( k3+5k2+6k+3)V1‬‬
‫‪C1 : shunt capacitance‬‬
‫‪V=V1+V2+V3+V4‬‬
‫ترتبط ‪ C‬مع ‪ C1‬بمعامل يرمز له ‪ k‬حسب العالقة التالية‬ ‫𝑉‬
‫‪Ƞ=4𝑉 *133%‬‬
‫‪4‬‬
‫‪C1=kC‬‬
‫ودائما ما تكون قيمة ‪ k‬اقل من واحد وكل ما كانت قليلة‬
‫ازدادت كفاءة السلسلة‬ ‫𝑉‬
‫=‪Ƞ‬‬ ‫‪*100%‬‬ ‫القانون العام للكفاءة }‬
‫𝑛𝑉𝑛‬
‫تكون كفاءة السلسلة اكبر ما يمكن عندما تكون الفولتية‬
‫متساوية تقريبا على جميع االقراص‬
‫‪𝑉𝑝ℎ‬‬
‫𝑉𝑛=‪ƞ‬‬
‫𝑛‬
‫‪ -2‬في حالة وجود الحلقة الحارسة‬
‫‪ n‬عدد االقراص‬
‫‪V1=V2=V3=V4=V‬‬
‫‪ Vn‬فولتية القرص القريب من المسند‬
‫يتم تحليل الدائرة اعتمادا على‬
‫التيارات الداخلة والخارجة في كل‬
‫طرق زيادة كفاءة السلسلة‬
‫عقدة في الدائرة المكافئة‬
‫‪ -1‬زيادة طول ذراع المسند‪ :‬حيث تقل قيمة ‪ k‬كلما زاد‬
‫الطول وتكون فولتيات االقراص قريبة من بعض‬
‫وبذلك تزداد الكفاءة ‪ ,‬ولكن مساوئها هو زيادة الكلفة‬
‫وكذلك تصبح المسافة بين النقاط متباعدة وبذلك‬
‫يزداد الشد‬ ‫مجموع التيارات الداخلة = مجموع التيارات الخارجة‬
‫‪ -2‬تدريج العوازل‪ :‬بما ان القرص القريب من الموصل‬
‫يتعرض الى االنهيار بصورة اكبر لذا فانه من‬
‫المستحسن صناعة القرص القريب من المسند بحجم‬
‫اكبر وسمك اكبر وبالتدريج بقية االقراص ‪ ,‬وفي‬
‫هذه الطريق نحتاج الى تصنيع حلقات بأحجام مختلفة‬
‫‪ -0‬استخدام الحلقة الحارسة‪ :‬وهي حلقة معدنية تحيط‬
‫بالقرص وعملها هو اضافة متسعات اضافية على‬
‫التوازي مع االقراص‬

‫‪45‬‬
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 1 : In 33 kv T.L there are three V2=( k+1)V1


units in the string of insulators, if the
V2=kV1+V1
capacitance between each insulator pin
and earth is 11% of self-capacitance of 𝑉2 −𝑉1 11−8
k= 𝑉1
= 8
= 0.375
each insulator , calculate (i) the
distribution of voltage over 3 insulator (ii) V3=( k2+3k+1)V1
string efficiency
V3=18.12 kv
SOLUTION:-
V=V1+V2+V3=37.12 kv
𝑠ℎ𝑢𝑛𝑡 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑎𝑛𝑐𝑒
k= 𝑠𝑒𝑙𝑓 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑎𝑛𝑐𝑒
VL=√3*37.12 = 64.28 kv
=0.11 𝑉 37.12
Ƞ = 3𝑉 ∗ 100% = 3∗18.12 ∗ 100%
33 𝑘𝑣 3
V= = 19.05 kv
√3
= 68.28 %
V2=( k+1)V1
EXAMPLE 3 : Each line of 3-phase system
=(0.11+1)V1 is suspended by a string of 3-similar
insulators, if the voltage across the line unit
= 1.11 V1 is 17.5 kV , calculate the line to neutral
V3=(k2+3k+1)V1 voltage , assume that the shunt capacitance
between each insulator and earth is 1/8 th of
= (0.112+3*0.11+1)V1 the capacitance of the insulator itself also
find the string efficiency
= 1.342 V1
SOLUTION:-
V=V1+V2+V3
k=1/8=0.125
= V1+1.11V1+1.342V1
V3=17.5 kV
V=3.452 V1
V3=(k2+3k+1)V1
19.05 = 3.452 V1
V1=V3/1.39 = 12.59 kV
V1=5.52 kv
V2=(k+1)V1=1.125*12.59=14.16 kV
V2=1.11V1=6.13 kv
V=V1+V2+V3=44.25 kV
V3=1.342 V1 = 7.4 kv
𝑉 19.05 VL=√3*44.25 = 76.64 kV
Ƞ= ∗ 100% = ∗ 100%
3𝑉3 3∗7.4
𝑉 44.25
Ƞ=3𝑉 ∗ 100% = 3∗17.5*100% = 84.28 %
= 85.8 % 3

EXAMPLE 2 :3-phase T.L , is being EXAMPLE 4 :A 3-phase T.L supported by


supported by 3 disks insulators , the units of post type insulators , each unit
potentials across top unit (near to the consist of a stack of a 3-pin type insulators
tower)and middle unit are 8 kv and 11 kv , fixed on the top of the other , the voltage
respectively , calculate (i) k (ii)the line across the lowest insulator is 13.1 kV and
voltage (iii)string efficiency that across the next unit is 11 kV , find the
bus bar voltage
SOLUTION:-
SOLUTION:-
V1=8 kv
V3=13.1 kV V2=11 kV
V2=11 kv

46
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

V2=(k+1)V1 => V1=V2/(k+1) ….. (1) Because C/C1=10


V3=(k2+3k+1)V1 XC1=10 Ω
V1=V3/(k2+3k+1) …………………..(2)
From (1) and (2)
k= 0.1
11 𝑘𝑉
V1= = 10 kV
1.1

Vph=V1+V2+V3=34.1 kV

VL=√3*34.1 = 59 kV
EXAMPLE 5 : An insulator string consist V1= 1 Ω * 1 A = 1 volt
of three units, each having a safe working V2= 1 Ω * 1.1 A = 1.1 volt
voltage of 15kV , k=1/8 , find the maximum
safe working voltage of the string , also V3 = 1 Ω * 1.31 A = 1.31 volt
find the string efficiency
V4= 1 Ω * 1.65 A = 1.65 volt
SOLUTION:-
V=V1+V2+V3+V4 = 5.06 volt
V3=15 kV k=0.125 1
V1/V = 5.06 *100% = 19.76 %
V2=(k+1)V1 => V1=0.89 V2
1.1
V3=(k2+3k+1)V1 V2/V = *100% = 21.74 %
5.06
1.31
V3= (1.39)*0.89 V2 V3/V = 5.06 *100% = 25.9 %
V3=1.236 V2 1.65
V4/V = 5.06 *100% = 32.9 %
15 𝑘𝑉
V2= 1.236 =12.13 kV 𝑉 5.06
Ƞ= ∗ 100% = ∗ 100%
4𝑉4 4∗1.65
V1=0.89V2=0.89*12.13=10.79 kV
= 76.6 %
V=V1+V2+V3=37.92 kV
EXAMPLE 7 :A string of 5 insulators is
𝑉 37.92
Ƞ= ∗ 100% = ∗ 100% connected across a 100 kV line, if the
3𝑉3 3∗15
capacitance of earth disk to earth is 0.1 of
= 84.26 % the capacitance of the insulator , calculate
(i) the distribution voltage on the insulator
EXAMPLE 6:A string of 4 insulators ,
discs (ii) ƞ
k=0.1 , find (i)the voltage distribution
across various units expressed as a SOLUTION:-
percentage of total voltage across the
string (ii)string efficiency Let XC=1 Ω

SOLUTION:- Because k=0.1 , XC1= 10Ω

‫ فان الحل بالطريقة‬0 ‫إذا كان عدد االقراص أكثر من‬


‫السابقة يكون صعبا ومعقدا لذا فان هناك طريقة مبسطة‬
‫لحل المسائل في هذه الحالة وهي تعويض قيم كل من‬
‫المتسعة الذاتية ومتسعة التوازي بما يساويها بالممانعة‬
Let XC= 1 Ω

47
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

V1= 1 Ω *1 A = 1 volt V4=(k3+5k2+6k+1)V1


V2= 1 Ω *1.1 A = 1.1 volt = 26.49 kV
V3= 1 Ω * 1.31 A = 1.31 volt V=V1+V2+V3+V4= 68.69 kV
V4 = 1 Ω * 1.65 A = 1.65 volt VL=√3*68.69 kV = 119 kV
V5 = 1 Ω * 2.16 A = 2.16 volt EXAMPLE 9 : A string of 4 insulators,
k=1/5 , find (i)voltage distribution across
V = V1+V2+V3+V4+V5 = 7.22 volt
various units as a percentage of a total
VL= 100 kV given voltage across the string (ii) string
100 𝑘𝑉
efficiency
Vph= =57.7 kV
√3
SOLUTION:-
V1=1/7.22 => V1=0.138*V
let XC= 1 Ω
V1=0.138*57.7=7.96 kV
because k=1/5
V2=1.1/7.22 => V2=0.152*V
XC1=5 Ω
V2= 0.152*57.7 = 8.77 kV
V3=0.182*V = 0.182*57.7 = 10.5 kV
V4=0.288*V = 0.288*57.7 = 13.16 kV
V5=0.3*V = 0.3*57.7 = 17.3 kV
57.7
Ƞ=3∗17.3*100% = 66.7 %

EXAMPLE 8 : Each conductor of 3-phase


transmission line is suspended by a string
of 4 suspension type disc insulators if the V1=1 volt
potential difference across the second unit V2=1.2 volt
from the top is 13.2 kV and across the third
from top is 18 kV , find the voltage between V3=1.64 volt
conductors V4=2.408 volt
SOLUTION:- V=V1+V2+V3+V4=6.246 volt
V2=13.2 kV 1
V1/V = 6.248 *100% = 16 %
V3=18 kV
1.2
V2/V = *100% = 19.2 %
V2=(k+1)V1 6.248

V3=(k2+3k+1)V1 V3/V = 26.3 %

𝑉3 𝑘 2 + 3𝑘 + 1 V4/V = 38.5 %
=
𝑉2 𝑘+1 6.248
Ƞ=4∗2.408 ∗ 100 % = 64.86 %
18 𝑘 2 + 3𝑘 + 1
=
13.2 𝑘+1
k=0.2
2 𝑉 13.2
V1=𝑘+1 = 1.2
= 11 𝑘𝑉

48
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 10 : The self-capacitance of each TUTORIAL PROBLEMS


unit in a string of three suspension insulators is
C , the shunting capacitance of the connecting 1- In a 3-phase overhead system ,each
metal work of each insulator to earth is 0.15 C line is suspended by a string of 3
while for line its 0.1 C , calculate (i)the voltage insulators , the voltage across the top
across each insulator as a percentage of the line unit and the middle unit are 10 kV and
voltage to earth (ii)ƞ 11 kV respectively , calculate (i) k
(ii)string efficiency (iii)line voltage
[(i)0.1 (ii)86.76% (iii)59kV]
2- Each line of 3-phase system is
suspended by a string of 3 similar
insulators , if the voltage across the line
At node A unit is 17.5 kV , calculate the line to
neutral voltage and string efficiency ,
𝐼2 + 𝑖1′ = 𝐼1 + 𝑖1 assume that k=0.1 [52kV , 86.67%]
V2 wC+(V2+V3)0.1 wC=V1 wC+0.15CV1 w 3- The three bus-bar conductors in an
outdoor sub-station are supplied by
0.1 V3=1.15 V1 – 1.1 V2 units of post insulators , each unit
V3=11.5 V1 – 11 V2 ………………(1) consist of a stack of 3-pin insulators
fixed one on the top of the other , the
At node B voltage across the lowest insulator is
𝐼3 + 𝑖2′ = 𝐼2 + 𝑖1 8.45 kV and that across the next is
7.25kV , find the bus-bar voltage of the
V3 wC+V3 0.1wC=V2 wC+(V1+V2)0.15wC station [38.8 kV]
1.1V3=1.15V2+0.15V1 …………..(2) 4- A string of suspension insulators
consists of three units , k=1/6 if the
From (1) and (2) maximum voltage per unit is not to
1.1(11.5V1 – 11V2)=1.15V2+0.15V1 exceed 35 kV , determine the maximum
voltage that the string can with stand ,
12.5𝑉
V2= 13.251 ……………………………(3) also calculate ƞ [84.7 kV , 80.67%]
5- A string of 4 insulators has self-
Put (3) in (2) capacitance equal to 4 times the pin to
12.5𝑉1 14.8𝑉1 earth capacitance , calculate (i) the
V3=11.5V1 – 11( )=
13.25 13.25 voltage distribution across various
V=V1+V2+V3 units as a percentage of total voltage
across the string (ii)string efficiency
12.5 14.8 40.55𝑉1
=V1(1 + + )= [(i)14.5% , 18.1% , 26.2% , 40.9%
13.25 13.25 13.25
(ii)61.2%]
13.25𝑉1
V1= = 0.326𝑉 𝑣𝑜𝑙𝑡 6- A string of 4 suspension insulators is
40.55
connected across a 285 kV line , k=1/5
12.25 ∗ 0.326𝑉
𝑉2 = = 0.307𝑉 𝑣𝑜𝑙𝑡 calculate (i)the potential difference
13.25
across each unit (ii)string efficiency
14.8 ∗ 0.326𝑉 [(i)27.65 kV , 33.04kV , 43.85kV,60kV
𝑉3 = = 0.364𝑉 𝑣𝑜𝑙𝑡
13.25 (ii)68.5%]
𝑉1 0.326𝑉
= ∗ 100% = 32.6%
𝑉 𝑉
𝑉2 0.306𝑉
= ∗ 100% = 30.6%
𝑉 𝑉
𝑉3 0.364𝑉
= ∗ 100% = 36.4%
𝑉 𝑉

49
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫‪7- Each of three insulators forming a‬‬ ‫‪Sag in overhead lines‬‬


‫‪string has self-capacitance of C farad ,‬‬
‫‪the shunt capacitance of each cap of‬‬ ‫في خطوط النقل الكهربائي تكون الموصالت معلقة على‬
‫‪insulators is 0.25 C to earth and 0.15 C‬‬ ‫ابراج عن طريق عوازل تعزلها عن جسم البرج ‪ ,‬وفي‬
‫‪to line , calculate the voltage‬‬ ‫المسافة بين برجين متتالين والتي تعرف بالباع او خطوة‬
‫‪distribution across each insulator as a‬‬ ‫البرج يكون السلك معلقا تحت تأثير ثقله – وثقل ما قد‬
‫‪percentage of line voltage to earth and‬‬ ‫يتراكم عليه من ثلوج وتأثير ضغط الرياح ان وجدت –‬
‫‪the string efficiency‬‬ ‫‪[(i)31.7% ,‬‬ ‫ويتخذ السلك شكل منحني ‪ ,‬ارتخاء السلك عند أي نقطة‬
‫]‪29.4% , 38.9% ,(ii)85.7%‬‬ ‫هو مقدار انخفاض هذه النقطة عن مستوى نقطة التعليق‬
‫‪8- Each of the three insulators forming a‬‬ ‫‪ ,‬وفي حالة كون نقطتي التعليق على نفس المستوى يحدث‬
‫‪string has a self-capacitance of C farad‬‬ ‫اقصى ارتخاء للسلك في منتصف المسافة بين البرجين ‪,‬‬
‫‪, the shunt capacitance of each‬‬ ‫ونظرا الهتمامنا بأقصى ‪ sag‬فقط حيث انه هو الذي يحدد‬
‫‪insulator is 0.2 C to earth and 0.1 C to‬‬ ‫مقدار الخلوص بين الموصل واالرض فانه عند اطالق‬
‫‪line , a guard ring increases the‬‬ ‫كلمة ‪ sag‬نقصد به مقدار االنخفاض الحادث للسلك عند‬
‫‪capacitance of line of the metal work of‬‬ ‫اقرب نقطة من سطح االرض‬
‫‪the lowest insulator to 0.3 C ,calculate‬‬
‫‪the string efficiency of the arrangement‬‬
‫‪(i)with the guard ring (ii) without‬‬
‫‪guard ring‬‬ ‫]‪[(i)95% (ii)86.13%‬‬
‫‪9- A 3-phase T.L is being supported by‬‬
‫‪three disc suspension insulators , the‬‬
‫‪potential across the first and second‬‬
‫‪insulator from the top are 8 kV and‬‬
‫‪11kV respectively , calculate (i) line‬‬
‫‪voltage (ii)k (iii) the string efficiency‬‬
‫] ‪[(i)64.28 V , (ii) 0.375 , (iii)68.28 %‬‬
‫‪10- A 3-phase T.L is supported on 4-disc‬‬
‫‪suspension insulators , the voltage‬‬ ‫العوامل التي تؤثر على ‪sag‬‬
‫‪across the second and third discs are‬‬
‫‪13.2 kV and 18 kV respectively , find‬‬ ‫وزن السلك ‪ : wc‬عادة ما يستخدم وزن السلك لكل وحدة‬ ‫‪-1‬‬
‫‪the line voltage and mention the‬‬ ‫طول كمقياس لوزن السلك ‪ ,‬وكلما زاد وزن السلك زاد‬
‫‪nearest‬‬ ‫‪standard‬‬ ‫‪voltage‬‬ ‫الـ ‪sag‬‬
‫المسافة بين البرجين ‪ : L‬كلما زادت المسافة بين الرجين‬ ‫‪-2‬‬
‫]‪[118.75kV , 120 kV‬‬
‫زاد الـ ‪sag‬‬
‫الشد في السلك ‪ : T‬هو من العوامل التي تؤثر تأثيرا كبيرا‬ ‫‪-0‬‬
‫في مقدار الـ ‪ sag‬وكلما زاد الشد في السلك قل الـ ‪sag‬‬
‫العوامل البيئية‪ :‬كتراكم الثلوج على االسالك وضغط‬ ‫‪-4‬‬
‫الرياح‬
‫درجة الحرارة‪ :‬كلما زادت درجة الحرارة تمدد السلك‬ ‫‪-5‬‬
‫وزاد طوله وزاد الـ ‪ Sag‬ويحدث العكس عند انخفاض‬
‫درجة الحرارة‬
‫اهمية حسابات الـ ‪sag‬‬
‫من خالل حسابات الـ ‪ sag‬يمكن تحديد مقدار الخلوص‬
‫بين السلك واالرض والتأكد مما اذا كان مطابقا لشروط‬
‫االمن والسالمة ‪ ,‬وايضا الن الـ ‪ sag‬يؤثر في مقدار الشد‬
‫الذي يتعرض له السلك فانه يجب ضبط الخلوص عند‬
‫تركيب الموصالت بحيث ال يتعدى الشد في الموصل‬
‫القيمة المسموح بها حتى عند تعرض االسالك الى اسوا‬
‫حاالت التحميل الميكانيكي الممكنة‬

‫‪50‬‬
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

1- When supports at equal 3- Effect of wind and ice


levels loading
‫ على سطح الموصل‬t ‫عند تراكم طبقة من الثلوج سمكها‬
‫فأنها تضيف وزنا اضافيا يؤثر الى االسفل ويضاف الى‬
‫ وهذا الوزن عبارة عن وزن الثلج‬, ‫وزن الموصل‬
‫المتراكم ولحساب هذا الوزن نحسب اوال حجم طبقة الثلج‬
‫المتراكم لوحدة االطوال‬

𝑙
𝑤 ( )2 𝑤 𝑙2
S= 2
=
2𝑇 8𝑇

Wt=√(𝑤 + 𝑤𝑖 )2 + (𝑤𝑤 )2
2- When the support are at
W = weight of conductor per unit length
unequal levels
Wi = weight of ice per unit length
𝜋
Wi =density of ice*4 [(d+2t)2-d2]*l

= density of ice * π t (d+t)


Ww = wind force per unit length
= wind pressure * [(d+2t) * l ]

𝑤𝑤
𝑡𝑎𝑛𝜃 =
𝑤 + 𝑤𝑖
𝑤 𝑥12 𝑤 𝑥22
S1= , S2= 𝑤𝑡 𝑙 2
2𝑇 2𝑇
𝑆=
𝑙 𝑇ℎ 𝑙 𝑇ℎ 2𝑇
X1= − , X2 = +
2 𝑤𝑙 2 𝑤𝑙 Vertical sag = S cosθ
𝑤𝑙
h= (x2 – x1)
2𝑇

Where
l: length of span
w: weight per unit length of conductor
T: tension in the conductor

51
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 1 :132 kV T.L has the data, EXAMPLE 3 : A T.L has aspan of 200 m
wt of conductor = 680 kg/km between level supports , the conductor has
length of span = 260 m across sectional area of 1.29 cm2 , wc=1770
ultimate strength = 3100 kg kg/km and has a breaking stress of 4218
safety factor = 2 kg/cm2 , calculate a sag of a safety factor of
calculate the height above the ground at 5 , allowing a wind pressure of 122 kg per
which the conductor should be supported , square meter of projected area , what is the
ground clearance required is 10 m vertical sag
SOLUTION:- SOLUTION:-
Wc=680/1000 =0.68 kg Wc = 1170/1000 =1.17 kg
𝑢𝑙𝑡𝑖𝑚𝑎𝑡𝑒 𝑠𝑡𝑟𝑒𝑛𝑔𝑡ℎ 3100 𝑏𝑟𝑒𝑎𝑘𝑖𝑛𝑔 𝑠𝑡𝑟𝑒𝑠𝑠 ∗ 𝑐𝑟𝑜𝑠𝑠 𝑠𝑒𝑐𝑡𝑖𝑜𝑛𝑎𝑙 𝑎𝑟𝑒𝑎
T= 𝑠𝑎𝑓𝑒𝑡𝑦 𝑓𝑎𝑐𝑡𝑜𝑟
= 2
= 1550 𝑘𝑔 T= 𝑠𝑎𝑓𝑒𝑡𝑦 𝑓𝑎𝑐𝑡𝑜𝑟

l = 260 m 4218 ∗ 1.29


= = 1088 𝑘𝑔
𝑤 𝑙 2 0.68∗(260)2
5
𝑆= = 8∗1550 =3.7 m
8𝑇 𝐴 = 𝜋𝑟 2
Conductor should be supported at the
height of 10+3.7=13.7 m 4 ∗ 𝑎𝑟𝑒𝑎 4 ∗ 1.29
𝑑=√ = √ = 1.28 𝑐𝑚
𝜋 𝜋
EXAMPLE 2 :A T.L has a span of 150 m
between level supports, the conductor has Ww =pressure*project area in m2
across sectional area of 2 cm2, the tension
in the conductor is 2000 kg, if the specific =122*(1.28*10-2*1)=1.56 kg
gravity of the conductor material is 9.9
gm/cm3 and wind pressure is 1.5 kg/m Wt=√(𝑤𝑡 + 𝑤𝑖𝑐𝑒 )2 + 𝑤𝑤2
length, calculate the sag and the vertical
= √(1.17)2 + (1.56)2 = 1.95 𝑘𝑔
sag
𝑤𝑡 𝑙2 1.95∗(200)2
SOLUTION:- S= = = 8.96 𝑚
8𝑇 8∗1088

Ww=1.5 kg , T=2000 kg , l=150 m 𝑤𝑤


𝜃 = tan−1 = 53.13𝑜
𝑤𝑐
Wc=specific gravity*volume of 1m conduc.
Vertical sag = S cosθ
=9.9*2*100=1.98 kg
= 8.96 cos 53.13
Wt=√𝑊𝑤2 + 𝑊𝑐2 =√(1.5)2 + (1.98)2
= 5.37 m
= 2.48 kg
EXAMPLE 4 :T.L has a span of 275 m
𝑤 𝑙2 2.48∗(150)2
S= 8𝑡 𝑇 = 8∗2000 =3.48 m between level supports , the conductor has
an effective diameter 1.96 cm and weight
𝑤𝑤
tanθ = 𝑤𝑐
= 0.76 0.865 kg/m , its ultimate strength is 8060 kg
, if the conductor has ice coating of radial
𝜃 = tan−1 0.76 = 37.23𝑜 thickness 1.27 cm and is subjected to a wind
pressure of 3.9 gm/cm2 of projected area ,
𝑣𝑒𝑟𝑡𝑖𝑐𝑎𝑙 𝑠𝑎𝑔 = 𝑆 cos 𝜃 = 3.48 cos 37.23 calculate the sag for a safety factor of 2
= 2.77 𝑚 weight of 1 C.C of ice is 0.91 gm
SOLUTION:-
l= 275 m , d= 1.96 cm

52
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

wc= 0.865 kg EXAMPLE 6 : An T.L span of 150 m


between level supports , the conductor has
ice coating thickness (t) = 1.27 cm
across sectional area of 2 cm2 , the ultimate
T = 8060/2 = 4030 kg strength is 5000 kg/cm2 and safety factor
is 5 , the specific gravity of a material is
Volume of ice =π t (d+t)*100 =1288 cm3 8.8 gm/c.c , the wind pressure is 1.5 kg/m ,
Wice = 0.91*1288 =1172 gm = 1.172 kg calculate the height of the conductor above
the ground level at which it should be
Wt = √(𝑤𝑐 + 𝑤𝑖𝑐𝑒 )2 + (𝑤𝑤 )2 supported if a minimum clearance of 7 m is
to be left between the ground and the
= √(0.865 + 1.172)2 + (1.755)2 conductor

= 2.688 𝑘𝑔 SOLUTION:-
𝑤𝑡 𝑙2 2.688∗(275)2 l= 150 m , ww=1.5 kg
S= 8𝑇
= 8∗4030
= 6.3 𝑚
wc=conduc. area*specific gravity*100 cm
EXAMPLE 5 : A T.L has a span of 214 m
between level supports, the conductor has a = 2 * 8.9 * 100 = 1780 gm = 1.78 kg
cross sectional area of 3.225 cm2 , 5000∗2
calculate the factor of safety under the T= 5
= 2000 𝑘𝑔
following conditions , vertical sag = 2.35
m , wind pressure = 1.5 kg/m , breaking Wt=√𝑤𝑤2 + 𝑤𝑐2 = √1.782 + 1.52
stress=2540 kg/cm2 , wc = 1.125 kg/m
=2.33 kg
SOLUTION:- 𝑤𝑡 𝑙2 2.33∗1502
S= 8𝑇
= 8∗2000
= 3.28 𝑚
l = 214 m , wc = 1.125 kg , ww = 1.5 kg
𝑤𝑐
Vertical sag = S * cosθ = S *
wt = √𝑤𝑤2 + 𝑤𝑐2 = √(1.125)2 + (1.5)2 𝑤𝑡

1.78
= 1.875 kg = 3.28*2.33 = 2.5 𝑚

1.5 Conductor should be supported at a height


𝜃 = tan−1 = 53. 13𝑜
1.125 of 7+2.5 = 9.5 m
Cosθ = 0.6
𝑣𝑒𝑟𝑡𝑖𝑐𝑎𝑙 𝑠𝑎𝑔 2.35
S= 𝑐𝑜𝑠𝜃
= 0.6
= 3.92 𝑚

𝑤𝑡 𝑙2 1.875∗(214)2
S= 8𝑇
→ 𝑇= 8∗3.92

T= 2738 kg
𝑏𝑟𝑒𝑎𝑘𝑖𝑛𝑔 𝑠𝑡𝑟𝑒𝑠𝑠∗𝑐𝑜𝑛𝑑𝑢𝑐𝑡𝑜𝑟 𝑎𝑟𝑒𝑎
T= 𝑠𝑎𝑓𝑒𝑡𝑦 𝑓𝑎𝑐𝑡𝑜𝑟

2540∗3.225
Safety factor= 2738
=3

53
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 7: And towers of 30 m and 90


m supports a T.L conductor at water
crossing the horizontal distance between
towers is 500 m , if the tension in the
conductor is 1600 kg , find the minimum
clearance of the conductor and water and
clearance mid-way between the supports ,
weight of conductor is 1.5 kg/m
SOLUTION:- 8000∗2.2
T= =3520 kg
5
wt = wc+wi=1.925+1 = 2.925 kg
𝑙 𝑇ℎ 600 3520∗15
X1 =2 − 𝑤 𝑙 = 2
− 2.925∗600 = 270 𝑚
𝑙 𝑇ℎ 600 3520∗15
X2=2 + 𝑤 𝑙 = 2
+ 2.925∗600 = 330 𝑚

𝑤𝑡 𝑥22 2.925 (330)2


S2= = = 45.24 𝑚
2𝑇 2∗3520

h = 90 – 30 = 60 m EXAMPLE 9 :A T.L at a river crossing is


𝑙 𝑇ℎ 500 1600∗60 supported from two towers at a heights of
x1 = − = − = 122 𝑚 40 m and 90 m above water level , the
2 𝑤𝑙 2 1.5∗500
𝑙 𝑇ℎ 500 1600∗60
horizontal distance between the towers
x2=2 + 𝑤 𝑙 = 2
+ 1.5∗500 = 378 𝑚 being 400 m , if the maximum allowable
tension is 2000 kg , find the clearance
𝑤 𝑥12 1.5∗(122)2
S1= = =7𝑚 between the conductor and water at a point
2𝑇 2∗1600
mid-way between the towers , wc=1 kg
Clearance of the lowest point O from
water level = 30 - 7 = 23 m SOLUTION:-

Mid-way = point P
x = 250 – x1 = 250 – 122 =128 m
𝑤 𝑥2 1.5 (128)2
Smid = 2𝑇
= 2∗1600
= 7.68 𝑚

Clearance of mid-point P from water level


is = 23+7.68 = 30.68 m
EXAMPLE 8 :A T.L , wc=1.925 kg , the h = 90 – 40 = 50 m
area of x-sectional of the conductor is 2.2
cm2 and the ultimate strength is 8000 l = 400 m , T=2000 kg
kg/cm2 , the supports are 600 m apart wc= 1 kg
having 15 m deference of levels , find the
𝑙 𝑇ℎ 400 2000∗50
sag from the taller of the two supports x1=2 − 𝑤 𝑙 = 2
− 1∗400 = −50 m
which must be allowed so that the factor of
𝑙 𝑇ℎ 400 2000∗50
the safety shall be 5 , assume that ice load x2=2 + 𝑤 𝑙 = 2
+ 1∗400 = 450 𝑚
is 1 kg per meter and there is no wind
pressure x = 𝑙/2 – x1 = 200 – (-50) = 250 m
SOLUTION:- 𝑤 𝑥2 1∗(250)2
Smid = 2𝑇
= 2∗2000
= 15.6 𝑚
l = 600 m , wi=1 kg , h=15 m ,
𝑤 𝑥22 1∗(450)2
wc=1.925 kg S2 = 2𝑇
= 2∗2000
= 50.6 𝑚

54
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

Height of B from P = S2 - Smid


=50.6 – 15.6 = 35 m
Clearance of mid-point P above water
level = 90 – 35 = 55 m

TUTORIAL PROBLEMS
5- A T.L has a span of 250 m between
1- A T.L conductor is supported from two supports, the supports being at the
towers at heights of 70 m above water same level, the conductor has a cross-
level , the horizontal distance between sectional area of 1.29 cm2, the ultimate
the towers is 300 m, if the tension in the strength is 4220 kg/cm2 and factor of
conductors is 1500 kg, find the safety is 2 , the wind pressure is 40
clearance at a point mid-way between kg/cm2, calculate the height of the
the towers, the size of the conductor is conductor above ground level at which
0.9 cm2 and density of conductor it should be supported if a minimum
material is 8.9 gm/cm3 [64 m ] clearance of 7 m is to be kept between
2- A T.L has a span of 260 m, the weight the ground and the conductor [10.24m]
of the line conductor is 0.68 kg/m , find 6- A T.L has a span of 150 m between level
the maximum sag in the line, the supports, the conductor has across-
maximum allowable tension in the line sectional area of 2 cm2, the ultimate
is 1550 kg [3.7 m ] strength is 5000 kg/cm2, the specific
3- A T.L has a span of 150 m between level gravity of the material is 8.9 gm/cm3,if
supports, the cross sectional area of the the wind pressure is 1.5 kg/m length of
conductor is 1.25 cm2 and weight 100 the conductor calculate the sag if the
kg per 100 m, the breaking stress is factor of safety is 5 [3.5 m ]
4220 kg/cm2, calculate the factor of 7- Two towers of height 40 m and 30 m
safety if the sag of the line is 3.5 m , respectively support a T.L conductor at
assume a maximum wind pressure of water crossing the horizontal distance
100 kg per square meter [4] between the towers is 300 m, if the
4- A T.L has a span of 150 m between the tension in the conductor is 1590 kg,
level supports , the conductor has a find the clearance of the conductor at
cross-sectional area of 2 cm2, the apoint mid-way between the supports ,
ultimate strength is 5000 kg/cm2, the weight of conductor is 0.8 kg/m, bases
specific gravity of the material is 8.9 of the towers can be considered to be at
gm/cm3, if the wind pressure is 1.5 kg/m the water level
length of conductor, calculate the sag 8- A T.L at a river crossing is supported
at the center of the conductor if factor from two towers at heights of 50 m and
of safety is 5 [3.28 m] 100 m above the water level, the
horizontal distance between the towers
is 400 m, if the maximum allowable
tension is 1800 kg and the conductor
weight 1 kg/m, find the clearance
between the conductor and water at
apoint mid-way between the supports
[63.8 m]

55
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫‪Underground cables‬‬
‫الكابالت الكهربائية هي احدى الوسائل التي تستخدم لنقل‬
‫وتوزيع الطاقة الكهربائية ‪ ,‬والفارق الجوهري بين‬
‫الخطوط الهوائية والكابالت هو ان الموصالت المستخدمة‬
‫في الخطوط الهوائية تكون موصالت مكشوفة أي غير‬
‫معزولة ويتم تثبيتها على ابراج للمحافظة على مسافات‬
‫فاصلة ثابتة بين الموصالت بعضها البعض وبين‬
‫الموصل واالرض ‪ ,‬في حين ان الموصالت المستخدمة‬
‫في الكابالت تكون مغطاة بأكملها بمادة عازلة ويتم تمديد‬
‫هذه الكابالت اما بالدفن المباشر في االرض او داخل‬
‫مواسير مدفونة في االرض او خالل مجاري تحت سطح‬
‫االرض مهيأة خصيصا لهذا الغرض‬
‫ان االختيار بين الكابالت االرضية والخطوط الهوائية ال‬
‫يتم وفقا لمعيار واحد ولكنه يخضع لعدة عوامل اقتصادية‬
‫وفنية عديدة اهمها‬
‫تكلفة الموصل‪ :‬لنقل نفس القدرة يكون الموصل المستخدم‬
‫في خط النقل الهوائي اقل تكلفة من الموصل المستخدم في‬
‫الكابل‬
‫تكلفة العازل‪ :‬تكلفة العازل في الكابل اكبر بكثير منها في‬
‫حالة خط النقل الهوائي ‪ ,‬حيث ان الموصالت في خط‬
‫النقل الهوائي يتم عزلها عن االبراح بواسطة عوازل قليلة‬
‫التكلفة نسبيا ويكون الهواء هو العازل الذي يعزلها عن‬
‫بعضها البعص ‪ ,‬اما الموصالت في الكابالت فيتم‬
‫احاطتها بمادة عازلة عالية التكلفة ويلزم غطاء معدني‬
‫‪UNDERGROUND‬‬ ‫لحماية العازل من تأثيرات التربة وحماية ميكانيكية للكابل‬
‫وفي بعض انواع الكابالت وخصوصا التي تستخدم‬
‫الورق العازل يلزم ملء الكابل بالزيت العازل او غاز‬
‫‪CABLES‬‬ ‫خامل لملء الفراغات بين طبقات الورق وفي هذه الحالة‬
‫يلزم تركيب خزانات للزيت او الغاز الخامل على طول‬
‫مسار الكابل مما يجعل تكلفة العزل اكبر بكثير للكابل منها‬
‫في حالة خط النقل الهوائي‬
‫تكلفة التركيب‪ :‬تكلفة تركيب الكابالت اعلى بكثير من‬
‫تكلفة تركيب خطوط النقل الهوائية حيث تصل احيانا الى‬
‫عشرة اضعاف او يزيد تكلفة خط النقل‬

‫اهم االماكن التي تستخدم فيها الكابالت لنقل الطاقة‬


‫داخل المنشآت الصناعية وداخل المدن والمناطق‬ ‫‪.1‬‬
‫الماهولة بالسكان‬
‫في االماكن التي قد تتسبب خطوط النقل الهوائية فيها‬ ‫‪.2‬‬
‫في حدوث اعطال او حوادث كما هي الحال بالقرب‬
‫من المطارات‬
‫عبر الموانع المائية المتسعة‬ ‫‪.0‬‬
‫داخل محطات القدرة ومحطات المحوالت‬ ‫‪.4‬‬

‫‪56‬‬
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫محاسن استخدام الكابالت‬ ‫الغطاء المعدني ‪ :metallic sheath‬وغالبا ما‬ ‫‪-0‬‬


‫يكون من الرصاص او االلمنيوم ويمنع دخول‬
‫اقل تعرضا لألعطال الكهربائية واقل تأثرا‬ ‫‪-1‬‬
‫الرطوبة والمواد الكيمياوية الى داخل الكابل وكذلك‬
‫بالكوارث الطبيعية والعوامل البيئية‬
‫الحتواء الغاز المضغوط او الزيت العازل في الكابل‬
‫أكثر امانا من الخطوط الهوائية‬ ‫‪-2‬‬
‫مادة عازلة من الجوت‪ :‬تستخدم إلعطاء مرونة‬ ‫‪-4‬‬
‫كلفة صيانتها اقل ألنها اقل تعرضا لألعطال‬ ‫‪-0‬‬
‫للكابل وتمنع تاكل الغطاء المعدني وتمنع التأثيرات‬
‫هبوط الفولتية فيها اقل‬ ‫‪-4‬‬
‫الميكانيكية التي يسببها الدرع‬
‫تضيف مظهرا جيدا لالماكن التي تستخدم فيها ألنها‬ ‫‪-5‬‬
‫الدرع ‪ : armour‬للحماية الميكانيكية واعطاء متانة‬ ‫‪-5‬‬
‫تحت االرض‬
‫للكابل‬
‫الغطاء الخارجي‪-‬غالف الخدمة ‪:serving cover‬‬ ‫‪-0‬‬
‫لحماية االجزاء المعدنية من التآكل‬
‫مساوئ استخدام الكابالت‬
‫‪ -1‬كلفة انشائها عالية جدا‬
‫‪ -2‬تحدث فيها مشاكل عند نقل فولتيات عالية لمسافات‬
‫طويلة حيث تكون السعة اكبر تأثيرا من المحاثة‬
‫ويكون تيار الشحن كبيرا جدا مما يسبب ارتفاعا‬
‫كبيرا في الجهد‬

‫متطلبات تصميم الكابالت‬


‫ان يكون الموصل اما من النحاس او من االلمنيوم‬ ‫‪-1‬‬ ‫رسم توضيحي لمكونات الكابل‬
‫وتكون موصالت مجدولة إلعطاء مرونة للموصل‬
‫وتحمل تيار اعلى‬
‫قطر الموصل يجب ان يتحمل تيار الحمل بدون‬ ‫‪-2‬‬ ‫الغاية من استخدام ‪ bedding‬و‬ ‫‪‬‬
‫حدوث تسخين وال يسبب هبوط كبير في الفولتية‬ ‫‪ armouring‬و ‪ serving‬هي لحماية‬
‫كمية العازل يجب ان تكون كافية لتحمل الفولتية‬ ‫‪-0‬‬ ‫العوازل وكذلك لحماية الغطاء المعدني من‬
‫المستخدمة دون حدوث انهيار للعازل‬ ‫المؤثرات الميكانيكية‬
‫يجب ان يحتوي الموصل على حماية ميكانيكية‬ ‫‪-4‬‬ ‫في ‪ single core cable‬غالبا ال يستخدم‬ ‫‪‬‬
‫كالدرع والغطاء المعدني لكي ال يتأثر بالمؤثرات‬ ‫الدرع وذلك لتجنب المفاقيد الناتجة عن‬
‫الميكانيكية الخارجية‬ ‫استخدام الغطاء المعدني‬
‫المواد المستخدمة في صناعته يجب ان تكون ذات‬ ‫‪-5‬‬
‫استقرارية فيزياوية وكيمياوية‬
‫خواص العوازل‬
‫مقاومة العزل عالية جدا لتجنب التيارات التسريبة‬ ‫‪-1‬‬
‫‪ Dielectric strength‬يحب ان يكون عالي لتجنب‬ ‫‪-2‬‬
‫تركيب الكابل‬ ‫انهيار الكابل‬
‫‪ -1‬القلب المعدني – الموصل – )‪:)conductor‬‬ ‫يتحمل اجهادات ميكانيكية كبيرة‬ ‫‪-0‬‬
‫ويكون على نوعين‬ ‫ال تسمح بامتصاص الرطوبة والحوامض والمواد‬ ‫‪-4‬‬
‫)‪i‬‬ ‫‪Single core‬‬ ‫االخرى التي تسبب تآكل العازل‬
‫)‪ii‬‬ ‫‪Three core‬‬ ‫غير قابلة لالشتعال‬ ‫‪-5‬‬
‫‪ -2‬العازل ‪ :insulator‬كل موصل يجب ان يلف بعازل‬ ‫ال تتأثر بالحوامض والمواد الكيميائية التي تؤدي الى‬ ‫‪-0‬‬
‫ذا سمك مناسب ليتحمل الفولتية التي يعمل بها الكابل‬ ‫تفتيت مكونات الكابل‬
‫وهناك عدة انواع للعازل‬
‫‪i.‬‬ ‫‪Impregnated paper‬‬
‫‪ii.‬‬ ‫‪Varnished cambric‬‬
‫‪iii.‬‬ ‫‪Rubber mineral compound‬‬

‫‪57‬‬
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫اهم انواع المواد العازلة‬ ‫تصنيف الكابالت‬


‫‪ -1‬المطاط ‪ :rubber‬وهناك نوعين من المطاط‬ ‫‪ -1‬حسب الفولتية‬
‫ا) مطاط نقي ب) مطاط ممزوج بمادة من النفط‬ ‫‪i.‬‬ ‫‪low tension‬‬ ‫‪11 kV‬‬
‫اما اهم صفاته فهي‬ ‫‪ii.‬‬ ‫‪high tension‬‬ ‫‪11-22 kV‬‬
‫‪iii.‬‬ ‫‪super tension‬‬ ‫‪22-33 kV‬‬
‫‪E=30 kV/mm , 𝜀𝑟 =2-3 , 𝜌 =1017 Ω-cm‬‬ ‫‪iv.‬‬ ‫‪extra high tension‬‬ ‫‪33-66 kV‬‬
‫وال يمكن استخدام المطاط النقي كعازل لألسباب التالية‬ ‫‪v.‬‬ ‫‪extra super voltage cable‬‬ ‫‪132 kV‬‬

‫يمتص الرطوبة‬ ‫‪.i‬‬


‫اعلى درجة حرارة يتحملها هي ‪ 00‬وهي‬ ‫‪.ii‬‬ ‫‪ -2‬حسب البنية‬
‫قليلة‬ ‫‪i.‬‬ ‫‪Single core cable‬‬
‫ناعم ويتأثر بسهولة بالمؤثرات الخارجية‬ ‫‪.iii‬‬ ‫‪ii.‬‬ ‫‪Two core cable‬‬
‫‪iii.‬‬ ‫‪Three core cable‬‬
‫‪iv.‬‬ ‫‪Four core cable‬‬
‫‪ -2‬الورق المشرب بالزيت ‪impregnated paper‬‬
‫يصنع من نشارة الخشب ويشرب بمادة من النفط‬
‫مثل البارافين او النفثالين ‪ ,‬واهم مميزاته هي‬
‫كلفته قليلة نسبيا‬ ‫‪.i‬‬
‫متسعة واطئة‬ ‫‪.ii‬‬
‫‪ E‬له عالية‬ ‫‪.iii‬‬
‫مقاومة العزل عالية‬ ‫‪.iv‬‬
‫اما اهم مساوئه فهي انه يتأثر بالرطوبة وبالتالي تقل‬
‫مقاومة العزل وتزداد التيارات التسريبة‬

‫‪ -0‬القماش المطلي ‪ varnish cambric:‬تتكون‬ ‫‪Single core low-tension cable‬‬


‫هذه المادة من قماش قطني مشرب بمادة من النفط‬
‫وملمع ولكن من مساوئه انه يتأثر بالرطوبة لذلك‬
‫يستخدم الغطاء المعدني ليمنع وصول الرطوبة الى‬
‫الكابل‬
‫‪ -4‬العوازل البوليميرية واهمها مادة ‪ :PVC‬وهي‬
‫مادة مركبة ناتجة عن بلمرة االستلين ويكون على‬
‫شكل مسحوق ابيض‬

‫‪58‬‬
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫تصنيف الكابالت طبقا لنوع المادة العازلة‬ ‫‪ii.‬‬ ‫‪S.L –type cable‬‬

‫‪1- Belted cables‬‬ ‫اهم ميزتين لهذا النزع هما‬

‫يتمتع العازل الورقي بخواص كهربائية جيدة ولكن‬ ‫أ) االغطية المعدنية المنفصلة تقلل من امكانية انهيار‬
‫عمليات اللحام وتوصيل النهايات لكابل العازل الورقي‬ ‫الموصل‬
‫تحتاج الى خبرة ودقة في االداء‬ ‫ب) يصبح طوي او انحناء الكابالت سهال بسبب ازالة الغطاء‬
‫المعدني الرئيسي‬
‫يعمل على ‪ 11‬كيلو فولت‬
‫ولكن المشكلة االساسية في هذا النوع هي التيارات‬
‫التسريبية التي تؤدي الى رفع درجة الحرارة وتسبب‬
‫فقدان خاصية العزل للعازل المحيط بالموصل‬

‫‪Screened cable S.L type‬‬

‫‪Belted cable‬‬ ‫‪ ‬االنواع السابقة من النوع المصمت ‪ solid‬وتمتاز‬


‫هذه االنواع ان لها محددات في العمل اهمها انه يعمل‬
‫بفولتية تصل الى ‪ 00‬كيلو فولت والسبب انه عندما‬
‫يزداد الحمل يسخن الكابل وقد يسبب تلف الكابل‬

‫‪2- Screened cables‬‬


‫يعمل على ‪ 00‬كيلو فولت‬ ‫‪3- Pressure cables‬‬
‫للتغلب على مشكلة التيارات الدوامة يتم لف الموصل‬ ‫يعمل تحت ضغط منخفض او تحت ضغط مرتفع وفيها‬
‫بمادة عازلة ومن ثم يلف بمادة معدنية يتم توصيلها‬ ‫يستخدم الزيت العازل او غاز النيتروجين الخامل للحد من‬
‫باالرض وهناك نوعين‬ ‫تكون الفقاعات الهوائية داخل العازل الورقي وكذلك‬
‫‪i.‬‬ ‫‪H-type cables‬‬ ‫للتبريد وتستخدم هذه الكابالت عند جهود تصل الى ‪.53‬‬
‫كيلو فولت ‪ ,‬وال تستخدم هذه الكابالت اال حين تكون هناك‬
‫سمي بذلك نسبة للعالم ‪ H. hochstadter‬واهم ما يميز‬ ‫ضرورة قصوى الستخدامها وذلك الرتفاع تكلفتها وتعقيد‬
‫هذا النوع هو ان الفجوات فيه قليلة‬ ‫التركيبات الخاصة بها وخصوصا التجهيزات الالزمة‬
‫لسريان الزيت او الغاز ‪ ,‬وهو على نوعين‬
‫‪a) Oil-filled cables‬‬
‫وهي ايضا بدوره يقسم الى ‪ 0‬انواع‬
‫‪i-‬‬ ‫‪Single core oil-filled cable‬‬
‫‪ii-‬‬ ‫‪Single core sheath channel oil-‬‬
‫‪filled cable‬‬
‫‪iii-‬‬ ‫‪3-core oil-filled cable‬‬

‫‪Screened cable H-type‬‬

‫‪59‬‬
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫‪b) Gas pressure cable‬‬


‫يستخدم غاز النتروجين والغاية منه هي لتقليل فجوات‬
‫المادة العازلة وكذلك لتقليل التأين الذي يحدث نتيجة جهد‬
‫الكابل‬

‫‪Single core oil-filled cable‬‬

‫‪Gas pressure cable‬‬

‫‪4- Polymer insulated cables‬‬


‫المادة المستخدمة للعزل في هذا النوع تكون احدى المواد‬
‫‪Single core sheath channel oil-filled cable‬‬ ‫البوليميرية المستخرجة من صناعة البتروكيمياويات‬
‫واكثر هذه المواد شيوعا هي‬
‫‪i-‬‬ ‫البولي فينيل كلورايد ‪PVC‬‬
‫يتميز بخواص كهربائية ممتازة عند الجهود المنخفضة‬
‫ودرجات الحرارة المنخفضة الى جانب رخص الثمن‬
‫مقارنة ببقية العوازل لذلك فهي تعتبر االفضل في جميع‬
‫انحاء العالم حتى جهد ‪ 0.0‬كيلو فولت اال انها غير‬
‫مناسبة للجهود االكبر من ذلك حيث ترتفع مفقودات‬
‫العزل‬
‫‪ii-‬‬ ‫البولي ايثيلين التشابكي ‪XLPE‬‬
‫‪3-core oil-filled cable‬‬ ‫تتميز بمقاومة عالية للرطوبة وتحمل درجات حرارة‬
‫مرتفعة وقلة الفقد في العزل تستخدم للجهود من ‪-0.0‬‬
‫‪ 2.5‬كيلو فولت‬
‫‪iii-‬‬ ‫العوازل المطاطية ‪Rubber‬‬
‫واهمها مطاط ‪ EPR‬ومطاط ‪ PR‬وتستعمل عند الحاجة‬
‫لخواص معينة متوفرة فيهما‬

‫‪60‬‬
‫‪ELECTRICAL POWER‬‬ ‫‪MOHAMMED HAMEED IBRAHIM‬‬

‫‪Laying of underground cables‬‬ ‫‪2- Draw in system‬‬

‫هناك ‪ 0‬طرق‬
‫‪1- Direct laying‬‬

‫تصب كتلة من الكونكريت في الشق وتترك فيها فتحات‬


‫لمد الكابالت ‪ ,‬في هذه الطريقة ال يحتاج الكابل الى درع‬
‫وانما يحتاج الى غالف خدمة لتسهيل عملية مد الكابل ‪,‬‬
‫ويجب ان تكون هناك فتحات الى السطح بين مسافة‬
‫واخرى وهذه المسافات ال يجب ان تكون طويلة جدا لكي‬
‫تبسط عملية مد او سحب الكابالت‬

‫يحفر شق بعمق ‪ 1.5‬متر وعرض ‪ 45‬سم ويتم مد الكابل‬ ‫محاسن الطريقة‬


‫وتضاف تحته طبقة من الرمل بسمك ‪ 13‬سم وفوقه ايضا‬ ‫‪ -i‬تبديل وصيانة الكابالت أسهل‬
‫والغاية منها هي لمنع وصول الرطوبة الى الكابل اما إذا‬ ‫‪ -ii‬بسبب استخدام الكابالت الغير مدرعة وبذلك تكون‬
‫كان هناك أكثر من كابل في شق واحد فمن الضروري ان‬ ‫التوصيالت مبسطة وصيانتها سهلة‬
‫تترك مسافة بين كابل واخر بحدود ‪ 03‬سم والغرض من‬ ‫‪ -iii‬احتمالية حدوث العطل قليل‬
‫ذلك لتقليل التبادل الحراري بين الكابالت وكذلك إذا حدث‬
‫عطل في أحد الكابالت ال تتأثر الكابالت االخرى‬ ‫اما مساوئها‬

‫محاسن هذه الطريقة‬ ‫‪ -i‬كلفة انشائية عالية‬


‫‪ -ii‬تحمل الكابالت للتيار تكون قليلة‬
‫طريقة بسيطة واقتصادية‬ ‫‪-i‬‬ ‫‪ -iii‬تصريف الحرارة اسوأ من الطريقة السابقة‬
‫توفر امكانية تصريف الحرارة الناتجة في‬ ‫‪-ii‬‬
‫الكابالت‬
‫طريقة امنة للكابل من أي تاثير خارجي‬ ‫‪-iii‬‬
‫‪3- Solid system‬‬
‫اما مساوئها‬
‫‪the cable is laid in open pipes or troughs‬‬
‫عملية تبديل الكابل او اصالح العطل صعبة‬ ‫‪-i‬‬ ‫‪dug out in earth a long the cable route, the‬‬
‫تحديد موقع العطل صعب‬ ‫‪-ii‬‬ ‫‪troughing is of cast iron, stoneware,‬‬
‫الصيانة مكلفة‬ ‫‪-iii‬‬ ‫‪asphalt, or treated wood, after the cable is‬‬
‫ال يمكن استخدامها في المناطق المأهولة‬ ‫‪-iv‬‬ ‫‪laid in position, the troughings is filled with‬‬
‫بالسكان‬ ‫‪a bituminous or asphaltic compound and‬‬
‫‪covered over, cables laid in this manner are‬‬
‫‪usually plain lead covered because‬‬
‫‪troughing affords good mechanical‬‬
‫‪protection‬‬
‫‪Disadvantages‬‬
‫‪i-‬‬ ‫‪Its more expensive than direct laid‬‬
‫‪system‬‬
‫‪ii-‬‬ ‫‪Its required skilled labour and‬‬
‫‪favourable weather conditions‬‬
‫‪iii-‬‬ ‫‪Due to poor heat dissipation‬‬
‫‪facilities, the current carrying‬‬
‫‪capacity of the cable is reduced‬‬

‫‪61‬‬
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

Insulation resistance & ρ = 4.5*1012 Ω-cm


capacitance of a single-core r1 = 2.5/2 = 1.25 cm
cable 𝜌 𝑟
R=2𝜋 𝑙 ln 𝑟2
1

4.5∗1012 𝑟
𝜌 𝑟2 495*106=2𝜋∗1000 ln 𝑟2
R= 𝑙𝑛 Ω 1
2𝜋 𝑙 𝑟1 𝑟2
𝑟1
=2 → r2=2*1.25
2𝜋𝜀𝑜 𝜀𝑟
C= 𝑟 F/m
𝑙𝑛𝑟2 r2 = 2.5 cm
1
Thickness of insulation = 2.5 - 1.25
‫القانون السابق الستخراج المتسعة يستخرج قيمة لكل‬
‫متر اما اذا اردنا حساب المتسعة الكلية فنستخدم القانون‬ =1.25 cm
‫التالي‬
EXAMPLE 3:A single core cable 5 km
𝜀𝑟 𝑙 -9 long has an insulation resistance of 0.4
C= 𝑟 * 10 F
41.4 𝑙𝑜𝑔 2 MΩ, the core diameter is 20 mm, the
𝑟1
diameter of the cable over the insulation is
‫نصف القطر الكلي للكابل‬ : 𝑟2 50 mm, find the resistivity of the insulating
material
‫ نصف قطر السلك‬: 𝑟1
SOLUTION:-
‫ طول السلك‬: l
r1 = 2/2 = 1 cm
EXAMPLE 1 : A single core cable has a
conductor diameter of 1 cm and insulation r2 = 5/2 = 2.5 cm
thickness of 0.4 cm, if the specific 𝜌 𝑟
resistance of insulation is 5*1014 Ω-cm R = 2𝜋 𝑙 ln 𝑟2
1
,calculate the insulation resistance for 2 km 𝜌 2.5
length of the cable 0.4*106 = 2𝜋∗5000 ln 1

SOLUTION:- 0.4∗106 ∗2𝜋∗5000


ρ= =13.72*109 Ω-m
ln 2.5
r1 = ½ = 0.5 cm
EXAMPLE 4 :A single core cable has a
l=2000 m conductor diameter of 1 cm and internal
ρ=5*1014 Ω-cm = 5*1012 Ω-m sheath diameter of 1.8 cm if the
impregnated paper of relative permittivity
r2 = 0.5+0.4 = 0.9 cm 4 is used as the insulation, calculate the
capacitance for 1 km length of the cable
𝜌 𝑟 5∗1012 0.9
R = 2𝜋 𝑙 ln 𝑟2 = 2𝜋∗2000 ln 0.5 = 234 𝑀Ω
1 SOLUTION:-
EXAMPLE 2 :The insulation resistance of 𝜀𝑟 = 4
a single core cable is 495 MΩ per km, if the
core diameter is 2.5 cm and resistivity of D=1.8 cm → r2 = 0.9 cm
insulation is 4.5*1014 Ω-cm, find the
d = 1 cm → r1 = 0.5 cm
insulation thickness
𝜀𝑟 𝑙 -9
SOLUTION:- C= 𝑟 *10 F
41.4 log𝑟2
1
l = 1000 m
4∗1000
R= 495 *106 Ω = 0.9 *10-9=0.387 μF
41.4 log
0.5

62
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 5 :Calculate the capacitance TUTORIAL PROBLEMS


and charging current of a single core cable
used on 3-phase , 66 kV system , the cable 1- A single-core cable has a conductor
is 1 km long having a core diameter of 10 diameter of 2.5 cm and insulation
cm and an impregnated paper insulation of thickness of 1.2 cm, if the specific
thickness 7 cm the relative permittivity of resistance of insulation is 4.5*1014 Ω-
the insulation may be taken as 4 and the cm, calculate the insulation resistance
supply at 50 Hz per km length of the cable [305.5 M Ω]
2- A single core cable 3 km long has an
SOLUTION:- insulation resistance of 1820 M Ω, if
d = 10 cm → r1=10/2 = 5 cm the conductor diameter is 1.5 cm and
sheath diameter is 5 cm, calculate the
D = 7+5 = 12 cm resistivity of the dielectric in the cable
𝜀𝑟 𝑙
[28.57*1012 Ωm]
𝑟 *10 = 0.254 μF
-9
C= 3- Determine the insulation resistance of
2𝜋 log 2
𝑟1 a single core cable of length 3 km and
66 𝑘𝑉 having conductor radius 12.5 mm,
Vph= =38.1 kV insulation thickness 10 mm and specific
√3
resistance of insulation of 5*1012 Ωm
IC=2π *50*0.254*10-6*38.1*103
[156 M Ω]
= 3.04 A 4- A single core cable has a conductor
diameter of 1 cm and internal sheath
EXAMPLE 6 :33 kV, 50 Hz, 3-phase diameter of 1.8 cm, if the impregnated
underground cable 4km long uses 3 single paper of relative permittivity 3 is used
core cables, each of the conductor has a as insulation, calculate the capacitance
diameter of 2.5 cm and the radial thickness for 1 km length of cable [0.282μF]
of the insulation is 0.5cm , determine 5- Calculate the capacitance and
(i) capacitance of the cable/phase charging current of a single core cable
(ii) charging current/phase used on 3-phase, 66 kV system, the
(iii) total charging kVAR , if the relative cable is 1 km long having a core
permittivity of insulation is 3 diameter of 15 cm and impregnated
SOLUTION:- paper insulation of thickness 22.5 cm,
the relative permittivity of the
r1 = 2.5/2 = 1.25 cm insulation may be taken as 3.5 and
supply at 50 Hz
r2 = 1.25+0.5 = 1.75 cm
6- An 11 kV, 50 Hz, single phase cable 2.5
𝜀𝑟 𝑙 3∗4000 km long, has a diameter of 20 mm and
C= 𝑟 ∗ 10−9 = 1.75 ∗10-9
41.4 log 2 41.4 log internal sheath radius of 15 mm, if the
𝑟1 1.25
dielectric has a relative permittivity of
= 1.98 μF 2.4, determine (i)capacitance
33 𝑘𝑉 (ii)charging current (iii)total
Vph= =19.05 kV
√3 charging kVAR [(i)0.822 μF
IC=2π f C Vph (ii)2.84 A (iii)31.24 kVAR]

= 2π*50*1.98*10-6*19.05*103
= 11.87 A
Total kVAR = 3Vph IC = 3*19.05*103*11.87
= 106.87 kVAR

63
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

‫حساب االجهاد على العوازل‬ Grading of cable


‫هي عملية تدريج العوازل في الكابل للحصول على‬
‫انحدار جهد متجانس ضمن عازل الكابل‬
‫أعظم اجهاد على سطح الموصل‬ ‫وهناك طريقتان‬
2𝑉 i- Capacitance grading
𝑔𝑚𝑎𝑥 = 𝐷 kV/cm
𝑑 𝑙𝑛
𝑑 ‫تصنع مادة العازل من عدة طبقات تختلف عن بعضها‬
2𝑉 ‫ حيث يكون اعلى في الطبقة القريبة من‬εr ‫البعض بـ‬
𝑔𝑚𝑎𝑥 = 𝑟 kV/cm ‫الموصل ثم يقل تدريجيا‬
𝑟1 𝑙𝑛 2
𝑟1
εr1 >εr2 > εr3
gmax1=gmax2=gmax3
‫اقل اجهاد على سطح العازل‬
2𝑉
𝑔𝑚𝑖𝑛 = 𝐷 kV/cm
gmax=2𝜋𝜀
𝑄
kV/cm
𝐷 ln
𝑑 𝑜 𝜀𝑟 𝑑

2𝑉 𝑄
𝑔𝑚𝑖𝑛 = 𝑟 kV/cm gmax1=2𝜋𝜀
𝑜 𝜀𝑟 𝑑1
kV/cm
𝑟2 ln 2
𝑟2
𝑄
gmax2=2𝜋𝜀 kV/cm
𝑜 𝜀𝑟 𝑑2

‫ قطر الكابل‬:D
‫قطر السلك‬: d
𝑔𝑚𝑎𝑥 𝑑1
V1= 𝑑 ln
2 𝑑

𝑔𝑚𝑎𝑥 𝑟2 𝑔𝑚𝑎𝑥 𝐷 V2=


𝑔𝑚𝑎𝑥 𝑑
𝑑1 ln 2
= 𝑂𝑅 = 2 𝑑1
𝑔𝑚𝑖𝑛 𝑟1 𝑔𝑚𝑖𝑛 𝑑 𝑔𝑚𝑎𝑥 𝐷
V3= 2
𝑑2 ln 𝑑
2

VT=V1+V2+V3
D/d = 2.718 ‫النسبة التي تمثل الحجم‬
‫االقتصادي االفضل للكابل‬
EXAMPLE 1: 33 kV, single core cable has
a conductor diameter of 1 cm and a sheath
of inside diameter 4 cm, find the maximum
and minimum stress in the insulation
SOLUTION:-
2𝑉 2∗33000
gmax = 𝐷 = 1 ln 4
= 47.61 kV/cm
𝑑 ln
𝑑

2𝑉 2∗33000
gmin = 𝐷 = 4 ln 4
= 11.9 kV/cm
𝐷 ln
𝑑

64
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 2:The maximum and minimum EXAMPLE 4:A single core leads sheathed
stress in the dielectric of the single core cable is graded by using three of dielectric
cable are 40kV/cm (r.m.s) and 10 kV/cm of relative permittivity 5,4 and 3
(r.m.s) respectively , if the conductor respectively, the conductor diameter is 2
diameter is 2 cm , find (i)the thickness of cm and overall diameter is 8 cm if the three
insulation (ii)operating voltage dielectrics are worked at the same
maximum stress of 40 kV/cm, find the safe
SOLUTION:- working voltage of the cable, what will be
gmax /gmin = D/d the value of safe working voltage for an
ungraded cable assuming the same
40/10=D/2 → D=8 cm conductor and overall diameter and with
𝐷−𝑑 8−2 maximum dielectric stress
Insulation thickness= 2
= 2
= 3 cm
SOLUTION
8
2𝑉 40∗103 ∗2 ln
gmax = 𝐷 → 𝑉= 3 d= 2 cm , d1=? , d2=? , D=8cm
𝑑 ln 2
𝑑
ε1=5 , ε2=4 , ε3=3 , gmax=40 kV/cm
V= 55.45 kV (r.m.s)
graded cable
EXAMPLE 3:A single core cable for use
ε1 d = ε2 d1 = ε3 d2
on 11 kV, 50 Hz system has conductor area
of 0.645 cm2 and internal diameter of d2 ‫ و‬d1 ‫من خالل العالقة السابقة نستخرج‬
sheath is 2.18 cm, the permittivity of the
dielectric used in the cable is 3.5 , find (i) d1 = 2.5 cm , d2 = 3.34 cm
gmax (ii) gmin (iii)capacitance of the cable 𝑑1 𝑑 𝐷
Vpeak= gmax/2 [𝑑 ln 𝑑
+ 𝑑1 ln 𝑑2 + 𝑑3 ln 𝑑 ]
per km length (iv) charging current 1 2

SOLUTION:- = 81.757

4𝐴
81.757
A = ¼ π d2 → d=√ 𝜋 Vrms= = 57.81 kV
√2

4∗0.645
Ungraded cable
d=√ π
=0.906 cm
𝑔𝑚𝑎𝑥 𝐷
Vpeak= 2
𝑑 ln 𝑑 = 20 ∗ 2 ln 4=55.45 kV
2𝑉 2∗11000
gmax= 𝐷 = 2.18 =27.65 kV/cm Vrms= 39.21 kV
𝑑 ln 0.906 ln
𝑑 0.906

2𝑉 2∗11000
gmin = 𝐷 = 2.18 =11.5 kV/cm
𝐷 ln 2.18 ln
𝑑 0.906

𝜀𝑟 𝑙
C= 𝐷 ∗10-9
41.4 log
𝑑

3.5∗1000
= 2.18 *10-9 = 0.22*10-6 F
41.4 log
0.906

Ic = V/XC = 2 π f C V
= 2 π *50*0.22*10-6*11*103=0.76 A

65
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 5:A single core lead sheathed 2∗53.9


gmax1 = 4 5 6 =39.38 kV/cm
cable has a conductor diameter of 3 cm the 2 [ln + ln ]
2 3 4
diameter of the cable being 9 cm the cable
is graded by using two dielectrics of 2𝑉
gmax2 = 𝜀 𝑑 𝐷
relative permittivity 5 and 4 respectively 𝑑1 [ 2 ln 1 +ln ]
𝜀1 𝑑 𝑑1
with corresponding safe working stresses
of 30 kV/cm and 20kV/cm, calculate the 2∗53.9
= 3 4 6 =32.81 kV/cm
radial thickness of each insulation and the 4[ ln +ln ]
5 2 4
safe working voltage of the cable
SOLUTION
𝒈𝑚𝑎𝑥1 𝜀2 𝑑1
=
𝒈𝑚𝑎𝑥2 𝜀1 𝑑
30 4𝑑1 ii- Inter sheath grading
= → 𝑑1= 5.625 cm
20 5∗3
‫تتم اضافة عدة عوازل معدنية داخل مادة العازل على‬
Thickness of inner insulator is ‫شكل طبقات والعازل يكون من نفس المادة‬
𝑑1 −𝑑 5.625−3 𝑉1
= = =1.312 cm gmax1 = 𝑑
2 2 𝑑
ln 1
2 𝑑
Thickness of second insulator is
𝑉2
𝐷−𝑑1 9−5.625 gmax2 = 𝑑1 𝑑
= = =1.68 cm ln 2
2 𝑑1
2 2
𝑔𝑚𝑎𝑥1 𝑑1 𝑔𝑚𝑎𝑥2 𝐷 𝑉3
Vpeak= 𝑑 ln + 𝑑1 ln 𝑑 gmax3 = 𝑑2 𝐷
2 𝑑 2 1 ln
2 𝑑2
30 5.625 20 9
= 2 3 ln + 5.625 ln 5.625
3 2

= 54.71 kV
Vrms = 38.68 kV EXAMPLE 1:A single core cable of
EXAMPLE 6:A 66 kV single core lead conductor diameter 2 cm and lead sheath of
5.3 cm is to be used on 66 kV, 3-phase
sheathed cable is graded by using two
system, two inter sheaths of diameter 3.1
dielectric of ε= 5 and 3 respectively,
cm and 4.2 cm are introduced between the
thickness of each being 1 cm , the core
diameter is 2 cm, find the maximum stress core and lead sheath, if the maximum stress
in the layers is the same find the voltage in
in the two dielectrics
the inter sheaths
SOLUTION
SOLUTION:
d= 2 cm , d1= 4 cm , d2= 6 =D 66 𝑘𝑉
V= √2 =53.9 kV
66 𝑘𝑉 √3
V= ∗ √2=53.9 kV
√3
𝑉1 𝑉1
𝑔𝑚𝑎𝑥1 𝜀1 𝑑 1 𝑑1 1 𝐷
gmax1=𝑑 𝑑 = 3.2 =2.28V1
ln 1 1 ln
V= [ ln + ln ] 2 𝑑 2
2 𝜀1 𝑑 𝜀2 𝑑1
𝑉2 𝑉2
2𝑉 gmax2 = 𝑑1 𝑑 = =2.12V2
4.2
gmax1 = 𝑑 𝜀 𝐷 ln 2 1.55 ln
3.1
2 𝑑1
𝑑[ln 1 + 1 ln ]
𝑑 𝜀2 𝑑1

66
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

𝑉3 𝑉3
gmax3=𝑑2 = =2.04 V3 𝑑12
ln
𝐷
2.1 ln
5.3
𝑑2 =
2 𝑑2 4.2 2
gmax1=gmax2=gmax3 𝑑1 𝑑2 = 𝐷 𝑑
2.28V1=2.12V2=2.04V3
𝑑1 𝑑2 = 5.3 ∗ 2 = 10.6 𝑐𝑚
V2=1.075 V1
𝑑12
V3=1.117 V1 𝑑1 = 10.6 → 𝑑1 = 2.76 𝑐𝑚
2
VT=V1+V2+V3 𝑑12 2.672
𝑑2 = = = 3.8 𝑐𝑚
53.9=V1+1.075V1+1.117V1 2 2
𝑖𝑖)
V1=16.88 kV
V2=1.075*16.88 = 18.15 kV 𝑉 = 𝑉1 + 𝑉2 + 𝑉3

V3=1.117*16.88 = 18.85 kV 𝑓𝑟𝑜𝑚 𝑒𝑞. 2


𝑑1
Voltage in the first inter sheath is 𝑉2 = 𝑉
𝑑 1
= V-V1=53.9-16.88=37.02 kV
𝑑2
𝑉3 = 𝑉
Voltage in the second inter sheath is 2 1
=V-V1-V2=53.9-16.88-18.15=18.88 kV 𝑑1 𝑑2
53.9 = 𝑉1 + 𝑉1 + 𝑉1
𝑑 𝑑
2.76 3.8
EXAMPLE 2:A single core 66 kV cable 53.9 = 𝑉1 (1 + + )
2 2
working on three phase system has a
conductor diameter of 2 cm and a sheath of 𝑉1 = 12.6 𝑘𝑉
inside diameter 5.3 cm, if two intersheaths 𝑑1 2.76
are introduced in such a way that the stress 𝑉2 = 𝑉1 = ∗ 12.6 = 17.39 𝑘𝑉
𝑑 2
varies between the same maximum and
minimum in the three layers , find 𝑣𝑜𝑙𝑡𝑎𝑔𝑒 𝑖𝑛 𝑡ℎ𝑒 𝑓𝑖𝑟𝑠𝑡 𝑖𝑛𝑡𝑒𝑟𝑠ℎ𝑒𝑎𝑡ℎ 𝑖𝑠
(i)positions of intersheaths (ii)voltage in = 𝑉 − 𝑉1 = 53.9 − 12.6 = 41.3 𝑘𝑉
the intersheaths (ii)maximum and minimum
stress 𝑣𝑜𝑙𝑡𝑎𝑔𝑒 𝑖𝑛 𝑡ℎ𝑒 𝑠𝑒𝑐𝑜𝑛𝑑 𝑖𝑛𝑡𝑒𝑟𝑠ℎ𝑒𝑎𝑡ℎ 𝑖𝑠
= 𝑉 − 𝑉1 − 𝑉2
SOLUTION:
66 𝑘𝑉 = 53.9 − 12.6 − 17.39 = 23.91 𝑘𝑉
V= ∗ √2 = 53.9 𝑘𝑉
√3
𝑖𝑖𝑖)
𝑖) 𝑉1
Maximum stress=𝑑 𝑑
𝑑1 𝑑2 𝐷 ln 1
= = … … … … … … … .1 2 𝑑
𝑑 𝑑1 𝑑2
12.6
= 2.76 =39 kV
𝑉1 𝑉2 𝑉3 1 ln
2
= = … … … … … .2
𝑑 𝑑1 𝐷2 𝑉1
Minimum stress = 𝑑1 𝑑
From eq. 1 ln 1
𝑑 𝑑
𝑑12 = 𝑑 ∗ 𝑑2 = 2𝑑2 [𝑑 = 2𝑐𝑚] 12.6
= 2.76 = 28.35 𝑘𝑉
1.38 ln
2

67
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

TUTORIAL PROBLEMS Capacitance of 3-core cable


1- A 33 kV,single core cable has a
conductor diameter of 1 cm and
insulation of 1.5 cm, find the maximum
and minimum stress in the insulation
[47.62 kV/cm(rms) , 11.9 kV/cm (rms)]
2- Find the economic size of a single core
cable working on 220 kV, 3-phase
system, the maximum permissible
stress in the dielectric is not to exceed
250 kV/cm [d=1.43 cm , D=3.88 cm]
3- The inner conductor of a concentric
cable has a diameter of 3 cm with
insulation of diameter 8.5 cm, the cable
is insulated with two materials having
relative permittivities of 5 and 3 with
corresponding safe working stresses of
38 kV/cm and 26 kV/cm, calculate the
radial thickness of insulating layers
and the safe working voltage of the
cable [2.15cm,0.6cm,46.1kV(rms)]
4- A single core lead covered cable is to
be designed for 66 kV to earth, its
conductor diameter is 2 cm and its Ceq=3CC+Ce
three insulating materials have
C1=3Ce , Ce=1/3 C1
permittivities of 5 , 4 and 3 respectively
with the corresponding maximum safe C2=2CC+Ce
working stress of 38 kV/cm (r.m.s) ,
C3=1/2 CN
26 kV/cm (r.m.s) and 20 kV/cm (r.m.s)
respectively, find the minimum
diameter of lead sheath [8.3 cm]
5- A single core 66 kV cable has a EXAMPLE 1:The capacitance per km of a
conductor diameter of 2 cm and a 3-phase belted cable is 0.3 μF between the
sheath of inside diameter 5.3 cm, the two cores with the third core connected to
cable has an inner layer of 1 cm thick the lead sheath, calculate the charging
of rubber of dielectric constant 4.5 and current taken by 5km of this cable when
the rest impregnated paper of dielectric connected to a three phase, 50 Hz, 11 kV
constant 3.6, find the maximum stress supply
in the rubber and in the paper SOLUTION:
[63 kV/cm , 39.5 kV/cm
6- A single core cable working on 66 kV C3 = 0.5*5 = 1.5 μF
on 3-phase system has a conductor 11 𝑘𝑉
diameter of 2 cm and a sheath of inside Vph= =6351 V ; f=50
√3
diameter 5.3 cm, if two intersheaths are
used, find the best positions , maximum CN=2C3 = 2*1.5 = 3 μF
stress and the voltage on the inter IC=2πf VphCN
sheaths [d1=2.77 cm ; d2=3.84 cm ;
38.7 kV/cm ; V1=41.1 kV ; V2=23.9 kV] = 2π*50*6351*3*10-6 = 5.98 A

68
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM

EXAMPLE 2:The capacitance of a 3- TUTORIAL PROBLEMS


phase belted cable are 12.6 μF between the
1- The capacitance per km of 3-phase
three cores bunched together and the lead
cable are 0.63 μF between the three
sheath and 7.4 μF between one core and the
cores bunched together and the sheath
other two connected to sheath, find the
and 0.37 μF between one core and the
charging current drawn by the cable when
other two connected to the sheath,
connected to 66 kV, 50 Hz
calculate the charging current taken by
SOLUTION: 8 km of this cable when connected to a
66 𝑘𝑉
three phase, 50 Hz, 6600 V supply
Vph= = 38105V [4.31 A]
√3
2- The capacitance of a 3-core belted type
C1=12.6 μF , C2=7.4 μF cable are measured as detailed below:
C1=3Ce → Ce=C1/3 =12.6/3 = 4.2 μF (i)between three cores bunched
together and sheath is 8 μF (ii)between
C2=2CC+Ce a conductor and the other two
𝐶2 −𝐶𝑒 7.4−4.2 connected to the sheath together is 6 μF
CC= 2
= 2
= 1.6 𝜇𝐹 , calculate the capacitance per phase
[23/3 μF]
CN=Ce+3CC=4.2+3*1.6=9 𝜇𝐹
3- A 3-core, 3-phase belted cable tested
IC=2π f Vph CN for capacitance between a pair of cores
on single phase, with the third core
=2π*50*38105*9*10-6 = 107.74 A earthed, gave a capacitance of 0.4 μF
EXAMPLE 3:The capacitance per km of a per km, calculate the charging current
3-phase belted cable is 0.18 μF between for 15 km length of this cable when
two cores with the third core connected to connected to 22 kV, 3-phase, 50 Hz
sheath, calculate the kVA taken by 20 km supply [48 A]
long cable when connected to 3-phase, 50
Hz,3300 V supply
SOLUTION:
C3=0.18*20 = 3.6 μF

Vph=3300/√3= 1905 V
CN= 2C3 = 2*3.6 = 7.2 μF
IC = 2 π f Vph CN
= 2*3.16*50*1905*7.2*10-6 = 4.3 A
kVA taken by the cable=3Vph IC
=3*1905*4.3*10-3 = 24.57 kVA

69