Chapter one: power stations
Contents
2
Steam power station 2
Tutorial problems 22
Tutorial problems 28
Tutorial problems 35
Tutorial problems 41
Insulators 41
Tutorial problems 49
Tutorial problems 55
Tutorial problems 64
Grading of cable 64
Tutorial problems 68
Tutorial problems 69
1
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
2
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
3
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
4
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
5
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
6
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
القوانين المهمة
𝑒𝑣𝑟𝑢𝑐 𝑟𝑒𝑑𝑛𝑢 𝑎𝑒𝑟𝑎 = 𝑦𝑎𝑑 𝑟𝑒𝑝 𝑑𝑒𝑡𝑎𝑟𝑒𝑛𝑒𝑔 𝑠𝑡𝑖𝑛𝑢
𝑑𝑎𝑜𝑙 𝑒𝑔𝑎𝑟𝑒𝑣𝑎
= )𝐹 𝑙𝑜𝑎𝑑 𝑓𝑎𝑐𝑡𝑜𝑟 (𝐿.
𝑑𝑛𝑎𝑚𝑒𝑑 𝑚𝑢𝑚𝑖𝑥𝑎𝑚
𝑑𝑎𝑜𝑙 𝑒𝑔𝑎𝑟𝑒𝑣𝑎
= 𝑟𝑜𝑡𝑐𝑎𝑓 𝑦𝑡𝑖𝑐𝑎𝑝𝑎𝑐 𝑡𝑛𝑎𝑙𝑝
𝑦𝑡𝑖𝑐𝑎𝑝𝑎𝑐 𝑡𝑛𝑎𝑙𝑝
مالحظة- :
Types of load curve
0 < L.F < 1
1-Daily load curve 24 h Connected load تشمل جميع االجهزة
2-Monthly load curve 720 h المربوطة على المحطة الشغالة وغير الشغالة
3-Yearly load curve 8760 h وفائدته هي لمعرفة سعة االجهزة المربوطة
الى المحطة
فوائد منحني الحمل اليومي
-1يبين لنا تغير الحمل مع الوقت
-2المساحة تحت المنحني = عدد
الوحدات المتولدة في اليوم
-0اعلى نقطة في المنحني تمثل الطلب
االعظم max, demand
-4النسبة بين المساحة تحت المنحني
والمساحة الكلية للمستطيل تعطينا
عامل الحمل L.F
-5منحني الحمل يساعد في اختيار
احجام واعداد وحدات التوليد
7
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
EXAMPLE 1:-A power station deliver a EXAMPLE 3:- A generated station has a
two consumers (A , B) as follow connected load of 43 MW and a maximum
Consumer A Consumer B demand of
(MW) (MW) 20 MW the units generated being
2 AM - 6 AM 5 10 61.5*106 per annum calculate
6 AM – 10 AM 10 10 a) Demand factor
10 AM – 2 PM 15 5 b) Load factor
2 PM – 6 PM 10 10 SOLUTION:
6 PM – 2 AM 5 15 a)
Plot the load curve then calculate the load 𝑑𝑒𝑚𝑎𝑛𝑑 𝑓𝑎𝑐𝑡𝑜𝑟 𝑖𝑠
factor of each load then find the load factor 𝑚𝑎𝑥. 𝑑𝑒𝑚𝑎𝑛𝑑
and diversity factor of station =
𝑐𝑜𝑛𝑛𝑒𝑐𝑡𝑒𝑑 𝑙𝑜𝑎𝑑
20 ∗ 103
= = 0.465
SOLUTION: 43 ∗ 103
b)
A+B 𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑑𝑒𝑚𝑎𝑛𝑑 𝑖𝑠
25 𝑢𝑛𝑖𝑡𝑠 𝑔𝑒𝑛𝑒𝑟𝑎𝑡𝑒𝑑 𝑖𝑛 𝑦𝑒𝑎𝑟
=
20 8760 ℎ
A+B (MW
15 61.5 ∗ 106
10 = = 7020 𝐾𝑊
8760 ℎ
5 𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑙𝑜𝑎𝑑
0 𝐿. 𝐹 =
𝑚𝑎𝑥. 𝑑𝑒𝑚𝑎𝑛𝑑
0 2 4 6 8 10 12 14 16 18 20 22 24 7020
TIME = = 0.351
20 ∗ 103
EXAMPLE 4:- A 100 MW power station
delivers 100 MW for 2 hours , 50 MW for
6 hours and is shut down for the rest of
𝑢𝑛𝑖𝑡𝑠 𝑔𝑒𝑛. 𝑝𝑒𝑟 𝑑𝑎𝑦 each day , it's also shut down for
𝐿. 𝐹 (𝐴) = maintenance for 45 days each year ,
24 ℎ ∗ 𝑚𝑎𝑥. 𝑑𝑒𝑚𝑎𝑛𝑑
calculate its annual L.F
5 ∗ 4 + 10 ∗ 4 + 15 ∗ 4 + 10 ∗ 4 + 5 ∗ 8
= SOLUTION:
24 ∗ 15
= 0.55 Energy supplied for each day
𝐿. 𝐹 (𝐵) = 0.72
=100*2+50*6=500 MWh
𝐿. 𝐹 𝑎𝑡 𝑡ℎ𝑒 𝑠𝑡𝑎𝑡𝑖𝑜𝑛 𝑖𝑠
2 ∗ 20 + 15 ∗ 4 + 20 ∗ 18 Station operates for=365-45=320 day
24 ∗ 20
= 0.958 Energy supplied in year is
=500*320=160000 MWh
EXAMPLE 2:- The max. Demand on
power station is 100 MW if the annual 𝑀𝑊ℎ 𝑠𝑢𝑝𝑝𝑙𝑖𝑒𝑑 𝑖𝑛 𝑦𝑒𝑎𝑟
L.Fyear=𝑚𝑎𝑥.𝑑𝑒𝑚𝑎𝑛𝑑∗𝑤𝑜𝑟𝑘𝑖𝑛𝑔 ℎ𝑜𝑢𝑟𝑠
load factor is 40% calculate the total
energy generated per year 160000
= 100∗320∗24 = 0.208
SOLUTION:
Units generated per year is
=max.demand*L.F*8760
=100*103*0.4*8760
=350.4 MW
8
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
65.7 ∗ 106
= = 18750 𝐾𝑊ℎ
0.4 ∗ 8760
𝑟𝑒𝑠𝑒𝑣𝑒 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦 𝑖𝑠
9
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
10
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
EXAMPLE 10:A generating station has EXAMPLE 11: A power station has to
the following daily load cycle meet the following demand
Time (hours) Load (MW) Group A : 200 KW 8 A.M – 6 P.M
0-6 40
6-10 50 Group B : 100 KW 6 A.M – 10 A.M
10-12 60 Group C : 50 KW 6 A.M – 10 A.M
12-16 50
16-20 70 Group D : 100 KW 10 A.M – 6 P.M
20-24 40
And 6 P.M – 6 A.M
Draw the load curve and find
Plot the daily load curve then find; the
a) Maximum demand
diversity factor, units generated per day
b) Units generated per day
and load factor
c) Average load
d) Load factor SOLUTION:-;
SOLUTION:- Time A B C D
نرسم منحني الحمل اعتماداً على القيم المعطاة في (hours) (KW) (KW) (KW) (KW)
السؤال 0-6 - - - 100
6-8 - 100 50 -
8-10 200 100 50 -
load curve 10-18 200 - - 100
80 18-24 - - - 100
60
40 load curve
20 400
load (KW
300
0 200
0 2 6 8 10 12 14 16 18 20 22 24 100
0
من الرسم يتضح لنا ان الطلب االعظم (اعلى نقطة في 0 2 4 6 8 10 12 14 16 18 20 22 24
70 MW الرسم) هو time
=40*10+50*8+60*2+70*4 =450 KW
11
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
12
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
load MW
6–8 20 15
8 – 12 40
10
12 – 16 60
16 – 20 20 5
20 – 24 50 0
24 - 6 20 0 time hours 8760
Plot the load curve and load duration
curve also calculate the energy generated 1
𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑑𝑒𝑚𝑎𝑛𝑑 = ∗ (20 + 4)
per day 2
= 12𝑀𝑊
SOLUTION:-
Plant capacity factor is
60
40 𝑢𝑛𝑖𝑡𝑠 𝑔𝑒𝑛𝑒𝑟𝑎𝑡𝑒𝑑 𝑖𝑛 𝑦𝑒𝑎𝑟 𝑖𝑠
20
1
0 = 4 ∗ 8760 + ∗ (16 ∗ 8760)
0 2 4 6 8 10 12 14 16 18 20 22 24 2
time (hours = 105120 𝑀𝑊
𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑑𝑒𝑚𝑎𝑛𝑑 12
Units gen. in day=area under curve 𝐿. 𝐹 = = = 0.6
𝑚𝑎𝑥𝑖𝑚𝑢𝑚 𝑑𝑒𝑚𝑎𝑛𝑑 20
max . 𝑑𝑒𝑚𝑎𝑛𝑑
80
load duration curve 𝑢𝑡𝑖𝑙𝑖𝑧𝑎𝑡𝑖𝑜𝑛 𝑓𝑎𝑐𝑡𝑜𝑟 =
𝑝𝑙𝑎𝑛𝑡 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦
60 20
= = 0.8
25
load (MW
13
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
15487 𝐾𝑊
Load(MW)
Time(hours)
load
time
load
time
load
time
= = 2212 𝐾𝑊
7
day
𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑑𝑒𝑚𝑎𝑛𝑑 2210
𝐿. 𝐹 = =
𝑚𝑎𝑥𝑖𝑚𝑢𝑚 𝑑𝑒𝑚𝑎𝑛𝑑 3040
= 0.727
Sun. 4 4 5 1 3 8 2 11
Mon. 3 9 4 6 2 7 0.25 2 TUTORIAL PROBLEMS
Tue. 1 4 4 7 5 1 3 12
Wed. 4 2 3 10 2 8 1 4 1- A consumer has the following load
Thur. 3 4 2 5 0.25 2 1 6 cycle for a day
Fri. 2 7 3 6 1 6 0.5 5 Load (W) Time (hours)
Sat. 1 8 2 4 3 7 0.5 5 200 0-6
Construct the weekly duration curve and 3000 6-12
calculate L.F 100 12-13
SOLUTION:- 4000 13-16
2000 16-21
𝑢𝑛𝑖𝑡𝑠 𝑔𝑒𝑛𝑒𝑟𝑎𝑡𝑒𝑑 𝑖𝑛 𝑑𝑎𝑦 1000 21-24
𝑎𝑣. 𝑙𝑜𝑎𝑑 =
24 ℎ Find the load factor
4 ∗ 4 + 5 ∗ 1 + 3 ∗ 8 + 2 ∗ 11 [0.461]
𝑠𝑢𝑛. =
24
2- a generating station has a connected
= 2800 𝐾𝑊 load of 43 MW and a maximum demand
of 20 MW the units generated being
𝑚𝑜𝑛𝑑𝑎𝑦 = 2770 𝐾𝑊
61500000 for the year , calculate the
Tuesday=3040 KW load factor and demand factor
Wednesday =2416 KW [0.351 , 0.465]
Thursday = 1180 KW 3- a 100 MW power station delivers 100
MW for 2 hours , 50 MW for 6 hours
Friday = 1680 KW
and is shut down for the rest of each
Saturday = 1640 KW day , its also shut down for
maintenance for 45 days each year ,
calculate the annual L.F
3500
[0.208]
3000
2500 4- a generating station has a connected
2000
load of 40 MW and a maximum demand
of 20 MW , the units generated being
1500
60*106 , calculate the demand factor
1000
and the load factor
500
0 [0.5 , 0.3425]
tue sun mon wed fri sat ther
14
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
15
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
1- Resistance of T.L
𝝆𝒍
𝑅𝒅𝒄 = 𝒂
Ω
𝑅2 = 𝑅1 ∗ [1 + 𝛼(𝑇2 − 𝑇1 )]
𝑅1 1 + 𝛼1 𝑇1
=
𝑅2 1 + 𝛼0 𝑇0
ELECTRICAL
DESIGN OF
TRANSMISSION
LINE
16
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
2- Inductance of T.L للحصول على فولتيات متساوية في نهاية الخط نقوم
بعملية تبديل المواقع
Transposition
1- Inductance of single conductor
نتيجة لمرور التيار في الموصل ينشأ فيض مغناطيسي
بعضه داخل الموصل وبعضه خارجه (على سطح
الموصل)
تستخدم هذه العملية للحصول على معدل محاثة على خط
*المحاثة في دوائر الـ dcتساوي صفر اما واحد يساوي معدل محاثة الخط االخر (معدل محاثة
في دوائر الـ acفعند مرور التيار في سلك متساوي في االطوار الثالثة) وبالتالي نحصل على
ينشا فيض مغناطيسي ومن هذا الفيض تنشا فولتية متزنة في نهاية الخط
المحاثة
𝐷 اما اذا لم نستخدم هذه العملية فستكون فولتية نهاية الخط
𝐿 = 2 ∗ 10−7 ∗ 𝑙𝑛 ′ غير متزنة
𝑟
r’=0.7788 r 5- Double circuit three phase T.L
2- Inductance for single phase T.L
𝑚𝐷
two wire system La=2*10-7ln
𝑠𝐷
𝐷
La=2*10-7 ln Dm:
𝑟′
𝐷 geometrical
Lb=2*10-7 ln 𝑟′ means distance
𝐷
Lt=4*10-7ln 𝑟′ 𝑚𝐻/ Ds: geometrical
mean radius
3- Inductance of symmetrical three
phase T.L Ds= 3√𝐷𝑠1 𝐷𝑠2 𝐷𝑠3
D Ds1= 4√𝐷𝑎𝑎 𝐷𝑎𝑎′ 𝐷𝑎′𝑎 𝐷𝑎′𝑎′
La=Lb=Lc=2*10-7ln r′
يسمى الخط ثالثي الطور Ds2= 4√𝐷𝑏𝑏 𝐷𝑏𝑏′ 𝐷𝑏′ 𝑏 𝐷𝑏′ 𝑏′
متماثال اذا وضعت
الموصالت الثالثة على Ds3= 4√𝐷𝑐𝑐 𝐷𝑐𝑐 ′ 𝐷𝑐 ′ 𝑐 𝐷𝑐 ′ 𝑐 ′
رؤوس مثلث متساوي
𝐴𝐶𝐷 𝐶𝐵𝐷 𝐵𝐴𝐷√Dm= 3
االضالع
DAB= 4√𝐷𝑎𝑏 𝐷𝑎𝑏′ 𝐷𝑎′ 𝑏 𝐷𝑎′ 𝑏′
17
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
4 L=2*10-7 ln D/r’
=√(0.7788 ∗ 1.3 ∗ 10−2 )2 ∗ 62
=2*10-7 ln 200/0.4828=1.2*10-6 H/m
=0.275 m
L=1.2*10-6*1000=1.2 mH/km
Ds3=Ds1=0.292 m
EXAMPLE 4:The three conductors of
Ds=0.275 m
three phase T.L are arranged at the
Dm= 3√𝐷𝐴𝐵 𝐷𝐵𝐶 𝐷𝐶𝐴 corners of a triangle of sides 2m,2.5m and
4.5m , calculate the inductance per km of
𝐷𝐴𝐵 = 4√𝐷𝑎𝑏 𝐷𝑎𝑏′ 𝐷𝑎′𝑏 𝐷𝑎′ 𝑏′ the line when the conductors are regularly
transposed , the diameter of each
4 2 conductor is 1.24 cm
= √32 ∗ (√32 + 62 )
SOLUTION:-
= 4.48 𝑚
r= 0.62 cm
DBC=4.48 m
r’ = 0.62*0.7788=0.4828 cm
4
𝐷𝐶𝐴 = √𝐷𝑐𝑎 𝐷 𝑐𝑎 ′ 𝐷 𝑐′𝑎 𝐷
𝑐 ′ 𝑎′
D12=2 m=200 cm
4
= √63 ∗3 =6 D23=2.5 m =250 cm
18
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
=1.274*10-6
L=1.272*10-6*100 = 1.272 mH/km
EXAMPLE 5 :Calculate the inductance of
each conductors in three phase 3 wires
system when the conductors are arranged
in horizontal such that :D31 =4 m
D12=D23=2m , the conductors are
transposed and have a diameter of 2.5 cm
Find the inductance per phase per km the
SOLUTION:- conductor are transposed and are of radius
0.75 cm each, the phase sequence is ABC
Deq = 3√𝐷12 𝐷23 𝐷31
SOLUTION:-
3
= √4 ∗ 2 ∗ 2 = 2.52 𝑚 = 252 𝑐𝑚
r’ = 0.75*0.7788=0.584 cm
′
𝑟 = 1.25 𝑐𝑚 𝑟 = 0.9735 2
Dab=√0.752 + 32 =3.1 m
𝐷𝑒𝑞
L=2*10-7 ln 𝑟′ H/m
Dab’=√32 + 4.752 =5.62 m
L=2*10-7 ln 252/0.9735=1.11*10-6 H/m
Daa’=√62 + 42 =7.21 m
-6
L=1.11*10 *1000=1.11 mH/km
Ds= 3√𝐷𝑠1 𝐷𝑠2 𝐷𝑠3
EXAMPLE 6 :Two conductors single
phase line each of 1 cm diameter , are Ds1= 4√𝐷𝑎𝑎 𝐷𝑎𝑎′ 𝐷𝑎′ 𝑎 𝐷𝑎′ 𝑎′
arranged in vertical plant which one
4
conductor mounted 1 m above the other a =√(0.584 ∗ 10−2 )2 ∗ 7.212=0.205 m
second identical line is mounted at the same
Ds3=Ds1=0.205 m
height as the first and spaced horizontally
0.25 m apart from it, the two upper and two Ds2= 4√𝐷𝑏𝑏 𝐷𝑏𝑏′ 𝐷𝑏′ 𝑏 𝐷𝑏′ 𝑏′
lower conductors are connected in parallel
4
, determine the inductance per km of the =√(0.584 ∗ 10−2 )2 ∗ 5.52 = 0.18 𝑚
resulting double circuit line
3
Ds=√0.18 ∗ 0.205 ∗ 0.205 = 0.195 𝑚
SOLUTION:-
Dm= 3√𝐷𝐴𝐵 𝐷𝐵𝐶 𝐷𝐶𝐴
r = 0.5 cm
r’ = 0.389 cm DAB= 4√𝐷𝑎𝑏 𝐷𝑎𝑏′ 𝐷𝑎′ 𝑏 𝐷𝑎′ 𝑏′
4
L=2*10-7 ln Dm/Ds =√3.1 ∗ 5.62 ∗ 3.1 ∗ 5.62 = 4.17 𝑚
DBC=DAB=4.17 m
Dm= 4√𝐷𝑎𝑏 𝐷𝑎𝑏′ 𝐷𝑎′ 𝑏 𝐷𝑎′ 𝑏′
DCA= 4√𝐷𝑐𝑎 𝐷𝑐𝑎′ 𝐷𝑐 ′ 𝑎 𝐷𝑐 ′ 𝑎′
4 2
= √252 ∗ (√252 + 1002 ) =50.76 cm 4
=√6 ∗ 6 ∗ 4 ∗ 4=4.9 m
19
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
3
Dm=√4.9 ∗ 4.17 ∗ 4.17=4.4 m 3- Capacitance of T.L
-7
L=2*10 ln Dm/Ds 1- Capacitance of single phase T.L
4.4
L=2*10-7 ln 0.195
n
=0.623*10-6 mH/m
L=0.623*10-6*1000 =0.623 mH/km
EXAMPLE 8 :Calculate the inductance QA+QB=0
per phase per meter for a three phase QA=-QB
double circuit line whose phase conductor
𝑞 𝐷
have a radius of 5.3 cm with the horizontal Vab=𝜋𝜀 ln 𝑟 V
0
conductor arrangement
𝜋𝜀0
SOLUTION:- Cab= 𝐷 F/m
ln
𝑟
0 2𝜋𝜀
Ds=0.995 Ca=Cb=Cc=ln 𝐷/𝑟 F/m
=14.518 m
14.518 نتيجة لوجود المتسعة ينشأ تيار الشحن:مالحظة مهمة
L=2*10-7 ln 0.995 charging current
=5.36*10-7 H/m Ic=jWCVph
هي ظاهرة زيادة فولتية االستالم: ظاهرة فيرانتي
نتيجة لوجود متسعات الشحن للخطوط الغير محملة
20
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
SOLUTION:-
3
Deq= 3√𝐷12 𝐷23 𝐷31 = √2 ∗ 2.5 ∗ 4.5
= 2.82 m = 282 cm
21
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
22
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
23
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
Vs=sending voltage
VR = receiving voltage
Is=sending current = IL =IR
R=total resistance of T.L
XL=total reactance of T.L
Performance of
Is =IR ………………………….….1
Overhead Lines Vs=VR+IR Z
VS=VR+(R+J XL )IR ………….....2
4 و3 مع المعادلتين2 و1 بمقارنة المعادلتين
VS=AVR+BIR ……………………3
الغاية من دراسة خطوط النقل هي لمعرفة هبوط الجهد IS=CVR+DIR …………………….4
والخسائر وكفاءة الخط
نستنتج ما يلي
وعلى اساسه تم تصنيف خطوط النقل الى ثالث اصناف
A=1 , B=Z , C=0 , D=1
خط النقل القصير-1
AD – CB = 1
kV 23 كم ويعمل على03-53
Voltage Regulation
خط النقل المتوسط-2
𝑉𝑆 −𝑉𝑅
V.R%= ∗ 100%
kV 102-23 كم ويعمل على023-03 𝑉𝑅
𝑜𝑢𝑡𝑝𝑢𝑡 𝑝𝑜𝑤𝑒𝑟
=𝑜𝑢𝑡𝑝𝑢𝑡 𝑝𝑜𝑤𝑒𝑟+𝑙𝑜𝑠𝑠𝑒𝑠 ∗ 100%
24
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
=33708.3+j250 V
׀Vs(√=׀33708.3)2 + (250)2
=33709 V
Phasor diagram for laggin p.f b) Line losses=I2R
=(41.67)2*10=17.364 KW
Output power delivered=1100 KW
Power sent=1100+17.364=1117.364 KW
𝑝𝑜𝑤𝑒𝑟 𝑑𝑒𝑙𝑖𝑣𝑒𝑟𝑒𝑑
Phasor diagram for unity p.f Efficiency = 𝑝𝑜𝑤𝑒𝑟 𝑠𝑒𝑛𝑡
∗ 100%
1100
=1117.364 ∗ 100%
=98.44%
EXAMPLE 2 :What is the maximum length
in km for a single phase T.L having copper
Phasor diagram for leading p.f conductor of 0.775 cm2 crass section over
which 200 KW at unity power factor and at
3300 V are to be delivered, the efficiency if
T.L is 90% , take specific resistance as
EXAMPLE 1 :A single phase overhead T.L 1.725 μΩ cm
delivers 1100 KW at 33 KV at 0.8 p.f SOLUTION:-
lagging , the total resistance and inductive
reactance of the line are 10 Ω and 15 Ω Receiving end power = 200 KW
respectively , determine
Efficiency =0.9
a) Sending end voltage
Sending end power=200/0.9 = 222.22 KW
b) Sending end p.f
c) Transmission efficiency Line losses = 22.22 KW
SOLUTION:-
200∗103
Line current = 3300∗1
= 60.6 𝐴
Zt =R+jXL=10+j15
VR=33000 V Line losses=2I2R
25
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
EXAMPLE 3:A 3-phase T.L delivers 5000 EXAMPLE 4 : Estimate the distance over
KW at 22 KV at p.f=0.8 lagging, the which a load of 15000 KW at p.f=0.8
resistance and reactance of each conductor lagging can be delivered by a 3-phase T.L
is 4Ω and 6Ω respectively, determine having conductor each of resistance 1 Ω
per km the voltage at the receiving end is to
a) Sending end voltage
be 132 KV and the losses in the line is to be
b) Percentage regulation
5% PR
c) Transmission efficiency
SOLUTION:- SOLUTION:-
Receiving end voltage per phase 15000
I= = 82 𝐴
√3∗132∗103 ∗0.8
22000
VR= = 12700 𝑉 Line losses=0.05*15000 = 750 KW
√3
line losses=3I2R
26
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
=3(81.36)2*5.31=105.447 KW VS=6351+262.43*1.5*0.8+262.43*4*0.6
3600 = 7295.8 V
Efficiency=3600+105.447 ∗ 100%
𝑉𝑆 −𝑉𝑅
= 97.15% V.R%= 𝑉𝑆
∗ 100%
120∗103 =4000 KW
VS= = 69282 𝑉
√3
I/p power=o/p power+losses
VS=VR+IRcosөR+IXLsin өR
=4000+310=4310 KW
69282=63508+I*6*0.9+I*8*0.435
5774
Transmission efficiency=4000/4310
I= 8.88 = 650.2 𝐴
=0.928=92.8 %
3𝑉 ∗𝐼∗𝑐𝑜𝑠𝜃𝑅
a) o/p power= 𝑅 𝐾𝑊 EXAMPLE 8:A 3-phase, 50 Hz , 16 km
1000
3∗63508∗650.2∗0.9
long overhead line supplies 1000 KW at
= 1000 11 KV , 0.8 p.f lagging ,the line resistance
is 0.03Ω per phase per km and line
= 111490 𝐾𝑊 inductance is 0.7Ω per phase per km ,
𝑉𝑅 𝑐𝑜𝑠𝜃𝑅 +𝐼𝑅 calculate The sending end voltage, voltage
p.fS=cosөS= 𝑉𝑆 regulation and efficiency of T.L
63508∗0.9+650.2∗6
= 69282
= 0.88 𝑙𝑎𝑔𝑔𝑖𝑛𝑔 SOLUTION:-
11 𝐾𝑉
EXAMPLE 7 : An 11 KV 3-phase T.L has VR= = 6351 𝑉
√3
a resistance of 1.5 Ω and reactance of 4 Ω
1000
per phase , calculate the percentage I=3∗11000∗0.8 = 65.6 𝐴
regulation and efficiency of the line when a
total load of 5000 KVA at 0.8 lagging p.f is R=0.03*16 = 0.48 Ω
supplied at 11 KV at the distant end XL=2πf l *16=2π*50*0.7*103*16
SOLUTION:- =3.52 Ω
11∗103
VR= 3 = 6351 𝑉 VS = VR + I R cosөR + I XL sinөR
√
27
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
28
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
2- Medium T.L 𝑌𝑍
𝐴=𝐷 =1+
2
طرق لتمثيل خط النقل المتوسط0 هناك
𝑌𝑍 2
𝐵 = (𝑍 + )
a) T-nominal method 4
b) Π-nominal method
c) End condenser method 𝐶=𝑌
AD-BC=1
a) T-nominal method
EXAMPLE 1:3-phase , 50 Hz , T.L , 100
km long has the following constants
R/km/phase=0.1 Ω
XL /km/phase=0.2 Ω
Equivalent circuit for T-nominal method Capacitance susceptance /km/phase
=0.04*10-4 S
Determine a) sending end current
b) Sending end voltage
c) Sending end p.f
d) Transmission efficiency
Phasor diagram for T-nominal method
When supplying a balanced load of
lagging p.f
10000KW at 66 KV p.f=0.8 lagging
𝐼𝑆′ = 𝐼𝐶′ + 𝐼𝑅′
SOLUTION:-
𝑍
𝑉𝐶′ = 𝑉𝑅′ + 𝐼𝑅
2
𝑍
𝑉𝑆′ = 𝑉𝐶′ + 𝐼𝑆
2
𝑍 𝑍
𝑉𝑆′ = 𝑉𝑅′ + 𝐼𝑅 + 𝐼𝑆
2 2 Rt=0.1*100=10 Ω
𝐼𝑆′ = 𝑌𝑉𝐶′ + 𝐼𝑅′ XLt=0.2*100=20 Ω
𝑍 Y=0.04*10-4*100=4*10-4 S
= 𝑌 (𝑉𝑅′ + 𝐼𝑅 ) 𝐼𝑅′
2 66000
VR= = 38105 𝑉
𝑍 √3
= 𝑌𝑉𝑅′ + (1 + 𝑌 ) 𝐼𝑅′
2 10000∗103
IR= = 109 𝐴
√3∗66∗103 ∗0.8
𝑍 𝑍 𝑍
𝑉𝑆′ = 𝑉𝑅′ + 𝐼𝑅′ + [𝑌𝑉𝑅′ + (1 + 𝑌 ) 𝐼𝑅′ ]
2 2 2 Cosөr=0.8 sinөr=0.6
𝑌𝑍 𝑍2 Z=R+jXL=10+j20
𝑉𝑆′ = 𝑉𝑅′ (1 + ) + (𝑍 + 𝑌 ) 𝐼𝑅′
2 4
VR=VR+j0=38105 V
𝑍
𝐼𝑆′ = 𝑌𝑉𝑅′ + (1 + 𝑌 ) 𝐼𝑅′ IR=IR(cosθR – jsinθR)
2
=109(0.8-j0.6)=87.2-j65.4
29
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
=39195+j545 XLt=0.4*100=40 Ω
IC=jYV1 Y=2.5*10-6*100=2.5*10-4 S
=j4*10-4(39195+j545) Z=20+j40
110∗103
=-0.218+j15.6 V R= = 63508 𝑉
√3
IS=IR+IC 20∗106
I R= = 116.6 𝐴
√3∗110∗103 ∗0.9
=(87.2-j65.4)+(-0.218+j15.6)
CosθR=0.9 SineθR=0.435
=87-j49.8=100∟-29.47o
VR=VR+j0=63508 V
IS=100 A
IR=IR(cosθR-jsinθR)
VS=V1+IS Z/2 =116.6(0.9-j0.435)=105-j50.7 A
=(39195+j545)+(87-j49.8)(5+j10) V1=VR+IR Z/2
=40128+j1170 =63508+(105-j50.7)(10+j20)
=40145 ∟1.4o =65572+j1593
ΘS=1.4o+29.47o=31.27o =-0.4+j16.4
IS=IR+IC
Cosθs=0.853
=105-j50.7-0.4+j16.4=104.6-j34.3 A
Sending end power is
IS=110∟-18.9 A
=3*40145*100*0.853
VS=V1+IS Z/2
=10273.105 KW
=(65572+j1593)+(104.6-j34.3)(10+j20)
Transmission efficiency is
=67304+j3342
1000
=10273.105*100% /VS/=67387
=97.34 % VS line =67387*√3=116.717 KV
EXAMPLE 2 :3-phase, 50 Hz , T.L 100 km Total line losses for the three phase is
long deliver 20 MW at 0.9 p.f lagging and at 110
KV , the resistance and reactance of the line per =3(IS)2 R/2 + 3(IR)2 R/2
phase per km are 0.2Ω and 0.4Ω while =3*1102*10+3*116.62*10
capacitance admittance is 2.5*10-6S/km/phase
calculate a) VS & IS b) efficiency of T.L =0.778*106 W = 0.77 MW
20
SOLUTION:- Transmission efficiency= = 0.9629
20+0.77
Rt=0.2*100=20 Ω
30
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
R=0.1*150 = 15 Ω
Phasor diagram for π method lagging p.f XL=0.5*150=75 Ω
𝑉𝑆′ = 𝑉𝑅′ + 𝐼𝐿′ 𝑍 Y=3*10-6*150=45*10-5 S
𝑌 110∗103
𝐼𝐿′ = 𝐼𝐶1
′
+ 𝐼𝑅𝐼 𝐼𝐶1 = 𝑉𝑅 VR= = 63508 𝑉
2 √3
𝑌 𝑌 50∗106
𝐼𝐿′ = 𝑉𝑅′ + 𝐼𝑅′ 𝐼𝐶2 = 𝑉𝑆 IR= = 328 𝐴
√3∗110∗103 ∗0.8
2 2
𝑌 CosθR=0.8 sinθR=0.6
𝑉𝑆′ = 𝑉𝑅′ + (𝑉𝑅′ + 𝐼𝑅′ ) 𝑍
2 IR=IR(cosθR-jsinθR)
𝑌𝑍 ′
𝑉𝑆′ = (1 + ) 𝑉 + 𝑍𝐼𝑅′ … … … .1 =328(0.8-j0.6)=262.4-j196.8
2 𝑅
IC1=jVR Y/2
𝐼𝑆 = 𝐼𝐿 + 𝐼𝐶2
45∗10−5
𝑌 𝑌 IC1=63508*j = 𝑗14.3
𝐼𝑆′ = 𝑉𝑅′ + 𝐼𝑅′ + 𝑉𝑆′ … … … … . .2 2
2 2
IL=IC1+IR
2 في م1 من مVS بتعويض قيمة
=(262.4-j196.8)+j14.3
𝑌 𝑌𝑍 𝑌
𝐼𝑆 = 𝑉𝑅 + 𝐼𝑅 + [(1 + ) 𝑉𝑅 + 𝑍𝐼𝑅 ] =262.4-j182.5 A
2 2 2
𝑌2𝑍 𝑌𝑍 VS=VR+IL Z
𝐼𝑆 = [𝑌 + ] 𝑉𝑅 + [1 + ] 𝐼𝑅
4 2 =63508+(262.4-j182.5)(15+j75)
=81131+j16942.5 V
𝑌𝑍 /Vs/=82881 V
𝐴=𝐷 =1+
2
Line to line sending end voltage
𝐵=𝑍
=82881*√3=143.55 KV
𝑌2𝑍
𝐶=𝑌+
2 IC2=jVS Y/2
31
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
45∗10−5 VS=VR+IL Z
=(81131+j16942.5)*j 2
=38105+(176-j66)(10+j50)
=-3.81+j18.25 A
=43165+j8140=43925∟10.65o
IS=IL+IC2
/VS/=43925 V
=(262.4-j182.5)+(-3.81+j18.25)
VS line to line =√3 ∗ 43925 = 76 𝐾𝑉
=258.6-j164.25
IC2=jVS Y/2
/IS/=306.4
10∗10−4
EXAMPLE 2: 100 km long, 3-phase T.L =(43165+j8140)* j 2
has the following line constants
=-4+j21.6 A
R/phase/km = 0.1 Ω
IS=IL+IC2=(176-j66)+(-4+j21.6)
XL/phase/km =0.5 Ω
=172-j44.4
Suspectance/phase/km =10*10-6 S
/IS/=177.6∟-14.5o A
If the line supplies load of 20MW at 0.9 p.f
lagging at 66 KV at the receiving end, ΘS=10.65o+14.5o=25.15o
calculate by nominal π method Sending end p.f = cosθS =0.905 lag
a) Sending end power factor 𝑉𝑠 −𝑉𝑅
V.R%= 𝑉𝑅
∗ 100%
b) Voltage regulation
c) Transmission efficiency 43925−38105
SOLUTION:- = ∗ 100% = 15.27 %
38105
R=0.1*100=10 Ω
XL=0.5*100 = 50 Ω
Y=10*10-6*100=10*10-4 S
66∗103
VR= = 38105 𝑉
√3
20∗106
IR= = 195 𝐴
√3∗66∗103 ∗0.9
SinθR=0.435
IR=IR(cosθR-jsinθR)
=195(0.9-j0.435)=176-j85
IC1=jVR Y/2
10∗10−4
=38105*j 2
= 𝑗19 𝐴
IL=IR+IC1=(176-j85)+j19=176-j66 A
32
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
A=(1+YZ) B=Z = j 92 A
C=Y D=1 a)
AD - BC=1 IS=IR+IC=(227-j170)+j90
= 227-j78
/IS/=240 A
33
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
b)
Home works
drop voltage=ISZ=IS(R+jXL)
1- Draw the phasor diagram of the
=(227-j78)(25+j80)
medium T.L T-nominal method for
=11915+j16210 V (i)unity power factor (ii) leading
power factor
VS=VR+ISZ=66000+11915+j16210 2- Draw the phasor diagram of the
= 77915+j16210 V medium T.L π-nominal method for
(i)unity power factor (ii) leading
/VS/=79583 V power factor
3- Draw the phasos diagram of the
c)
medium T.L end condenser method
𝑉𝑆 −𝑉𝑅 for (i)unity power factor
V.R%= 𝑉𝑅
∗ 100% = 20.58 %
(ii)leading power factor
d)
−78
θ1=tan−1 =-18.96oR
227
16210
θ2=tan−1 77915 =11.5o
θS=18.96o+11.5o=30.46
supply p.f =cos 𝜃𝑠 = cos 30.46
=0.86 lag
34
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
35
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
طريقة التحليل المعتمدة لتحليل واخراج قيم الثوابت في To find the overall constants of two T.L
Rigorous method خط النقل الطويل تسمى بـ connected in series
𝑉𝑆 𝐴 𝐵1 𝐴2 𝐵2 𝑉𝑅
=[ 1 ][ ]
𝐼𝑆 𝐶1 𝐷1 𝐶2 𝐷2 𝐼𝑅
A=A1A2+B1C2
B=A1B2+B1D2
C=C1A1+D1C2
𝑍
VS=VR cosh√𝑍 𝑌+IR√𝑌 𝑠𝑖𝑛ℎ√𝑍 𝑌 D=C1B2+D1D2
إذا كان الخطين متماثلين
𝑌
𝐼𝑆 = 𝑉𝑅 √ sinh √𝑍 𝑌 + 𝐼𝑅 cosh √𝑍 𝑌 A1=A2=A A=A2+BC
𝑍
B1=B2=B B=AB+BD
𝑍
A=cosh√𝑍 𝑌 , 𝐵= √ sinh √𝑍 𝑌 C1=C2=C C=CA+DC
𝑌
D1=D2=D D=CB+D2
𝑌
𝐶 = √ 𝑠𝑖𝑛ℎ√𝑍 𝑌 , 𝐷 = cosh √𝑍 𝑌 2- Parallel connection
𝑍
𝐴𝐷 − 𝐵𝐶 = 1
IS=IS1+IS2 VS=VS1=VS2
IR=IR1+IR2 VR=VR1=VR2
𝑉𝑆1 𝐴 𝐵1 𝑉𝑅
=[ 1 ]
𝐼𝑆1 𝐶1 𝐷1 𝐼𝑅
𝑉𝑆2 𝐴 𝐵2 𝑉𝑅2
=[ 2 ]
𝐼𝑆2 𝐶2 𝐷2 𝐼𝑅2
𝐴1 𝐵1 +𝐴2 𝐵2 𝐵1 𝐵2
𝐴= , B=
𝐵1 +𝐵2 𝐵1 +𝐵2
(A1 − A2 )(D1 − D2 )
C = (C1 + C2 ) −
B1 + B2
𝐵1 𝐷2 + 𝐵2 𝐷1
𝐷=
𝐵1 + 𝐵2
36
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
Corona
وهي ظاهرة ظهور وهج شاحب اللون حول الموصل عند
الفولتيات العالية ويمكن رؤيته في الظالم
إذا كان البعد بين موصلين أكثر من 15مرة من نصف
قطر الموصل فان زيادة الجهد عن قيمة فولتية القطع وهي
الفولتية التي تؤدي الى حدوث ظاهرة الهالة تؤدي الى
حدوث قفز وميض وشرارة الى جميع مناطق الفراغ
الواصل بين الموصلين
اما إذا كان البعد بين الموصلين اقل من 15مرة من نصف
قطر الموصل فان قفز الوميض او الشرارة تحدث قبل
ظهور الهالة المرئية
هناك عدة ظواهر تصاحب هذه الظاهرة
تأين الهواء المحيط بالموصل -1
ظهور ضوء بنفسجي يحيط بالموصل -2
ضوضاء وازيز يصاحب الظاهرة -0
انبعاث غاز االوزون -4
العوامل المؤثرة على ظاهرة الهالة
الجو المحيط بالموصل :إذا كان الجو عاصف او -1
ممطر تحدث الهالة بفولتية اقل منها من الجو
الطبيعي
MECHANICAL سطح الموصل :إذا كان املسا تكون اقل حدوثا وإذا -2
DESIGN OF كان خشنا يحتوي على نتوءات يكون حدوث هذه
الظاهرة بنسبة أكبر
OVERHEAD T.L نصف قطر الموصل :يقل حدوث هذه الظاهرة -0
بزيادة نصف القطر
المسافة بين الموصالت :يقل حدوث هذه الظاهرة -4
بزيادة المسافة بين الموصالت
الفولتية العاملة :كلما ارتفعت فولتية الخط ازداد -5
حدوث ظاهرة الهالة
االجزاء الرئيسية لخط النقل هي
طرق تجنب ظاهرة الهالة
1. Conductors
2. Insulators -1زيادة قطر السلك او استخدام الموصالت المجوفة
3. Cross arm -2زيادة المسافة بين الموصالت
4. Tower محاسن ظاهرة الهالة
-1تأين الهواء المحيط بالموصل حيث تكثر به عدد
االيونات كأنما قطر الموصل الفعلي يزداد فتقل
المقاومة
-2تقلل من االجهادات الساكنة الكهربائية التي تعمل
على سطح الموصل
-0تقلل من – serge voltagesوهي فولتيات اعلى
من الفولتية العادية – حيث تصل الفولتية الى قيم
عالية جدا خالل فترة زمنية قليلة وعادة ما تحدث
نتيجة للبرق او فتح وغلق قواطع الدورة
37
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
38
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
EXAMPLE 1 :Find the corona By using Peterson formula for fair weather
characteristic of a 110 KV , 50 Hz , 3-phase 21.1 𝑓 𝑉 2 ∗10−6
T.L 175 km long consisting of three 1cm PC= 𝐷 𝐹 KW/phase/km
(ln )2
𝑟
diameter stranded copper conductors
spaced in 3 m delta arrangement , V/VC=63.5/55.6 = 1.142
temperature 26o C and barometric pressure F= 0.0713
is 74 cm , m=0.85 mv for local
corona=0.72 and mv for general corona = 21.1∗50∗(63.5)3 ∗10−6
PC= 300 2 *0.0713
0.82 (ln )
0.5
We given mv=0.72 for local corona & Total power loss=3*2.165*175 = 1138 KW
mv=0.82 for general corona EXAMPLE 2:A certain 3-phase , 220 KV
0.3 𝐷 ,50Hz T.L consist of 1.5 cm radius
Vv=E r δ m ( 1+ ) ln 𝑟
√𝑟 𝛿 conductor spaced 2 m apart in equilateral
0.3 300 triangle if the irregularity factor is 0.85 ,
𝑉𝑣 = 21.1 ∗ 0.97 ∗ 0.72 ∗ 0.5 (1 + ) ln
√0.5 ∗ 0.97 0.5 the temperature is 40o C and atmospheric
pressure is 76 cm calculate the corona
= 67.5 KV
losses per km
0.3 300
Vv=21.1*0.97*0.82*0.5(1+ ) ln 0.5 SOLUTION:-
√0.5∗0.97
39
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
= 120.66 KV/phase
EXAMPLE 6:A 3-phase ,220 KV ,50Hz
T.L consists of 1.5 cm radius conductor
220
V= = 127 KV/phase spaced 2 m apart in equilateral triangle
√3
formation , if the temperature is 40o C and
242.2 𝑟 atmospheric pressure is 76 cm , calculate
P= (𝑓 + 25)√ (𝑉 − 𝑉𝐶 )2 ∗ 10−5
𝛿 𝐷
the corona loss per km of the line, take
m=0.85
242.2 1.2
= ∗ 75√ (127 − 120.66)2 ∗ 10−5 SOLUTION:-
0.966 200
3.92 𝑏 3.92 ∗ 76
= 0.579 KW/km/phase 𝛿= = = 0.952
273 + 𝑡 273 + 40
Total power losses=3*0.579 = 1.737 KW/km
VC= E r m δ ln D/r
EXAMPLE 4 :A 3-phase line has
conductors 2 cm in diameter spaced =21.2*1.5*0.85*0.952*ln200/1.5
equilaterally 1 m apart , if E=21.2 kV/cm , = 125.9 KV
find the disruptive critical voltage for the
220
line , take air density factor 0.952 and V= = 127 𝐾𝑉
√3
irregularity factor m=0.9
242.2 𝑟
SOLUTION:- P= 𝛿
(𝑓 + 25)√𝐷 (𝑉 − 𝑉𝐶 )2 ∗ 10−5
VC=E r m δ ln D/r
242.2 1.5
P = 0.952 ∗ 75√200 (127 − 125.9)2 ∗ 10−5
=21.2*1*0.9*0.952*ln100/1
= 0.019999 KW/km/phase
=83.64 KV/phase]*√3 =144.8 KV
Total power loss=3*0.019999=0.05998 KW
EXAMPLE 5 :A 132 KV line with 1.956 cm
diameter, conductors is built so that corona
takes place if the line voltage exceeds 210
KV (r.m.s) , if the value of potential
gradient at which ionization occurs can be
taken as 30 KV/cm , find the spacing
between conductors
SOLUTION:-
r= 1.956/2 = 0.978 cm
E=21.2 KV/cm
40
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
TUTORIAL PROBLEMS
العوازل
1- Estimate the corona loss for a 3-phase ,
110 KV , 50 Hz ,150 km long T.L consisting من المعلوم ان موص الالالالالالت خطوط النقل المعلقة عارية
of three conductors each of 10 mm وليسالالت معزولة ولذلك فان الوظيفة االولى التي تسالالتخدم
diameter and spaced 2.5 m apart in an العوازل من اجلها هي عزل الموص الالالالالالت عن بعض الالالالالها
equilateral triangle formation , the البعض وعن ج سم البرج تحت اق صى الجهود وفي ا سوأ
temperature of air is 30o C and the الظروف الجوية المتوقعة ,اما الوظيفة الثانية فهي اسناد
atmospheric pressure is 750 mm of او حمل الموصالت تحت اسوأ االجهادات الميكانيكية
mercury , take irregularity factor as 0.85 ,
ionization of air may be assumed to take المواد المستخدمة في صناعة العازل
place , take the dielectric strength of air as
الخزف ((porcelain .1
30 KV/cm ][316.8 KW
الزجاج المقوى ()toughened-glass .2
2- Taking the dielectric strength of air to be
30 KV/cm , calculate the disruptive critical تمتاز العوازل الزجاجية عن الخزفية بما يلي
voltage for a 3-phase line with conductors
of 1 cm radius and spaced symmetrically في العوازل الزجاجية من الممكن رؤية عدم التجانس .1
4 m apart ][220 KV line voltage من خالل الفقاعات او غيرها
3- A 3-phase ,220 KV ,50 Hz T.L consists of من المزايا العملية للعوازل الزجاجية هو انه عند .2
1.2 cm radius conductors spaced 2 m at the تعرض العازل للضغط نتيجة للجهود العالية او إلي
corners of an equilateral triangle , سبب ميكانيكي خارجي فان ذلك يؤدي الى تكسر
calculate the corona loss per km of the line الزجاج الى شظايا صغيرة يمكن رؤيتها على االرض
, the condition of the wire is smoothly وبذلك يمكن تمييز العازل المتضرر عن غيره ,اما في
weathered and the weather is fair with حالة العوازل الخزفية فان تمييز العازل المتضرر ال يتم
temperature of 20o C and barometric بسهولة إذ ان الخزف يتشقق او يتفطر عند تعرضه
pressure of 72.2 cm of Hg لالنهيار الكهربائي
معامل التمدد الحراري للزجاج اقل من معامل التمدد .0
الحراري للخزف وهذا يجعل االجهاد الذي يسببه تغير
درجة الحرارة المحيط قليال في حالة العوازل الزجاجية
ان تسخين العازل نتيجة تعرضه ألشعة الشمس يكون .4
اقل في حالة العازل الزجاجي الن معظم اشعة الحرارة
تخترق الزجاج بدال من امتصاصها
41
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
مزايا عوازل المسمار لها مضالت متماثلة ذات اقطار متساوية وتبعد عن -1
بعضها البعض بمسافات متساوية مما يجعل مسار
يتكون عازل المسمار من قطعة واحدة او أكثر من -1 التسرب منتظما
الخزف او الزجاج المقسى وتسمى كل قطعة بالمظلة لها متسعة كهربائية واطئة وتدرج جهد واطئ عن -2
تكون المظالت مسارا مناسبا للتسرب بين الموصل -2 الموصالت الحية (المكهربة)
واالرض يكون الجهد الذي تتكون عنده الهالة عاليا -0
يصمم السطح الخارجي للمظالت بحيث ينطبق على -0 اجزاء تثبيت العازل تكون خارج مادة العازل وهذا -4
الخطوط المتساوية الجهد للمجال الكهربائي الذي يمنع حدوث اجهادات تسبب انفجار العازل
تسببه منظومة الموصالت والمسند وبذلك تكون تكسر المظالت نتيجة الجهد الكهربائي او ضرر -5
جميع نقاط هذه السطوح متساوية الجهد مما يؤدي ميكانيكي خارجي ال يؤثر في قيمة جهد قفز الوميض
الى منع سريان تيار التسرب عبر هذه السطوح في يمكن تصميم العازل بحيث يكون محور العازل -0
الظروف االعتيادية بوضع افقي دون الحاجة الى استخدام ذراع المسند
تكون المظالت عادة متباعدة عن بعضها البعض -4
وذلك للحصول على أكبر فائدة ممكنة من عملية
التنظيف التي تسببها االمطار مساوئ عوازل العمود
تستعمل عوازل المسمار ذات المظلة الواحدة عندما -5
يكون جهد الخط 00كيلو فولت او اقل -1يستخدم لغاية جهد 00كيلو فولت
تستخدم عوازل المسمار المتعددة المظالت عندما -0 -2صعوبة تجفيف وتحميص الخزف لعازل العمود ذي
يكون جهد الخط 22-00كيلو فولت القلب الصلد عندما يزداد قطره
يتم تثبيت عازل المسمار الى ذراع المسند بواسطة -.
مسمار محوري فوالذي يتصل من الناحية الثانية
بحلقة معدنية مسننة من االخل ومثبتة بواسطة
االسمنت في تجويف داخل العازل
عوازل المسمار يمكن ان تقارن من حيث السلوك -0 عوازل التعليق
الكهربائي بمجموعة معقدة من المتسعات مزايا عوازل التعليق
والمقاومات المربوطة على التوالي حيث تشكل
المظالت والفسحات الفاصلة بينها متسعات تكون الكلفة االولية لسلسلة عوازل التعليق اقل من -1
المنظومة كما يمكن تمثيل مسارات التسرب على الكلفة االولية لعازل مسمار مكافئ لها من حيث
سطح العازل وعبر العازل نفسه بمقاومات مقدار الجهد
صنع عوازل التعليق من مادة عازلة متجانسة أسهل -2
مما هي عليه في عوازل المسمار الكبيرة الحجم
مساوئ عوازل المسمار مرونة سلسلة عوازل التعليق تؤدي الى تقليل -0
االجهادات الميكانيكية والى تعادل التوتر بين
-1تكون الهالة الموصالت على جهتي المسند
-2زيادة الكلفة االولية عند استخدامه في الفولتيات من الممكن استخدام سلسلة عوازل التعليق مع -4
العالية خطوط نقل ذات جهود مختلفة وذلك بتغيير عدد
العوازل في السلسلة حسب متطلبات خط النقل
في حالة حصول عطب في أحد عوازل السلسلة -5
يستبدل ذلك العازل دون الحاجة الى استبدال السلسلة
بكاملها
عندما يكون الحمل الميكانيكي على خط النقل عاليا -0
يمكن استعمال سلسلتين او أكثر من عوازل التعليق
على التوازي
42
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
عازل عمود
مجوف
عازل مسمار متعدد المضالت من النوع المضاد
للضباب
عازل تعليق
43
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
اختبارات عوازل خطوط النقل -.اختبار المسامية :هذا االختبار هو اختبار للطالء
على العوازل الخزفية ,في هذا االختبار يوزن
اختبار قفز الوميض الجاف :يركب العازل وهو -1 العازل وبعد ذلك يغطس لمدة 24ساعة في ماء
نظيف في الوضع الذي يكون عليه اثناء االستعمال مضغوط وبعدها يوزن مرة ثانية فاذا لوحظت زيادة
ويسلط عليه جهد ذو تردد 53هرتز وتزداد قيمة هذا في وزن العازل فانه يدل على ان العازل فشل في
الجهد تدريجيا حتى تصل الى قيمة صغرى محددة اختبار المسامية
تعتمد على نوع وحجم العازل ويجب ان يتحمل -0اختبار النبض :ان انهيار العازل او عدم انهياره ال
العازل هذه القيمة من الجهد لفترة ال تقل عن 03 يعتمد على الفولتية المسلطة فقط بل يعتمد كذلك على
ثانية دون حدوث قفز الوميض النسبة التي يزداد فيها هذا الجهد ,بما ان العوازل
اختبار قفز الوميض الرطب :ان هذا االختبار مماثل -2 يجب ان تتحمل الصواعق وتحويرات الفتح والغلق
لالختبار السابق اال انه يجري بعد تسليط مطر اللتين لهما موجات ذات جبهات حادة االنحدار فيجب
اصطناعي نظيف ذي مقاومة ودرجة حرارة تصميم العازل بحيث تكون قيمة جهد قفز الوميض
محددتين وتحدد كذلك نسبة سقوط المطر والزاوية ذي الموجة النبضية ذات الجبهة الحادة االنحدار
التي يسقط فيها ,يجب ان يتحمل العازل اثناء هذا اعلى من قيمة جهد قفز الوميض ذي الموجة الجيبية
االختبار قيمة صغرى محددة للجهد اقل من القيمة التي ترددها 53هرتز ,ان النسبة النبضية تتراوح
المحددة في االختبار االول وذلك لمدة 03ثانية على بين 1.2و 1.0بالنسبة لعوازل التعليق وبين 1.0
االقل دون حدوث قفز الوميض و 2.0بالنسبة لعوازل المسمار ,يمكن اجراء هذا
اختبار قفز وميض التلوث :ان هذا االختبار مماثل -0 االختبار للتوصيل الى قيمة جهد قفز الوميض
لالختبار الثاني ولكنه يجري بعد تسليط ضباب النبضي بتسليط نبضات ذات شكل موجة كما في
وزخات ملحية ودخان وغبار وبعض الكيمياويات , الشكل ادناه
ان القيمة الصغرى للجهد الذي يجب ان يتحمله
العازل لمدة 03ثانية دون حدوث قفز الوميض في 120
هذا االختبار هي نصف القيمة المحدد لالختبار
100
الثاني
انهيار الثقب :يحدث الثقب عندما تنهار مادة العازل -4 80
وتسمح لسريان التيار داخل العازل بين الموصل
60
وذراع المسند ,يتمكن العازل من البقاء صالحا
لالستعمال بعد حدوث قفز الوميض اما في حالة 40
حدوث الثقب فيجب استبداله وعلى ذلك يجب تصميم
20
العازل بحيث تكون قيمة الجهد التي يحدث فيها
الثقب اعلى من تلك التي يحدث فيها قفز الوميض , 0
في هذا االختبار يغطس العازل في زيت عازل 0 10 20 30 40 50
نظيف لمنع حدوث قفز الوميض ويزداد الجهد
المسلط عليه تدريجيا ويجب ان يتحمل العازل في
هذه الحالة قيمة جهد مقدارها 1.0مرة بقدر قيمة
الجهد التي يحدث فيها قفز الوميض الجاف دون
حدوث ثقب في العازل
االختبار الميكانيكي :تعرض عوازل التعليق الى -5
توتر مقداره 1.2مرة بقدر اعظم حمل ميكانيكي
تتعرض له اثناء استعمالها اما عوازل المسمار
فتتعرض الى عزم انحناء يعادل 2.5مرة ألعظم
حمل ميكانيكي تتعرض له اثناء االستعمال وبعدئذ
يعاد االختبار االول
اختبار درجة الحرارة :يغطس العازل في حوض -0
ماء بدرجة حرارة .مئوية لمدة ساعة وبعدها
يوضع في حوض ماء درجة حرارته .3مئوية لمدة
ساعة ايضا وتكرر هاتان العمليتان 0مرات
تستغرق كل منها فترة ساعة وبعدها يجفف العازل
ويعاد عليه االختبار االول
44
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
45
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
46
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
Vph=V1+V2+V3=34.1 kV
VL=√3*34.1 = 59 kV
EXAMPLE 5 : An insulator string consist V1= 1 Ω * 1 A = 1 volt
of three units, each having a safe working V2= 1 Ω * 1.1 A = 1.1 volt
voltage of 15kV , k=1/8 , find the maximum
safe working voltage of the string , also V3 = 1 Ω * 1.31 A = 1.31 volt
find the string efficiency
V4= 1 Ω * 1.65 A = 1.65 volt
SOLUTION:-
V=V1+V2+V3+V4 = 5.06 volt
V3=15 kV k=0.125 1
V1/V = 5.06 *100% = 19.76 %
V2=(k+1)V1 => V1=0.89 V2
1.1
V3=(k2+3k+1)V1 V2/V = *100% = 21.74 %
5.06
1.31
V3= (1.39)*0.89 V2 V3/V = 5.06 *100% = 25.9 %
V3=1.236 V2 1.65
V4/V = 5.06 *100% = 32.9 %
15 𝑘𝑉
V2= 1.236 =12.13 kV 𝑉 5.06
Ƞ= ∗ 100% = ∗ 100%
4𝑉4 4∗1.65
V1=0.89V2=0.89*12.13=10.79 kV
= 76.6 %
V=V1+V2+V3=37.92 kV
EXAMPLE 7 :A string of 5 insulators is
𝑉 37.92
Ƞ= ∗ 100% = ∗ 100% connected across a 100 kV line, if the
3𝑉3 3∗15
capacitance of earth disk to earth is 0.1 of
= 84.26 % the capacitance of the insulator , calculate
(i) the distribution voltage on the insulator
EXAMPLE 6:A string of 4 insulators ,
discs (ii) ƞ
k=0.1 , find (i)the voltage distribution
across various units expressed as a SOLUTION:-
percentage of total voltage across the
string (ii)string efficiency Let XC=1 Ω
47
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
𝑉3 𝑘 2 + 3𝑘 + 1 V4/V = 38.5 %
=
𝑉2 𝑘+1 6.248
Ƞ=4∗2.408 ∗ 100 % = 64.86 %
18 𝑘 2 + 3𝑘 + 1
=
13.2 𝑘+1
k=0.2
2 𝑉 13.2
V1=𝑘+1 = 1.2
= 11 𝑘𝑉
48
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
49
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
50
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
𝑙
𝑤 ( )2 𝑤 𝑙2
S= 2
=
2𝑇 8𝑇
Wt=√(𝑤 + 𝑤𝑖 )2 + (𝑤𝑤 )2
2- When the support are at
W = weight of conductor per unit length
unequal levels
Wi = weight of ice per unit length
𝜋
Wi =density of ice*4 [(d+2t)2-d2]*l
𝑤𝑤
𝑡𝑎𝑛𝜃 =
𝑤 + 𝑤𝑖
𝑤 𝑥12 𝑤 𝑥22
S1= , S2= 𝑤𝑡 𝑙 2
2𝑇 2𝑇
𝑆=
𝑙 𝑇ℎ 𝑙 𝑇ℎ 2𝑇
X1= − , X2 = +
2 𝑤𝑙 2 𝑤𝑙 Vertical sag = S cosθ
𝑤𝑙
h= (x2 – x1)
2𝑇
Where
l: length of span
w: weight per unit length of conductor
T: tension in the conductor
51
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
EXAMPLE 1 :132 kV T.L has the data, EXAMPLE 3 : A T.L has aspan of 200 m
wt of conductor = 680 kg/km between level supports , the conductor has
length of span = 260 m across sectional area of 1.29 cm2 , wc=1770
ultimate strength = 3100 kg kg/km and has a breaking stress of 4218
safety factor = 2 kg/cm2 , calculate a sag of a safety factor of
calculate the height above the ground at 5 , allowing a wind pressure of 122 kg per
which the conductor should be supported , square meter of projected area , what is the
ground clearance required is 10 m vertical sag
SOLUTION:- SOLUTION:-
Wc=680/1000 =0.68 kg Wc = 1170/1000 =1.17 kg
𝑢𝑙𝑡𝑖𝑚𝑎𝑡𝑒 𝑠𝑡𝑟𝑒𝑛𝑔𝑡ℎ 3100 𝑏𝑟𝑒𝑎𝑘𝑖𝑛𝑔 𝑠𝑡𝑟𝑒𝑠𝑠 ∗ 𝑐𝑟𝑜𝑠𝑠 𝑠𝑒𝑐𝑡𝑖𝑜𝑛𝑎𝑙 𝑎𝑟𝑒𝑎
T= 𝑠𝑎𝑓𝑒𝑡𝑦 𝑓𝑎𝑐𝑡𝑜𝑟
= 2
= 1550 𝑘𝑔 T= 𝑠𝑎𝑓𝑒𝑡𝑦 𝑓𝑎𝑐𝑡𝑜𝑟
52
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
= 2.688 𝑘𝑔 SOLUTION:-
𝑤𝑡 𝑙2 2.688∗(275)2 l= 150 m , ww=1.5 kg
S= 8𝑇
= 8∗4030
= 6.3 𝑚
wc=conduc. area*specific gravity*100 cm
EXAMPLE 5 : A T.L has a span of 214 m
between level supports, the conductor has a = 2 * 8.9 * 100 = 1780 gm = 1.78 kg
cross sectional area of 3.225 cm2 , 5000∗2
calculate the factor of safety under the T= 5
= 2000 𝑘𝑔
following conditions , vertical sag = 2.35
m , wind pressure = 1.5 kg/m , breaking Wt=√𝑤𝑤2 + 𝑤𝑐2 = √1.782 + 1.52
stress=2540 kg/cm2 , wc = 1.125 kg/m
=2.33 kg
SOLUTION:- 𝑤𝑡 𝑙2 2.33∗1502
S= 8𝑇
= 8∗2000
= 3.28 𝑚
l = 214 m , wc = 1.125 kg , ww = 1.5 kg
𝑤𝑐
Vertical sag = S * cosθ = S *
wt = √𝑤𝑤2 + 𝑤𝑐2 = √(1.125)2 + (1.5)2 𝑤𝑡
1.78
= 1.875 kg = 3.28*2.33 = 2.5 𝑚
𝑤𝑡 𝑙2 1.875∗(214)2
S= 8𝑇
→ 𝑇= 8∗3.92
T= 2738 kg
𝑏𝑟𝑒𝑎𝑘𝑖𝑛𝑔 𝑠𝑡𝑟𝑒𝑠𝑠∗𝑐𝑜𝑛𝑑𝑢𝑐𝑡𝑜𝑟 𝑎𝑟𝑒𝑎
T= 𝑠𝑎𝑓𝑒𝑡𝑦 𝑓𝑎𝑐𝑡𝑜𝑟
2540∗3.225
Safety factor= 2738
=3
53
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
Mid-way = point P
x = 250 – x1 = 250 – 122 =128 m
𝑤 𝑥2 1.5 (128)2
Smid = 2𝑇
= 2∗1600
= 7.68 𝑚
54
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
TUTORIAL PROBLEMS
5- A T.L has a span of 250 m between
1- A T.L conductor is supported from two supports, the supports being at the
towers at heights of 70 m above water same level, the conductor has a cross-
level , the horizontal distance between sectional area of 1.29 cm2, the ultimate
the towers is 300 m, if the tension in the strength is 4220 kg/cm2 and factor of
conductors is 1500 kg, find the safety is 2 , the wind pressure is 40
clearance at a point mid-way between kg/cm2, calculate the height of the
the towers, the size of the conductor is conductor above ground level at which
0.9 cm2 and density of conductor it should be supported if a minimum
material is 8.9 gm/cm3 [64 m ] clearance of 7 m is to be kept between
2- A T.L has a span of 260 m, the weight the ground and the conductor [10.24m]
of the line conductor is 0.68 kg/m , find 6- A T.L has a span of 150 m between level
the maximum sag in the line, the supports, the conductor has across-
maximum allowable tension in the line sectional area of 2 cm2, the ultimate
is 1550 kg [3.7 m ] strength is 5000 kg/cm2, the specific
3- A T.L has a span of 150 m between level gravity of the material is 8.9 gm/cm3,if
supports, the cross sectional area of the the wind pressure is 1.5 kg/m length of
conductor is 1.25 cm2 and weight 100 the conductor calculate the sag if the
kg per 100 m, the breaking stress is factor of safety is 5 [3.5 m ]
4220 kg/cm2, calculate the factor of 7- Two towers of height 40 m and 30 m
safety if the sag of the line is 3.5 m , respectively support a T.L conductor at
assume a maximum wind pressure of water crossing the horizontal distance
100 kg per square meter [4] between the towers is 300 m, if the
4- A T.L has a span of 150 m between the tension in the conductor is 1590 kg,
level supports , the conductor has a find the clearance of the conductor at
cross-sectional area of 2 cm2, the apoint mid-way between the supports ,
ultimate strength is 5000 kg/cm2, the weight of conductor is 0.8 kg/m, bases
specific gravity of the material is 8.9 of the towers can be considered to be at
gm/cm3, if the wind pressure is 1.5 kg/m the water level
length of conductor, calculate the sag 8- A T.L at a river crossing is supported
at the center of the conductor if factor from two towers at heights of 50 m and
of safety is 5 [3.28 m] 100 m above the water level, the
horizontal distance between the towers
is 400 m, if the maximum allowable
tension is 1800 kg and the conductor
weight 1 kg/m, find the clearance
between the conductor and water at
apoint mid-way between the supports
[63.8 m]
55
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
Underground cables
الكابالت الكهربائية هي احدى الوسائل التي تستخدم لنقل
وتوزيع الطاقة الكهربائية ,والفارق الجوهري بين
الخطوط الهوائية والكابالت هو ان الموصالت المستخدمة
في الخطوط الهوائية تكون موصالت مكشوفة أي غير
معزولة ويتم تثبيتها على ابراج للمحافظة على مسافات
فاصلة ثابتة بين الموصالت بعضها البعض وبين
الموصل واالرض ,في حين ان الموصالت المستخدمة
في الكابالت تكون مغطاة بأكملها بمادة عازلة ويتم تمديد
هذه الكابالت اما بالدفن المباشر في االرض او داخل
مواسير مدفونة في االرض او خالل مجاري تحت سطح
االرض مهيأة خصيصا لهذا الغرض
ان االختيار بين الكابالت االرضية والخطوط الهوائية ال
يتم وفقا لمعيار واحد ولكنه يخضع لعدة عوامل اقتصادية
وفنية عديدة اهمها
تكلفة الموصل :لنقل نفس القدرة يكون الموصل المستخدم
في خط النقل الهوائي اقل تكلفة من الموصل المستخدم في
الكابل
تكلفة العازل :تكلفة العازل في الكابل اكبر بكثير منها في
حالة خط النقل الهوائي ,حيث ان الموصالت في خط
النقل الهوائي يتم عزلها عن االبراح بواسطة عوازل قليلة
التكلفة نسبيا ويكون الهواء هو العازل الذي يعزلها عن
بعضها البعص ,اما الموصالت في الكابالت فيتم
احاطتها بمادة عازلة عالية التكلفة ويلزم غطاء معدني
UNDERGROUND لحماية العازل من تأثيرات التربة وحماية ميكانيكية للكابل
وفي بعض انواع الكابالت وخصوصا التي تستخدم
الورق العازل يلزم ملء الكابل بالزيت العازل او غاز
CABLES خامل لملء الفراغات بين طبقات الورق وفي هذه الحالة
يلزم تركيب خزانات للزيت او الغاز الخامل على طول
مسار الكابل مما يجعل تكلفة العزل اكبر بكثير للكابل منها
في حالة خط النقل الهوائي
تكلفة التركيب :تكلفة تركيب الكابالت اعلى بكثير من
تكلفة تركيب خطوط النقل الهوائية حيث تصل احيانا الى
عشرة اضعاف او يزيد تكلفة خط النقل
56
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
57
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
58
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
تصنيف الكابالت طبقا لنوع المادة العازلة ii. S.L –type cable
يتمتع العازل الورقي بخواص كهربائية جيدة ولكن أ) االغطية المعدنية المنفصلة تقلل من امكانية انهيار
عمليات اللحام وتوصيل النهايات لكابل العازل الورقي الموصل
تحتاج الى خبرة ودقة في االداء ب) يصبح طوي او انحناء الكابالت سهال بسبب ازالة الغطاء
المعدني الرئيسي
يعمل على 11كيلو فولت
ولكن المشكلة االساسية في هذا النوع هي التيارات
التسريبية التي تؤدي الى رفع درجة الحرارة وتسبب
فقدان خاصية العزل للعازل المحيط بالموصل
59
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
60
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
هناك 0طرق
1- Direct laying
61
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
4.5∗1012 𝑟
𝜌 𝑟2 495*106=2𝜋∗1000 ln 𝑟2
R= 𝑙𝑛 Ω 1
2𝜋 𝑙 𝑟1 𝑟2
𝑟1
=2 → r2=2*1.25
2𝜋𝜀𝑜 𝜀𝑟
C= 𝑟 F/m
𝑙𝑛𝑟2 r2 = 2.5 cm
1
Thickness of insulation = 2.5 - 1.25
القانون السابق الستخراج المتسعة يستخرج قيمة لكل
متر اما اذا اردنا حساب المتسعة الكلية فنستخدم القانون =1.25 cm
التالي
EXAMPLE 3:A single core cable 5 km
𝜀𝑟 𝑙 -9 long has an insulation resistance of 0.4
C= 𝑟 * 10 F
41.4 𝑙𝑜𝑔 2 MΩ, the core diameter is 20 mm, the
𝑟1
diameter of the cable over the insulation is
نصف القطر الكلي للكابل : 𝑟2 50 mm, find the resistivity of the insulating
material
نصف قطر السلك: 𝑟1
SOLUTION:-
طول السلك: l
r1 = 2/2 = 1 cm
EXAMPLE 1 : A single core cable has a
conductor diameter of 1 cm and insulation r2 = 5/2 = 2.5 cm
thickness of 0.4 cm, if the specific 𝜌 𝑟
resistance of insulation is 5*1014 Ω-cm R = 2𝜋 𝑙 ln 𝑟2
1
,calculate the insulation resistance for 2 km 𝜌 2.5
length of the cable 0.4*106 = 2𝜋∗5000 ln 1
62
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
= 2π*50*1.98*10-6*19.05*103
= 11.87 A
Total kVAR = 3Vph IC = 3*19.05*103*11.87
= 106.87 kVAR
63
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
2𝑉 𝑄
𝑔𝑚𝑖𝑛 = 𝑟 kV/cm gmax1=2𝜋𝜀
𝑜 𝜀𝑟 𝑑1
kV/cm
𝑟2 ln 2
𝑟2
𝑄
gmax2=2𝜋𝜀 kV/cm
𝑜 𝜀𝑟 𝑑2
قطر الكابل:D
قطر السلك: d
𝑔𝑚𝑎𝑥 𝑑1
V1= 𝑑 ln
2 𝑑
VT=V1+V2+V3
D/d = 2.718 النسبة التي تمثل الحجم
االقتصادي االفضل للكابل
EXAMPLE 1: 33 kV, single core cable has
a conductor diameter of 1 cm and a sheath
of inside diameter 4 cm, find the maximum
and minimum stress in the insulation
SOLUTION:-
2𝑉 2∗33000
gmax = 𝐷 = 1 ln 4
= 47.61 kV/cm
𝑑 ln
𝑑
2𝑉 2∗33000
gmin = 𝐷 = 4 ln 4
= 11.9 kV/cm
𝐷 ln
𝑑
64
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
EXAMPLE 2:The maximum and minimum EXAMPLE 4:A single core leads sheathed
stress in the dielectric of the single core cable is graded by using three of dielectric
cable are 40kV/cm (r.m.s) and 10 kV/cm of relative permittivity 5,4 and 3
(r.m.s) respectively , if the conductor respectively, the conductor diameter is 2
diameter is 2 cm , find (i)the thickness of cm and overall diameter is 8 cm if the three
insulation (ii)operating voltage dielectrics are worked at the same
maximum stress of 40 kV/cm, find the safe
SOLUTION:- working voltage of the cable, what will be
gmax /gmin = D/d the value of safe working voltage for an
ungraded cable assuming the same
40/10=D/2 → D=8 cm conductor and overall diameter and with
𝐷−𝑑 8−2 maximum dielectric stress
Insulation thickness= 2
= 2
= 3 cm
SOLUTION
8
2𝑉 40∗103 ∗2 ln
gmax = 𝐷 → 𝑉= 3 d= 2 cm , d1=? , d2=? , D=8cm
𝑑 ln 2
𝑑
ε1=5 , ε2=4 , ε3=3 , gmax=40 kV/cm
V= 55.45 kV (r.m.s)
graded cable
EXAMPLE 3:A single core cable for use
ε1 d = ε2 d1 = ε3 d2
on 11 kV, 50 Hz system has conductor area
of 0.645 cm2 and internal diameter of d2 وd1 من خالل العالقة السابقة نستخرج
sheath is 2.18 cm, the permittivity of the
dielectric used in the cable is 3.5 , find (i) d1 = 2.5 cm , d2 = 3.34 cm
gmax (ii) gmin (iii)capacitance of the cable 𝑑1 𝑑 𝐷
Vpeak= gmax/2 [𝑑 ln 𝑑
+ 𝑑1 ln 𝑑2 + 𝑑3 ln 𝑑 ]
per km length (iv) charging current 1 2
SOLUTION:- = 81.757
4𝐴
81.757
A = ¼ π d2 → d=√ 𝜋 Vrms= = 57.81 kV
√2
4∗0.645
Ungraded cable
d=√ π
=0.906 cm
𝑔𝑚𝑎𝑥 𝐷
Vpeak= 2
𝑑 ln 𝑑 = 20 ∗ 2 ln 4=55.45 kV
2𝑉 2∗11000
gmax= 𝐷 = 2.18 =27.65 kV/cm Vrms= 39.21 kV
𝑑 ln 0.906 ln
𝑑 0.906
2𝑉 2∗11000
gmin = 𝐷 = 2.18 =11.5 kV/cm
𝐷 ln 2.18 ln
𝑑 0.906
𝜀𝑟 𝑙
C= 𝐷 ∗10-9
41.4 log
𝑑
3.5∗1000
= 2.18 *10-9 = 0.22*10-6 F
41.4 log
0.906
Ic = V/XC = 2 π f C V
= 2 π *50*0.22*10-6*11*103=0.76 A
65
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
= 54.71 kV
Vrms = 38.68 kV EXAMPLE 1:A single core cable of
EXAMPLE 6:A 66 kV single core lead conductor diameter 2 cm and lead sheath of
5.3 cm is to be used on 66 kV, 3-phase
sheathed cable is graded by using two
system, two inter sheaths of diameter 3.1
dielectric of ε= 5 and 3 respectively,
cm and 4.2 cm are introduced between the
thickness of each being 1 cm , the core
diameter is 2 cm, find the maximum stress core and lead sheath, if the maximum stress
in the layers is the same find the voltage in
in the two dielectrics
the inter sheaths
SOLUTION
SOLUTION:
d= 2 cm , d1= 4 cm , d2= 6 =D 66 𝑘𝑉
V= √2 =53.9 kV
66 𝑘𝑉 √3
V= ∗ √2=53.9 kV
√3
𝑉1 𝑉1
𝑔𝑚𝑎𝑥1 𝜀1 𝑑 1 𝑑1 1 𝐷
gmax1=𝑑 𝑑 = 3.2 =2.28V1
ln 1 1 ln
V= [ ln + ln ] 2 𝑑 2
2 𝜀1 𝑑 𝜀2 𝑑1
𝑉2 𝑉2
2𝑉 gmax2 = 𝑑1 𝑑 = =2.12V2
4.2
gmax1 = 𝑑 𝜀 𝐷 ln 2 1.55 ln
3.1
2 𝑑1
𝑑[ln 1 + 1 ln ]
𝑑 𝜀2 𝑑1
66
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
𝑉3 𝑉3
gmax3=𝑑2 = =2.04 V3 𝑑12
ln
𝐷
2.1 ln
5.3
𝑑2 =
2 𝑑2 4.2 2
gmax1=gmax2=gmax3 𝑑1 𝑑2 = 𝐷 𝑑
2.28V1=2.12V2=2.04V3
𝑑1 𝑑2 = 5.3 ∗ 2 = 10.6 𝑐𝑚
V2=1.075 V1
𝑑12
V3=1.117 V1 𝑑1 = 10.6 → 𝑑1 = 2.76 𝑐𝑚
2
VT=V1+V2+V3 𝑑12 2.672
𝑑2 = = = 3.8 𝑐𝑚
53.9=V1+1.075V1+1.117V1 2 2
𝑖𝑖)
V1=16.88 kV
V2=1.075*16.88 = 18.15 kV 𝑉 = 𝑉1 + 𝑉2 + 𝑉3
67
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
68
ELECTRICAL POWER MOHAMMED HAMEED IBRAHIM
Vph=3300/√3= 1905 V
CN= 2C3 = 2*3.6 = 7.2 μF
IC = 2 π f Vph CN
= 2*3.16*50*1905*7.2*10-6 = 4.3 A
kVA taken by the cable=3Vph IC
=3*1905*4.3*10-3 = 24.57 kVA
69