DESIGN DOCUMENTATION
FUNCTIONAL DESCRIPTION

FOR
ELECTRICAL SERVICES
UPS
SIT TEMASEK POLYTECNIC

21st May 2013

RFA Reference: RFA-TPSIT-IBMS-FDS-003

Project: SIT_TEMASEK POLYTECNIC Page 1 of 7


Document: SIT_TP_ES_FDS
Date: 14st-April-2014
Rev: 2
Honeywell

Revision History

Date Description Prepare Checked By Approved By


Rev
d By
0 08th May 2013 Initial Release HAIL Edward Bird
Comments
1 21st May 2013 HAIL
Incorporated

Project: SIT_TEMASEK POLYTECNIC Page 2 of 7


Document: SIT_TP_ES_FDS
Date: 14st-April-2014
Rev: 2
Honeywell

Table of Contents
1 ELECTRICAL SERVICES......................................................................................................... 4
1.1 CONTROL DESCRIPTION....................................................................................................... 4
1.2 UPS SYSTEM........................................................................................................................ 5
1.2.1 Alarm Management................................................................................................. 5
1.2.2 Monitoring Points.................................................................................................... 5
1.2.3 High Level Interface Point summary (via Modbus)....................................................6

Project: SIT_TEMASEK POLYTECNIC Page 3 of 7


Document: SIT_TP_ES_FDS
Date: 14st-April-2014
Rev: 2
Honeywell

1 ELECTRICAL SERVICES

1.1 Control Description

The electrical services consist of the following equipment.

 UPS System

Project: SIT_TEMASEK POLYTECNIC Page 4 of 7


Document: SIT_TP_ES_FDS
Date: 14st-April-2014
Rev: 2
Honeywell

1.2 UPS System

This section consists of the following system:

SYSTEM QUANTITY (No.)


UPS 1

1.2.1 Alarm Management


The following conditions will result in an alarm being enunciated on the
operator’s terminal of the control system. The alarms are displayed in the alarm
section of the control system and will remain active until they have been
acknowledged by the operator. Once acknowledged that alarm will only be
removed once it has returned to normal. A default 10 sec (Adjustable) on delay
is in-built for all the digital alarm points.

 Input Power Failure Alarm


 Output Power Failure Alarm
 Input Breaker Trip Alarm
 Battery Breaker Trip Alarm
 Battery Electrolyte Level Low Alarm
 Fan Failure Alarm
 Rectifier/Charger Failure Alarm
 Inverter Failure Alarm
 Logic Power Supply Failure Alarm
 System Overload
 Overload Shutdown
 High Temperature
 DC over Voltage/Over current

1.2.2 Monitoring Points


The following points of the UPS system will be monitored and recorded by the
Honeywell DDC controller.

Project: SIT_TEMASEK POLYTECNIC Page 5 of 7


Document: SIT_TP_ES_FDS
Date: 14st-April-2014
Rev: 2
Honeywell

 Grounded DC Bus
 Load on By-pass Mode

1.2.3 High Level Interface Point summary (via Modbus)


Tag Name Description Type Engineering
Unit
_IPFAlm Input Power Failure Alarm BV Normal / Alarm
_OPFAlm Output Power Failure Alarm BV Normal / Alarm
_IBTAlm Input Breaker Trip Alarm BV Normal / Alarm
_BBTAlm Battery Breaker Trip Alarm BV Normal / Alarm
_BELLAlm Battery Electrolyte Low Level Alarm BV Normal / Alarm
_FFAlm Fan Failure Alarm BV Normal / Alarm
_RFAlm Rectifier Failure Alarm BV Normal / Alarm
_IFAlm Invertor Failure Alarm BV Normal / Alarm
_LPSFAlm Logic Power Supply Failure Alarm BV Normal / Alarm

_GnDDCBs Grounded DC Bus BV Normal / Alarm

_ SysOver System Overload BV Normal / Alarm

_ OverShdn Overload Shutdown BV Normal / Alarm

_HiTemp High Temperature BV Normal / Alarm

_LoadMode Load on By-Pass mode BV Normal / Alarm

_Volt DC Over Voltage/Over Current BV Normal / Alarm

Project: SIT_TEMASEK POLYTECNIC Page 6 of 7


Document: SIT_TP_ES_FDS
Date: 14st-April-2014
Rev: 2
Honeywell

Project: SIT_TEMASEK POLYTECNIC Page 7 of 7


Document: SIT_TP_ES_FDS
Date: 14st-April-2014
Rev: 2