LiFePO4 48V50AH
Battery model: FP-4850-Li
Edition: V2.0
Release date: Aug. 2018
Trademark Notice
Declaration
1. The specification details the performance of the battery pack. Please read the specification carefully
before operations and please abide by relevant industrial safety regulations. We will not be
responsible for any damage to the product due to improper operations or use under conditions that
are not prescribed in the specification.
2. As the product version upgrades or other reasons, this document is subject to change without
notice. Unless otherwise agreed, this document only as a guide, all statements, information, and
recommendations in this document do not constitute any express or implied warranty.
Contact information:
Address: Mall Mega Glodok Kemayoran, Office Tower A Lantai 6, Superblok MGK, JI.Angkasa Kav. B-6,
Gunung Sahari Selatan, Kota Baru Bandar Kemayoran, Jakarta Pusat 10610, Indonesia
Maximum Continuous
12 50A
Charge Current
Maximum Continuous
13 50A
Discharge Current
Charging
14 Current limit 10A
Current>50A
Operation Temperature Charge: 0~45℃ 60±25%R.H.
15 Range Bare Cell
Discharge : -20~60℃
Charging/Discharging @0.2C Charge &
16 98%
Efficiency Discharge, 25℃
@0.2C Charge &
17 Cycle Life ≥3000(DOD 80%)
Discharge, 25℃
Less than 12 months : -20~25℃
60±25%R.H.
Storage Temperature
18 less than 3 months: -20~40℃ at the shipment
Range
state
Less than 7 day : -20~65℃
Gravimetric energy
22 80Wh/Kg
density
Volumetric energy
23 106.7Wh/L
density
It has RS232 and double RS485 standard communication interface, it can real-time
Communication monitoring the capacity of battery, the voltage, current, environment temperature,
and charging/discharging current, current limit.
It has over-temperature, over charge, under-voltage, over-current, short circuit alarm
Alarm
function.
5. Function Description
Note: Address Switch function (Only in Parallel), support max 15 units in parallel in one system.
When battery work in parallel, main pack and slave packs need address as follows:
-20°C - 40°C Every 3 months Do a charge and discharge cycle, the battery charge storage
6.2. Maintenance
The battery system operates with hazardous voltages. Only qualified maintenance personnel may
carry out repairs.
Even after the unit is disconnected from the mains, components inside are still connected to the
battery cells, which are potentially dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that
no current is present and no hazardous voltage exists in the terminals.
Only persons are adequately familiar with batteries and with the required precautionary measures
may replace batteries and supervise operations. Unauthorized persons must be kept well away from the
batteries.
Verify that no voltage between the battery terminals and the ground is present before
maintenance or repair. In this product, the battery circuit is not isolated from the input voltage. Hazardous
voltages may occur between the battery terminals and the ground.
Batteries may cause electric shock and have a high short-circuit current. Please remove all
wristwatches, rings and other metal personal objects before maintenance or repair, and only use tools
with insulated grips and handles for maintaining or repairing.
When replace the batteries, install the same number and same type of batteries.
When replace the parallel batteries, make sure the new battery is full charged.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may
be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
Model: FP-4850-Li-ico
User Manual
Version: 1.0
Please comply with all warnings and operating
instructions carefully.
1
CONTENT
2
Safety Precaution
1. When Using battery
Danger of High Voltage:
The high voltage power supply the equipment power, wet object contact high voltage power supply
directly or indirectly, can cause fatal danger.
Working in high voltage and AC power, be sure to use a special tool instead of individual tools.
Static-free:
Static electricity would damage veneer on the electrostatic sensitive components, before touching the
plug‐ in, circuit board or chips, be sure to use correct electrostatic prevention measures.
When operate the power supply, you must first cut off power supply, power operation is prohibited.
Power system provides DC regulated power supply. DC short circuit could cause fatal damage to the e
quipment.
2. When Charging
CAUTION
The temperature range over which the battery can be charged is 0°C to 45°C. Charging the battery at
temperatures outside of this range may cause the battery to become hot or to blow. Charging the
battery outside of this temperature range may also harm the performance of the battery or reduce the
battery’s life expectancy.
3
3. When Discharging the Battery
DANGER
Do not discharge the battery using any device except for the specified device. When the battery is
used in devices aside from the specified device it may damage the performance of the battery or
reduce its life expectancy, and if the device causes an abnormal current to flow, it may cause the
battery to become hot and cause serious injury.
CAUTION
The temperature range over which the battery can be discharged is -20°C to 60°C. Use of the
battery outside of this temperature range may damage the performance of the battery or may
reduce its life expectancy.
4. Battery Parameters
4.1 Battery Pack
Weight 30kg
4
4.2 Battery Management System (BMS)
No Item Parameter Remarks
3600mV
Cell Over-charge Voltage Alarm
Cell Over-charge
3700mV
Cell Over-charge Voltage Protection
2800mV
Cell Over-discharge Voltage Alarm
Cell
Over-discharge Cell Over-discharge Voltage 2500mV
Protection
the state gets into low-
2 Cell Over-discharge Protection 1.0S power mode after 30S
Delay Time
Cell 3050mV
Cell Over-discharge Release Voltage
Over-discharge Charger Connection is
Release Release Once Charge
detected
54.0V
Pack Over-charge Voltage Alarm
44.0V
Pack Over-discharge Voltage Alarm
Pack
Over-discharge Pack Over-discharge Voltage 40.5V
Protection
the state gets into low-
4 Pack Over-discharge Protection 1.0S power mode after 30S
Delay Time
48.0V
Pack Pack Over-discharge Release
Over-discharge
Protection Charger Connection is
Release Once Charge
Release detected
50A
Over-current Charge Alarm The state gets locked
Over-current 60A after 10 times over-
Charge Protection Over-current Charge Protection current charging
1.0S continuously and
5 Over-current Protection
cannot release
Delay Time
automatically
Over-current Auto Release After 1min
Protection
Release
Release Once Discharge Discharge Current >1.0A
5
Over-current Discharge 52A
Alarm The state gets locked
Over-current after 10 times over-
Over-current Discharge 60A
Discharge current discharging
Protection-1 Protection
continuously and
6 Over-current Protection 1.0S cannot release
Delay Time automatically
Over-current Auto Release After 1min
Protection
Release Release Once Charge
Charge Current >1.0A
≥300A
Short Circuit Threshold
Short Circuit
Current Protection Short Circuit Current 300μS
8 Protection Delay Time
Release Once Charge
Short Circuit Current Protection
Release Release Once Remove Load
6
ENV Under Temperature -20℃
Alarm
ENV Under Temperature -25℃
Protection
ENV Under Temperature -20℃
ENV Temperature Protection Release
11
Alarm
ENV Over Temperature 65℃
Alarm
ENV Over Temperature 75℃
Protection
ENV Over Temperature 65℃
Protection Release
≤30mA(LCD)
Consumption
12 ≤20mA(NO LCD)
Operation Mode
Low Power Mode ≤100μA
3400mV
Cell Balance Balance Threshold
13
Balance ΔVcell 30mV
● One Battery
NOTE: Before installation, please inspect the battery. Make sure that nothing inside the package is
damaged during transportation. Do not turn on the unit and notify the carrier and manufacture
immediately if there is any damage or lacking of some parts. Please keep the original package in a safe
place for future use.
Barrier terminal
2 +/- Positive/Negative terminal
block
8
6.3. Single battery Installation
Installation and wiring must be performed in accordance with the local electric laws/regulations and
execute the following instructions by professional personnel.
1) Make sure the utility power wire and breakers in the building are in compliance with the standard of
rated capacity of battery to avoid the hazards of electric shock or fire.
NOTE: Do not use the wall socket as the input power source for the battery, as its rated current is less
than the battery’s maximum input current. Otherwise the socket may be burned and destroyed.
2) Switch off the utility power switch in the building before installation.
3) Turn off all the connected devices before connecting to the battery.
<50Ah 8 6
50Ah 6 16
100Ah 4 25
NOTE : It is recommended to use suitable wire in above table or thicker for safety and efficiency.
5) Put the terminal block cover back to the front panel of the battery.
NOTE: Make sure the battery pack breaker in “OFF” position while installation.
9
6.6. Installation Precautions
(1) Prior to installation, unpacking to check the quantity of the parts and battery appearance.
(2) Install the hanger and handle and measure the battery voltage with a multi-meter. The general
Installation of standard cabinet (rack): Install the matching hanger for the battery pack and fix them
in the standard cabinet and the tray protection is added for the battery box.
Installation of wall-mounted box: Prior to installation, please ensure that the wall complies with the
wall-mounted requirements; according to the location in the design plan, install the special wall-mounted
box of the lithium battery; the battery pack is fixed in the wall-mounted box in a hanger manner.
Installation of integrated indoor and outdoor cabinets (boxes): Install them according to the
10
Press the reset key RST on the front panel for 3S for startup. During startup, 4 capacity indicator
lights on the front panel, ALM alarm indicator light (red) and RUN running indicator light lights up. Check
whether all indicator lights light up normally; then the ALM alarm indicator light goes out, the RUN
running indicator light lights up and the capacity indicator light lights up according to the capacity.
If the ALM alarm indicator light flashes after startup, it means that the battery has an alarm. The
newly installed battery seldom has alarm. The common alarm is the battery under-voltage alarm (which
is resulted from non-use of the battery for a long time). Such case may be cleared after the battery is
charged for 30min; if the alarm may not be removed, please press the reset key RST for 10S, until all
LEDs light up for reset, execute the battery reset operation and confirm whether the alarm cleared. If the
alarm is cleared, the battery may be used normally. Otherwise the battery shall be repaired.
2) For the battery which is normal after detection, please press the reset key RST for 3S
Make the battery pack in a standby status, install it in the battery cabinet one by one, the battery
negative and positive terminals are connected respectively, which are connected to the switching mode
power supply or UPS (Please note that the switching mode power supply and UPS shall be disconnected
from the AC). Press the reset key RST of one of battery packs for 3S for startup. Such startup battery may
activate other batteries which are connected in parallel (or press the reset key RST of each battery pack
for 3S successively) and the whole battery pack with high capacity enters the working state. Later, apply
AC to the power supply equipment such as switching mode power supply and UPS to make the whole
The specification of the connecting line is selected according to the load current, with the common
1) When the battery pack with the capacity of 200Ah or below is connected in parallel, it
is suggested to select 16mm2 copper wire.
11
2) When the battery pack with the capacity of 200Ah~300Ah is connected in parallel, it is
suggested to select 16mm2 or 25mm2 copper wire.
3) When the battery pack with the capacity of 300Ah or above is connected in parallel, it
is suggested to select 25mm2 copper wire.
Note: We do not equip with the battery connecting wire by default, which shall be selected
according to the total capacity of the battery pack.
Step 4: Set the dial-up addresses of all battery modules from top to bottom one by one, which are
1000, 0100, 1100 and 0010 (the dial-up addresses are set according to the number of battery modules
actually used) respectively; (this step may be skipped if there is no need to access to the remote
monitoring platform).
Step 5: Perform the cascade connection to RS485 communication interface of the battery module
with the RS485 connecting line; lead to the collector of the monitoring platform from the RS232 interface
of the battery module with the address of 1000 with the RS232 connecting line; (this step may be skipped
if there is no need to access to the remote monitoring platform).
Step 6: Draw out two wires from the negative and positive of a battery pack at the top or in the
middle respectively as the main connecting line of the battery pack in parallel, which are connected with
the switching mode power supply or UPS.
Step 7: Press the RST key of each battery pack for Reset and the whole battery pack with high
capacity enters the working state.
6.8. Circuit breaker of battery circuit is set to OFF, connect it to switch power
supply, and output voltage of switch power supply is set to 48-50V, current set to
0.2C; after all settings done, switch the circuit breaker ON.
13
6.11 Upper machine instructions
A、 Software includes:
14
Figure 1:Realtime Monitoring
(2)Open the main interface(As shown in figure 1),the software automatically search serial port,
and automatically open, realtime read battery voltage, power, temperature, and protection of the state of
battery parameters.
Operating authority is divided into general rights and administrator privileges.
(3)In Multi Monitoring interface (As shown in figure 2), there are two checkboxes: Display and
AutoSave.
Check “ Display”, can real-time display battery status.
Check “AutoSave”, can automatically record battery status in the excel file, which is kept in data folder,
named after pack number and time. For example packNo1_20150306145010.xls.
protection, alarm, time of occurrence, fault type, fault cell voltage, total voltage, charge/discharge
capacity, charge/discharge current, temperature, etc., moreover it can record battery status within a
certain period of time by setting:Cell voltage, total voltage, charge/discharge capacity, charge/discharge
(5)In Parameter Settings interface (As shown figure 3), it can read the battery parameters.
16
Figure 3: Parameter Settings
(6)In System Configuration interface (As shown in figure 4), only administrator is authorized to set
parameter.
17
6.13 Communication Function
7. Operations
7.1. LED Indicators
LED Indicators:
There are 6 LEDs on front panel to show the battery working status:
18
Capacity Indication Status
8. Troubleshooting
If the battery does not operate correctly, please solve the problem by using the table below.
Red LED Flashing when Standby Battery cell low voltage Charge battery immediately
Charge the battery at least 5 hours @ 0.2C, and store in a cool and dry location. Recommend long-
term storage temperature is 15°C -25°C. During storage, recharge the battery in accordance with the
following table:
9.2. Maintenance
The battery system operates with hazardous voltages. Repairs may be carried out only by
qualified maintenance personnel.
Even after the unit is disconnected from the utility power, components inside are still connected to
20
the battery cells which are potentially dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify
there is no current and no hazardous voltage existing in the terminals.
Only persons who are very familiar with batteries and with the required precautionary measures
may replace batteries and supervise operations. Unauthorized persons must be kept well away from the
batteries.
Please remove all wristwatches, rings and other metal personal objects before maintenance or
repair, and only use tools with insulated grips and handles for maintaining or repairing.
When replace the batteries, install the same number and same type of batteries.
When replace the parallel batteries, make sure the new battery is full charged.
Do not open or destroy batteries, leaked electrolyte can cause injury to the skin and eyes. It may
be toxic.
2) We will not send separate notice about specification upgrade due to quality improvement or
technological upgrading; please contact us for the latest information if any question.
3) The warranty is within 36 months after it is delivered, we will maintain the product free of
charge within warranty period. If there is quality problems, firstly replace the relevant parts,
if not working, our after-sales service personnel will propose the specific maintenance and
troubleshooting methods.
21