Summary of Results:
PRODUCT MANUFACTURER: Sunview Patio Doors Ltd.
PRODUSCT TYPE: Sliding Door (SD)
PRODUCT SERIES/MODEL: 2021 Series Sliding Door
PRODUCT DESIGNATOR: Class CW – PG60: Size tested 2407 x 2391 mm (~95 x 94 in) – Sliding Door
OPTIONAL SECONDARY Positive Design Pressure (DP) = 2880 Pa (60 psf)
DESIGNATION: Negative Design Pressure (DP) = -2880 Pa (-60 psf)
Water Penetration Resistance Test Pressure = 510 Pa (10.65 psf)
Canadian Air Infiltration / Exfiltration = Pass for a Sliding Seal Product
TEST COMPLETION DATE: May 31, 2021
SAMPLE ID: 2021 Series Thermally Broken Extruded Aluminum Sliding Glass Door.
SAMPLE DESCRIPTION: Width: 2407 mm (94-3/4"); Height: 2391 mm (94-1/8"), having one fixed
panel and one operating panel. See pages 6- 9 for full description.
SAMPLING DETAIL: Test sample from Sunview Patio Doors Ltd. submitted directly to QAI.
DATE OF RECEIPT: April 20, 2021 (air and water testing at Sunview) April 27, 2021 received at QAI
for remainder of testing.
TESTING PROCUDURE: Testing was performed following the methods and requirements
outlined in the following standards:
AAMA/WDMA/CSA 101/I.S.2/A440-17 NAFS - North American
Fenestration Standard / Specification for windows, doors and
skylights.
A440S1:19 Canadian Supplement to NAFS-17.
TEST RESULTS: See pages 4 and 5 for the test results.
CONTENTS: Test report pages 1 through 13, appendix A1 through A33.
TESTING LOCATION: Sunview Patio Doors and QAI Laboratories Ltd., Toronto. Air and water
tightness testing was conducted at the Sunview facility by QAI personnel
using calibrated QAI equipment. The remainder of the test program was
conducted at the QAI Toronto laboratory.
Page 1 of 13
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM
THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL
PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Report No.: T1277-8B
Date: June 2, 2021
Page 2 of 13
Reported by Reviewed by
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM
THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL
PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Report No.: T1277-8B
Date: June 2, 2021
Page 3 of 13
Test Conditions:
QAI Laboratories Ltd. (QAI) was retained by Sunview Patio Doors Ltd. to perform testing in accordance with the
mandatory test requirements of AAMA/WDMA/CSA 101/I.S.2/A440-17 NAFS - North American Fenestration
Standard / Specification for windows, doors and skylights and A440S1-19 Canadian Supplement to
AAMA/WDMA/CSA 101/I.S.2/A440-17 NAFS - North American Fenestration Standard / Specification for
windows, doors and skylights on a representative sample of a 2407 mm (94-3/4″) wide by 2391 mm (94-1/8″)
high aluminum sliding glass door. This report includes tests performed on a specimen of specific dimensions.
Actual product performance may be affected by variations in the products dimensions, assembly details and
installation method. The assembly drawings and detailed profile drawings supplied by Sunview Patio Doors Ltd.
were verified by QAI for the unit tested and are shown in Appendix A.
The test specimen was installed by Sunview into a wood test buck as described below. A bead of silicone
sealant was applied between the door frame and the wooden test buck on the exterior. The frame was fastened
to the wooden test buck as follows: There were five #8 x 2" long flat head screws installed along each interior
jamb track, and five installed along each exterior jamb track (the heads of these fasteners along the fixed jamb
were sealed with silicone), nominally 510 mm (20″) to 560 mm (22″) apart o/c. An additional two #10 x 1-3/4"
long pan head screws also secured the lock keeper. Three #10 x 1-3/4" long pan head screws were installed
along the inner head track, spaced nominally 1016 mm (40") apart o/c. Five #10 x 1-3/4" long pan head screws
were installed along the outer head track, spaced nominally 508 mm (40") apart o/c. Along the sill, a section of
38 mm x 38 mm x 4.8 mm (1-1/2" x 1-1/2" x 3/16") aluminum angle measuring nominally 305 mm (12") long
anchored the interior of the sill to the adjacent buck at mid-width. Three #10 x 3/4" long flat head screws
fastened the angle to the interior face of the sill on nominal 127 mm (5") centres, the heads of the fasteners
being countersunk into the angle. Three #8 x 2" long flat head screws fastened the angle to the buck, the
fastener heads countersunk into the angle. At the fastener locations along the jamb, 32 mm (1-1/4") wide cedar
shims measuring 114 mm (4-1/2") long were fitted between the buck and door frame. Along the head, 32 mm (1-
1/4") wide cedar shims measuring 114 mm (4-1/2") long were fitted between the buck and door frame only at the
fasteners at the ends of the head. Six 152 mm (6") long by 114 mm (4-1/2") wide by 9.5 mm (3/8") thick plywood
shims supported the sill, located 229 mm (9"), 635 mm (25"), and 1054 mm (41-1/2") o/c either side of mid-width.
The wooden test buck consisted of an outer perimeter frame 2x10 SPF lumber with a 2x2 SPF lumber extension
on the interior. The sill of the buck was lined with an inner section of 2x6 SPF lumber spanning the jambs, the
inner edge of the 2x6 flush with the inner edge of the 2x10. The test specimen was leveled and set plumb in the
wooden test buck and fastened as above. The exposed exterior surface of the buck was sealed with a silicone-
based waterproof coating.
The sample size tested was larger than the CW Class Gateway test size of 2400 mm x 2100 mm (~94-1.2" x 82-
11/16"). The larger test sample size is considered to be the worse-case scenario condition and therefore the test
results of the larger tested sample are also applicable to the smaller Gateway size. The tested size is the largest
for which compliance is sought.
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM
THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL
PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Report No.: T1277-8B
Date: June 2, 2021
Page 4 of 13
Product Ratings:
Table 1: Summary of test results
Test Name AAMA/WDMA/CSA 101/I.S.2/A440-17 NAFS - North
American Fenestration Standard / Specification for
windows, doors and skylights and A440S1:19 Canadian
Supplement to AAMA/WDMA/CSA 101/I.S.2/A440-17
NAFS - North American Fenestration Standard /
Specification for windows, doors and skylights
Result:
Operating Force Test (ASTM E2068)
Test Date and Time: May 13/21 8:15 am Pass
Air Leakage Resistance Test1 (ASTM Pressure differential = 75 Pa (1.57 psf)
E283)
Pass
Test Date and Time: April 20/21 10:00 am
Airstream Temperature During Test: 20.9⁰C Infiltration result = 0.3 L/s/m² (0.05 cfm/ft²)
Barometric Pressure During Test: 98.7 kPa Exfiltration result = 0.3 L/s/m² (0.07 cfm/ft²)
Relative Humidity During Test: 39.3%
Infiltration/Exfiltration Maximum Allowable = 1.0 L/s/m² (0.2
cfm/ft²) for sliding seal products
1
-Testing was performed without stile reinforcement; considered to be the
worse-case scenario.
Water Penetration Resistance Test1
(ASTM E547) Maximum pressure differential = 510 Pa (10.5 psf)
Test Date and Time: April 20/21 2:05 pm Observations: No leakage or trapped water at 510 Pa
Temperature During Test: 21.0⁰C
The door was tested with the insect screen open and closed
Water Application Rate: 1.492 L/min 1
-Testing was performed without stile reinforcement; considered to be the
worse-case scenario.
Uniform Load Deflection Test at Design Maximum pressure differential = 2880 Pa (60.2 psf)
Pressure (ASTM E330 – Procedure A) Component Measured: Operating Panel Interlock Stile
Test Date and Time: May 26/21 9:15 am Maximum Deflection (+ve WL)= -12.62 mm (-0.497")
Temperature During Test: 26.0⁰C
Maximum Residual Deflection (+ve WL)= -0.37 mm (-0.015ʺ)
Load Duration (+ve WL): 10 sec.
Load Duration (-ve WL): 10 sec. Maximum Deflection (-ve WL)= 12.29 mm (0.484")
Use of Tape or Film: Yes Maximum Residual Deflection (-ve WL)= 0.37 mm (0.015ʺ)
Effect of Tape/Film: No effect
Maximum Allowable Deflection (1/175 of Span)= 12.67 mm
Span = 2216 mm (87.25")
(0.499")
Observations: No damage.
Uniform Load Structural Test (ASTM E330
– Procedure A) Design pressure= 2880 Pa (DP 60)
Test Date and Time: May 26/21 11:25 am Maximum pressure differential= 4320 Pa (90.2 psf)
Temperature During Test: 26.0⁰C Component Measured: Operating Panel Interlock Stile
Load Duration (+ve WL): 10 sec. Maximum Residual Deflection (+ve WL)= -0.55 mm (-0.022ʺ)
Load Duration (-ve WL): 10 sec. Maximum Residual Deflection (-ve WL)= 0.31 mm (0.012ʺ)
Use of Tape or Film: Yes Maximum Allowable Residual Deflection = 6.65 mm (0.262")
Effect of Tape/Film: No effect
Observations: No damage.
Span = 2216 mm (87.25")
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM
THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL
PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Report No.: T1277-8B
Date: June 2, 2021
Page 5 of 13
Result:
Forced-entry Resistance Test1 (ASTM Pass-F20 rating
F842 for Sliding Doors) 1
-Testing was performed without stile reinforcement; considered to be the
Test Date and Time: May 13/21 1:30 pm worse-case scenario.
Deglazing Test1 (Clause 9.3.6.2) Pass
Test Date and Time: May 13/21 10 am 1
-Testing was performed without stile reinforcement; considered to be the
worse-case scenario.
Insect Screen Serviceability Test (CSA
A440S1:19 Canadian Supplement Clause
Pass
5.1)
Test Date and Time: May 31/21 11:00 am
Performance Classification: CW
Performance Grades: PG 60
Maximum Size Tested: 2407 mm wide x 2391 mm high (94-3/4" x 94-1/8")
Primary Designator:
Class CW– PG60: Size tested 2407 x 2391 mm (~95 x 94 in) – Sliding Door (Type SD)
Class CW – PG2880 (SI): Size tested 2407 x 2391 mm – Sliding Door (Type SD)
Secondary Designator:
Positive Design Pressure (DP) = 2880 Pa (60 psf)
Negative Design Pressure (DP) = -2880 Pa (-60 psf)
Water Penetration Resistance Test Pressure = 510 Pa (10.65 psf)
Canadian Air Infiltration / Exfiltration = Pass for a Sliding Seal Product
Note: AAMA/WDMA/CSA 101/I.S.2/A440-17, Clause 9.2.5: The air, water and structural tests were performed
on test specimens installed per the method outlined in the test conditions section of this report. The test
procedures are designed to test the performance of the test specimen only and are not used to test the
performance of the installation, in particular the perimeter sealant joint and the anchoring of the assembly.
However, products not installed according to the installation method described in this report may not perform to
an equivalent performance level.
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM
THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL
PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Report No.: T1277-8B
Date: June 2, 2021
Page 6 of 13
Description:
2021 Series Aluminum Sliding Door
Frame: Description: Head- Two extruded aluminum sections, exterior header (Hydro Die No. AS-
76970), and interior header (Hydro Die No. AS-76977). Each section was
complete with a poured-and-debridged thermal break. The two sections
engaged each other along the frame cavity, and were bonded/sealed together
along their length with double-sided adhesive-backed acrylic tape (3M VBH
Tape RP25F) sandwiched between the overlapping portions of the sections. A
plastic cover (Futureline Plastics Part No. 6547) spanning the jambs, fitted to
upstanding parting (middle) track leg, the cover, complete with two flexible co-
extruded fins along the exterior, and a weather-strip kerf along the interior. An
extruded aluminum pocket cover (Hydro Die No. AS-76967) was fitted to the
exterior head track and spanned the lock jamb pocket cover to the fixed panel
interlock stile. The cover was sealed across the ends to the adjacent
members. A 108 mm (4-1/4") long PVC bumper (Anplex Part No. AP-531) was
fitted to the interior head track at the fixed jamb.
Sill- Two extruded aluminum sections, exterior sill (Hydro Die No. AS-76989),
and interior sill (Hydro Die No. AS-76990). Each section was complete with a
poured-and-debridged thermal break. The two sections engaged each other
along the underside of the sill, and were bonded/sealed together along their
length with double-sided adhesive-backed acrylic tape (3M VBH Tape RP25F)
sandwiched between the overlapping portions of the sections. A plastic cover
(Futureline Plastics Part No. 6548) spanning the jambs, fitted to upstanding
parting (middle) track leg, and was complete with two co-extruded flexible vinyl
fins along the exterior and a weather-strip kerf along the interior. An extruded
aluminum threshold cover (Hydro Die No. AS-76969) was fitted to the exterior
sill track and spanned the lock jamb pocket cover to the fixed panel interlock
stile. The cover was sealed across the ends to the adjacent members. A 108
mm (4-1/4") long PVC bumper (Anplex Part No. AP-531) was fitted to the
interior sill track at the fixed jamb.
Jamb- Two extruded aluminum sections, exterior jamb (Hydro Die No. AS-
76978), and interior jamb (Hydro Die No. AS-76971). Each section was
complete with a poured-and-debridged thermal break. The two sections
engaged each other along the frame cavity, and were bonded/sealed together
along their length with double-sided adhesive-backed acrylic tape (3M VBH
Tape RP25F) sandwiched between the overlapping portions of the sections.
An extruded aluminum pocket cover (Hydro Die No. AS-7697) was fitted to the
exterior lock jamb track, spanning the head to the sill.
Frame dimensions: Width: 2407 mm (94-3/4"); Height: 2391 mm (94-1/8").
Joints: Frame corners were stepped and fastened using #8 x 1" long self-drilling pan
head screws, two per head corner and four per sill corner, into screw-ports.
Closed cell 6.4 mm (1/4") thick polyethylene foam pads were sandwiched
between the members at all four corners (A&M Rubber Part Nos. V20003
Header Gasket and V20006 Sill Gasket). The pads at the sill corners were
sealed with silicone to the jambs along the top edge and down the screen
track edge.
Reinforcement: None.
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM
THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL
PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Report No.: T1277-8B
Date: June 2, 2021
Page 7 of 13
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM
THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL
PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Report No.: T1277-8B
Date: June 2, 2021
Page 8 of 13
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM
THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL
PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Report No.: T1277-8B
Date: June 2, 2021
Page 9 of 13
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM
THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL
PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Report No.: T1277-8B
Date: June 2, 2021
Page 10 of 13
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM
THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL
PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Report No.: T1277-8B
Date: June 2, 2021
Page 11 of 13
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM
THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL
PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Report No.: T1277-8B
Date: June 2, 2021
Page 12 of 13
MODIFICATIONS:
• Interior lock jamb track weather-strip changed from 0.210" x 0.187" finned pile to 0.210" x 0.187" pile only
(without fin) pile along interior track leg.
• Knurled jamb stile thermal breaks prior to crimping to minimize twisting of stiles.
• Operating Panel adjusted upwards.
DECISION RULE:
Unless specifically stated or identified otherwise, QAI has utilized a simple acceptance rule to make conformity
decisions on testing results contained in this report, as applicable.
CONCLUSION:
QAI Laboratories Ltd., with lab facilities located in Vaughan, Ontario, performed testing in accordance with
AAMA/WDMA/CSA 101/I.S.2/A440-17 NAFS - North American Fenestration Standard / Specification for
windows, doors and skylights and A440S1-19 Canadian Supplement to AAMA/WDMA/CSA 101/I.S.2/A440-17
NAFS - North American Fenestration Standard / Specification for windows, doors and skylights on a
representative sample of a Sunview Patio Doors Ltd. 2021 Series Aluminum Sliding Glass Door.
Test results in this report may not be reproducible in the field. Test results relate only to those products tested.
See Table 1 for a summary of test results and window ratings. The sample tested was found to comply with the
applicable requirements and obtained test results as reported in Table 1 of this report.
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM
THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL
PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Report No.: T1277-8B
Date: June 2, 2021
Page 13 of 13
APPENDIX A
Page Title
A1-A2 Bill of materials
A3-A4 Cross-sectional assembly drawings
A5-A32 Cross-sectional drawings of parts
A33 Photos
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM
THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL
PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A1 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A2 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A3 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A4 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A5 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A6 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A7 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A8 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A9 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A10 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A11 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A12 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A13 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A14 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A15 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A16 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A17 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A18 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A19 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A20 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A21 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A22 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A23 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A24 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A25 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A26 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A27 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A28 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A29 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A30 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A31 of A33
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A32 of A33
QAI Laboratories Ltd.
Date: June 7, 2021
Checked By:
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG
info@qai.org
Client: Sunview Patio Doors Ltd.
Job No.: T1277-8B
Date: June 2, 2021
Page Appendix A33 of A33
PHOTOS
Photo #1- Dust plugs (pile and closed cell Photo #2-Sill end of jamb- PVC foam jamb
vinyl nitrile) at top end of fixed panel pocket foam pad above closed cell
interlock stile. polypropylene foam corner pad.
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS
FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR
THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.
WWW.QAI.ORG