Professional Documents
Culture Documents
Solved Problems
Protection Zones
•Draw the zones of protection for the power system shown
in Fig. 3 (Hint: there will be 14 zones).
•Which circuit breakers will open for a fault at (a) P1, (b) P2 and
(c) P3?
Problem:
Motor Protection
50
Time (sn)
1000
Uzun dönem hafif aşırı
yüklenme bölgesi Rotor kilitlenme akımı
200
Motor yol alma bölgesi
100
Rotor kilitlenme zaman aralığı
10
Motor Kalkış Eğrisi
Solution:
Rated Current
Prospective Current
Amps, rms
Trip Trip
Remember:
Relay b must provide protection load side after Bus B
Relay ab must provide primary protection for line AB, back
up protection for the load side
11/11/2020 ELK415E,O USTA, ITU ELECTRICAL ENGINEERING 14
Trip Trip
1-If there is a fault within the load side, Rb provide primary protection and for
a fault current of 600A, it will trip after 0.22 s.
2- Relay ab will trip for the same fault after 0.63s as a back up protection.
Also Rab provide primary protection for the line setion AB:
Instantaneous OC Protection
The closer the fault is to the source, the greater the fault
current magnitude, yet the longer the tripping time. The
addition of instantaneous overcurrent relays makes this
system of protection viable. If an instantaneous relay can be
set to see almost up to, but not including, the next bus, all of
the fault-clearing times can be lowered
Since the instantaneous relay must not see beyond its own
line section, the values for which it must operate are very
much higher than even emergency loads. Therefore, load is
not usually a consideration for the instantaneous relay
setting.
Check to see how the relay will perform for a minimum fault at
bus B. The minimum fault at bus B is 800 A, divided by the
relay pickup of 1350 A, giving a multiple of pickup of 0.59: the
relay will not operate.
Directional Relaying
With switch X closed, assume that the current through (4) and
(5) for a fault at F1 is 100 A and for a fault at F2 is 400 A.
THANKS to
Stanley H. Horowitz
Arun G. Phadke