Construction Team Denim Studio Ltd. Unit-1 Report on Static Load Test on Precast Pile
1. INTRODUCTION
1.1 General
This report is prepared for the evaluation / verification of pile ultimate load bearing capacity
at Team Denim Studio Ltd. Unit-1 building, precast pile was installed by dop hammer method
& as a third-party test service agency GIPSOL conduct the static load test on the pile. Starting
date of load test is 27th January 2023.
The static axial compressive load is to be provided by hydraulic jack acting against sandbag
platform counterweight Kentledge as reaction system.
Cyclic Load (ML) method with standard loading procedure was followed under the
compliance of the contract documents.
Reference Standard:
ASTM D1143: Standard Method of Testing Piles Under Static Axial Compressive Load
Page 2 of 10 SE-G-RPT-06-A1
Construction Team Denim Studio Ltd. Unit-1 Report on Static Load Test on Precast Pile
2. LOCATION
Location of test pile is at Unit-2, Southend sweater co. ltd. Dour, Ashulia, with pile
demarcation ID TP-02.
WORK LOCATION
St. Ver. Test
Pile Location Co-Ordinate
No.
Physical description of test piles and equipment used are provided in Table 1 and table 2
below. The design load of pile is 175 Mt and maximum theorical applied load is 350 Mt
what is 200% of design load. This maximum applied load refers to the following table 1
Page 3 of 10 SE-G-RPT-06-A1
Construction Team Denim Studio Ltd. Unit-1 Report on Static Load Test on Precast Pile
Y= 10.17x-
17010515 360 565 435 K; G-4 30.03.2022 0-1000
131.73
4. REACTION SYSTEM
The reaction system called Kentledge shall be prepared, comprising of steel I-beams (cross
beam, test beam, rocker beam, etc) and sand bag for counter weight against which the pile
shall be tested. Crib wall was made by Sand bag (refer to Fig 1).
Page 4 of 10 SE-G-RPT-06-A1
Construction Team Denim Studio Ltd. Unit-1 Report on Static Load Test on Precast Pile
The general guideline of ASTM 1143 “Standard Method of Testing Piles Under Static
Axial Compressive Load” was followed. For evaluation of result IS 2911-IV was followed.
Reaction System- Static axial compressive load was conducted by hydraulic jack acting
against steel platform counterweight kentledge as reaction system. Kentledge was
prepared, comprising of steel I-beams (spreader beam, main beam, rocker beam etc.) and
sandbags. Crib walls were made by sandbag crib wall with a base of 2.2 m width to top
0.50 m & height 1.55m.
Page 5 of 10 SE-G-RPT-06-A1
Construction Team Denim Studio Ltd. Unit-1 Report on Static Load Test on Precast Pile
The load on pile was applied by using hydraulic jack seated on bearing plate. Piston pump
was used to develop pressure. Calibrated pressure gauges fitted with jack to monitor load.
25% of proof load was added with counter weight to avoid the tilting of kentledge. Total
load of the kentledge was about 430 Mt > 385 Mt (110% of 350 Mt).
Loading Procedure- The maximum load to be applied on the pile has been specified as
300% by the engineer. The loading and unloading have been performed in stages, and this
loading and unloading stages are shown in (Appendix-3). In the event of a failure (as
indicated by excessive pile head displacement) further loading shall be halted and
maximum applied load shall be maintained for 12 hours. After wards, unloading sequence
shall be undertaken. Hence, at maximum loading as the failure has not been occurred,
further load has been increased up to 300% of the design load.
Following each application of an increment of load, the load was held for not less than the
period shown in [Appendix-3], or until the rate of settlement is less than 0.25mm/h and is
slowing down. The rate of settlement has been calculated from the slope of the curve
obtained by plotting values of settlement versus time and drawing a smooth curve through
the points. Each stage of unloading shall proceed after the expiry of the period is also
shown in [Appendix-3],
Page 6 of 10 SE-G-RPT-06-A1
Construction Team Denim Studio Ltd. Unit-1 Report on Static Load Test on Precast Pile
6. OBSERVATION
Test Result
Pile Load against
Pile Length Ultimate
Dimension Gross Net 12mm
ID (m) Max. Applied Capacity from
(mmxmm) Settlemen Settlemen Settlement,
Load (kN) Davisson line
t (mm) t (mm) (kN)
(Mt)**
IS 2911-IV**
~2217 1650 2040
TP-02 12 400x400 44.91 35.01
(226 MT) (168 MT) (208 MT)
LOAD (KN) →
0 400 800 1200 1600 2000 2400
0
10
SETTLEMENT (MM)→
20
30
40
50
Page 7 of 10 SE-G-RPT-06-A1
Construction Team Denim Studio Ltd. Unit-1 Report on Static Load Test on Precast Pile
LOAD (KN) →
0 400 800 1200 1600 2000 2400 2800
0
1650
2040
2180
IS 2911-IV IS 2911-IV
15
SETTLEMENT (MM)→
30
45
60
2000.00
1000.00
Load (kN)→
0.00
-1000.00
-2000.00
Settlement (0.01 mm) →
-3000.00
-4000.00
-5000.00
0 2 4 6 8 10 12
Time (Hr) →
Page 8 of 10 SE-G-RPT-06-A1
Construction Team Denim Studio Ltd. Unit-1 Report on Static Load Test on Precast Pile
TP-02 was tested under static axial compressive load. Pile is of 400x400 mm and 12 m long from
pile top level. Pile was given 2217 kN (1.29 times of working load) of load that resulted in gross
settlement of 44.91 mm and net settlement of 35.01 mm.
As ASTM provides test procedures/methodology only. The test is performed as per ASTM 1143.
However, ASTM does not specify the method of working out the safe pile load carrying capacity.
Hence different methods are available for estimating ultimate carrying capacity of piles. Off them,
we have estimated ultimate capacity by:
As per Clause 7.1.5, IS 2911 (Part 4) 2013 “The safe load on single pile for the initial test should
be least of the following:
a) Two thirds of the final load at which the total displacement attains a value of 12 mm unless
otherwise required in a given case on the basis of nature and type of structure in which case, the
safe load should be corresponding to the stated total displacement permissible. (Referred by BS
:8004 also)
b) 50 percent of the final load at which the total displacement equal 10 percent of the pile diameter
in case of uniform diameter piles and 7.5 percent of bulb diameter in case of under-reamed piles.”.
As per Clause 6.1.5, IS 2911 (Part 4) 2013, pile safe load carrying capacity can be determine from
actual settlement curve. From the load-settelement curve we can estimate safe bearing capacity 1100
kN [112 mt] (1650x2/3 kN)
As per clause (b) load against 10% of settlement is 2180 kN (222 Mt) is ultimate capacity of pile
Page 9 of 10 SE-G-RPT-06-A1
Construction Team Denim Studio Ltd. Unit-1 Report on Static Load Test on Precast Pile
From above result & on the basis of working pile construction method & quality performance we can
consider ultimate capacity of 2180 kN. So, the maximum recommended working load for pile can
consider 1100 kN or 112 MT with a practical settlement 8.01 mm.
Page 10 of 10 SE-G-RPT-06-A1
Construction Team Denim Studio Ltd. Unit-1 Report on Static Load Test on Precast Pile
Field Data
Appendix 1
Construction Team Denim Studio Ltd. Unit-1 Report on Static Load Test on Precast Pile
Corrected Data
Appendix 2
DATASHEET FOR ROUTINE LOAD TEST BY MAINTAINED LOADING LOAD METHOD USING ASTM D1143 1 of 2
Test Pile ID: TP-02 A. Pile B. Hydraulic Jack Information C. Pressuregauge Information 1. Retantion of load up to 275% is any time if the rate of settlement dosen't
exceed 0.25mm/h or maximum 2h
Location of Test Pile: Team Denim Studio Ltd. Dimension of Pile (mm): 500 Jack ID: 17010515 Gauge ID: K,G-4 2. Ultimate load should retain any time after 12h or the rate of settlement
Design Load (kN) 1144 117 MT (1 MT = 9.806 kN)] dosen't exceed 0.25mm/h
Cutoff Level: (-) Capacity: 750 Ton Made: WIKA
3. As per Clause 7.1.5.1, IS 2911 (Part 4) 2013 “Routine test shall be carried
Maximum Test Load (kN) : 3432 (300% of design Load) Founding Level (-) Plunger Dia: 360 mm Range: 0-1000 kg/cm2 for a test load of at least 1.5 times the working load; the maximum
Start of Test: 27-Jan-23 settlement at the test load being not greater than 12 mm for piles diameter
Test Level: (-) Body Dia: 565 mm Cal. Eq. Individual, Y (kg/cm2) = x -
up to and including 600 mm
End of Test: 28-Jan-23 Existing Ground Level: (-) Body Ht. 435 mm Pressure area of Hydraulic jack (cm2)= 10.17 x - 121.73
Load, Applied, Observation Maintained up to 125% of Increment and Decrement Observation Maintained for Ultimate Loading and Final Decrement
Reading, Reading, kN
% kN Hr Min
kg/cm2 kg/cm2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2 M1 M2
Average Reading
CYCLE-1
0 0 0 0 0
1.36
3.06
1.40
3.10
1.41
3.10
1.41
3.10
1.42
3.10
25 286 40.0914 40.00 1 0
285
16:00
2.26
3.01
4.67
3.08
4.47
3.09
4.74
3.09
4.74
3.10
4.75
50 572 68.2134 70.00 1 0
590
17:00
3.93
5.03
6.01
5.09
6.03
5.10
6.04
5.10
6.05
5.12
6.07
75 858 96.3353 95.00 1 0
844
18:00
5.60
8.50
8.75
8.30
8.84
8.33
8.87
8.38
8.90
8.40
8.92
100 1144 124.457 125.00 1 0
19:00
8.66
1150
8.63 8.57 8.60 8.64 8.66
9.90
125 1430 152.579 155.00 1 0
10.44
10.03
10.53
10.09
10.59
10.13
10.30
10.15
10.65
20:00
1455
10.40
12.40
12.84
12.49
12.89
12.55
12.94
12.58
12.97
12.63
12.99
21:00
1709
12.81
18.07
19.50
18.16
19.60
18.23
19.65
18.28
19.70
18.38
19.83
18.55
19.95
22:00
2014
19.25
41.65
42.42
41.86
42.60
41.98
42.76
42.33
43.05
42.46
43.22
42.75
43.50
42.98
43.73
43.18
43.96
43.40
44.17
43.53
44.35
43.73
44.51
43.90
44.68
44.08
44.86
44.30
44.99
44.53
45.24
44.56
45.26
0:00
2217
44.91
42.04 42.23 42.37 42.69 42.84 43.13 43.36 43.57 43.79 43.94 44.12 44.29 44.47 44.65 44.89 44.91
44.30
45.09
44.28
45.07
44.27
45.06
1:00
1709
44.67
43.65
44.20
43.63
44.17
43.62
44.17
1:20
1150
43.90
41.70
42.09
41.66
42.05
41.63
42.03
1:40
590
41.83
0
0 0 0 0.00 1 0
36.02
36.20
35.29
35.40
35.17
35.31
35.11
35.25
34.93
35.09
2:00
35.01