Professional Documents
Culture Documents
1 Introduction
Integration of renewable distributed generation units, such as solar photovoltaic
systems and wind turbine generators , into existing power systems because they
can offer several benefits to power systems, including support during normal
operation and enhanced reliability during contingencies. However, system op-
erating constraints, uncertainties in generation availability for renewable DG
systems, and time-varying load demand are major barriers in their effective
integration.
The reliability assessment of distribution systems embedded with renewable
DG sources has been carried out giving importance to system uncertainties(such
as variation of load demand,wind speed,and solar radiation) and optimal the
systems restoration plan.. The optimization of restoration processes involves
minimising customer interruption duration, which can improve customer-side
supply reliability by reducing the customer interruption duration of each fault
event, thus reducing the system average interruption duration index (SAIDI).
Conventional distribution systems typically balance supply capacity with
maximum load demand to meet customer needs without considering the need
for DG unit support.Constant load demand and DG output are often used
for short-term restoration, but this can mask system uncertainties and cause
unrealistic solutions, resulting in fewer customers being restored or additional
interruptions due to mismatch between actual generation and load demand.
1
The total interruption hours due to a system fault event is denoted by T.The
total number of system nodes in out-of-service areas is denoted by N.The binary
status of load point n at time t is represented by Bt,n, with 1 representing the
restored load point.The number of customers at load point n is denoted by Ln.
The total number of switches in the out-of-service areas can be represented by
M. SW is a binary matrix representing the status of switches in an M x T format
at each time step
system Constraints to be considered are modelled as :
loadpoint, also known as the child node, may only be restored in conjunction
with the restoration of the related candidate node, also known as the parent
node, and the closure of the switch between the loa dpoint and the candidate
node. The constraint mentioned above can be written as
Bj,t ≤ SWj,t Bi,t
J and I are the child and parent nodes respectively. where SWj,t is the binary
state of the jth switch at time t. Bj,t and Bi,t represent the binary status of
the jth and ith node( restored or not restored).
A DG unit’s total loads restored shouldn’t be greater than its capacity at
any given time step (t).
X
PDGt ≥ Bt,n Pt,n
nϵßt
Pt,n (kW) is the required capacity at load point n, including its associated loss
component in time t. And Bt,n is the status of load point n at time t.
The minimum time tmin required to operate the corresponding manual
switches shall not be less than the time difference between two consecutive
manual switching operations:
SWm,t1 = SWm,t2 ∀ |t1 − t2 | < tmin
It is anticipated that the load point that was reenergized earlier won’t be
de-energized later on.This constraint can be modelled using binary variables as
Bt,n ≥ Bt−1,n
2
The choice to either restore or not restore new customers is represented by
T integers in the first set. N numbers in the second set represent the choice
of the potential restoration nodes. After the initial issue variables are trans-
formed into a vector containing T + N integers, the numbers may be translated
into decisions that have real significance by using the suggested transformation
function provided as
xi
yi = 1 + xi − f loor · ai
ai
The number of candidate nodes, or alternative possibilities, is denoted by ai ,
and the priority index of the nodes that need to be restored is indicated by yi .
Xi is the ith integer input from the set X.
3
3.3 Selection Guide for a Multi Generator System
When there are more than one DG, the suggested dynamic selection method
is used on each one to find a unique restoration process. If more than one
restoration sequence overlaps, the restoration sequence is chosen by treating
these DG units as a single unit and picking the largest DG node as a potential
node.
4 CONCLUSION
In this article, we have discussed the different system constraints which are re-
quired to be taken into consideration for reliability assessment of a power system,
and how to model those constraints using variables and equations. Secondly ,
we have undergone the study of optimization algorithms for system restoration
after a failure , to ensure lesser customer interruption and to ensure the already
restored networks are not interrupted again. A more intelligent TRIBE PSO
method is used in the paper that we have referred to , to optimise the restoration
procedure. For reliability assessment under different scenarios a time sequential
Monte Carlo methods were used and the reliability indices SAIDI and SAIFI
were used to show the customer side reliability .