Professional Documents
Culture Documents
1
COEP
CHAPTER 6
SIMULATION DESIGN
The p-q theory based shunt APF is implemented for Harmonic compensation and power
factor correction. Logic utilized for shunt APF is discussed in chapter 5 and is summarized
in fig.5.2
6.1 Specification of the design:
Simulation is performed on 2 types of Three phase Balanced Non –Linear Load as
fallows:
System Parameters
Source Voltage VSa,VSb,VSc 220 Vrms(line- line)
System Frequency f 60 Hz
APF
Dc-link voltage Vdc 800V
Dc side capacitance C 1100μF
Ac side inductance Lc 3.75mH
Ac side resistance Rc 0.01 Ω
(Rating of APF is generally decided by peak voltage and RMS Current)
Load2 Diode rectifier (of rating around 3KVA) supplying to purely resistive load
AC side inductance LLac NA
AC side resistance RLac NA
DC side Resistance RLdc 18 Ω
DC side Inductance LLdc NA
2
COEP
(NOTE: Rating of APF is generally decided by peak voltage and RMS Current[14]
APF rating for Load1 is Vpeak=312v and Irms=3A will result in rating of
12 ×312×3= 0.661 KVA .Thus in practical cases can be assumed to be around 1-1.5KVA}.
3
COEP
Fig 6.1 p-q theory based control block diagram of three-phase shunt APF system.
Continuous
pow ergui
Va [isa]
i
+ i
- +
-
Vb A
[isb]
i
+ i
- +
-
B
Vc [isc]
i
+ i
- +
- C
220 V rms L-L
3-phase Source Lc non-linear load
-
-
+
+
v
g11
Rc
g12
g21
Load Current measurement g22
g31 Vdc
+
Voltage measurement
+
g32
-
-
i
-
i
a
[Vsa] [Vsb] [Vsc]
b
c Goto7 [Vdc]
Current measurement Compensator
[Vsa] Vsa
Valpha Valpha
current measurement1
Ia*
[Vsb] Vsb
Isalf a Isalpha
Isa* A1
Vbeta
Ib*
[Vsc] Vsc Isb* A2
Capacitor voltage
pdc Isbeta
Vbeta
Ic* Isc* B1
800 In1 Isbeta
[isa] Isa
ploss Inverse Transformation Isa B2
Out1
[Vdc] In2
[isa] Isb C1
[isb] Isb
p
Isc C2
butter
Clarke Transformation
[isc]
Low Pass FIlter
4
COEP
6.2 Clark Transformation:
is done in accordance with section 4.2.2
1 a
alpha
Vsa
2 b
Vsb beta
Vbeta
3 c
Ibeta
Vsc Subsystem1 p 3
Valpha
p
Ialpha
Subsystem5
4 a
alpha
Isa
5 b 1
Isb beta Valpha
6 c
Isc Subsystem2
2
Vbeta
1 1
a
2 -K- -K- 1
b alpha
K=-1/2 Sum of K=sqrt(2/3)
Elements
3 -K-
c
K=-1/2
-K- 2
beta
Sum of K=sqrt(2/3)
-1
Elements1
5
COEP
6.3 Calculation of p
According p-q theory real and imaginary power can be separated into two parts:
Real power: p=p+p
Thus, inverse transformation iap will produce reference current iS* for each phase.
iap can deduced from p which is filtered out using low pass filter from p.
1
Vbeta 1
p
2
Product
Ibeta
3
Valpha
4
Product1
Ialpha
p p
1
Vdc PID 1
2
ploss
constant PID Controller
Subtract
It can be noted that if Kp and KI are large, the DC-bus voltage regulation is dominant, and
the steady-state DC-bus voltage error is low. On the hand, if Kp and KI are small, the real
power unbalance give little effect to the transient performance. Therefore, the proper
selection of Kp and KI is essentially important to satisfy above mentioned two control
performances.
7
COEP
3 1
pdc Isalfa
Divide
Product
4
ploss 1
Valpha
Product1
2
Vbeta
Product2
2
Product3 Isbeta
Divide1
1 -K- 1
Isalpha Ia*
Gain
-K-
Gain1 2
Ib*
2 -K- -K-
Isbeta 3
Gain2 Gain3
Ic*
Subtract
8
COEP
4 Isa 1
A1
Subtract2 Relay3
1
NOT 2
Isa*
A2
Logical
Operator
3
5 Isb
B1
Subtract1 Relay1
2
Isb*
NOT 4
B2
Logical
Operator1
6 Isc 5
C1
Subtract3 Relay2
3
NOT 6
Isc*
C2
Logical
Operator2
6.7 Compensator:
Switching is done according to gating signals from Hysteresis Band Current Controller.
Capacitor Voltage is continuously measured and fed to PI controller as explained earlier.
9
COEP
2
m
2
m
m
g
1
+
1 g11 v 1
C -
3 g21 Vdc
5 g31 Voltage Measurement3
1 2 3
a
b c
2
m
2
m
m
g
1
2 g12 4 g22 6 g32
10
COEP
Rlac Llac DC motor equivalent circuit
g
i
+ +
-
A
Id
B
-
C
Thyristor Converter
Synchronization Voltages
+
v alpha_deg
-
1 A Vab AB
+
v BC pulses
-
2 B Vbc CA
+
v 0 Block
-
3 C Vca Synchronized
6-Pulse Generator
PI Curent Regulator
1
100
s
Id_Refence
90
11
COEP
case2:Diode Rectifier supplying to pure resistive load
1 A
3 C
Fig 6.12 Block diagram for Diode rectifier supplying to pure Resistive Load
A pure resistive load is taken in order to APF performance. As in this load phase current
varies in abrupt manner on the contrary to RL load where load phase current is smooth
varying curve.
12
COEP
CHAPTER 7
SIMULATION RESULTS
7.1 Case 1: Thyristor converter supplying to DC motor Equivalent(R-L Type Load)
VSa
ILa
VSb
ILb
VSc
ILc
13
COEP
Fig 7.2 Harmonic Analysis of Load Current with APF(Case 1)
ISa*
ILa ICa
15
COEP
VSa
ISa
VSb
ISb
VSc
ISc
16
COEP
Fig7.7 Harmonic Analysis of Source Current (Case 1)
17
COEP
Vc
18
COEP
7.2 Case 2: Diode Rectifier supplying to pure resistive
VSa
ILa
VSb
VSc ILb
ILc
Fig 7.9 load Source Voltage & Load Current with APF
19
COEP
Fig 7.10 Harmonic Analysis of Load Current
20
COEP
ISa
ICa
ILa
21
COEP
VSa
ISa
VSb
ISb
VSc
ISc
22
COEP
Fig 7.14 Harmonic analysis of Source Current(Case 2)
23
COEP
Fig 7.15 DC Capacitor voltage for three-phase APF(Case 2)
24
COEP
As the source current and voltage are in phase,also the source current is almost
sinusoidal(very low THD) it can be said that source is providing only active power required
by the circuit. In instantaneous power theory view, source current is providing only average
real power component(p) while remaining components i.e real oscillating power(p),
imaginary average power(q) and imaginary oscillating power(q), is being provided by
Shunt APF.(see Discussion in section 6.3 )
From source currents and THD in case1 (RL load) and case 2 (purely resistive load )
it can be said that the effectiveness of the active filter in compensating for harmonic
components of the load current depends on the specific load current waveform involved.
Two different waveforms may have the same rms harmonic content but the active filter may
do a better job of compensating for one of the waveforms because of the waveshapes
involved. Source current has very less THD in case of RL load compared to purely resistive
one. Thus it can be inferred performance of shunt APF with RL load is much better than
purely resistive load.
In general, the current waveform of an ac regulator with resistive load is an example
of the waveshape that poses the severest challenge for an active filter. The problem is the
high di/dt that is required of the filter to compensate for the high di/dt at turn on of the
regulator. The problem is most severe when the regulator is turned on with a firing angle
close to 90 degrees because this is when the available driving voltage stored on the dc
capacitor is at a minimum. The output di/dt capability can be raised either by increasing the
dc voltage setting or by reducing the size of the interfacing inductance. The limiting factor
for increasing the dc voltage is the voltage withstand capability of the IGBT devices. The
limiting factors for reducing the interfacing inductance include the IGBT di/dt withstand
capability, control requirements, the interface passive filter requirement, and overall system
stability. If the interfacing inductance becomes too small, the dc voltage cannot be kept
constant for normal operation.
From harmonics analysis of Source Current it can be seen due to uneven switching
of compensator large number of interharmonics are introduced. But,it should be noted that
those components have very less magnitude.(Maximum magnitude of interharmonic is 0.11
% in case 1)
25
COEP
Using PI Controller DC capacitor is maintained at reference value. It was seen that
Settling time improved drastically using PI controller.
It is worth to also to note that p-q based APF can be used for complete harmonic
elimination not selective harmonic elimination.
CHAPTER 8
CONCLUSION
26
COEP
The validity in terms of eliminating p-q theory in terms of eliminating harmonics and power
factor improvement is confirmed from low THD source current which is in phase with source
voltage. But p-q theory utilizes large number of sensors and reference current calculation block.
Large number of calculation in p-q theory demands higher processing power. Resulting in utility to
be complex and expensive. The p-q theory base APF is predominantly utilized in three phase circuits
thus can not be used at remote single phase customer. As a result, Harmonics are present in large part
of system. From source currents of the both cases (i.e. RL Load and purely resistive load) it can be
inferred that APF is most effective when the load current waveform does not have abrupt changes.
The overall filtering effectiveness depends significantly on the types of loads being compensated. As
a result, it is very effective for most voltage source inverter-type loads, even when the distortion is
high.
From comparing reference current and source waveforms it can be concluded that hysteresis
band current controller done the compensation at the cost of high switching frequency. Which can
result in high switching losses in practical high power APF applications. PI controller performance is
also validated from the DC-bus capacitor voltage which shows decreased settling time.
In theoretical view p-q theory has some shortcomings which need to be addressed. Like
mathematical expression of instantaneous power does not fallow power conservation and real and
imaginary power needed to be more accurately defined as zero sequence instantaneous power can
not be defined by the theory. In practical approach also it can be noted that p-q theory is incapable of
providing selective harmonic elimination and specific power factor compensation.
References
28
COEP
29
COEP