SPARK TEST VOLTAGE

INSULATION:

Refernce Standard : IEC 62230 and BS 5099

Table A.1 – Recommended minimum spark-test voltages for cables having rated voltage (U 0) between 300 V and 3000 V
acc. to IEC 62230 ANNEX A.2

Table 1 — Spark test voltage values for insulation for cables having a rated voltage between 300 V and 3300 V
acc. to BS 5099 Clause 5.2

Radiul Thickness of Insulation Test Voltage (KV)


From Up to ac
- 0.25 3
0.26 0.50 5
0.51 0.75 6
0.76 1.00 7
1.01 1.25 9
1.26 1.50 10
1.51 1.75 12
1.76 2.00 13
2.01 2.25 14
2.26 2.50 16
2.51 2.75 17
2.76 3.00 19
3.01 - 25

SHEATH:
According to BS 5099 Clause 5.4

When spark testing of sheath is specified in the relevant cable standard, it shall be subjected to the following spark test voltage values, unless otherwise
specified in the cable standard: a) a.c.: 6 kV per millimetre of the tabulated radial thickness of sheath, up to a maximum voltage of 25 kV

Spart Test Voltage (KV) for Sheath = Sheath Thickness (mm) x 6 KV


Note: Maximum Voltage 25 kV