You are on page 1of 36

Feeder Protection Relay REX 521

Product Guide
Feeder Protection Relay REX 521
1MRS752177-MBG
Issued: 20.11.2001
Status: Updated
Version: F/15.02.2006
Data subject to change without notice

General The protection relay REX 521 is designed for protection relay is provided with energizing
protection, control, measuring, and supervi- inputs for conventional current and voltage
sion in medium voltage networks. Typical transformers. Also a hardware version with
applications include incoming and outgoing inputs for current and voltage sensors is
feeders as well as substation protection. The available.

Design The protection relay is based on a multipro- and informs the user via indication messages.
cessor environment. The human-machine Modern technology is applied both in hard-
interface (HMI)1 including an LCD display ware and software solutions.
with different views makes the local use easy
The protection relay is part of the ABB Sub-
1. HMI is referred to as MMI in the relay and in the station Automation system and extends the
Relay Setting Tool.
functionality and flexibility of the concept
further.

3
Feeder Protection Relay REX 521
1MRS752177-MBG

Features Standard configuration B01: Standard configuration B02:


• Three-phase non-directional overcurrent • Three-phase non-directional overcurrent
protection with three stages protection with three stages
• Non-directional earth-fault protection with • Three-phase transformer inrush and motor
three stages start-up current detector
• Phase discontinuity protection for three • Non-directional earth-fault protection with
phases three stages
• Three-phase thermal protection for cables • Phase discontinuity protection for three
phases
• Three-phase transformer inrush and motor
start-up current detector • Three-phase thermal protection for cables
• Supervision function for the energizing cur- • Supervision function for the energizing cur-
rent input circuit rent input circuit
• Current waveform distortion measurement • Current waveform distortion measurement
• Three-phase current measurement • Three-phase current measurement
• Neutral current measurement • Neutral current measurement
• Calculation of the accumulated electric • Calculation of the accumulated electric
breaker wear of the circuit breaker (CB) breaker wear of the circuit breaker (CB)
• Transient disturbance recorder • Transient disturbance recorder
• Trip-circuit supervision • Trip-circuit supervision
• Delayed trip output for the circuit-breaker • Delayed trip output for the circuit-breaker
failure protection (CBFP) function failure protection (CBFP) function
• Circuit breaker control with indication • Automatic reclosing 1...5 shots
• Lockout function • Circuit breaker control with indication
• Object indication • Lockout function
• Logic control position selector • Object indication
• User-configurable I/Os • Logic control position selector
• Interlocking • User-configurable I/Os
• User-configurable alarm LEDs • Interlocking
• User-configurable alarm LEDs
3I > 50/51 MCS 000

I 0> TCS 3I > 50/51 MCS 000


50N/51N
CBCM 0 I I 0> 50N/51N TCS
3I 2f > 68
R 3I 2f> CBCM 0 I
3I~harm 68
I> 46
3I~harm R
I> 46
3 49F

CBFP 3 49F
62 3I I0

0 I 79 I0
LO 86 3I

CBFP 62
REX 521 B01
LO 86
Fig. 1 Block diagram of B01
REX 521 B02

Fig. 2 Block diagram of B02

4
Feeder Protection Relay REX 521
1MRS752177-MBG

Features (cont´d) Standard configuration M01: Standard configuration M02:


• Three-phase non-directional overcurrent • Three-phase non-directional overcurrent
protection with three stages protection with three stages
• Three-phase transformer inrush and motor • Three-phase transformer inrush and motor
start-up current detector start-up current detector
• Directional earth-fault protection with three • Directional earth-fault protection with three
stages stages
• Phase discontinuity protection for three • Phase discontinuity protection for three
phases phases
• Three-phase thermal protection for cables • Three-phase thermal protection for cables
• Supervision function for the energizing cur- • Supervision function for the energizing cur-
rent input circuit rent input circuit
• Current waveform distortion measurement • Current waveform distortion measurement
• Three-phase current measurement • Three-phase current measurement
• Neutral current measurement • Neutral current measurement
• Residual voltage measurement • Residual voltage measurement
• Calculation of the accumulated electric • Calculation of the accumulated electric
breaker wear of the circuit breaker (CB) breaker wear of the circuit breaker (CB)
• Transient disturbance recorder • Transient disturbance recorder
• Trip-circuit supervision • Trip-circuit supervision
• Delayed trip output for the circuit-breaker • Delayed trip output for the circuit-breaker
failure protection (CBFP) function failure protection (CBFP) function
• Circuit breaker control with indication • Automatic reclosing 1...5 shots
• Lockout function • Circuit breaker control with indication
• Object indication • Lockout function
• Logic control position selector • Object indication
• User-configurable I/Os • Logic control position selector
• Interlocking • User-configurable I/Os
• User-configurable alarm LEDs • Interlocking
• User-configurable alarm LEDs

3I > 50/51 MCS 000

3I > 50/51 MCS 000


I 0> 67N TCS

I 0> 67N TCS


CBCM 0 I
3I 2f> 68
CBCM 0 I
3I~harm R 3I 2f> 68
I> 46
3I~harm R
I> 46
3 49F
3 49F
CBFP 62 3I I0
0 I 79 I0
LO 86 3I

U0 CBFP 62

REX 521 M01 LO 86


U0

Fig. 3 Block diagram of M01 REX 521 M02

Fig. 4 Block diagram of M02

5
Feeder Protection Relay REX 521
1MRS752177-MBG

Features (cont´d) The main difference between the standard • Interlocking


configurations B01/B02 and standard config- • User-configurable alarm LEDs
urations M01/M02 is the directional earth-
fault protection, which is included in the stan-
dard configurations M01 and M02. The dif- 3I> 67 MCS 000
ference between configurations B01 and B02,
TCS1
and likewise between M01 and M02, is the 3I> 50
auto-reclosure function in B02 and M02. CBCM 0 I
I 0> 67N
3I~harm R
Standard configuration H01: 3I 2f> 68
• Three-phase directional overcurrent pro- 3U~harm
tection with two stages I> 46

• Three-phase non-directional overcurrent 3I I0 P


3 49F
protection with one stage
SYNC 25
• Three-phase transformer inrush and motor 3U U
0 Q
start-up current detector 0 I 79

• Directional earth-fault protection with three CBFP */62 f pf E


stages
LO 86
• Phase discontinuity protection for three
phases REX 521 H01

• Three-phase thermal protection for cable Fig. 5 Block diagram of H01


• Synchro-check/voltage-check function with
one stage Note! The standard configuration H01 is
• Supervision function for energizing current available only with the sensor HW version.
input circuit
Standard configuration H02:
• Supervision function for energizing voltage • Three-phase directional overcurrent pro-
input circuit tection with two stages
• Current waveform distortion measurement • Three-phase non-directional overcurrent
• Voltage waveform distortion measurement protection with two stages
• Three-phase current measurement • Three-phase transformer inrush and motor
start-up current detector
• Neutral current measurement
• Directional earth-fault protection with three
• Three phase-to-earth voltage measure- stages
ments
• Underfrequency or overfrequency protec-
• Residual voltage measurement tion with one stage
• System frequency measurement • Phase discontinuity protection for three
• Three-phase power and energy measure- phases
ment • Three-phase thermal protection for cables
• Calculation of the accumulated electric • Supervision function for energizing current
breaker wear of the circuit breaker (CB) input circuit
• Transient disturbance recorder • Supervision function for energizing voltage
• Trip-circuit supervision input circuit
• Delayed trip output for the circuit-breaker • Current waveform distortion measurement
failure protection (CBFP) function • Voltage waveform distortion measurement
• Automatic reclosing 1...5 shots • Three-phase current measurement
• Circuit breaker control with indication • Neutral current measurement
• Lockout function • Three phase voltage measurements
• Object indication • Residual voltage measurement
• Logic control position selector • System frequency measurement
• User-configurable I/Os
6
Feeder Protection Relay REX 521
1MRS752177-MBG

Features (cont´d) • Three-phase power and energy measure- • Synchro-check/voltage-check function with
ment one stage
• Calculation of the accumulated electric • Supervision function for energizing current
breaker wear of the circuit breaker (CB) input circuit
• Transient disturbance recorder • Supervision function for energizing voltage
input circuit
• Trip-circuit supervision
• Current waveform distortion measurement
• Delayed trip output for the circuit-breaker
failure protection (CBFP) function • Voltage waveform distortion measurement
• Automatic reclosing 1...5 shots • Three-phase current measurement
• Circuit breaker control with indication • Neutral current measurement
• Lockout function • Three phase voltage measurements
• Object indication • Residual voltage measurement
• Logic control position selector • System frequency measurement
• User-configurable I/Os • Three-phase power and energy measure-
ment
• Interlocking
• Calculation of the accumulated electric
• User-configurable alarm LEDs
breaker wear of the circuit breaker (CB)
• Transient disturbance recorder
3I> 67 MCS1 000
• Trip-circuit supervision
TCS
3I > 50/51 • Delayed trip output for the circuit-breaker
CBCM 0 I failure protection (CBFP) function
I0 > 67N
3I~harm R • Automatic reclosing 1...5 shots
f</f> 81U/81O
3U~harm • Circuit breaker control with indication
3I2f> 68
• Lockout function
I> 46
• Object indication
3 49F I0
3I P • Logic control position selectorUser-config-
urable I/Os
0 I 79
3U U0 Q • Interlocking
CBFP */62
• User-configurable alarm LEDs
LO 86
f pf E
REX 521 H02
3I > 50/51 MCS 000

Fig. 6 Block diagram of H02 TCS


I0 > 67N
CBCM 0 I
Standard configuration H03: 3I 2f> 68
• Three-phase non-directional overcurrent 3I~harm R
I> 46
protection with three stages
3U~harm
• Three-phase transformer inrush and motor 3 49F

start-up current detector 3I I0 P


SYNC 25
• Directional earth-fault protection with three
stages 0 I 79
3U U0 Q
• Phase discontinuity protection for three CBFP */62
phases
LO 86 f pf E
• Three-phase thermal protection for cable REX 521 H03

Fig. 7 Block diagram of H03

7
Feeder Protection Relay REX 521
1MRS752177-MBG

Features (cont´d) Standard configuration H04:


• Three-phase non-directional overcurrent
3I > 50/51 MCS 000
protection with three stages
3I> 67 TCS1
• Three-phase directional overcurrent pro-
tection with one stage I0 >
CBCM 0 I
67N
• Underfrequency or overfrequency protec- 3I~harm R
I0 > 50N/51N
tion with one stage
3U~harm
• Three-phase transformer inrush and motor f</f> 81U/81O
start-up current detector 3I2f> 68
• Directional earth-fault protection with three
I> 46
stages
• Non-directional earth-fault protection with 3 49F 3I I P
0
three stages
0 I 79
• Phase discontinuity protection for three 3U U0 Q
phases CBFP */62

• Three-phase thermal protection for cable LO 86 f pf E

• Supervision function for energizing current REX 521 H04


input circuit
Fig. 8 Block diagram of H04
• Supervision function for energizing voltage
input circuit
Standard configuration H05:
• Current waveform distortion measurement • Three-phase non-directional overcurrent
• Voltage waveform distortion measurement protection with three stages

• Three-phase current measurement • Non-directional earth-fault protection with


three stages
• Neutral current measurement
• Three-phase overvoltage protection with
• Three phase voltage measurements two stages
• Residual voltage measurement • Three-phase undervoltage protection with
• System frequency measurement two stages
• Three-phase power and energy measure- • Residual overvoltage protection with three
ment stages
• Calculation of the accumulated electric • Three-phase transformer inrush and motor
breaker wear of the circuit breaker (CB) start-up current detector
• Transient disturbance recorder • Three-phase thermal overload protection
for devices
• Trip-circuit supervision
• Supervision function for energizing current
• Delayed trip output for the circuit-breaker input circuit
failure protection (CBFP) function
• Supervision function for energizing voltage
• Automatic reclosing 1...5 shots input circuit
• Circuit breaker control with indication • Current waveform distortion measurement
• Lockout function • Voltage waveform distortion measurement
• Object indication • Three-phase current measurement
• Logic control position selector • Neutral current measurement
• User-configurable I/Os • Three phase voltage measurements
• Interlocking • Residual voltage measurement
• User-configurable alarm LEDs • System frequency measurement
• Three-phase power and energy measure-
ment

8
Feeder Protection Relay REX 521
1MRS752177-MBG

Features (cont´d) • Calculation of the accumulated electric • Supervision function for energizing current
breaker wear of the circuit breaker (CB) input circuit
• Transient disturbance recorder • Supervision function for energizing voltage
input circuit
• Trip-circuit supervision
• Current waveform distortion measurement
• Delayed trip output for the circuit-breaker
failure protection (CBFP) function • Voltage waveform distortion measurement
• Circuit breaker control with indication • Three-phase current measurement
• Lockout function • Neutral current measurement
• Object indication • Three phase voltage measurements
• Logic control position selector • Residual voltage measurement
• User-configurable I/Os • System frequency measurement
• Interlocking • Three-phase power and energy measure-
ment
• User-configurable alarm LEDs
• Calculation of the accumulated electric
breaker wear of the circuit breaker (CB)
3I > 50/51 MCS 000
• Transient disturbance recorder
TCS
I 0> 50N/51N • Trip-circuit supervision
CBCM 0 I
3I2f 68 • Delayed trip output for the circuit-breaker
3I~harm R failure protection (CBFP) function
U 0> 59N
3U~harm • Circuit breaker control with indication
3U> 59
• Lockout function
3I I0 P
3U< 27 • Object indication
CBFP */62 • Logic control position selector
3U U0 Q
LO 86 • User-configurable I/Os
• Interlocking
3 49 f pf E
• User-configurable alarm LEDs

Fig. 9 Block diagram of H05 3I > 50/51 MCS 000

TCS
U 0> 59N
Standard configuration H06:
CBCM 0 I
• Three-phase non-directional overcurrent 3U> 59
protection with two stages 3I~harm R
3U< 27
• Three-phase overvoltage protection with 3U~harm
two stages f</f> 81U/81O
• Three-phase undervoltage protection with 3I I0 P
CBFP 62
two stages
• Residual overvoltage protection with three LO 86 U0
3U Q
stages
• Underfrequency or overfrequency protec- f pf E
tion with two stages REX 521 H06

Fig. 10 Block diagram of H06

9
Feeder Protection Relay REX 521
1MRS752177-MBG

Features (cont´d) Standard configuration H07: • Logic control position selector


• Three-phase non-directional overcurrent • User-configurable I/Os
protection with three stages
• Interlocking
• Non-directional earth-fault protection with
two stages • User-configurable alarm LEDs

• Directional earth-fault protection with two


stages 3I> 50/51 MCS 000

• Three-phase overvoltage protection with TCS


I0> 67N
two stages
CBCM 0 I
I0>
• Three-phase undervoltage protection with 50N/51N

two stages 3U> 59


3I~harm R

• Underfrequency or overfrequency protec- 3U~harm


3U< 27
tion with one stage
3I I0 P
f</f> 81U/81O
• Negative phase sequence (NPS) protec-
tion with two stages Is2t,n< 48,14,66
U0
• Three-phase motor start-up supervision 3I
3U Q
3I 46R
• Three-phase thermal overload protection
for devices I2> 46 f pf E

• Phase reversal protection 3I< 37

• Phase sequence voltage protection F


60

• Fuse failure protection 3 49

• Three-phase non-directional undercurrent U1<


U2> 27,47,59
protection with one stage U1>

• Supervision function for energizing current CBFP */62


input circuit
LO 86
• Supervision function for energizing voltage
input circuit Fig. 11 Block diagram of H07
• Current waveform distortion measurement
• Voltage waveform distortion measurement Standard configuration H08:
• Three-phase non-directional overcurrent
• Three-phase current measurement
protection with three stages
• Neutral current measurement
• Non-directional earth-fault protection with
• Three-phase voltage measurements three stages
• Residual voltage measurement • Three-phase overvoltage protection with
two stages
• System frequency measurement
• Three-phase undervoltage protection with
• Three-phase power and energy measure-
two stages
ment
• Residual overvoltage protection with three
• Calculation of the accumulated electric
stages
breaker wear of the circuit breaker (CB)
• Three-phase transformer inrush and motor
• Transient disturbance recorder
start-up current detector
• Trip-circuit supervision
• Three-phase thermal overload protection
• Delayed trip output for the circuit breaker for devices
failure protection (CBFP) function
• Supervision function for energizing current
• Circuit breaker control with indication input circuit
• Operation time counter • Supervision function for energizing voltage
• Lockout function input circuit

• Object indication • Current waveform distortion measurement


• Voltage waveform distortion measurement
10
Feeder Protection Relay REX 521
1MRS752177-MBG

Features (cont´d) • Three-phase current measurement Standard configuration H09:


• Neutral current measurement • Three-phase non-directional overcurrent
protection with three stages
• Three phase voltage measurements
• Non-directional earth-fault protection with
• Residual voltage measurement three stages
• System frequency measurement • Three-phase overvoltage protection with
• Three-phase power and energy measure- two stages
ment • Three-phase undervoltage protection with
• Calculation of the accumulated electric two stages
breaker wear of the circuit breaker (CB) • Residual overvoltage protection with three
• Transient disturbance recorder stages

• Trip-circuit supervision • Three-phase transformer inrush and motor


start-up current detector
• Delayed trip output for the circuit-breaker
failure protection (CBFP) function • Underfrequency or overfrequency protec-
tion with two stages
• Circuit breaker control with indication
• Supervision function for energizing current
• Lockout function input circuit
• Object indication • Supervision function for energizing voltage
• Logic control position selector input circuit
• User-configurable I/Os • Current waveform distortion measurement

• Interlocking • Voltage waveform distortion measurement

• User-configurable alarm LEDs • Three-phase current measurement


• Automatic reclosing 1...5 shots
3I > 50/51 MCS 000 • Neutral current measurement

I 0> TCS • Three phase voltage measurements


50N/51N
CBCM 0 I • Residual voltage measurement
3I2f 68
3I~harm R • System frequency measurement
U 0> 59N
3U~harm • Three-phase power and energy measure-
3U> 59 ment
3I I0 P • Calculation of the accumulated electric
3U< 27
breaker wear of the circuit breaker (CB)
CBFP */62
3U U0 3U_B • Transient disturbance recorder
LO 86 • Trip-circuit supervision
3 49 Q f pf • Delayed trip output for the circuit-breaker
failure protection (CBFP) function
E • Circuit breaker control with indication
• Lockout function
Fig. 12 Block diagram of H08 • Object indication
• Logic control position selector
Note! The standard configuration H08 is
available only with the voltage transformer • User-configurable I/Os
(VT) HW version.VTs are used to measure • Interlocking
phase-to-earth voltages.
• User-configurable alarm LEDs

11
Feeder Protection Relay REX 521
1MRS752177-MBG

Features (cont´d) • Three-phase current measurement


3I > 50/51 MCS 000 • Neutral current measurement

I 0> 50N/51N
TCS • Three phase voltage measurements
CBCM 0 I • Residual voltage measurement
3I2f 68
3I~harm R • System frequency measurement
U 0> 59N
3U~harm • Three-phase power and energy measure-
3U> 59 ment
3I I0 P • Calculation of the accumulated electric
3U< 27
breaker wear of the circuit breaker (CB)
CBFP */62
3U U0 3U_B • Transient disturbance recorder
LO 86 • Trip-circuit supervision
f</f> 81U/81O Q f pf • Delayed trip output for the circuit-breaker
failure protection (CBFP) function
0 I 79
E • Automatic reclosing 1...5 shots
• Circuit breaker control with indication
Fig. 13 Block diagram of H09
• Lockout function
• Object indication
Note! The standard configuration H09 is
available only with the voltage transformer • Logic control position selector
(VT) HW version. VTs are used to measure
phase-to-earth voltages. • User-configurable I/Os
• Interlocking
Standard configuration H50:
• Three-phase non-directional overcurrent • User-configurable alarm LEDs
protection with three stages.
• Three-phase directional overcurrent pro-
3I> 50/51 MCS 000
tection with two stages
I0> 50N/51N TCS
• Directional earth-fault protection with two
stages 3I2f 68
CBCM 0 I

• Non-directional earth-fault protection with 3I~harm R


U0> 59N
two stages 3U~harm
• Three-phase overvoltage protection with 3U> 59

two stages 3U< 27 3I I


0 P

• Three-phase undervoltage protection with


CBFP */62
two stages 3U U Q
0
• Residual overvoltage protection with two LO 86

stages 3I> 67 f pf E
• Three-phase transformer inrush and motor U1<
start-up current detector U2> 27,47,59
U1>

• Underfrequency or overfrequency protec- I0 > 67N


tion with two stages
f</f> 81U/81O
• Phase-sequence voltage protection
O I 79
• Supervision function for energizing current
input circuit
• Supervision function for energizing voltage Fig. 14 Block diagram of H50
input circuit
• Current waveform distortion measurement Note! The standard configuration H50 is
• Voltage waveform distortion measurement
available only with the voltage transformer
(VT).

12
Feeder Protection Relay REX 521
1MRS752177-MBG

Features (cont´d) Standard configuration H51: • Transient disturbance recorder

• Three-phase non-directional overcurrent • Trip-circuit supervision


protection with three stages. • Delayed trip output for the circuit breaker
• Three-phase directional overcurrent pro- failure protection (CBFP) function
tection with one stage. • Circuit breaker control with indication
• Non-directional earth-fault protection with • Operation time counter
two stages
• Lockout function
• Directional earth-fault protection with two
• Object indication
stages
• Logic control position selector
• Three-phase overvoltage protection with
one stage • User-configurable I/Os
• Three-phase undervoltage protection with • Interlocking
one stage
• User-configurable alarm LEDs
• Underfrequency or overfrequency protec-
tion with two stages
3I> 50/51 MCS 000
• Negative phase-sequence (NPS) protec-
tion with one stage I0 > 67N TCS

• Three-phase motor start-up supervision I0>


CBCM 0 I
50N/51N
• Three-phase thermal overload protection 3I~harm R
3U> 59
for devices
3U~harm
• Residual overvoltage protection with one 3U< 27
stage f</f> 81U/81O 3I I P
0
• Phase-sequence voltage protection
Is2t,n< 48,14,66
• Fuse-failure protection 3U U
0 Q
3I
3I 46R
• Three-phase non-directional undercurrent
protection with one stage I2> 46 f pf E
• Supervision function for energizing current U0> 59N
input circuit
F
60
• Supervision function for energizing voltage
input circuit 3 49

• Current waveform distortion measurement U1<


U2> 27,47,59
U1>
• Voltage waveform distortion measurement
CBFP */62
• Three-phase current measurement
LO 86
• Neutral current measurement
3I> 67
• Three-phase voltage measurements
• Residual voltage measurement
Fig. 15 Block diagram of H51
• System frequency measurement
• Three-phase power and energy measure-
ment Note! The standard configuration H51 is
available only with the voltage transformer
• Calculation of the accumulated electric (VT).
breaker wear of the circuit breaker (CB)

13
Feeder Protection Relay REX 521
1MRS752177-MBG

Applications Several standard configurations are available The H03 standard configuration is designed
for the protection relay. Refer to the REX 521 to be used in single busbar systems using one
“Technical Reference Manual, Standard Con- circuit-breaker for selective non-directional
figurations” for more detailed information. short-circuit protection, non-directional time-
overcurrent protection, directional earth-fault
The B01 standard configuration for REX 521 protection and automatic reclosing with syn-
is designed to be used in single busbar sys- cro- and voltage-check functionality.
tems using one circuit breaker for selective
short-circuit, time overcurrent and earth-fault The H04 standard configuration is designed
protection of radial isolated neutral networks, to be used in single busbar systems using one
solidly earthed networks, resistant earthed circuit-breaker for selective non-directional
networks and resonant earthed networks. short-circuit protection, non-directional time-
overcurrent protection, directional and non-
The B02 standard configuration is designed directional earth-fault protection and auto-
to be used in single busbar systems using one matic reclosing.
circuit-breaker for selective short-circuit pro-
tection, time-overcurrent protection, earth- The H05 standard configuration is designed
fault protection and automatic reclosing. The to be used in single busbar systems using one
configuration can be used in different types of circuit-breaker for selective non-directional
networks such as radial isolated neutral net- short-circuit protection, non-directional time-
works, solidly earthed networks, resistant overcurrent protection, non-directional earth-
earthed networks and resonant earthed net- fault protection, overvoltage protection, und-
works. ervoltage protection, residual overvoltage
protection and thermal overload protection
The M01 standard configuration is designed for devices.
to be used in single busbar systems using one
circuit-breaker for selective short-circuit, The H06 standard configuration is designed
time overcurrent and directional earth-fault to be used in single busbar systems using one
protection of radial isolated neutral networks, circuit-breaker for selective non-directional
solidly earthed networks, resistant earthed short-circuit protection, non-directional time-
networks and resonant earthed networks. overcurrent protection, overvoltage protec-
tion, undervoltage protection, residual over-
The M02 standard configuration is designed voltage protection, underfrequency protection
to be used in single busbar systems using one and overfrequency protection.
circuit-breaker for selective short-circuit pro-
tection, time-overcurrent protection, direc- The H07 standard configuration is designed
tional earth-fault protection and automatic for protection of large or medium-size three-
reclosing. The configuration can be used in phase AC motors in circuit-breaker controlled
different types of networks such as of radial motor drives. Due to the large number of pro-
isolated neutral networks, solidly earthed net- tective functions integrated, the relay pro-
works, resistant earthed networks and reso- vides a complete protection against motor
nant earthed networks. damage caused by electrical faults. The H07
configuration can also be applied to other
The H01 standard configuration is designed objects needing thermal overload protection,
to be used in single busbar systems using one such as power transformers. It can also be
circuit-breaker for selective directional and used in applications requiring overcurrent
non-directional short-circuit protection, protection, under or overvoltage protection
directional time-overcurrent protection, and/or directional or non-directional earth-
directional earth-fault protection and auto- fault protection.
matic reclosing with syncro- and voltage-
check functionality. The H08 standard configuration is designed
to be used in single busbar systems using one
The H02 standard configuration is designed circuit-breaker for selective non-directional
to be used in single busbar systems using one short-circuit protection, non-directional time-
circuit-breaker for selective directional and overcurrent protection, non-directional earth-
non-directional short-circuit protection, fault protection, overvoltage protection, und-
directional and non-directional time-overcur- ervoltage protection, residual overvoltage
rent protection, directional earth-fault protec- protection and thermal overload protection
tion and automatic reclosing. for devices. The protection is based on phase-

14
Feeder Protection Relay REX 521
1MRS752177-MBG

Applications (cont´d) to-earth voltages. In addition, phase-to-phase protection, undervoltage protection, residual
voltages are available in the measurement overvoltage protection, underfrequency pro-
view. tection, over-frequency protection and auto-
matic reclosing.
The H09 standard configuration for REX 521
is designed to be used in single busbar sys- The H51 standard configuration for REX 521
tems using one circuit breaker for selective is designed for protection of large or medium-
non-directional short-circuit protection, non- size three-phase AC motors in circuit breaker
directional time-overcurrent protection, non- controlled motor drives. Due to the large
directional earth-fault protection, overvolt- number of protective functions integrated, the
age protection, undervoltage protection, relay provides a complete protection against
residual overvoltage protection, underfre- motor damage caused by electrical faults.
quency protection, overfrequency protection
and automatic reclosing. The H51 configuration can be applied to
other objects that need the thermal overload
The H50 standard configuration for REX 521 protection (such as power transformers). It
is designed to be used in single busbar sys- can also be used in applications requiring
tems by using one circuit breaker for selective overcurrent protection, directional overcur-
non-directional short-circuit protection, rent protection, under/overvoltage protec-
directional and non-directional time-overcur- tion, directional or non-directional earth-fault
rent protection, directional and/or non-direc- protection, underfrequency protection and/or
tional earth-fault protection, overvoltage overfrequency protection.

15
Feeder Protection Relay REX 521
1MRS752177-MBG

Design, hardware Different hardware versions of REX 521 are


shown in the table below.

Table 1: REX 521 hardware versions


Relay type REX 521
Version name Basic Medium High Sensor

REX521xMxxx
REX521xBxxx

REX521xHxxx

REX521xSxxx
Transformer modules (MIM) 1 1 1 1

Transformers
• Current transformers 1/5 A 4 4 4 1
• Current transformers 0.2/1 A 1 1 1
• Voltage transformers 100 V 1 4 1
Sensor channels
• Current sensor inputs 3
• Voltage sensor inputs 3
Main CPU modules 1 1 1 1

CPU_SP (SPA/ IEC plastic)


CPU_SG (SPA/ IEC glass)
CPU_LP (SPA/ IEC/ LON plastic)
CPU_LG (SPA/ IEC/ LON glass)
Power supply modules 1 1 1 1

PS_87H (DItresh.=80 VDC)


PS_87L (DItresh.=18 VDC)
Display module 1 1 1 1

6 x 16 character display
Digital inputs 9

High-speed power outputs 1

Power outputs (PO) 3

Signalling outputs (SO) 2

IRF outputs 1

Trip-circuit supervision (TCS) 1

16
Feeder Protection Relay REX 521
1MRS752177-MBG

Design, software Functionality is available as part of the stan- Functions available for use in the different
dard configurations B01, B02, M01, M02, standard configurations are listed below.
H01, H02, H03, H04, H05, H06, H07, H08,
H09, H50 and H51.

Table 2: Standard configurations for REX 521


HW versions Basic Medium High/Sensor

Standard configurations B01 B02 M01 M02 H011 H02 H03 H04 H05 H06 H07 H0823 H0923 H502 H512

ANSI
IEC FB name
device
symbol (CD-ROM)
number
Protection
3I> 51-1 NOC3Low x x x x x x x x x x x x x x
3I>> 51-2 NOC3High x x x x x x x x x x x x x x
3I>>> 51-3 NOC3Inst x x x x x x x x x x x x x
Io> 51N-1 NEF1Low x x x4 x x x x x x
Io>> 51N-2 NEF1High x x x4 x x x x x x
Io>>> 51N-3 NEF1Inst x x x4 x x x
Io>-->5 67N-1 DEF2Low x x x x x x x x x
Io>>-->5 67N-2 DEF2High x x x x x x x x x
Io>>>-->5 67N-3 DEF2Inst x x x x x x
3I>--> 67-1 DOC6Low x x6 x x
3I>>--> 67-2 DOC6High x x6 x x
3U> 59-1 OV3Low x x x x x x x
3U>> 59-2 OV3High x x x x x x
3U< 27-1 UV3Low x x x x x x x
3U<< 27-2 UV3High x x x x x x
3I2f> 68 Inrush3 x x x x x x x x x x x x
Iub> 46 CUB3Low x x x x x x x x
3Ith> 49F TOL3Cab x x x x x x x x
O-->I 79 AR5Func x x x x x x x x
Uo> 59N-1 ROV1Low x x x x x x
Uo>> 59N-2 ROV1High x x x x x
Uo>>> 59N-3 ROV1Inst x x x x
f1 81-1 Freq1St1 x x x x x x x
f2 81-2 Freq1St2 x x x x
SYNC1 25-1 SCVCSt1 x x
Is2t n< 48 MotStart x x
3I() 46R PREV3 x x
I2> 46-1 NPS3Low x x
I2>> 46-2 NPS3High x
3I< 37-1 NUC3St1 x
FUSEF 60 FuseFail x x
3Ithdev> 49M/G/T Tol3Dev x x x x
U1U2<>_1 47-1 PSV3St1 x x x
Control functions
I<->O CB1 COCB1 COCB1 x x x x x x x x x x x x x x x
I<->O IND1 COIND1 COIND1 x x x x x x x x x x x x x x x
I<->O IND2 COIND2 COIND2 x x x x x x x x x x x x x x x
17
Feeder Protection Relay REX 521
1MRS752177-MBG

Table 2: Standard configurations for REX 521 (continued)


HW versions Basic Medium High/Sensor

Standard configurations B01 B02 M01 M02 H011 H02 H03 H04 H05 H06 H07 H0823 H0923 H502 H512

ANSI
IEC FB name
device
symbol (CD-ROM)
number
I<->O IND3 COIND3 COIND3 x7 x7
I<->O POS COLOCAT COLOCAT x x x x x x x x x x x x x x x
ALARM1-8 ALARM1-8 MMIALAR1-8 x x x x x x x x x x x x x x x
Measurement
3I 3I MECU3A x x x x x x x x x x x x x x x
Io Io MECU1A x x x x x x x x x x x x x x x
Uo Uo MEVO1A x x x x x x x x x x x x x
DREC DREC MEDREC x x x x x x x x x x x x x x x
3U 3U MEVO3A x x x x x x x x x x x
3U_B 3U_B MEVO3B x x
f f MEFR1 x x x x x x x x x x x
PQE PQE MEPE7 x x x x x x x x x x x
AI1 AI1 MEAI1 x x
Condition monitoring
CB wear1 CB wear1 CMBWEAR1 x x x x x x x x x x x x x x x
TCS1 TCS1 CMTCS1 x x x x x x x x x x x x x x x
MCS 3I MCS 3I CMCU3 x x x x x x x x x x x x x x x
MCS 3U MCS 3U CMVO3 x x x x x x x x x x x
TIME1 TIME1 CMTIME1 x x
Power quality monitoring
PQ 3Inf PQ 3Inf PQCU3H x x x x x x x x x x x x x x x
PQ 3Unf PQ 3Unf PQVO3H x x x x x x x x x x x
Standard
SWGRP SWGRP SWGRP x x x x x x x x x x x x x x x
1
H01 available only as sensor version
2
Available only as VT version
3
VTs are used to measure phase-to-earth voltages, calculated phase-to-phase voltages are shown by 3U_B
4Configured fixedly to the Io (1/5 A) channel or Ios if selected
5
Can be used as Io>, Io>> and Io>>> or Uo>, Uo>> and Uo>>> function block with some limitations
6
3I>-> and 3I>>-> cannot be set to operate as 3I>, 3I>> or 3I>>>
7
Motor status indication

Note: Calculated Uo (Uos) is used in the Sen- For more information, see REX 521 Techni-
sor versions of H01 and H03 configurations. cal Reference Manual, Standard Configura-
Calculated Io (Ios) is available in H01-H05, tions.
H08, H09 and H50 configurations.

18
Feeder Protection Relay REX 521
1MRS752177-MBG

Technical data
Table 3: Energizing inputs
Rated frequency 50.0/60.0 Hz
Current inputs rated current 0,2 A/1 A/5 A
Thermal withstand continuously 1.5 A/4 A/20 A
capability for 1 s 20 A/100 A/500 A
dynamic current withstand, half-wave value 50 A/250 A/1250 A
input impedance <750 mΩ/<100mΩ/
<20 mΩ
Voltage inputs rated voltage 100 V/110 V/115
V/120 V (parametri-
zation)
voltage withstand, continuous 2 x Un (240 V)
burden at rated voltage <0.5 VA
Sensor inputs voltage range RMS 9.4 V RMS
voltage range peak ± 12 V
input impedance >4.7 MΩ
input capacitance <1 nF

Table 4: Auxiliary power supplies


Type PS_87H PS_87L
(REX521xxHxx) (REX521xxLxx)
Input voltage, AC 110/120/220/240 V -
Input voltage, DC 110/125/220 V 24/48/60 V
Voltage variation AC 85…110%, DC DC 80…120%
80…120% of rated value of rated value
Burden <20 W
Ripple in DC auxiliary voltage max. 12% of the rated DC value (IEC 60255-11)
Interruption time in auxiliary DC <40 ms, 110 V <15 ms, 24 V
voltage without resetting <100 ms, 200 V <50 ms, 48 V
Interruption time in auxiliary DC <40 ms, 110 V <15 ms, 24 V
voltage without resetting <100 ms, 200 V <50 ms, 48 V
Internal overtemperature +78°C (+75…+83°C)
indication

19
Feeder Protection Relay REX 521
1MRS752177-MBG

Technical data (cont´d)


Table 5: Digital inputs
Type PS_87H PS_87L
(REX521xxHxx) (REX521xxLxx)
Operating range, DC 80…265 V DC 18...265 V
(for DI9 18...265 V)
Input voltage, DC 110/125/220 V 24/48/60/110/125/
(for DI9 also 220 V
24/48/60 V)
Current drain ~2…25 mA
Power consumption/input <0.8 W

Table 6: Signal outputs


Max system voltage 250 V AC/DC
Continuous carry 5A
Make and carry for 0.5 s 10 A
Make and carry for 3 s 8A
Breaking capacity when control circuit time- 1 A/0.25 A/0.15 A
constant L/R <40 ms, at 48/110/220 V DC

Table 7: Power outputs


Max system voltage 250 V AC/DC
Continuous carry 5A
Make and carry for 0.5 s 30 A
Make and carry for 3 s 15 A
Breaking capacity when control circuit time 5 A/3 A/1 A
constant L/R <40 ms, at 48/110/220 V DC
Minimum contact load 100 mA, 24 V AC/DC (2.4 VA)
TCS (Trip-circuit Control voltage 20…265 V AC/DC
supervision) range
Current drain approx. 1.5 mA (0.99…1.72 mA)
through the supervi-
sion circuit
Minimum voltage 20 V AC/DC (15…20 V)
(threshold) over a
contact

20
Feeder Protection Relay REX 521
1MRS752177-MBG

Technical data (cont´d)


Table 8: Environmental conditions
Specified service temperature range -10…+55°C
Transport and storage temperature range -40…+70°C
Enclosure class Front side, flush-mounted IP 54
Rear side, connection terminals IP 20
Dry heat test according to IEC 60068-2-2
Dry cold test according to IEC 60068-2-1
Damp heat test, cyclic according to
IEC 60068-2-30,
r.h. >93%, T = 25…55°C
Storage temperature tests according to
IEC 60068-2-48

Table 9: Standard tests


Insulation tests Dielectric test Test voltage 2 kV, 50 Hz, 1 min.
IEC 60255-5
Impulse voltage test Test voltage 5 kV, unipolar impulses,
IEC 60255-5 waveform 1,2/50 µs, source
energy 0.5 J
Insulation resis- Insulation > 100 MΩ, 500 V DC
tance measure- resistance
ments
IEC 60255-5
Mechanical tests Vibration tests (sinusoidal) IEC 60255-21-1, class I
Shock and bump test IEC 60255-21-2, class I
Seismic test IEC 60255-21-3, class 2

21
Feeder Protection Relay REX 521
1MRS752177-MBG

Technical data (cont´d)


Table 10: Electromagnetic compatibility tests
The EMC immunity test level fulfills the requirements listed below
1 MHz burst distur- common mode 2.5 kV
bance test, class III, differential mode 1.0 kV
IEC 60255-22-1
Electrostatic dis- for contact discharge 6 kV
charge test, for air discharge 8 kV
class III
IEC 61000-4-2 and
60255-22-2
Radio frequency conducted, common mode 10 V (rms), f = 150
interference test IEC 61000-4-6, IEC 60255-22-6 kHz…80 MHz
radiated, amplitude-modulated 10 V/m (rms),
IEC 61000-4-3, IEC 60255-22-3 f = 80…1000 MHz
radiated, pulse-modulated 10 V/m, f = 900
ENV 50204, IEC 60255-22-3 MHz
Fast transient dis- power supply 4 kV
turbance test I/O ports 2 kV
IEC 60255-22-4
and IEC 61000-4-4
Surge immunity test power supply 2 kV, common
IEC 61000-4-5 and mode
IEC 60255-22-5 1 kV, differential
mode
I/O ports 2 kV, common
mode
1 kV, differential
mode
Power frequency 100 A/m continuous
(50 Hz) 300 A/m 1 to 3 s
magnetic field
IEC 61000-4-8
Voltage dips and 30%, 10 ms; 60%, 100 ms; 60%, 1000 ms
short interruptions >90%, 5000 ms
IEC 61000-4-11
Electromagnetic conducted RF emission (mains terminal) EN 55011, class A,
emission tests EN 60255-25
EN 55011 and radiated RF emission EN 55011, class A
EN 60255-25 EN 60255-25
CE approval Complies with the EMC directive EN 50263
89/336/EEC and EN 50081-2
the LV directive 73/23/EEC. EN 61000-6-2
EN 60255-6

22
Feeder Protection Relay REX 521
1MRS752177-MBG

Technical data (cont´d)


Table 11: Data communication
Rear interface, Fibre-optic interface
connector X3.2 and X3.3 protocol SPA, IEC_103, Modbus,
DNP 3.0
Also LON in the
REX 521 xxxxL versions.
Using SPA-ZC 402 SPA/Ethernet adapter:
protocols IEC 61850 and SPA TCP/IP
Rear interface, RS-485 connection
connector X3.1:9,10 protocols SPA, Modbus, DNP 3.0
Using SPA-ZC 302 Profibus-DPV1/SPA Gateway:
protocol Profibus
Front panel optical RS 232 connection
protocol SPA
communication cable 1MCK 950001-2
SPA protocol baud rates 4.8/9.6/19.2 kbps
start bits 1
data bits 7
parity even
stop bits 1
IEC_103 protocol baud rates 9.6/19.2 kbps
data bits 8
parity even
stop bits 1
Modbus protocol baud rates 0.6/1.2/2.4/4.8/9.6/19.2 kbps
data bits 7/8 (ASCII/RTU)
parity no parity/odd/even
stop bits 1/2
Modbus modes ASCII, RTU
DNP 3.0 protocol baud rates 0.3/0.6/1.2/2.4/4.8/9.6/19.2
kbps
data bits 8
parity no parity/odd/even
stop bits 1/2
LON protocol bit rates 78.0 kbps/1.25 Mbps

23
Feeder Protection Relay REX 521
1MRS752177-MBG

Technical data (cont´d)


Table 12: General
Toolboxes CAP 501, CAP 505, LIB 510, SMS 510
110 All events are recorded in higher level syn-
tax: reason, time, date are in clear text for-
mat in the selected language. The last 50
events are recorded.
Data recording Records operate values
Protection functions See REX 521 Technical Reference Manual,
Standard Configurations (see “Refer-
ences” on page 32).
Control functions See REX 521 Technical Reference Manual,
Standard Configurations (see “Refer-
ences” on page 32).
Condition monitoring functions See REX 521 Technical Reference Manual,
Standard Configurations (see “Refer-
ences” on page 32).
Measurement functions See REX 521 Technical Reference Manual,
Standard Configurations (see “Refer-
ences” on page 32).
Self-supervision See REX 521 Technical Reference Manual,
General (see “References” on page 32).
Mechanical dimensions Width: 148.8 mm (1/3 of a 19” rack)
Height, frame: 265.9 mm (6U)
Height, box: 249.8 mm
Depth: 235 mm
For dimension drawings, refer to Installa-
tion Manual (see “References” on
page 32).
Weight of the unit <5 kg

24
Feeder Protection Relay REX 521
1MRS752177-MBG

Terminal diagram of the REX 521: Basic

L1 L3
A
0 -
+
Q0
N

*) - I
X4.1
+
ACFail Mains 1
X1.1
2
TempAlarm -

L1 L3
P1 S1 5
IRF 4

S2 3
P2 8
7
S1

SO1 6
12 1A
CT4
S2 11 5A I0 10
10 11
9
8
1A
5A CT3 IL3
7 SO2 9
6 1A
CT2 12
5 5A IL2
13
4
3
2
1A
5A
CT1 IL1
1 PO1
14
15

PO2
17
18 +

PO3

X4.2
4
3
2 **)

HSPO1

X4.2 TCS1 1 +
5 DI1
- 6
7 X3.2
DI2 SERIAL BUS

8 DI3
9
10 X3.3
DI4

11 DI5
12
13
14 DI6

15 DI7
16
17
18 DI8

X3.1
1
DI9
2

9 DATA A
RS-485
DATA B
10
*) Power flow direction
**) The jumper is not assembled by default when
the protection relay is delivered

A051916

25
Feeder Protection Relay REX 521
1MRS752177-MBG

Terminal diagram of the REX 521: Medium

L1 L3
A
0 -
+
Q0
N

*) - I
da dn X4.1
+
ACFail Mains 1
X1.1
Source 2
TempAlarm -

L1 L3
P1 S1 5
IRF 4

S2 3
18
P2 100V
VT1 U0 8
16 7
S1 15 0,2A
CT5
14 1A I0B
13
SO1 6
12 1A
CT4
S2 11 5A I0 10
10 11
9
8
1A
5A CT3 IL3
7 SO2 9
6 1A
CT2 12
5 5A IL2
13
4
3
2
1A
5A
CT1 IL1
1 PO1
14
15

PO2
17
18 +

PO3

X4.2
4
3
2
**)

HSPO1

X4.2 TCS1 1 +
5 DI1
- 6
7 X3.2
DI2 SERIAL BUS

8 DI3
9
10 X3.3
DI4 SERIAL BUS

11 DI5
12
13
14 DI6

15 DI7
16
17
18 DI8

X3.1
1
DI9
2

9 DATA A
RS-485
DATA B
10

*) Power flow direction


**) The jumper is not assembled by default
when the protection relay is delivered

A051917

26
Feeder Protection Relay REX 521
1MRS752177-MBG

Terminal diagram of the REX 521: High, excluding H08 and H09

L1 L3
A
0 -
+
Q0
N
n

*) - I
a
da dn X4.1
+
ACFail Mains 1
X1.1
27 VT4 U31**) 2
100V TempAlarm -
25
L1 L3 24 VT3
P1 S1 100V U23 5
22 IRF 4
21 VT2
100V U12
S2 19 3
P2 18
100V
VT1 U0 8
16 7
S1 15 0,2A
CT5
14 1A I0B
13
SO1 6
12 1A
CT4
S2 11 5A I0 10
10 11
9
8
1A
5A CT3 IL3
7 SO2 9
6 1A
CT2 12
5 5A IL2
13
4
3
2
1A
5A
CT1 IL1
1 PO1
14
15

PO2
17
18 +

PO3

X4.2
4
3
***)
2

HSPO1

X4.2 TCS1 1 +
5 DI1
- 6
7 X3.2
DI2 SERIAL BUS

8 DI3
9
10 X3.3
DI4 SERIAL BUS

11 DI5
12
13
14 DI6

15 DI7
16
17
18 DI8

X3.1
1
DI9
2

9 DATA A
RS-485
10 DATA B

*) Power flow direction


**) Connected to U12b in H03
***) The jumper is not assembled by default
when the protection relay is delivered

A051918

27
Feeder Protection Relay REX 521
1MRS752177-MBG

Terminal diagram of the REX 521: High, H08 and H09

L1 L3
A
0 -
+
Q0
N
n

*) - I
a
da dn X4.1
+
ACFail Mains 1
X1.1
27 VT4 U3 2
100V TempAlarm -
25
L1 L3 24 VT3
P1 S1 100V U2 5
22 IRF 4
21 VT2
100V U1
S2 19 3
P2 18
100V
VT1 U0 8
16 7
S1 15 0,2A
CT5
14 1A I0B
13
SO1 6
12 1A
CT4
S2 11 5A I0 10
10 11
9
8
1A
5A CT3 IL3
7 SO2 9
6 1A
CT2 12
5 5A IL2
13
4
3
2
1A
5A
CT1 IL1
1 PO1
14
15

PO2
17
18 +

PO3

X4.2
4
3
2
**)

HSPO1

X4.2 TCS1 1 +
5 DI1
- 6
7 X3.2
DI2 SERIAL BUS

8 DI3
9
10 X3.3
DI4 SERIAL BUS

11 DI5
12
13
14 DI6

15 DI7
16
17
18 DI8

X3.1
1
DI9
2

9 DATA A
RS-485
10 DATA B

*) Power flow direction


**) The jumper is not assembled by default
when the protection relay is delivered

A051919

28
Feeder Protection Relay REX 521
1MRS752177-MBG

Terminal diagram of the REX 521: Sensor

X4.1
+
ACFail Mains 1
X1.1
27 2
TempAlarm -
25
24
5
22 IRF 4
21

19 3
18 VT1
100V U0 *) 8
16 7
15 0,2A
CT5
14 1A I0B
13
SO1 6
12 1A
CT4
11 5A
I0 10
10 11
9
8
7 SO2 9
6 12
5 13
4
3
2
1 PO1
14
Sensor VD3 15
Voltage input, U3 X2.1
DIFF

X2.2 Sensor VD2 PO2


Voltage input, U2
DIFF
17
Voltage input, U1 Sensor VD1 18
X2.3
DIFF

Sensor RS3
Current input, IL3 X2.4 PO3
DIFF

Sensor RS2
Current input, IL2 X2.5
DIFF

Current input, IL1 Sensor RS1


X2.6
DIFF
X4.2
4
3 **)
2

HSPO1

X4.2 TCS1 1
5 DI1
6
7 X3.2
DI2 SERIAL BUS

8 DI3
9
10 X3.3
DI4 SERIAL BUS

11 DI5
12
13
14 DI6

15 DI7
16
17
18 DI8

X3.1
1
DI9
2

9 DATA A
RS-485
DATA B
10

*) Connected to U12b in H01S and H03S


**) The jumper is not assembled by default
when the protection relay is delivered
A051920

29
Feeder Protection Relay REX 521
1MRS752177-MBG

Ordering infor- When ordering REX 521 protection relays, Each protection relay has a specific order
mation specify the following: number that identifies the protection relay
type as well as the hardware and the software
• order number as described in the figure below. The order
number is labelled on the marking strip on the
• quantity
front panel of the relay delivered, for example,
• additional language Order No: REX521GMHPSM01G..
• optional Chinese front panel (Order No:
1MRS121025)

REX521GMHPSM01G XX

Display language (see the table about display language codes)

Configuration revision
Configuration name: B01, B02, M01, M02, H01, H02, H03, H04, H05,
H06, H07, H08, H09, H50, H51
Rear communication: S=SPA/IEC/Modbus/DNP 3.0
L=SPA/IEC/Modbus/DNP 3.0/LON
Optical connectors for rear communication: P = plastic-fibre
G = glass-fibre
Power supply: H = PS_87H, L = PS_87L
Type of hardware: B = Basic, M = Medium, H = High, S = High sensor
Revision
A051925

English is always available in REX 521. Code Language combination


When ordering, the additional language must
be defined according to the table: FI English-Finnish
SE English-Swedish
DE English-German
ES English-Spanish
FR English-French
PT English-Portuguese
PL English-Polish
ZH English-Chinese

Accessories
Semi-flush mounting kit 1MRS050254
Wall mounting kit 1MRS050240
Rack mounting kits:
Enclosure size (x 19”): Mounting kit order number:
1/2 + 1/3 1MRS050241 and 1MRS050238
1/3 1MRS050258
1/3 + 1/3 1MRS050241 and 1MRS050377
1/3 + 1/3 + 1/4 1MRS050241 (2 pcs) and 1MRS050381
1/4 + 1/4 + 1/3 1MRS050241 (2 pcs) and 1MRS050382
1/3 + 1/4 1MRS050609 and 1MRS050241
Connection cable for front
panel connector 1MKC950001-2

30
Feeder Protection Relay REX 521
1MRS752177-MBG

Ordering information Configuration, setting and SA system • CAP 505 Relay Configuration Tool;
(cont´d) tools CAP 505 v. v.2.4.0 or later
The following tool versions are needed to • LIB 500 Library for MicroSCADA Pro;
support the new functions and features of LIB 500 v.4.2-1 or later
Release Q1/2006 revisions of REX 521:
• LIB 510 Library for MicroSCADA Pro;
• CAP 501 Relay Configuration Tool; LIB 510 v.4.2-1 or later
CAP 501 v.2.4.0 or later
• SMS 510 v.1.3.0 or later

31
Feeder Protection Relay REX 521
1MRS752177-MBG

References Manuals for REX 521

• Installation Manual 1MRS750526-MUM


• Operator’s Manual 1MRS751107-MUM
• Technical Reference manual, General 1MRS751108-MUM
• Technical Reference Manual, Standard Configurations 1MRS751802-MUM
• Technical Descriptions of Functions (CD-ROM v. 2.10 or later) 1MRS750889-MCD
• Modbus Remote Communication Protocol for REX 521,
Technical Description 1MRS755017
• DNP 3.0 Remote Communication Protocol for REF 54_, RET
54_ and REX 521, Technical Description 1MRS755260
Parameter and event lists for REX 521

• Parameter List for REX 521 1MRS751999-RTI


• Event List for REX 521 1MRS752000-RTI
• General Parameters for REX 521 1MRS752156-RTI
• Interoperability List for REX 521 1MRS752157-RTI
Tool-specific manuals

• CAP505 Installation and Commissioning Manual 1MRS751273-MEN


• CAP505 Operator’s Manual 1MRS751709-MUM
• CAP505 Protocol Mapping Tool Operator’s Manual 1MRS755277
• CAP501 Installation and Commissioning Manual 1MRS751270-MEN
• CAP501 Operator’s Manual 1MRS751271-MUM
• Tools for Relays and Terminals, User’s Guide 1MRS752008-MUM

For more information, see:


http://www.abb.com/substationautomation

32
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 Vaasa, FINLAND
Tel +358 10 22 11
Fax +358 10 224 1094
www.abb.com/substationautomation

You might also like