You are on page 1of 188

Cat. No.

H113-E1-1

E5ZN
Temperature Controller

OPERATION MANUAL
E5ZN Temperature Controller
Operation Manual
Produced January 2001
iv
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator
and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed
the information provided with them. Failure to heed precautions can result in injury to people or dam-
age to property.

!DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.

!WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.

!Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury, or property damage.

Visual Aids
The following headings appear in the left column of the manual to help you locate different types of
information.
Note Indicates information of particular interest for efficient and convenient opera-
tion of the product.
1,2,3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc.

Ó OMRON, 2001
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or
by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of
OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is con-
stantly striving to improve its high-quality products, the information contained in this manual is subject to change without
notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility
for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in
this publication.

v
Abbreviations
The following table lists the main abbreviations used in parameters, diagrams, and in the text itself.
Abbreviation Meaning
PV Process value
SP Set point
AT Autotuning
EU Engineering units (See note.)
ch Channel

Note Scaled data is expressed in °C, m, g, and other engineering units. EU is used
as the minimum unit for engineering units For example, the smallest unit of
50.02 (m) is 0.01 (m) and 0.01 is thus one EU.

Parameter Notation
The following table shows the alphabet notation used for parameter abbreviations and settings dis-
played on the E5ZN-SDL Setting Display Unit.
a b c d e f g h i j k l m
A B C D E F G H I J K L M

n o p q r s t u U w x y =
N O P Q R S T U V W X Y Z

vi
TABLE OF CONTENTS
PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiii
1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiv
2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiv
3 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiv

SECTION 1
Outline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1-1 Name and Function of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-2 I/O Configuration and Main Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

SECTION 2
Preparations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2-1 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2-2 Using the I/O Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2-3 Installation Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

SECTION 3
Temperature Control Settings . . . . . . . . . . . . . . . . . . . . . 21
3-1 Setting the Input Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3-2 Selecting °Centigrade/°Farenheit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3-3 Selecting PID Control or ON/OFF Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3-4 Setting Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3-5 Setting the SP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3-6 Executing ON/OFF Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3-7 Determining PID Constants: Autotuning and Manual Setup . . . . . . . . . . . . . . . . . 30
3-8 Alarm Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3-9 Using Heater Burnout Alarm (HBA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3-10 Starting and Stopping Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3-11 Operating Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

SECTION 4
Settings Used Only when Required . . . . . . . . . . . . . . . . . 39
4-1 Shifting Input Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4-2 Alarm Hysteresis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4-3 Setting Scaling Upper and Lower Limits (Analog Input) . . . . . . . . . . . . . . . . . . . . 46
4-4 Executing Heating and Cooling Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4-5 Using the Event Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
4-6 Setting the SP Upper and Lower Limit Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
4-7 SP Ramp Function: Limiting SP Change Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4-8 Key Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
4-9 Manual Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
4-10 Reading Temperatures for Multiple E5ZN Units . . . . . . . . . . . . . . . . . . . . . . . . . . 56
4-11 Remote PV Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

vii
TABLE OF CONTENTS
SECTION 5
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
5-1 Communication Protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
5-2 Data Format Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
5-3 Structure of Command/Response Text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
5-4 Variable Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
5-5 Read from Variable Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
5-6 Write to Variable Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
5-7 Operation Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
5-8 Setting Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
5-9 Commands and Responses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
5-10 Variable Area Map. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85

SECTION 6
Using the E5ZN-SDL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
6-1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
6-2 Names of Parts on the Front Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
6-3 Setup Level Configuration and Front Panel Keys . . . . . . . . . . . . . . . . . . . . . . . . . 102
6-4 Initial Setup Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
6-5 Using Copy Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
6-6 List of Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108

SECTION 7
Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
7-1 Conventions Used in this Chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
7-2 Protect Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
7-3 Operation Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
7-4 Adjustment Level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
7-5 Initial Setting Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
7-6 Advanced Function Setting Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
7-7 Communications Setting Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145

SECTION 8
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
8-1 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
8-2 Communications Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
8-3 Temperature Sensing Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
8-4 Temperature Control Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
8-5 Output Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
8-6 HB Alarm Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155

viii
TABLE OF CONTENTS
Appendices
A Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
B Error Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
C Sensor Input Setting Ranges/Control Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
D ASCII Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165

Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171

ix
x
About this Manual:
This manual describes how to use the E5ZN and includes the sections described below.
Before using your E5ZN, thoroughly read and understand this manual in order to ensure correct use.
Also, store this manual in a safe place so that it can be accessed whenever necessary.

The E5ZN Temperature Controller allows the user to perform the following:
• Control temperature for two channels with one Temperature Controller. The Temperature Controller
can be expanded to control up to 32 channels.
• Use an E5ZN-SDL Setting Display Unit to set the Temperature Controller.
• Input non-contact temperature sensors, analog voltages, thermocouples, or platinum-resistance ther-
mometers.
• Select heating/cooling control in addition to standard control.
• Select autotuning as the tuning function.
• Use multi-SP and a RUN/STOP function with event inputs.
• Use a HBA (heater burnout alarm).
• Use communications.
The E5ZN conforms to UL/CSA/ICE safety standards and EMC standards.

Precautions provides general precautions for using the E5ZN.


Section 1 describes E5ZN features, part names, and main functions.
Section 2 describes mounting, wiring, and other preparatory work that must be done before the E5ZN
can be used.
Section 3 describes the basic settings required by the E5ZN.
Section 4 describes scaling, SP ramp, and other functions to enable maximum use of the E5ZN func-
tions.
Section 5 describes performing communications for the E5ZN.
Section 6 describes how to operate the E5ZN-SDL Setting Display Unit.
Section 7 describes the parameters used to control E5ZN operation.
Section 8 classifies problems by situation and describes the methods for checking any possible mal-
functions.

!WARNING Failure to read and understand the information provided in this manual may result in per-
sonal injury or death, damage to the Temperature Controller, or product failure. Please
read each section in its entirety and be sure you understand the information provided in
the section and related sections before attempting any of the procedures or operations
given.

xi
xii
PRECAUTIONS
This section provides general precautions for using the E5ZN Temperature Controller.

The information contained in this section is important for the safe and reliable application of the Temperature
Controller. You must read this section and understand the information contained before attempting to set up or
operate an Temperature Controller.

1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiv


2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiv
3 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiv

xiii
Intended Audience 1

1 Intended Audience
This manual is intended for the following personnel, who must also have
knowledge of electrical systems (an electrical engineer or the equivalent).
• Personnel in charge of installing automation systems.
• Personnel in charge of designing automation systems.
• Personnel in charge of managing automation systems and facilities.

2 General Precautions
The user must operate the Temperature Controller according to the perfor-
mance specifications described in the operation manuals.
Before using the Temperature Controller under conditions which are not
described in the manual or applying the Temperature Controller to nuclear
control systems, railroad systems, aviation systems, vehicles, combustion
systems, medical equipment, amusement machines, safety equipment, and
other systems, machines, and equipment that may have a serious influence
on lives and property if used improperly, consult your OMRON representative.
Make sure that the ratings and performance characteristics of the Tempera-
ture Controller are sufficient for the systems, machines, and equipment, and
be sure to provide the systems, machines, and equipment with double safety
mechanisms.
This manual provides information for installing and operating OMRON Tem-
perature Controllers. Be sure to read this manual before operation and keep
this manual close at hand for reference during operation.

!WARNING It is extremely important that a Temperature Controller be used for the speci-
fied purpose and under the specified conditions, especially in applications that
can directly or indirectly affect human life. You must consult with your OMRON
representative before applying a Temperature Controller to the above men-
tioned applications.

3 Application Precautions
!WARNING Do not touch the terminals while the power is ON. Doing so may cause an
electric shock.

!WARNING It may be necessary to install a power supply breaker to turn OFF the power
supply before working on the Temperature Controller. Not turning OFF the
power supply may result in electrical shock.

!WARNING Do not allow metal fragments or lead wire scraps to fall inside this Tempera-
ture Controller. These may cause electric shock, fire, or malfunction.

!WARNING Do not use the Temperature Controller in flammable and explosive gas atmo-
spheres. There is danger of explosion.

!WARNING Never disassemble, repair, or modify the Temperature Controller. Doing so


may cause electric shock, fire or malfunction.

!Caution Set all settings according to the control target of the Temperature Controller. If
the settings are not appropriate for the control target, the Temperature Con-
troller may operate in an unexpected manner, resulting in damage to the Tem-
perature Controller or resulting in accidents.

xiv
Application Precautions 3

!Caution Tighten the terminal screws properly. Tighten them to a torque of 0.40 to
0.56 N·m.

!WARNING To maintain safety in the event of a Temperature Controller malfunction,


always take appropriate safety measures, such as installing an alarm on a
separate line to prevent excessive temperature rise. If a malfunction prevents
proper control, a major accident may result.

Observe the following precautions when using the Temperature Controller.


• Use and store the Temperature Controller within the specified tempera-
ture and humidity ranges. If the Temperature Controller is installed incor-
rectly, heat will build up inside, shortening the life of the Temperature
Controller. If heat buildup is a problem, used forced cooling, e.g., install a
cooling fan.
• Do not touch the patterns or components on a board with your bare
hands. Hold it by the case.
• To allow heat to escape, do not block the area around the Temperature
Controller. (Ensure that enough space is left for the heat to escape.) Do
not block the ventilation holes on the casing.
• Use the Temperature Controller within the specified power supply voltage
and rated load ranges.
• Wire properly using the correct terminal polarity.
• Use the specified size of solderless terminals for wiring (M3, width 5.8
mm or less).
• Use the specified wire sizes for wiring. Power supply terminals: AWG22 to
AWG14 (cross-sectional area of 0.326 to 2.081 mm2), Other terminals:
AWG28 to AWG16 (cross-sectional area of 0.081 to 1.309 mm2), Length
of exposed wire: 6 to 8 mm.
• Do not wire unused terminals.
• Make sure that the rated voltage is reached within 2 seconds after the
power supply is turned ON.
• Allow a warmup period of 30 minutes.
• Attach a surge suppressor or noise filter to peripheral devices that gener-
ate noise (in particular, motors, transformers, solenoids, magnetic coils or
other equipment that have an inductance component). When mounting a
noise filter on the power supply, be sure to first check the filter's voltage
and current capacity, and then mount the filter as close as possible to the
E5CN. Allow as much space as possible between the Temperature Con-
troller and devices that generate powerful high-frequency noise (e.g.,
high-frequency welders, high-frequency sewing machines) or surges.
• To reduce induction noise, separate the high-voltage or large-current
power lines from other lines, and avoid parallel or common wiring with the
power lines when you are wiring to the terminals. We recommend using
separating pipes, ducts, or shielded lines.
• Install a switch or circuit breaker in a location easily accessible to the
operator and label it appropriately.
• Do not use this Temperature Controller in the following places:
• Places subject to dust or corrosive gases (in particular, sulfide gas and
ammonia gas)
• Places subject to high humidity, condensation or freezing
• Places subject to direct sunlight
• Places subject to vibration and large shocks
• Places subject to splashing liquid or oily atmosphere

xv
Application Precautions 3

• Places directly subject to heat radiated from heating equipment


• Places subject to intense temperature changes
• Cleaning: Do not use paint thinner or the equivalent. Use standard grade
alcohol to clean the Temperature Controller.
• Install DIN track vertically.
• When mounting the Terminal Unit to the Temperature Controller, make
sure that the hooks on the Temperature Controller are inserted properly
into the Terminal Unit.
• Remove the dust sticker from the Temperature Controller after completing
wiring to enable heat radiation.
• When you draw out the internal mechanism from the housing, never
touch electric components inside or subject the internal mechanism to
shock.

xvi
SECTION 1
Outline

1-1 Name and Function of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2


1-1-1 External Appearance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-1-2 Front Panel Names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-1-3 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1-1-4 Setting Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1-2 I/O Configuration and Main Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1-2-1 I/O Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1-2-2 Main Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

1
Name and Function of Parts Section 1-1

1-1 Name and Function of Parts


1-1-1 External Appearance
• The E5ZN Temperature Controller can be mounted inside another device.
• RS-485 communications is a standard feature with the E5ZN, allowing
monitoring of process values and reading/writing parameters from the
host.
• The Terminal Unit and the Temperature Controller Module can be sepa-
rated, making wiring and maintenance of the E5ZN easier.
• Space and wiring can be reduced by using an Expansion Terminal Unit
when connecting two or more E5ZN Controllers to the same host.
Basic Controller Expansion Controller

Terminal Unit
Front Panel

E5ZN
Controller
Module

1-1-2 Front Panel Names

34 5 Unit number
ユニット番号
F01 2
67

UNIT switch
設定スイッチ
89

AB E
CD

2 3 Baud
通信速度rate
4

BPS switch
9 0 1

設定スイッチ
5 6

78

POWER

ERROR

SD/RD

OUT1 Operation indicators


動作表示LED
(LED)

OUT2

SUB1

SUB2

E5ZN

2
Name and Function of Parts Section 1-1

1-1-3 Display

Operation Display
1,2,3... 1. POWER
Lit when power is ON.
2. ERROR
Flashes when a memory error or an input error to either channel has oc-
curred.
3. SD/RD (send data/receive data)
Flashes during communications with the host computer.
4. OUT1, OUT2 (control output 1, control output 2)
Lit when control output 1 or 2 is ON.
5. SUB1, SUB2 (auxiliary output 1, auxiliary output 2)
Lit when auxiliary outputs 1 or 2 is ON.

1-1-4 Setting Switches


Use the switches to change the communications conditions for communica-
tions with the host computer. Before using the E5ZN, match the settings to the
host.
Operate the switches under the following conditions only.
• The power supply must be turned OFF. The settings will be enabled only
when the power is turned ON again.
• To change the switch setting, use a flat-blade screwdriver and turn the
switch to the required position.

Unit Number A unit number is set for each Temperature Controller to identify the Tempera-
ture Controllers connected to the host and to an E5ZN-SDL Setting Display
Unit.
The unit number is set in hexadecimal.
The switch settings are 0 to F, which correspond to unit numbers 00 to 15.
Setting 0 1 2 3 4 5 6 7 8 9 A B C D E F
Unit No. 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
­ Default
Set a different unit number for each Temperature Controller when more than
one E5ZN Temperature Controller is connected for RS-485 communications.
Communications cannot be performed if the same unit number is used more
than once in one system.

Baud Rate Match the E5ZN Temperature Controller baud rate to the host baud rate.
Setting 0 1 2 3 4 5 6 7 8 9
Baud rate 4800 9600 19200 38400 Do not use these settings.
(bit/s)
­ Default

3
I/O Configuration and Main Functions Section 1-2

1-2 I/O Configuration and Main Functions


1-2-1 I/O Configuration
Control ch1
Controller
Heating Control output
Temperature control output 1
input/ analog input
OR of Alarm 1
and HBA
Aux. output 1
CT input Alarm 2

Alarm 3

Cooling
control output

Control ch2

Heating Control output


Temperature control output
input/ analog input 2

OR of Alarm 1
and HBA
CT input Aux. output 2
Alarm 2

Alarm 3

Cooling
control output
Communica-
tions

Event input
(one)

4
I/O Configuration and Main Functions Section 1-2

1-2-2 Main Functions

Communications Communications according to CompoWay/F (See note.) are supported and


Functions are performed through the RS-485 interface.
Up to 16 E5ZN Temperature Controllers can be operated from the host.
Note CompoWay/F is a general-purpose serial communications-based unified communica-
tions protocol developed by OMRON. CompoWay/F uses commands compatible with
the well-established FINS, together with a unified frame format on OMRON program-
mable Controllers to facilitate communications between personal computers and com-
ponents.

Number of Control One E5ZN Temperature Controller has two channels for controlling tempera-
Points ture.

Input Sensor Types The following input sensors can be connected for temperature input. Both
channels will use the same type of sensor.
Thermocouple: K, J, T, E, L, U, N, R, S, B
Infrared temperature sensor type: ES1A
K (10 to 70°C), K (60 to 120°C), K
(115 to 165°C), K (160 to 260°C)
Platinum resistance thermometer: Pt100, JPt100
Analog input: 0 to 50 mV

Control Output The control output is either a voltage pulse output or a transistor (open-collec-
tor) output, depending on the model of E5ZN.

Alarms • Set the alarm type and alarm value, or set upper- and lower-limit alarms.
• If necessary, a more comprehensive alarm function can be achieved by
setting the “standby sequence,” “alarm hysteresis,” and “close for alarm/
open for alarm,” parameters.

Control Adjustment Optimum PID constants can be set easily by autotuning.

Event Input • The following functions can be achieved using the event input (one input
per Temperature Controller): Set point selection (multi-SP, 2 points max.)
and RUN/STOP.
• The event input is used by both temperature control channels.

HBA A heater burnout alarm (HBA) is supported.

5
I/O Configuration and Main Functions Section 1-2

6
SECTION 2
Preparations

2-1 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2-1-1 External Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2-1-2 Assembling Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2-2 Using the I/O Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2-2-1 Terminal Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2-2-2 Precautions when Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2-2-3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2-3 Installation Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2-3-1 Ensuring Prolonged Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2-3-2 Reducing the Influence of Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2-3-3 Ensuring Precise Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2-3-4 Enclosure Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

7
Installation Section 2-1

2-1 Installation
2-1-1 External Dimensions
(Unit: mm)
The following diagrams show the E5ZN with a Terminal Unit attached.

UNIT UNIT

BPS BPS

POWER POWER

ERROR

72.8
ERROR

130
SD/RD
72.8

SD/RD

130
OUT1 OUT1

OUT2 OUT2

SUB1
SUB1
SUB2
SUB2
E5ZN E5ZN

27
5.2 22.5

4.7
4.7

27 30 35
35 46
46 112
112

E5ZN-SCT24S-500 Terminal Unit E5ZN-SCT18S-500 Terminal Unit


Note: Always use this basic E5ZN-SCT24S-500 Note: Use the Expansion E5ZN-SCT18S-500
Terminal Unit if using only one E5ZN Unit. Terminal Unit for dense mounting with two or more
Units. Use this Terminal Unit for all but the first Unit.

2-1-2 Assembling Units

Joining Terminal Units Up to 15 Expansion E5ZN- SCT18S-500 Terminal Units can be connected to
Together a basic E5ZN-SCT24S-500 Terminal Unit.
Two Terminal Units can be connected by joining the side connector on each
Terminal Unit.

Side
connectors

8
Installation Section 2-1

Attach a connector cover to the rightmost Terminal Unit.

コネクタカバー
Connector cover

Mounting to DIN Track Mounting the Unit


Pull the hook down on the bottom, latch the top hook onto the track, push the
Unit until the hook locks onto the track, and then push the hook back up to
lock the Unit in place.

(2) Latch the top hook


onto the track

(3) Push the Unit into place.

(1) Lower the hook. (4) Lock the Unit in place.

9
Installation Section 2-1

Removing the Unit


Use a flat-blade screwdriver to pull down the hook and lift the Unit from the
bottom.

Flat-blade screwdriver

Mounting End Plates


Always mount end plates to both ends of the E5ZN Temperature Controllers.

up up up
up

For only one For dense mounting of multiple


Temperature Controller Temperature Controllers

10
Installation Section 2-1

Mounting Bracket
Mount the E5ZN Temperature Controller to DIN track. Use screws to attach
the DIN track to the control panel in at least three places.
• PFP-50N (50 cm)/PFP-100N (100 cm) DIN Track

Vertical: OK Horizontal: NG

Position the DIN track vertical to the ground.

Mounting the E5ZN Mounting the Module


Module Line up the Module with the guides on the Terminal Unit and push firmly into
place.

Line up with guides and push firmly until


the Module clicks into place.

IT
UN


BP

WER
PO
R
RO
ER

/R
SD
T1
OU

T2
OU

B1
SU

B2
SU

Removing the Module

Push the hooks on both ends of the


① Module and pull out the Module to
remove it.

IT
UN

② BP

PO
WE

R
RO
ER

/R
SD
T1
OU

T2
OU

B1
SU

B2
SU

11
Installation Section 2-1

Covers When wiring, open the E53-COV12 Terminal Cover attached to the E5ZN-
SCT24S-500 Terminal Unit or the E53-COV13 Terminal Cover attached to the
E5ZN-SCT18S-500 Terminal Unit. When wiring has been completed, close
the cover until it clicks shut.
Both E5ZN-SCT24S-500 Terminal Units and E5ZN-SCT18S-500 Terminal
Units have Terminal Covers.

Terminals Terminals
Covered Exposed

12
Using the I/O Section Section 2-2

2-2 Using the I/O Section


2-2-1 Terminal Arrangement
Refer to the E5ZN-SCT18S-500 for the layout for terminals 1 to 18.
+
19 13 7 1
Input power
supply
24 DC ー 20 14 8 2

21 15 9 3
B(+)
Setting Display Unit
communications
RS-485
A(ー)
22 16 10 4
B(+)
23 17 11 5
Host communications
RS-485
24 18 12 6
A(ー)
E5ZN-SCT24S-500

Voltage-output type Transistor-output type


+ +
13 13 13 7 1 7 1 7 1
12 VDC 12 VDC
Event input OUT1 21 mA OUT2 21 mA OUT1 OUT2
SUB1 14 SUB1 14 14 8 2 8 2 8 2
Contact Non- - -
SUB2 SUB2 input contact
15 15 15 9 3 input ch1 ch2 ch1 ch2
COM COM
+
PNP (sourcing) type NPN (sinking) type -
E5ZN-2@PH03@-FLK E5ZN-2@NH03@-FLK
16 10 4 10 4 10 4 10 4
CT1
- 11 - 5 11 5 - 11 -
CT2 ch1 17 11 5 5
ch2 V V
18 12 6 + 12 + 6 12 6 + 12 + 6
E5ZN-SCT18S-500 ch1 ch2 ch1 ch2 ch1 ch2
Thermocouple/infrared temperature Pt Analog input
sensor

2-2-2 Precautions when Wiring


• Separate signal leads and power lines in order to protect the E5ZN and its
lines from external noise.
• We recommend using solderless terminals when wiring the E5ZN.
• Tighten the terminal screws using a torque between 0.40 and 0.56 N·m.
• Use the following type of solderless terminals for M3 screws.

5.8 mm max.

5.8 mm max.

13
Using the I/O Section Section 2-2

2-2-3 Wiring
The left sides of the terminal numbers in the following diagram are on the out-
side of the Unit and the right sides are on the inside of the Unit.

Power Supply • Connect to terminals 19 and 20, as shown in the following diagram.

+
19
24-DC input
power supply
20

• When reinforced insulation is required, connect the I/O to a device without
an exposed charged section or to a device with basic insulation suitable
for the maximum usage voltage of the I/O section.
• UL/CSA/CE Safety Standards
Use a SELV power supply with an overcurrent protection function.
A SELV power supply refers to a power supply with redundant I/O or with
increased insulation and with an output voltage of 30 Vr.m.s and a 42.4-V
peak or maximum 60 VDC.
Recommended power supply: S8PS-05024 CD (OMRON)

Inputs Connect channel 1 to terminals 10 to 12 and channel 2 to terminals 4 to 6 as


follows, according to the input type:

10 4 10 4 10 4
- 11 - 5 11 5 - 11 - 5
V V
+ 12 + 6 12 6 + 12 + 6
ch1 ch2 ch1 ch2 ch1 ch2
Thermocouple/infrared Pt Analog input
TC/非接触温度センサ
temperature sensor Pt アナログ入力

Note Connect the terminals according to the following instructions to prevent error indicators
being lit for channels not being used.
• For thermocouple, non-contact temperature sensor, or analog input:
Form a short-circuit between terminals 5 and 6 when channel 2 is not used, or between
terminals11 and 12 when channel 1 is not used.
• For Pt:
Connect a resistance of 100 to 125 9 between terminals 4 and 5 when channel 2 is not
used, or between terminals 10 and 11 when channel 1 is not used.
Form a short-circuit between terminals 5 and 6 when channel 2 is not used and between ter-
minals 11 and 12 when channel 1 is not used.

14
Using the I/O Section Section 2-2

Control Output 1/2 • Terminals 7 and 8 are for control output 1 (OUT1) and terminals 1 and 2
are for control output 2 (OUT2).
+V +V
+ +
7 1 7 1
OUT1 OUT2 OUT1 OUT2
ー 8 GND ー 2 GND 8 2

Control
制御出力1 output 1 Control
制御出力2 output 2 Control output 1 Control output 2
制御出力1 制御出力2
Pulse voltage output type Transistor output type
パルス電圧出力タイプ
E5ZN-2Q@H03@-FLK
トランジスタ出力タイプ
E5ZN-2T@H03@-FLK
E5ZN-2Q□H03□-FLK E5ZN-2T□H03□-FLK

• The following table shows the specifications for each output.


Output Specifications
Pulse voltage 12 VDC output voltage ± 15% (PNP)
Max. load current 21mA, with short-circuit protection circuit
Transistor Max. usage voltage 30 VDC, max. load current 100 mA.
Max. residual voltage 1.5 V, max. leakage current 0.4 mA
max.

• The pulse voltage output (control output) is not electrically insulated from
the internal circuits.
When using grounded thermocouples, do not connect any of the control
output terminals to the ground. If the terminals are connected to ground,
unwanted current paths may result in incorrect temperature measure-
ments.

Auxiliary Outputs 1/2 • Terminals 13 and 15 are for auxiliary output 1 (SUB1) and terminals 14
and 15 are for auxiliary output 2 (SUB2.)

13 13

SUB1 14 SUB1 14
SUB2 SUB2
15 15
COM COM
PNP (sourcing) type NPN (sinking) type
PNP(ソース)タイプ
E5ZN-2@PH03@-FLK NPN(シンク)タイプ
E5ZN-2@NH03@-FLK
E5ZN-2□PH03□-FLK E5ZN-2□NH03□-FLK
• The transistor output specifications are given below.
Maximum applicable voltage: 30 VDC, maximum load current: 50 mA.
Maximum residual voltage: 1.5 V, maximum leakage current: 0.4 mA.

CT Input • When the heater burnout alarm is used, connect a current transformer
(CT) across terminals 16 and 17 for channel 1 and terminals 16 and 18 for
channel 2 (no polarity).

16
CT1
CT2 ch1 17
ch2
18

• Use E54-CT1 or E54-CT3 Current Transformers.

15
Using the I/O Section Section 2-2

Event Input • When event input is used, connect to terminals 3 and 9.

+
3

9
-
Contact input Non-contact input
有接点入力 無接点入力

• Use event inputs under the following conditions:


Contact input ON: 1 kW max., OFF: 100kW min.
No-contact input ON: residual voltage of 1.5 V max., OFF: leakage current of
0.1 mA max.

Communications • When communicating with a host, connect across terminals 23 and 24.

B(+) 23

A(ー) 24

• The RS-485 connection can be either one-to-one to one-to-N. Up to 16


Temperature Controllers can be connected in one-to-N systems.
• Keep the total cable length to 500 m maximum.
• Use shielded, twisted-pair cable (with wire sizes of AWG 28 or larger).
Cable

AWG 28 or larger
0.081 mm2 or larger
conductor cross-section

16
Using the I/O Section Section 2-2

• Attach a terminator to both ends of the transmission path, including the


host.
• Use a RS-232C/RS-485 Converter when connecting personal computers
with an RS-232C port.

RS-232C RS-232C/RS-485
Converter

+ -

Terminator 100 to 23 (B) Terminator 100 to


1259 (1/2W) 23 (B) 23 (B) 1259 (1/2W)
24 (A) 24 (A) 24 (A)

E5ZN E5ZN E5ZN


(No 0, 1, 2) (No 3, 4, 5) (No 13, 14, 15)

• When using an E5ZN-SDL Setting Display Unit, connect across terminals


21 and 22. Refer to Section 6 Using the E5ZN-SDL for information on
how to use the Setting Display Unit.

B(+) 21

A(ー) 22

17
Installation Precautions Section 2-3

2-3 Installation Precautions


2-3-1 Ensuring Prolonged Use
Use the Temperature Controller in the following operating environment:
Temperature: -10 to +55°C (with no icing or condensation)
Humidity: 25% to 85%
When the Temperature Controller is incorporated in a control panel, make
sure that the Controller's ambient temperature (not the panel's ambient tem-
perature) does not exceed 55°C.
The life of electronic equipment like Temperature Controllers is influenced not
only by the life determined by the relay switching count but also by the life of
internal electronic components. The service life of components is dependent
on the ambient temperature: The higher the ambient temperature becomes,
the shorter the service life becomes, and vice versa. For this reason, the ser-
vice life of the Temperature Controller can be extended by lowering its internal
temperature.
Mounting Temperature Controllers in any way other than the specified mount-
ing method may cause heat to build up inside the Temperature Controllers,
which will shorten their service life. When mounting Temperature Controllers
like this, forced cooling measures, such as a cooling fan for cooling the Tem-
perature Controllers, must be taken into consideration.
Be sure that the cooling method in not cooling just the terminal block. If only
the terminal block is cooled, measurement errors may occur.

2-3-2 Reducing the Influence of Noise


To reduce inductive noise, the leads on the Temperature Controller's terminal
block must be wired separately from high-voltage/high-current power lines.
Also, avoid wiring lines in parallel with or in the same wiring path as power
lines. Other methods, such as separating conduits and wiring ducts or using
shielded cables, are also effective.
Attach a surge absorber or noise filter to peripheral equipment that generates
noise (in particular, motors, transformers, solenoids, or other equipment that
has a magnetic coil or other inductance component).
When a noise filter is used at the power supply, first check the voltage or cur-
rent, and attach the noise filter as close as possible to the Temperature Con-
troller.
Also, install the Temperature Controller as far away as possible from equip-
ment that generates strong, high frequencies (e.g., high-frequency welders or
high-frequency sewing machines) or surges.

2-3-3 Ensuring Precise Measurements


When the thermocouple leads are extended, be sure to use a compensating
lead wire matched to the type of thermocouple.
When the platinum resistance detector leads are extended, use a lead having
the smallest resistance to equalize the resistance of the three leads.
Mount to DIN track that has been installed vertical to the ground.
If there is a large error in the measurement values, make sure that input com-
pensation has been set correctly.

18
Installation Precautions Section 2-3

2-3-4 Enclosure Ratings


The enclosure ratings are shown in the following table. The E5ZN is not water-
proof.
Temperature Controller IP00
Module
Terminal Units IP00

19
Installation Precautions Section 2-3

20
SECTION 3
Temperature Control Settings
This section describes the basic functions of the E5ZN.

3-1 Setting the Input Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22


3-1-1 Input Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3-2 Selecting Centigrade/Farenheit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3-3 Selecting PID Control or ON/OFF Control . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3-4 Setting Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3-4-1 Control Period. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3-4-2 Direct (Cooling)/Reverse (Heating) Operation. . . . . . . . . . . . . . . . . 25
3-4-3 Output Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3-5 Setting the SP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3-5-1 Changing the SP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3-6 Executing ON/OFF Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3-6-1 ON/OFF Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3-6-2 Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3-7 Determining PID Constants: Autotuning and Manual Setup . . . . . . . . . . . . . 30
3-7-1 Autotuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3-7-2 Manual Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3-8 Alarm Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3-8-1 Alarm Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3-8-2 Alarm Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3-9 Using Heater Burnout Alarm (HBA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3-9-1 HBA Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3-9-2 Operating Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3-9-3 Calculating the Detection Current Value . . . . . . . . . . . . . . . . . . . . . 36
3-10 Starting and Stopping Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3-10-1 Starting Control (RUN)/Stopping Control (STOP) . . . . . . . . . . . . . 37
3-11 Operating Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

21
Setting the Input Type Section 3-1

3-1 Setting the Input Type


Set the input type corresponding to the sensor used. The E5ZN specifications
support two types of inputs, platinum resistance thermometers and thermo-
couples. Refer to the following tables and set the correct value for the temper-
ature range and the sensor used.

3-1-1 Input Type


To set the input type to a K thermocouple from -20.0 to 500.0°C, use host
communications or the E5ZN-SDL Setting Display Unit to set 1 as the set
value for the input type.

List of Input Types


Type Input type Name Set Value Input Temperature Setup Range
Platinum resis- Platinum resis- Pt100 0 -200 to 850 °C or -300 to 1,500 °F
tance thermome- tance thermometer 1 -199.9 to 500.0 °C or -199.9 to 900.0 °F
ter input
2 0.0 to 100.0 °C or 0.0 to 210.0 °F
JPt100 3 -199.9 to 500.0 °C or -199.9 to 900.0 °F
4 0.0 to 100.0 °C or 0.0 to 210.0 °F

Type Input type Name Set Value Input Temperature Setup Range
Thermocouple Thermocouple K 0 -200 to 1,300 °C or -300 to 2,300 °F
input 1 -20.0 to 500.0 °C or 0.0 to 900.0 °F
J 2 -100 to 850 °C or -100 to 1500 °F
3 -20 to 400.0 °C or 0.0 to 750.0 °F
T 4 -200 to 400 °C or -300 to 700 °F
17 -199.9 to 400.0 °C or -199.9 to 700.0 °F
E 5 0 to 600 °C or 0 to 1,100 °F
L 6 -100 to 850 °C or -100 to 1,500 °F
U 7 -200 to 400 °C or -300 to 700 °F
18 -199.9 to 400.0 °C or -199.9 to 700.0 °F
N 8 -200 to 1,300 °C or -300 to 2,300 °F
R 9 0 to 1,700 °C or 0 to 3,000 °F
S 10 0 to 1,700 °C or 0 to 3,000 °F
B 11 100 to 1,800 °C or 300 to 3,200 °F
Infrared tempera- K10 to 70°C 12 0 to 90 °C or 0 to 190 °F
ture sensor K60 to 120°C 13 0 to 120 °C or 0 to 240 °F
ES1A
K115 to 165°C 14 0 to 165 °C or 0 to 320 °F
K160 to 260°C 15 0 to 260 °C or 0 to 500 °F
Analog input 0 to 50 mV 16 One of the following ranges depending on the
results of scaling:
-1,999 to 9,999 or -199.9 to 999.9

Default is 0.

22
Selecting Centigrade/Farenheit Section 3-2

3-2 Selecting Centigrade/Farenheit


Select either °C or °F as the temperature unit.
Refer to the following table and select the value that corresponds to the
desired temperature unit. The same temperature unit is used for both channel
1 and channel 2.
To use °C, use host communications and set 0 as the temperature unit or use
the E5ZN-SDL Setting Display Unit and set c.
Unit Setting
°C 0
°F 1

Default is 0.

23
Selecting PID Control or ON/OFF Control Section 3-3

3-3 Selecting PID Control or ON/OFF Control


Either 2-PID control (PID control with two degrees of freedom) or ON/OFF
control can be selected. The control method is selected by using host commu-
nications or the E5ZN-SDL Setting Display Unit to change the “PID/OnOff”
parameter. Set the control method for channels 1 and 2 separately. Default is
for PID control.

2-PID Control For PID control, the “proportional band (P),” “integral time (I),” and “derivative
time (D)” parameters must be set.
These PID constants can be set by autotuning or manual setup.

ON/OFF Control In ON/OFF control, the control output is turned ON when the process value is
lower than the current set point, and the control output is turned OFF when
the process value is higher than the current set point (for reverse operation).

24
Setting Output Specifications Section 3-4

3-4 Setting Output Specifications


3-4-1 Control Period
• Set the output period (control period). Though a shorter period provides
better control performance, we recommend setting the control period to
20 seconds or more when using a relay output for heater control (to
increase the effective life of the relay). If necessary, readjust the control
period according to the results of trial operation with the control period
parameters set to their defaults.
• Use host communications or the E5ZN-SDL Setting Display Unit to set
the “heating control period” and “cooling control period” parameters.
Default is 2 s.
• The “cooling control period” parameter is used only in heating and cooling
control.
• Set the control periods for channels 1 and 2 separately.

3-4-2 Direct (Cooling)/Reverse (Heating) Operation


• Direct operation refers to control where the manipulated variable (MV) is
increased for an increase in the process value (e.g.,cooling). Alternatively,
reverse operation refers to control where the manipulated variable (MV) is
decreased for an increase in the process value (e.g., heating).
MV MV
100% 100%

0% 0%

Low temperature Set value High temperature Low temperature Set value High temperature

Direct operation Reverse operation

• For example, when the process value (temperature) is lower than the set
point (temperature) in a heating control system, the manipulated variable
(MV) increases by the difference between the process value and the set
value.
Reverse operation is thus used in a heating control system and direct
operation is used in a cooling control system.
• Use host communications or the E5ZN-SDL Setting Display Unit to set
“Direct/reverse operation” to “0: Reverse” or “1: Direct.” Default is for
reverse operation (heating).
• Set the direct/reverse operation for channels 1 and 2 separately.

25
Setting Output Specifications Section 3-4

3-4-3 Output Allocations


• The E5ZN has four outputs. The following tables shows the default func-
tions allocated to each output terminal.
Name Terminal Setting
No.
OUT1 (control output 7, 8 Heating control output for ch 1
1)
OUT2 (control output 1, 2 Heating control output for ch 2
2)
SUB1 (auxiliary out- 13, 15 Alarm 1 and heater burnout alarm OR output for
put 1) ch 1
SUB2 (auxiliary out- 14, 15 Alarm 1 and heater burnout alarm OR output for
put 2) ch 2

• The functions allocated to these four outputs can be changed by chang-


ing the output allocation settings. Refer to the following table for the func-
tions that can be allocated to the outputs.
The same functions can be allocated to different outputs.
Set value Function
0 Heating control output for ch 1
1 Cooling control output for ch 1
2 Alarm 1 and heater burnout alarm OR output for
ch 1
3 Alarm 2 output for ch 1
4 Alarm 3 output ch 1
5 Heating control output for ch 2
6 Cooling control output for ch 2
7 Alarm 1 and heater burnout alarm OR output for
ch 2
8 Alarm 2 output for ch 2
9 Alarm 3 output for ch 2

• When “Heating control output for ch 1” has been set for an output, ch 1
performs heating/cooling control. When “Cooling control output for ch 2”
has been allocated to the output, ch 2 performs heating/cooling control.

Allocating Alarm 2 Use host communications or the E5ZN-SDL Setting Display Unit to set 3 as
Output for ch 1 to the auxiliary output 2 allocation.
Auxiliary Output (SUB2)

26
Setting the SP Section 3-5

3-5 Setting the SP


3-5-1 Changing the SP
Use host communications or the E5ZN-SDL Setting Display Unit to set the SP.
Default is 0°C.
In this example, the set point will be changed from 0°C to 200°C.
• Use host communications to set the “SP” parameter to “000000C8H
(200°C).”
• To use the Setting Display Unit to change the SP, select the channel to be
changed and use the Up and Down Keys to set the SP to 200°C.
• To start control, an operation start (RUN) must be specified after changing
the SP. Refer to 3-10 Starting and Stopping Control for details.

27
Executing ON/OFF Control Section 3-6

3-6 Executing ON/OFF Control


In ON/OFF control, the control output turns OFF when the process value
(temperature) reaches the preset set point. When the control output turns
OFF, the temperature begins to fall and the control output turns ON again.
This operation is repeated between certain points. How much the temperature
must fall in relation to the SP before control output turns ON again is deter-
mined by the “heating hysteresis” parameter. Also, whether the manipulated
variable (MV) must be increased or decreased in response in an increase or
decrease in the process value is determined by the “direct/reverse operation”
parameter.

3-6-1 ON/OFF Control


Either 2-PID control or ON/OFF control can be set using the “PID/OnOff”
parameter. When this parameter is set to “PID,” 2-PID control is used, and
when set to “OnOff,” ON/OFF control is used. Default is “PID.”

Hysteresis • In ON/OFF control, hysteresis is provided in the program when switching


between ON and OFF to stabilize operation. The hysteresis width pro-
vided during ON/OFF control is simply referred to as “hysteresis.” Heating
control output and cooling control output functions are set in the “heating
hysteresis” and “cooling hysteresis” parameters.
• In standard heating or cooling control, the hysteresis can only be set at
the “heating hysteresis” parameter.
Heating hysteresis

ON

OFF PV

Set point

3-position Control In heating and cooling control, a dead band (an area where both control out-
puts are 0) can be set between the heating and cooling sides, enabling 3-
position control.
Dead band

Heating hysteresis Cooling hysteresis

ON

Heating side Cooling side

OFF PV

Set point

28
Executing ON/OFF Control Section 3-6

3-6-2 Setup
To execute ON/OFF control, set the set point, the PID/OnOff parameter, and
the hysteresis.

Setting ch1 to ON/OFF Use host communications or the E5ZN-SDL Setting Display Unit to make the
Control with an SP of following settings.
200°C and Hysteresis of • Set the PID/OnOff parameter for ch1 to “0: ON/OFF”
2°C • Set the set point for ch1 to 200.
• Set the hysteresis for ch1 to 2.0.

29
Determining PID Constants: Autotuning and Manual Setup Section 3-7

3-7 Determining PID Constants: Autotuning and Manual Setup


3-7-1 Autotuning
• When executing autotuning, the optimum PID constants for the set point
during program execution are automatically set by changing the manipu-
lated variable (MV) to calculate the characteristics of the control target.
This is called the limit cycle method.
• Autotuning cannot be executed while stopped or during manual mode or
ON/OFF control.
• To start autotuning, use host communications operation commands or the
E5ZN-SDL Setting Display Unit and set “AT execute/stop” to “execute.”
• To stop autotuning, use host communications operation commands or the
E5ZN-SDL Setting Display Unit and set “AT execute/stop” to “stop.”
• During execution of autotuning, only “communications writing,” “RUN/
STOP,” “AT execute/stop,” and “auto/manual” parameters can be
changed. No other settings can be changed.
• If “RUN/STOP” is set to “STOP” during execution of autotuning, autotun-
ing and operation will stop. Autotuning will not start again even if “RUN/
STOP” is set to “RUN” again.

30
Determining PID Constants: Autotuning and Manual Setup Section 3-7

3-7-2 Manual Setup


To set PID parameters manually, use host communications or the E5ZN-SDL
Setting Display Unit and set values for the “proportional band” (P), “integrated
time” (I) and “derivative time” (D) parameters.
Note 1. When control characteristics are already known, the PID parameters can be set di-
rectly to adjust control. PID parameters are set in the “proportional band” (P), “in-
tegrated time” (I), and “derivative time” (D) parameters.
2. When PID constants I (integral time) and D (derivative time) are set to 0, control is
executed according to proportional operation. The default set point becomes the
center value of the proportional band.

When P (Proportional
Band) Is Changed When P is The curve rises gradually, and
increased a long adjustment time is
Set Value required, but there is no over-
shooting.

When P is Overshooting and hunting


decreased occur, but the set point is
Set Value

quickly reached after which


the curve stabilizes.

When I (Integral Time) Is


Changed When I is It takes a long time for the pro-
increased cess value to reach the set
Set Value

point. It takes time to adjust,


bit there is little overshooting,
undershooting, and hunting.

When I is Overshooting, undershooting,


decreased and hunting occur, but the
Set Value

curve rises quickly.

When D (Derivative
Time) Is Adjusted When D is Overshooting, undershooting,
Set Value

increased and adjustment time are


reduced, but fine hunting
occurs on changes in the
curve itself.

When D is Overshooting and under-


decreased shooting increase, and it
Set Value

takes time for the process


value to return to the set point.

31
Alarm Outputs Section 3-8

3-8 Alarm Outputs


This section describes the “alarm type,” “alarm value,” “upper limit alarm,” and
“lower limit alarm” parameters.

3-8-1 Alarm Type

Alarms 1 and 2
Set value Alarm type Alarm output operation
When alarm value When alarm value
X is positive X is negative
0 Alarm function OFF Output OFF
1 (See Upper and lower limit L H See note 2.
note 1.) ON
OFF SP

2 Upper limit x X
ON ON
OFF SP OFF SP

3 Lower limit X X
ON ON
OFF SP OFF SP

4 (See Upper and lower limit range L H See note 3.


note 1.) ON
OFF SP

5 (See Upper and lower limit alarm L H See note 4.


notes 1, with standby sequence ON
6.) OFF SP

See note 5
6 (See Upper limit alarm with x X
note 6.) standby sequence ON ON
OFF SP OFF SP

7 Lower limit alarm with X X


standby sequence ON ON
OFF SP OFF SP

8 Absolute-value upper limit X X


ON ON
OFF 0 0 OFF 0

9 Absolute-value lower limit X X


ON ON
OFF 0 OFF 0

10 (See Absolute-value upper limit X X


note 6.) with standby sequence ON ON
OFF 0 0 OFF 0

11 (See Absolute-value lower limit X X


note 6.) with standby sequence ON ON
OFF 0 OFF 0

Note 1. With set values 1, 4, and 5, the upper and lower limit values can be set indepen-
dently for each alarm point and are expressed as “L” and “H.”

32
Alarm Outputs Section 3-8

2. Operation for set value 1 (upper and lower limit alarms) would be as follows:
Case 1 Case 2 Case 3
H < 0, L < 0

L H ・
SP
・ L
SP H H SP L
H < 0, L > 0 H > 0, L < 0
|H| < |L| |H| > |L| H < 0, L > 0
・ |H| > |L|
H L SP

H > 0, L < 0

SP H L |H| < |L|

3. Operation for set value 4 (upper and lower limit ranges) would be as follows:
Case 1 Case 2 Case 3
H < 0, L < 0
・ ・
SP L ・
L H SP H H SP L
H < 0, L > 0 H > 0, L < 0
H < 0, L > 0

H L SP
|H| > |L|

H > 0, L < 0
・ |H| < |L|
SP H L

4. Set value 5 (upper and lower limit alarms with standby sequence):
For upper and lower limit alarm cases in the above diagram, hysteresis is always
OFF for cases 1 and 2 if the upper and lower limits overlap. Hysteresis is always
OFF for case 3.
5. Set value 5 (upper and lower limit alarms with standby sequence):
Hysteresis is always OFF if the upper and lower limits overlap.
6. Refer to 4-2 Alarm Hysteresis for information on standby sequences.

Alarm 3
Set value Alarm type Alarm output operation
When alarm value When alarm value
X is positive X is negative
0 Alarm function OFF Output OFF
1 upper and lower limit (devia- X X Always ON.
tion) ON
OFF SP

2 Upper limit (deviation) x X


ON ON
OFF SP OFF SP

3 Lower limit (deviation) X X


ON ON
OFF SP OFF SP

4 Upper and lower limit range X X Always OFF.


(deviation) ON
OFF SP

5 Upper and lower limit alarm X X Always OFF.


with standby sequence (devi- ON
ation) OFF SP

6 Upper limit alarm with x X


standby sequence (deviation) ON ON
OFF SP OFF SP

7 Lower limit alarm with X X


standby sequence (deviation) ON ON
OFF SP OFF SP

33
Alarm Outputs Section 3-8

Set value Alarm type Alarm output operation


When alarm value When alarm value
X is positive X is negative
8 Absolute-value upper limit X X
ON ON
OFF 0 0 OFF 0

9 Absolute-value lower limit X X


ON ON
OFF 0 OFF 0

10 Absolute-value upper limit X X


with standby sequence ON ON
OFF 0 0 OFF 0

11 Absolute-value lower limit X X


with standby sequence ON ON
OFF 0 OFF 0

Use host communications or the E5ZN-SDL Setting Display Unit to set the
alarm type separately for each alarm for alarms 1 to 3. Defaults are “2: Upper
limit.” Set the alarms separately for each channel.

3-8-2 Alarm Values


Alarm values are indicated by “X” in the table in the above section. When the
upper and lower limits are set independently, “H” is displayed for upper limit
values, and “L” is displayed for lower limit values.
When upper and lower limit, upper and lower limit range, or upper and lower
limit alarm with standby sequence have been selected as the alarm type, set
the alarm upper limit and alarm lower limit parameters separately.
When other alarm types have been selected, set the alarm value parameter.
The upper and lower limits cannot be set independently for alarm 3.

34
Using Heater Burnout Alarm (HBA) Section 3-9

3-9 Using Heater Burnout Alarm (HBA)


3-9-1 HBA Detection
To CT terminal

CT

Heater lead

Heater burnout detection works as follows:


1,2,3... 1. Pass the heater lead through the current transformer (CT) hole. For spec-
ifications, models, and external dimensions of current transformers that
can be used on this Controller, refer to Current Transformer (CT) in Appen-
dix A.
2. When current flows through the lead, the current transformer generates AC
current proportional to the current value. The E5ZN measures this AC cur-
rent to calculate the current flowing to the heater.
3. If the heater is burned out, the current measured at the current transformer
will decrease. If this value becomes larger than the value set as the heater
burnout set value, the output is turned ON to indicate a heater burnout
alarm.
• Set the heater burnout detection value in the “heater burnout detection”
parameter. To monitor the current value of the current transformer, use
the “heater current monitor” parameter.
• When you are not using the HBA function, set the “heater burnout”
parameter to “0: OFF.”
• Make separate heater burnout settings for ch1 and ch2.

3-9-2 Operating Conditions


• Be sure to connect the CT to the E5ZN, and pass the heater lead through
the CT hole.
• Turn ON the heater at the same time as or before turning the E5ZN. If the
heater is turned ON after turning the E5ZN, the heater burnout alarm will
activate.
• Control is continued even if the heater burnout alarm is turned ON. (That
is, the E5ZN attempts to control heaters for which the heater burnout
alarm has not occurred.)
• Heater burnout detection is performed when the control output is continu-
ously ON for 190 ms or more.
• The rated current value may sometimes differ slightly from the actual cur-
rent flowing to the heater. Check the current value in an actual operating
state in the “heater current monitor” parameter.
• If there is little difference between the current in a normal state and the
current in the burnout state, detection may be unstable. On a heater with
a current 10.0 A or less, maintain a difference of 1.0 A or more. On a
heater with a current 10.0 A or more, maintain a difference of 2.5 A or
more.
• The HBA function cannot be used when the heater is controlled by a
phase control system or cycle control system. Also, 3-phase heaters can-
not be used.

35
Using Heater Burnout Alarm (HBA) Section 3-9

Note To detect heater burnout for a 3-phase heater, use the K2CU-F@@A-@GS (with gate
input terminal). For details, see the data sheet.

3-9-3 Calculating the Detection Current Value


• Calculate the set value by the following equation:
(Normal current + Current at heater burnout)
Set value =
2

• To set the value of the heater burnout when two or more heaters are con-
nected through the CT, use the current value of the smallest heater con-
nected. If all the heaters have the same current value, use the current
value when one of the heaters burns out.
• Make sure that the following conditions are satisfied:
Heater of current 10.0 A or less:
Normal current -Current at heater burnout ³ 1 A
(When the resultant current is less than 1 A, detection is unstable.)
Heater of current 10.0 A or more:
Normal current -
Current at heater burnout ³ 2.5 A
(When the resultant current is less than 2.5 A, detection is unstable.)
• The setting range is 0.1 to 49.9 A. Heater burnout is not detected if the set
value is 0.0 or 50.0. If the set value is 0.0, the heater burnout alarm is
turned OFF, and if the set value is 50.0, the heater burnout alarm is turned
ON.
• Set the total current value at normal heater operation to 50 A or less.

Application Examples Example 1 Using a 200-VAC, 1-kW Heater for OUT1


1000
Control output Current during normal operation = = 5 A (< 10 A)
200
Heater
Current at heater burnout = 0 A
5+0
Set value = = 2.5 A
1 kW 2
200 VAC
(Normal current - Current at heater burnout) = 5 - 0 = 5 A (³ 1 A)
CT

Example 2 Using Three 200-VAC, 1-kW Heaters for OUT2


1000
Control output Current during normal operation = ´ 3 = 15 A (³ 10 A)
200
Heater 1000
Current at burnout of one heater = ´ 2 = 10 A
200
15 + 10
1 kW ´ 3 Set value =
2
= 12.5 A
200 VAC
(Normal current - Current at heater burnout) = 15 - 10 = 5 A (³ 2.5 A)
CT

36
Starting and Stopping Control Section 3-10

3-10 Starting and Stopping Control


3-10-1 Starting Control (RUN)/Stopping Control (STOP)
Set the RUN/STOP operation command to RUN to start E5ZN control. To stop
control, set the RUN/STOP operation command to STOP.
There are three ways to set the RUN/STOP operation command.
1,2,3... 1. Using host communications.
2. Using the E5ZN-SDL Setting Display Unit.
3. Using an external contact for an event input.

Operation after Turning • Set the operation status after the power supply for the E5ZN has been
ON the Power Supply turned ON. Choose one of the following two statuses.
Set value Operation
Stop Control will always stop when the power supply is turned ON.
Continue Returns control to the status for the last time the power supply
was turned OFF.

• The following table gives additional information for each of the operation
settings.
Operation after Additional information
power turned ON
Stop When the power is turned ON, the RUN/STOP setting will
always be set to STOP and the E5ZN will start when the com-
mand is changed to RUN.
Continue 1. If the E5ZN was in manual mode the last time the power was
turned OFF, it will be in manual mode when the power is
turned ON and the manual manipulated variable will be 0%.
2. When the setting for operation after the power is turned ON
is changed from “stop” to “continue,” the “RUN/STOP” oper-
ation command will be set to “STOP.” This setting change will
always be saved to internal non-volatile memory even if the
E5ZN is in RAM backup mode.
3. When the E5ZN is used in RAM write mode, change the
“RUN/STOP” operation command from the host communi-
cations and then be sure to execute the RAM DATA SAVE
operation command. If the power is turned OFF before the
RAM DATA SAVE operation command is executed, the op-
eration status will not be continued.

• Default is stop.
• This parameter setting is used by both channels.

37
Operating Precautions Section 3-11

3-11 Operating Precautions


1,2,3... 1. About four seconds is required for outputs to turn ON after the power is
turned ON. Take this into consideration when the Temperature Controller
is incorporated into a sequence circuit.
2. The Temperature Controller may be subject to the influence of radio inter-
ference if used near a radio, TV, or wireless equipment.

38
SECTION 4
Settings Used Only when Required

4-1 Shifting Input Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40


4-1-1 Shifting Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4-1-2 Calculating Input Shift Values for Non-contact Sensors . . . . . . . . . 41
4-2 Alarm Hysteresis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4-2-1 Standby Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4-2-2 Alarm Latch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4-2-3 Close for Alarm/Open for Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4-3 Setting Scaling Upper and Lower Limits (Analog Input) . . . . . . . . . . . . . . . . 46
4-3-1 Analog Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
4-4 Executing Heating and Cooling Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4-4-1 Heating and Cooling Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4-5 Using the Event Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
4-5-1 Setting the Event Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
4-5-2 Using Control Start (RUN)/Control Stop (STOP) . . . . . . . . . . . . . . 48
4-5-3 Using the Multi-SP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
4-6 Setting the SP Upper and Lower Limit Range . . . . . . . . . . . . . . . . . . . . . . . . 50
4-6-1 Set Point Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
4-7 SP Ramp Function: Limiting SP Change Rate . . . . . . . . . . . . . . . . . . . . . . . . 51
4-7-1 SP Ramp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4-8 Key Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
4-8-1 Key Protect Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
4-9 Manual Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
4-9-1 Auto/Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
4-9-2 Manual Manipulated Variable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
4-10 Reading Temperatures for Multiple E5ZN Units . . . . . . . . . . . . . . . . . . . . . . 56
4-10-1 PV Hold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
4-11 Remote PV Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
4-11-1 Using Remote PV Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

39
Shifting Input Values Section 4-1

4-1 Shifting Input Values


4-1-1 Shifting Input
The input shift type matched to the sensor currently selected in the “input
type” parameter is displayed.
• A 2-point shift is used only for infrared temperature sensors.
• With a 1-point shift, only the value set for the “Temperature input shift”
parameter is applied to the entire temperature input range. For example, if
the input shift value is set to 1.2°C and the process value is 200°C, the
process value will be treated as 201.2°C after the input shift has been
applied.

One-point Shift: Inputs


for Sensors other than Temperature
Non-contact
Temperature Sensors Upper limit value

After shift
Before shift

Input shift value

Input
0
100% FS

• Default for both ch1 and ch2 is 0.

Two-point Shift: Input


for Infrared Temperature
Upper limit temperature input shift value
Temperature Sensors
Upper limit value

After shift
Before shift

Lower limit value


Input
0 Lower limit temperature input
shift value 100% FS

• The input temperature range of infrared temperature sensors can be


shifted by setting different shift values for the upper and lower ends of the
sensor range. Setting different shift values means that the slop of the line
will change. For example, if the upper limit value is set to “2°C” and the
lower limit value is set to “1°C,” the sensor range is shifted by 1.5°C at a
50% input.
• Set the upper limit value in the “upper limit temperature input shift value”
parameter and the lower limit value in the “lower limit temperature input
shift value” parameter.
• Default for the upper and lower limit temperature input shift values are 0
for both ch1 and ch2.

40
Shifting Input Values Section 4-1

4-1-2 Calculating Input Shift Values for Non-contact Sensors


When a ES1A Infrared Temperature Sensor is connected to the E5ZN, an off-
set of several degrees to several tens of degrees can occur due to internal
impedance. Furthermore, if the rate of heat radiation of the control target is
not 0.9, errors may occur.
For this reason, offset the readout value using a 1-point or 2-point shift as
described in this section. This offset occurs because a bias current for detect-
ing Controller sensor error flows to the output impedance of the non-contact
temperature sensor. A 2-point shift can be performed only on infrared temper-
ature sensors, and cannot be set for other input types.
Preparations
1,2,3... 1. Set the temperature range matching the input specifications of the non-
contact temperature sensor.
2. Prepare a thermometer capable of measuring the temperature of the con-
trol target as shown in Figure 1 so that 1-point shift or 2-point shift can be
performed.

(D) Infrared temperature


sensor
(C) Control target

_+

(B) Thermometer
(A) E5ZN

Figure 1 Configuration when Compensating a Infrared Temperature Sensor

One-point Shift
1,2,3... 1. In the configuration shown in Figure 1, bring the set point to near the value
at which the temperature of the control target is to be controlled. Let's as-
sume that the control target temperature (C) and the control target temper-
ature (B) are the same.
2. Check the control target temperature (B) and the Controller readout (A).
Take the following value as the input shift value, and set the same numer-
ical values for both the lower limit temperature input shift value and the up-
per limit temperature input shift value.
Control target temperature (B) - Controller readout (A)

Figure 2 shows the effect of 1-point temperature input shift.

41
Shifting Input Values Section 4-1

3. After you have set the input shift values, check Controller readout (A) and
control target temperature (B). If they are almost the same, the tempera-
ture input shift value is correct.
Controller readout (A)
Upper limit temperature
Temperature readout After shift
after shift (e.g., 120°C) Input shift value (e.g., 10°C)
Temperature readout Before shift
before shift (e.g.,

Lower limit
temperature
input shift (e.g., Temperature readout of
10°C) 0 Near set point control target (B)
(e.g., 120°C)

Figure 2 One-point Temperature Input Shift

Two-point Shift Use a 2-point input shift if you want to increase the accuracy of the readout
values across the range of the sensor.
1,2,3... 1. The Controller readout will be shifted at two points, near room temperature
and near the value at which the temperature of the control target is to be
controlled. For this reason, bring the control target temperature to near
room temperature and to near the set point, and check the control target
temperature (B) and Controller readout (A) at both points.
2. Using equations 1 and 2, calculate the upper and lower limit temperature
input shift values from values obtained in step 1.
Figure 3 shows the effect of using a 2-point temperature input shift.
Controller readout (A)

Set temperature upper After shift


limit YH (e.g., 260°C)
Upper limit temperature
Temperature readout input shift value
after input shift X2 (e.g., 110°C)
Before shift
Temperature readout
before input shift Y2 (e.g.,
Temperature readout
before input shift Y1 (e.g., 40°C)
Temperature readout Temperature
after input shift X1 (e.g., 25°C) 0 X1 room temperature readout of control
(e.g., 25°C) target (B)
Lower limit temperature
input shift value Set temperature Near X2 set point
lower limit YL (e.g., 110°C)
(e.g., 0°C)

Figure 3 Two-point Temperature Input Shift


• Use the following equation to calculate the lower limit temperature input
shift value.
YL - Y1
Equation 1 ´ {(X2 - Y2) - (X1 - Y1)} + (X1 - Y1)
Y2 - Y1

• Use the following equation to calculate the upper limit temperature input
shift value.
Equation 2 YH - Y1
´ {(X2 - Y2) - (X1 - Y1)} + (X1 - Y1)
Y2 - Y1

3. After you have set the calculated values for the lower limit temperature in-
put shift value and the upper limit temperature input shift value, check the
Controller readout (A) and control target temperature (B) at both points.

42
Shifting Input Values Section 4-1

4. Although the input shift was performed at two points, close to room tem-
perature (ambient temperature) and near to the set point, select points
close to each end of the sensor range to improve accuracy across the full
range of sensor measurement.

Example of 2-point In this example, we use the ES1A K 160 to 260°C specification, where the
Temperature Input Shift input temperature setting range is 0 to 260°C.
In equations 1 and 2, the set temperature lower limit YL is 0°C and the set
temperature upper limit YH is 260°C. Check the temperature of the control tar-
get.
We will assume that when the room temperature X1 is 25°C, the readout on
the Controller Y1 is 40°C, and when the temperature near the set point X2 is
110°C, the readout on the Controller Y2 is 105°C.
Lower Limit Temperature Input Shift Value
0 - 40
´ {(110 - 105) - (25 - 40)} + (25 - 40) = -27.3 (°C)
105 - 40

Upper Limit Temperature Input Shift Value


260 - 40
´ {(110 - 105) - (25 - 40)} + (25 - 40) = 52.7 (°C)
105 - 40

43
Alarm Hysteresis Section 4-2

4-2 Alarm Hysteresis


• The hysteresis of alarm outputs when alarms are switched ON and OFF
can be set as follows:
Upper limit Lower limit
alarm alarm
Alarm hysteresis Alarm hysteresis

ON ON

OFF OFF

Alarm value Alarm value

• Alarm hysteresis is set independently for each alarm in the “alarm hyster-
esis 1” to “alarm hysteresis 3” parameters.
• Default is 0.2 for both ch1 and ch2.

4-2-1 Standby Sequence


• The standby sequence allows alarm outputs to be temporarily disabled
until the temperature leaves the alarm range (i.e., until an alarm condition
does not exist). Once the alarm range has been left, the alarm output will
then operate whenever the alarm range is entered.
• For example, in a standard heating application, if you use the standard
“low alarm,” the alarm output would be turned ON when the Controller is
turned ON. However, if the standby sequence is used, the alarm output is
disabled during the warmup period until the temperature goes above the
alarm set point. The alarm becomes active after the low alarm set point
has been exceeded and the output is turned ON if the temperature falls
below the alarm set point.

Restart The standby sequence is ended when an alarm is output. It is, however,
restarted (reset) later by the conditions specified in the “standby sequence
restart” parameter.

4-2-2 Alarm Latch


• The alarm latch function holds the alarm output ON once it has been
turned ON regardless of the temperature.
• The alarm latch can be canceled by turning OFF the power.
• Default is “0: OFF.”

44
Alarm Hysteresis Section 4-2

4-2-3 Close for Alarm/Open for Alarm


• When the E5ZN is set to “close for alarm,” the status of the alarm output
function is normally open. When set to “open for alarm,” the status of the
alarm output standby is normally closed.
• The close for alarm/open for alarm status can be set independently for
each alarm.
• The close for alarm/open for alarm settings are set in the “Alarm 1 to 3
open for alarm” parameters.
• Default is “0: Close for alarm.”
• When “alarm 1 open for alarm” is set, the heater burnout alarm and input
error outputs are both open for alarm.
Setting Alarm output function Alarm output Operation indicator
(LED)
Close for ON ON Lit
alarm OFF OFF Not lit
Open for ON OFF Lit
alarm OFF ON Not lit

• The alarm output will turn OFF (open) when power is interrupts and for
about four seconds after the power is turned ON regardless of the close
for alarm/open for alarm setting.

Summary of Alarm The figure below visually summarizes the above description of alarm opera-
Operations tions when a lower limit alarm with standby sequence and close for alarm are
set.
Alarm type: Lower limit alarm with
standby sequence

Alarm value
Alarm hysteresis

PV

Time
Standby sequence
canceled ON
Alarm output function OFF
ON (closed)
Alarm output OFF (open)

45
Setting Scaling Upper and Lower Limits (Analog Input) Section 4-3

4-3 Setting Scaling Upper and Lower Limits (Analog Input)


4-3-1 Analog Input
• An analog voltage input can be scaled matched to the control application.
• Scaling is set in the “scaling upper limit,” “scaling lower limit,” and “deci-
mal point” parameters. These parameters cannot be used when a tem-
perature input is selected.
• The “scaling upper limit” parameter sets the physical quantity to be
expressed by the upper limit value of input, and the “scaling lower limit”
parameter sets the physical quantity to be expressed by the lower limit
value of input. The “decimal point” parameter specifies the number of dig-
its past the decimal point.
• The following figure shows a scaling example for a input of 0 to 50 mVDC
for humidity. After scaling, the humidity(%) can be directly read.
Readout
(humidity)

Upper limit value


(95.0%)

Lower limit value


(10.0%)

Input (mV)
0
50

In this example, the scaling upper and lower limits are set so that inputs 0 to
50 mV are scaled to 10.0% to 95.0%.
Scaling upper limit: 950
Scaling lower limit: 100
Decimal point position: 1

46
Executing Heating and Cooling Control Section 4-4

4-4 Executing Heating and Cooling Control


4-4-1 Heating and Cooling Control
Heating and cooling control operates when a cooling control output has been
allocated to one of the outputs. For example, to set heating and cooling con-
trol for ch1, allocate “cooling control output for ch1” to one of the outputs.
• When heating and cooling control is selected, the “dead band” and “cool-
ing coefficient” parameters can be used.
• Refer to 3-4 Setting Output Specifications for allocation methods for heat-
ing and cooling control.
• The default allocation is “heating control output.”

Dead Band The dead band is set with the set point as its center. The dead band width is
set in the “dead band” parameter in the adjustment level. Setting a negative
value produces an overlap band.
Dead band: Overlap band:
Dead band width = positive Output Dead band width = negative
Output

Heating Cooling Heating Cooling


side side side side

0 PV 0 PV
Set point Set point

Default is “0.0% EU.”

Cooling Coefficient If the heating and cooling characteristics of the control target differ enough to
prevent satisfactory control characteristics from being obtained using the
same PID constants, control between the heating and cooling sides can be
balanced by adjusting the proportional band (P) at the cooling side control
output using the cooling coefficient. In heating and cooling control, P at the
heating or cooling control output sides is calculated using the following for-
mula: Heating side P = P
Cooling side P = Heating side P ´ Cooling coefficient
The cooling coefficient is applied to heating side P to obtain cooling side out-
put control whose characteristics (i.e., the cooling side P) differ from those on
the heating side control output.
Output Output

Cooling side P

Cooling side
P
Heating side Heating side
P P
PV PV
0 0
Set point Set point
Heating Side P ´ 0.8 Heating Side P ´ 1.5

47
Using the Event Input Section 4-5

4-5 Using the Event Input


4-5-1 Setting the Event Input
The event input, which uses an external contact input, is set using the “No. of
multi-SP uses” and “event input assignment” settings.
The multi-SP function is allocated for event input by setting the “No. of multi-
SP uses” parameter. The RUN/STOP control function is set using the “event
input allocation” parameter.
When the event input is not used as a multi-SP function, the multi-SP function
can be used via host communications or the E5ZN-SDL Setting Display Unit
by setting the “multi-SP use” parameter.
The following table shows the relationship between the three settings.
Settings Function allocated Changing multi-SP via host
Number of Event input Multi-SP use to event input communications or Setting
multi-SP uses allocation Display Unit
0 None ON None Possible
OFF Not possible
RUN/STOP ON RUN/STOP Possible
OFF Not possible
1 None ON Multi-SP from event Not possible
OFF input
RUN/STOP ON
OFF

The shaded areas indicate the default values for the “No. of multi-SP uses,”
“event input allocation,” and “multi-SP use” parameters.
The three communications parameters given in the left columns of the above
table are given priority in the following order: “No. of multi-SP uses,” “event
input allocation,” and “multi-SP use.”

4-5-2 Using Control Start (RUN)/Control Stop (STOP)


When the “No. of Multi-SP uses” parameter is set to 0 and the event input allo-
cation is set to “RUN/STOP,” the RUN/STOP function can be controlled using
the event input. The following table shows the relationship between event
input contact status and control status.
Event input contact Control status
ON (closed) RUN
OFF (open) STOP

4-5-3 Using the Multi-SP


The multi-SP function is used to switch between two set points. Different set
points are set in advance for set point 0 and set point 1 and the event input
contact signals or E5ZN-SDL Setting Display Unit is used to switch them.

Using the Event Input The set points listed in the following table can be selected by turning ON and
OFF the event input.
Event input contact Set point
OFF (open) Set point 0
ON (short) Set point 1

Note 1. Switch event inputs during communications with the host computer.
ON/OFF is detected for inputs of 50 ms or more.
2. Set points for ch1 and ch2 are both switched using event input.

48
Using the Event Input Section 4-5

Using Communications The set point can be selected using the communications parameters shown in
the following table.
Multi-SP Set point
0 Set point 0
1 Set point 1

Note The set point can be switched independently for ch 1 and ch2.

Using Key Operations The set point can be selected using the E5ZN-SDL Setting Display Unit.

49
Setting the SP Upper and Lower Limit Range Section 4-6

4-6 Setting the SP Upper and Lower Limit Range


4-6-1 Set Point Limits
The upper and lower set point limits can be set within the input temperature
setting range.
Once the input set point limit is set, the set point is automatically returned to
the upper or lower set point limit if it goes outside the set point limit range.
For example, If the set point upper limit is changed to 150°C when the set
point is 200°C, the set point upper limit was 300°C, and the set point lower
limit is 100°C, the set point will have gone outside the existing set point limit
range of 100°C to 150°C. In this situation the set point will be changed to
150°C (i.e., the new upper limit).
If the input type or temperature unit is changed, the set point upper and lower
limits will be automatically reset to the upper and lower limits of the input tem-
perature setting range.
Set the set point limit separately for ch1 and ch2.
Input temperature setting range

Set point limit

Setting range
Changed to A B
the new upper
limit value (Setting not
allowed)
Changed upper limit
value Set point

Input temperature setting range

Input type changed Set point

C B
Set point upper and lower limit values
Sensor upper and lower limit values (setting allowed)

50
SP Ramp Function: Limiting SP Change Rate Section 4-7

4-7 SP Ramp Function: Limiting SP Change Rate


4-7-1 SP Ramp
The SP ramp function controls the rate of change of the set point. If a change
larger than the rate of change is specified when the SP ramp function has
been enable, changes in the set point will be limited as shown below. Thus,
when changes are made to the set point with the SP ramp function enabled,
control is performed according to the rate of change rather than the target
value.
SP

SP ramp
SP after change

SP ramp set value

Time unit of SP ramp rate (min.)

SP before change

Time

Change point

The change rate during SP ramp is specified in the “SP ramp set value”
parameter. The “SP ramp set value” default is 0, i.e., the SP ramp function is
disabled.
The ramp set point can be monitored in the “Set point during SP ramp”
parameter.

Operation at Start When the power is turned ON, operation is performed with the process value
treated as the set point before the change was made.
The direction of the SP ramp changes according to the relationship between
the process value and the set point, as shown in the following diagram.

PV < SP PV > SP
SP SP
SP ramp SP ramp
Set point PV
Same change rate

Set point
PV

Time Time
Power ON Power ON

Restrictions during SP • Autotuning starts after the SP ramp function ends.


Ramp Operation • When control is stopped or an error occurs, the SP ramp function is dis-
abled.

51
Key Protection Section 4-8

4-8 Key Protection


4-8-1 Key Protect Function
The protect function limits the settings that can be changed to prevent inad-
vertently changing settings.
There are three protect mechanisms: “Communications writing” prohibits set-
ting changes from host communications, while “operation/adjustment protec-
tion” and “initial setting/communications protection” limit settings from the
E5ZN-SDL Setting Display Unit.

Communications If the ‘communications writing” parameter is set to “0: Prohibited (off),”


Writing changes to parameters other than “communications writing” are prohibited
from host communications.
Default is “1: Not prohibited (on).”

Operation/Adjustment The following table shows the relationship between set values and the range
Protection of protection.
oapt
0u 0

Level Set value


0 1 2 3
Operation PV m m m m
level PV/SP u u u m
Other u u ´ ´
Adjustment level u ´ ´ ´

u: Can be displayed and changed


m: Can be displayed
´: Cannot be displayed and moving to other levels not possible
• When this parameter is set to 0, parameters are not protected.
• Default is 0.

Initial Setting/ This protect level restricts movement to the initial setting level, communica-
Communications tions setting level, and advanced function setting level.
Protection icpt
0u 0

Set value Initial setting level Communications Advanced function


setting level setting level
0 m m m
1 m m ´
2 ´ ´ ´

m: Moving to otherlevels possible


´: Moving to other levels not possible
Default is 0.

52
Key Protection Section 4-8

Setting Change This protect level protects the setup from being changed by operating the
Protection keys on the front panel.

wtpt
0u off

Set value Description


OFF Setup can be changed by key operation.
ON Setup cannot be changed by key operation. (The protect level can
be changed.)

Default is OFF.

53
Manual Mode Section 4-9

4-9 Manual Mode


4-9-1 Auto/Manual
• If the “auto/manual” operation command is used by host communications
to set “01: manual (ch1)” or “11: manual (ch2),” the E5ZN will operate in
manual mode.
• If ON/OFF control is selected, operation cannot be switched to manual
mode. Always switch to PID control before selecting manual mode.
If manual mode has been selected and then operation is switched to ON/
OFF control, the mode will automatically be changed to automatic mode.
• In manual mode, the standard control functions are stopped and the val-
ues set in the manual manipulated variable will be output.
• Make separate settings for ch1 and ch2 for auto/manual switching.
• To switch from manual to automatic mode, use the “auto/manual” opera-
tion command to set “00: auto (ch1)” and “10: auto (ch2).”
• Switching between automatic and manual modes and manual manipu-
lated variable settings cannot be made from the E5ZN-SDL Setting Dis-
play Unit.
• To check whether the E5ZN is in automatic or manual mode, use host
communications to read the “status” parameter.
• Even if the “operation after power turned ON” setting is on “continue”
(continue operation status before power OFF), the manual manipulated
variable before the power was turned OFF will not be saved. It will always
change to 0%.
Output (100%)
The output at switching
100% will be saved.

20%

Time
RUN (During To manual Sets manual To automatic
control) mode, manipulated mode, using
using auto/ variable to auto/manual
manual 20%. switching
switching

54
Manual Mode Section 4-9

Relationship with RUN/ • The E5ZN can switch between auto and manual modes during both RUN
STOP (control operating) and STOP (control stopped).
• Even if the manual manipulated variable is set to STOP during output in
manual mode, the operation status will not change and the output of the
manual manipulated variable will continue. (Refer to the following dia-
gram.)
Output (100%)

100%

Changes to
STOP status.

Time
To manual To STOP, To automatic
mode, with RUN/ mode, using
using auto/ STOP auto/manual
manual setting switching
switching

4-9-2 Manual Manipulated Variable


Use host communications to set the manual manipulated variable to output in
manual mode.
The following table shows the relationship between the manual manipulated
variable setting range and the actual output.

Normal Control
Manual manipulated Heating side control
variable setting output
100.0% to 105.0% 100.0%
0.1% to 99.9% Outputs the value set to
manual manipulated vari-
able.
-5.0% to 0.0% Outputs 0.0%

Heating/Cooling Control
Manual manipulated Heating side control Cooling side control
variable setting output output
100.0% to 105.0% Outputs 100% Outputs 0.0%
0.1% to 99.9% Outputs the value set to
manual manipulated vari-
able.
0.0% Outputs 0.0%
-0.1% to -99.9% Outputs the absolute value
for the value set to manual
manipulated variable.
-100.0% to 105.0% Outputs 100%

55
Reading Temperatures for Multiple E5ZN Units Section 4-10

4-10 Reading Temperatures for Multiple E5ZN Units


If the present temperature was read from multiple Temperature Controllers
using host communications, there are time differences in the process temper-
atures read from each Temperature Controller, making it difficult to obtain con-
current data.
The PV hold function can be used with the E5ZN to ensure that the data is
concurrent to within 500 ms.
To read present temperatures from all
Temperature Controllers, the present value is
read in order from Unit No. 1 to Unit No. 31. Time
passes between the execution of the first process
Host (reading from Unit No. 0) until the execution of the
computer thirty-second process (reading from Unit. No. 31.)

For this reason, there is a time difference


affecting the temperatures obtained from
…… Units 0 and 31.
Unit No. 0 Unit No. 31

4-10-1 PV Hold
• The PV hold function temporarily stores the present temperature for that
moment as the PV hold value, when the “PV hold” operation command
sent by host communications is received.
Host
computer
(1) “PV hold” is executed from the host computer.
(3) “PV hold (2) The present temperature for each E5ZN Unit
value” read. from Units No. 0 to 15 is written simultaneously to
PV hold values.
(3) The PV hold values are read in order, starting
with Unit. No. 0.

(1) “PV hold”


executed. Unit No. Unit No.
0 15
(2) The present
temperature is held

• When using multiple E5ZN Units, use host communications to execute


the “PV hold” operation command simultaneously and then read the “PV
hold value” for each E5ZN. This enables highly concurrent temperature
logging.
• PV hold values are overwritten every time the “PV hold” operation com-
mand is executed. Once the PV hold values have been read for the chan-
nel that requires highly simultaneous reading of present temperatures,
execute the next “PV hold” operation command.
• The “PV hold” operation command cannot be executed and the “PV hold
value” cannot be read from the E5ZN-SDL Setting Display Unit.
• When the power is turned OFF, the PV hold values change to 0.

56
Remote PV Mode Section 4-11

4-11 Remote PV Mode


Remote PV mode forces PID equation output using the input value from the
external sensor with communications functions as the PV of the E5ZN,
instead of using normal thermocouple or platinum resistance thermometer
sensor input.
This function is useful when using a remote external sensor with communica-
tions functions.

4-11-1 Using Remote PV Mode


1,2,3... 1. Connect the sensor input according to the following specifications.
• For TC, Infrared Temperature Sensors, or Analog Input
Short between terminal numbers 5 and 6 and 11 and 12.
• For Pt
Connect a resistance of 100 to 125 W between terminal numbers 4 and 5
and 10 and 11.
• Short between terminal numbers 5 and 6 and 11 and 12.
2. Set the cycle for communications data sent from the external sensor to “re-
mote PV communications wait time.” This setting affects both channels.
If the refresh cycle for data from the external sensor is longer than the “re-
mote PV communications wait time,” the E5ZN will determine that the ex-
ternal sensor has been disconnected, and an input error will occur.
3. To switch to remote PV mode, turn ON the “remote PV mode” parameter.
This parameter setting is used for both channels.
4. The PV from the external sensor is written to the remote PV.
5. To switch from remote PV mode to normal mode, turn OFF the “remote PV
mode” parameter.
Default Settings
The default settings are shown below.
• Remote PV mode: OFF (normal mode)
• Remote PV communications wait time: 2,000 ms

57
Remote PV Mode Section 4-11

58
SECTION 5
Communications

5-1 Communication Protocols. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60


5-1-1 CompoWay/F Communication Protocol. . . . . . . . . . . . . . . . . . . . . . 60
5-1-2 Communications Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
5-1-3 Communications Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
5-2 Data Format Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
5-2-1 Command Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
5-2-2 Response Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
5-3 Structure of Command/Response Text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
5-4 Variable Area. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
5-5 Read from Variable Area. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
5-6 Write to Variable Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
5-7 Operation Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
5-8 Setting Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
5-9 Commands and Responses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
5-9-1 Read Monitor Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
5-9-2 Read Setting Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
5-9-3 Multiple Reads of Monitor Values/Setting Data. . . . . . . . . . . . . . . . 72
5-9-4 Write Protect Level Setting Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
5-9-5 Write Setting Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
5-9-6 Multiple Writes of Setting Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
5-9-7 Communications Writing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
5-9-8 Control Start (RUN)/Control Stop (STOP). . . . . . . . . . . . . . . . . . . . 76
5-9-9 Multi-SP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
5-9-10 AT Execute/Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
5-9-11 Write Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
5-9-12 RAM Data Save . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
5-9-13 Software Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
5-9-14 Move to Setting Area 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
5-9-15 Move to Protect Level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
5-9-16 Auto/Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
5-9-17 PV Hold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
5-9-18 Parameter Initialize . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
5-9-19 Read Controller Attribute . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
5-9-20 Read Controller Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
5-9-21 Echoback Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
5-10 Variable Area Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85

59
Communication Protocols Section 5-1

5-1 Communication Protocols


5-1-1 CompoWay/F Communication Protocol
CompoWay/F is a standard OMRON communications protocol for general-
purpose serial communications. It uses a standard frame format as well as
FINS commands that have been proven in data exchange between OMRON's
Programmable Controllers (PCs). The CompoWay/F format facilitates serial
communications between components or a PC and components.
FINS (Factory Interface Network Service)
FINS is a protocol for message communications between Controllers in
OMRON FA networks.
Note The program for communications is created on the host PC and E5ZN's parameters
are monitored or set from the host PC. In this manual, descriptions of communications
are given from the standpoint of the host PC.

5-1-2 Communications Specification


Transmission line connection: Multipoint
Communications method: RS-485 (Two-wire, half-duplex)
Synchronization method: Start-stop synchronization
Baud rate: 4.8 k, 9.6 k, 19.2 k, or 38.4 k bit/s
Communications code: ASCII
Word length: 7 or 8 bits
Stop bit length: 1 or 2 bits
Parity check: Vertical parity - None, Odd, or Even
BCC (block check character)
Start-stop synchronization data composition
Flow control: None
Interface: RS-485
Retry function: None
Note Default settings are underlined.

5-1-3 Communications Procedure


Communications between the Temperature Controller and the host PC are
implemented on a frame-by-frame basis.
When the host PC sends a command frame to the Temperature Controller, the
Temperature Controller returns to the host PC a response frame that corre-
sponds to the command frame.
Command and response frames are transmitted as follows:
Host PC
Com e
Co m e

fram
fram

framsponse

framsponse
m
m

and
and

e
Re

Re

Temperature Controller

Allow a minimum wait time of 5 ms from when the host PC receives the re-
sponse from the Temperature Controller until the host sends the next com-
mand.

60
Data Format Structure Section 5-2

5-2 Data Format Structure


Communications conforming to the CompoWay/F serial communications pro-
tocol involve transmission of blocks of data called frames. Those sent from
the host PC are command frames and those sent from the Temperature Con-
troller are response frames. The structure of these frames is shown below.
In the following frame description, the suffix H added to a numeric value, as in
02H, means the value is a hexadecimal number. And quotation marks around
an alphanumeric value, as in “00,” mean that the value is an ASCII character
set. The number underneath each delimiter in a frame indicates the number of
bytes.

5-2-1 Command Frame


FINS-mini
STX Node No. Sub- SID command text ETX BCC
address
02H “00” “0” 03H
1 2 2 1 1 1 byte

BCC calculation range

STX Code indicating the start of a command frame (02H). Be sure to


place this code in the first byte of a command frame.
Node No. Node ID specifying the destination of a command frame. Set this
No. to the unit number of the Temperature Controller.
If you want to broadcast a command, set the node number to
“XX.” No response is given from the Temperature Controllers for
broadcast commands.
Sub-address Not used for E5ZN. Always set the sub-address to “00.”
SID (Service ID) Not used for E5ZN. Always set the SID to “0.”
FINS-mini Command text
command text
ETX Code indicating the end of text (03H)
BCC Block Check Character
The result of a block check on the BCC calculation range is
stored in this field.

STX Node No. Sub- SID FINS-mini ETX BCC


address command text
02H 30H 30H 30H 30H 30H 30H 35H 30H 30H 03H 36H

BCC = 30H Å 30H Å 30H Å 30H Å 30H Å 30H Å 35H Å 30H Å 30H Å 03H = 36H
Å: XOR (exclusive OR) operation

Note How to Determine the BCC:


The BCC is determined by XOR operation on a byte-by-byte basis of the values within
the range from the node number field to the ETX field. The result (36H in the example
shown above) is placed in the BCC field.

61
Data Format Structure Section 5-2

5-2-2 Response Frame


STX Node No. Sub- End code FINS-mini ETX BCC
address response text
02H “00” 03H

1 2 2 2 1 1 byte

Note The Temperature Controller will not respond to any command frame that does not end
in the ETX and BCC.
STX Code indicating the start of a response frame (02H).
Be sure to place this code in the first byte of the response frame.
Node No. The node number is set to the value that was specified in the corre-
sponding command frame.
The unit number of the Temperature Controller that returns the
response is set in this field.
Sub-address Not used for E5ZN. This field is always set to “00.”
End code This field contains the result of execution of the corresponding com-
mand frame.
FINS-mini Response text
response text
ETX Code indicating the end of text (03H)
BCC Block Check Character
The result of a block check on the BCC calculation range is stored
in this field.

End Code
End Code name Description Error
code detection
priority
“0F” FINS command error The specified FINS command could 8
not executed.
“10” Parity error The sum of the bits (received data (1)) 2
does not match.
“11” Framing error The number of character stop bits for 1
the command frame was 0.
“12” Overrun error A data transfer was attempted when 3
the reception data buffer was already
full.
“13” BCC error The received BCC was different from 5
the calculated BCC
“14” Format error The command text contains charac- 7
ters other than “0” to “9” and “A” to “F.”
No SID and command text.
MRC and SRC in the command text
were not included in the command
text.
“16” Sub-address error No sub-address, SID, and command 6
text.This error is not covered by the
echoback test.
The size of the sub-address was less
than two characters, and no SID and
command text were found.
“18” Frame length error The size of the received frame 4
exceeded the specified number of
bytes.
“00” Normal completion The command was successfully exe- None
cuted.

62
Structure of Command/Response Text Section 5-3

5-3 Structure of Command/Response Text


The command/response text constitutes the main body of a command/
response frame. The structure of the command/response text is described
below.

Command Text The command text consists of the MRC (Main Request Code) and the SRC
(Sub Request Code), followed by the required data.
Node Sub- FINS-mini
STX No. address SID command text ETX BCC
02H “00” “0” 03H

MRC SRC Data

2 2 bytes

Response Text The response text consists of the MRC and SRC, followed by the MRES
(Main Response Code), the SRES (Sub Response Code), and the required
data.
Node Sub- End FINS-mini
STX No. address code response text ETXBCC
02H “00” 03H

MRC SRC MRES SRES Data

2 2 2 2 bytes

If the Temperature Controller fails to execute a specified command, it gener-


ates a response consisting of the MRC, SRC, MRES, and SRES only.

List of Services
MRC SRC Service name Description
“01” “01” Read from Variable Area This service reads from the variable
area.
“01” “02” Write to Variable Area This service writes to the variable area.
“01” “04” Read from Multiple Vari- This service performs non-consecutive
able Area multiple reads from the variable area.
“01” “13” Write to Multiple Variable This service performs non-consecutive
Area multiple writes to the variable area.
“05” “03” Read Controller Attribute This service reads the model number
and the communications buffer size.
“06” “01” Read Controller Status This service reads the run status of the
Controller.
“08” “01” Echoback Test This service performs the echoback
test.
“30” “05” Operation Commands This service performs RUN/STOP, AT
Execute/Cancel, Move for Setting Area
1, etc.

63
Variable Area Section 5-4

5-4 Variable Area


The section of memory in the Temperature Controller that holds the data to be
transmitted via communications is called the variable area. The variable area
is to read current process values or read/write parameter settings.
The variable area is not used for operation commands or for reading Control-
ler attributes.
E5ZN

nd Microcomputer
m ma
n co
ti o
era Variable area
Op

Data reading/writing

To specify the position of a variable in the variable area, use the variable type
and address.
Address
0000 0001 0002 0003 012C 012D 012E
Variable type C0
C1
C3
C5
C7

Variable

The address is a 4-digit hexadecimal code. Each variable contains an eight-


digit value in hexadecimal. Negative values are expressed as the two's com-
plement. When the current value of a variable is read as 105.0 on the main
indicator of the Temperature Controller, for example, its hexadecimal notation
is read in the form 0000041AH (the decimal point is ignored; 105.0 ® 1050 ®
0000041AH).
The variable area is mapped as shown below. The variable type is converted
to a 2-byte ASCII code and loaded to the frame. Available variable types are
shown in the following map.
00 E

00
1A

2D
2F

1A

2E
00 0
00 1
00 2
03

07

19

01 1
01 2
06

03

01 6
07

19
2
0
0
0

0
0

0
00

01
00

00

00
00

01
00

01

01
01

01
01

C0 ch1 PV etc. Not used ch2 PV etc. Not used

C1 ch1 SP etc. Not used ch2 SP, etc. Not used

C3 ch1 input Not used ch2 input


type etc. type etc.

C5 ch1 remote Not used ch2 remote


PV PV Not used

C7 ch1 remote Not used ch2 remote Not used


PV mode PV mode

Variable type C0: Read-only data for settings area 0 in double-word format
Variable type C1: Read/write data for settings area 0 in double-word format
Variable type C3: Read/write data for settings area 1 in double-word format
Variable type C5: Read/write data for settings area 0 in double-word format
Variable type C7: Read/write data for settings area 1 in double-word format

64
Read from Variable Area Section 5-5

5-5 Read from Variable Area


This service reads data from the variable area.

Command Command Text


Variable Read start Bit No. of
MRC SRC type address position elements
“01” “01” “00”
Command Text
2 2 2 4 2 4 bytes

Item Description
MRC/SRC Specify the FINS-mini command for reading a variable area.
Variable type Set this item to “C0,” “C1,” “C3,” “C5,” or “C7.”
Read start address Specify the read start address.
Bit position Not used for E5ZN. Always set this item to “00.”
No. of elements Set this item to the quantity of variables that are to be read (up
to 6). Not required for multiple reads.

Response Response Text


Response code
MRC SRC (MRES/SRES) Readout data
“01” “01”
2 2 4 No. or elements ´ 8 bytes (No. of
elements ´ 10 bytes for multiple reads)

Item Description
MRC/SRC This field returns the FINS-mini command text.
Response code This field contains the execution result of the command.
Readout data This field returns the values of the variables that have been
read out.

Response Codes
Response Code name Description
code
“1001” Command length over The command is too long.
“1002” Command length short The command is too short.
“1101” Area type error The specified variable type is invalid.
“110B” Response length over The number of elements exceeds 6.
“1100” Parameter error The bit position is set to a value other than
“00.”
“2203” Operation error EEPROM error
“0000” Normal completion The command was successfully executed.

65
Write to Variable Area Section 5-6

5-6 Write to Variable Area


This service writes data to the variable area.

Command Command Text


Variable Write start Bit No. of
MRC SRC type address position elements Writing data
“01” “02” “00”
2 2 2 4 2 4 bytes (No. of elements ´ 8) bytes

Item Description
MRC/SRC Specify the FINS-mini command for writing to a variable area.
Area type Set this item to “C1,” “C3,” “C5,” or “C7.”
Write start address Specify the write start address at this field.
Bit position Not used for E5ZN. Always set this item to “00.”
No. of elements Set this item to the quantity of variables that are to be written
(up to 6). Not required for multiple writes.
Data to be written Place the desired data in this field.

Response Response Text

Response code
MRC SRC (MRES/SRES)
“01” “02”
2 2 4

Item Description
MRC/SRC This field contains the same value (“01”/“02”) as specified in
the command text.
Response code This field contains the result of execution of the command.

Response Codes
Response Code name Description
code
“1002” Command length short The command is too short.
“1101” Area type error The specified variable type is invalid.
“1003” Data quantity mismatch A mismatch between the number of ele-
error ments and the quantity of variables occurs.
“1100” Parameter error The bit position is set to a value other than
“00.”
The value of data to be written is outside the
valid range.
“3003” Read only error An attempt is made to write data to an
address of variable type C0.
“2203” Operation error Communications writing is disabled.
An attempt is made to write data from setting
area 0 to setting area 1.
An attempt is made to write setting data at a
level other than protect level.
Executing AT.
An error occurs in EEPROM.
“0000” Normal completion The command was successfully executed.

66
Operation Commands Section 5-7

5-7 Operation Commands


To send an operation command to the Temperature Controller, set the items in
the command text as follows:

Command Command Text


MRC SRC Command Related
code information
“30” “05”
2 2 2 2 bytes

Item Description
MRC/SRC Specify the FINS-mini operation command (operation com-
mand service).
Command code Place a command code in this field.
Related information Place information related to the operation command in this
field.

E5ZN Command Codes


Command Command code Related information
code
“00” Communications writing “00” or “10”: OFF (disable)
“01” or “11”: ON (enable)
“01” RUN/STOP “00”: Run ch1
“01”: Stop ch1
“10”: Run ch2
“11”: Stop ch2
“02” Multi-SP “00”: Select SP0 for ch1
“01”: Select SP1 for ch1
“10”: Select SP0 for ch2
“11”: Select SP1 for ch2
“03” AT execute/cancel “00”: Stop ch1 AT
“01”: Execute ch1 AT
“10”: Stop ch2 AT
“11”: Execute ch2 AT
“04” Write mode “00” or “10”: Backup
“01” or “11”: RAM
“05” RAM data save “00” or “10”
“06” Software reset ”00” or “10”
“07” Move to setting area 1 ”00” or “10”
“08” Move to protect level ”00” or “10”
“09” Auto/manual “00”: Auto for ch1
“01”: Manual for ch1
“10”: Auto for ch2
“11”: Manual for ch2
“0A” PV hold ”00” or “10”
“0B” Parameter initialize ”00” or “10”

67
Operation Commands Section 5-7

Response Response Text


Response code
MRC SRC (MRES/SRES)
“30” “05”
2 2 4 bytes

Item Description
MRC/SRC This field contains the same value (“30”/“05”) as specified in
the command text.
Response code This field contains the execution result of the command.

Response Codes
Response Code name Description
code
“1001” Command length over The command is too long.
“1002” Command length short The command is too short.
“1100” Parameter error The command code or related information is
invalid.
“2203” Operation error Communications writing is disabled.
The specified operation cannot be executed.
For details, refer to 5-9 Commands and
Responses.
An error occurs in EEPROM.
“0000” Normal completion The command was successfully executed.

68
Setting Areas Section 5-8

5-8 Setting Areas


E5ZN Temperature Controllers can be set to either setting area 0 or setting
area 1.
Control operation is executed in setting area 0. In this state, you can perform
operations that are permitted only during control or those that cause no prob-
lems even if control is in progress. These operations include reading process
values, writing set points, and change RUN/STOP status.
Setting area 0, however, prohibits operations affect control, including writing
data at the initial setting level. (Reading setting data is always allowed.)
In setting area 1, control operation is stopped. In this state, you can perform
operations that are not allowed in setting area 0. These operations include
writing data at the initial setting level.
At power-ON, the Temperature Controller is set in setting area 0. To move to
setting area 1, use the “move-to-setting area 1” command. To return to setting
area 0, turn the power OFF and ON again, or use the “software reset” com-
mand.

Power ON
Software reset command

Setting area 0 Setting area 1


“Move-to-setting area
1” command

Control in progress Control stopped.

69
Commands and Responses Section 5-9

5-9 Commands and Responses


Various commands are provided for the application layer to implement ser-
vices, such as variable area reading/writing and operation commands, sup-
ported by the CompoWay/F communications protocol.
This section describes the commands provided for the application layer.

5-9-1 Read Monitor Value

Command Variable Bit No. of


MRC SRC type Address position elements
“01” “01” “C0” “00” “0001”

Address Monitor value Address Monitor value


ch Data name ch Data name
“0000” 1 Process value “0100” 2 Process value
“0001” Status “0101” Status
“0002” Internal set point “0102” Internal set point
“0003” Heater current value “0103” Heater current value
monitor monitor
“0004” MV monitor for heating “0104” MV monitor for heating
“0005” MV monitor for cooling “0105” MV monitor for cooling
“0006 PV hold value “0106” PV hold value

This command reads the current process value, status, or other monitor val-
ues. If the number of elements is set between “2” and “6”, consecutive
address monitor values can be read.
If the Temperature Controller is in setting area 1 when the command is
received, it returns a response with the “unknown” data for all data except
“status,” which shows the operation status.

Response MRC SRC Response code Data


“01” “01” “0000” Monitor value

Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-5 Read from Variable Area.

70
Commands and Responses Section 5-9

5-9-2 Read Setting Data

Command Variable Bit No. of


MRC SRC type Address position elements
“01” “01” “00” “0001”

Variable Address Setting data


type ch Description
“C1” “0000” to “0019” 1 Setting data for setting area 0
“0100” to “0119” 2
“C3” “0000” to “002E” 1 Setting data for setting area 1
“0100” to “012E” 2
“C5” “0000” 1 Setting data for setting area 0
“0100” 2
“C7” “0000” to “0001” 1 Setting data for setting area 1
“0100” to “0101’ 2

This command reads setting data. If the number of elements is set between
“2” and “6”, consecutive address setting data can be read.
Refer to 5-10 Variable Area Map for information on specifying variable types
and addresses.
This command can be used in either setting area 0 or 1.

Response MRC SRC Response code Data


“01” “01” “0000” Status

Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-5 Read from Variable Area.

71
Commands and Responses Section 5-9

5-9-3 Multiple Reads of Monitor Values/Setting Data

Command MRC SRC


Variable Bit Variable Bit
type Address position type Address position
“01” “04” “00” “00”
Variable Bit
type Address position
“00”

Variable Address Monitor value/setting data


type ch Description
“C0” “0000” to “0006” 1 Monitor value
“0100” to “0106” 2
“C1” “0000” to “0019” 1 Setting data for setting area 0
“0100” to “0119” 2
“C3” “0000” to “002E” 1 Setting data for setting area 1
“0100” to “012E” 2
“C5” “0000” 1 Setting data for setting area 0
“0100” 2
“C7” “0000” to “0001” 1 Setting data for setting area 1
“0100” to “0101’ 2

Multiple monitor values or setting data values can be read with the execution
of one command. Up to 5 values can be read, even if the addresses are not
consecutive.
Refer to 5-10 Variable Area Map for information on specifying variable types
and addresses.
This command can be used in either setting area 0 or 1.
No data will be read if an area type error or parameter error occurs in any of
the data.

Response Variable
MRC SRC Response code type Data
“01” “04” “0000” Type Monitor value/setting data
Variable
type Data
Type Monitor value/setting data

Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-5 Read from Variable Area.

72
Commands and Responses Section 5-9

5-9-4 Write Protect Level Setting Data

Command Variable Bit No. of


MRC SRC type Address position elements Data
“01” “02” “C1” “00” “0001” Protect level setting data

Address Setting data


“0000” Operation/adjustment protection
“0001” Initial setting/communication protec-
tion
“0002” Setting change protection
“0100” Operation/adjustment protection
“0101” Initial setting/communication protec-
tion
“0102” Setting change protection

This command writes protect level setting data. For details on protect levels,
refer to 6-3 Setup Level Configuration and Front Panel Keys.
This command can be used in setting area 0 only. If the Temperature Control-
ler is in setting area 1 when the command is received, it returns an error.
Before executing the command, use operation commands to enable writing
and to enter the protect level.

Response MRC SRC Response code


“01” “02” “0000”

Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-6 Write to Variable Area.

73
Commands and Responses Section 5-9

5-9-5 Write Setting Data

Command Variable Bit No. of


MRC SRC type Address position elements Data
“01” “02” “00” “0001” Setting data (setting area 1)

Variable Address Setting data


type ch Description
“C1” “0000” to “0019” 1 Setting data for setting area 0
“0100” to “0119” 2
“C3” “0000” to “002E” 1 Setting data for setting area 1
“0100” to “012E” 2
“C5” “0000” 1 Setting data for setting area 0
“0100” 2
“C7” “0000” to “0001” 1 Setting data for setting area 1
“0100” to “0101’ 2

This command writes setting data. If the number of elements is set between
“2” and “6”, consecutive address setting data can be written.
For details on addressing, refer to 5-10 Variable Area Map.
This command can be used in setting area 1 only. If the Temperature Control-
ler is in setting area 0 when the command is received, it returns an error.
Before executing the command, use operation commands to enable commu-
nications writing.
To save the operation/adjustment level setting data to internal non-volatile
memory, use the “write mode” operation command to set the write mode to
“backup.” If it is not set to backup mode, the setting data will not be stored
when the power is turned OFF. Refer to 6-3 Setup Level Configuration and
Front Panel Keys for details on the operation/adjustment level.

Response MRC SRC Response code


“01” “02” “0000”

Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-6 Write to Variable Area.

74
Commands and Responses Section 5-9

5-9-6 Multiple Writes of Setting Data

Command Variable Bit


MRC SRC type Address Data
position
“01” “13” “00” Setting data
Variable Bit
type Address position Data
“00” Setting data

Variable Address Setting data


type ch Description
“C1” “0000” to “0019” 1 Setting data for setting area 0
“0100” to “0119” 2
“C3” “0000” to “002E” 1 Setting data for setting area 1
“0100” to “012E” 2
“C5” “0000” 1 Setting data for setting area 0
“0100” 2
“C7” “0000” to “0001” 1 Setting data for setting area 1
“0100” to “0101’ 2

Multiple setting data can be written with the execution of one command. Up to
3 values can be written, even if the addresses are not consecutive.
Refer to 5-10 Variable Area Map for information on specifying variable types
and addresses.
Setting area 1 setting data can be written in setting area 1 only. An error will
be returned if this command is executed for setting area 0.
Before executing the command, use an operation command to enable com-
munications writing.
To save the operation/adjustment level setting data to internal non-volatile
memory, use the “write mode” operation command to set the write mode to
“backup.” If it is not set to backup mode, the setting data will not be stored
when the power is turned OFF. Refer to 6-3 Setup Level Configuration and
Front Panel Keys for details on the operation/adjustment level.

Response MRC SRC Response code


“01” “13” “0000”

Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-6 Write to Variable Area.

75
Commands and Responses Section 5-9

5-9-7 Communications Writing

Command MRC SRC CommandRelated


code information
“30” “05”

Related information Description


”00” or “10” Communications writing prohibited
”01” or “11” Communications writing not pro-
hibited

This command enables/disables communications writing.


It rewrites the setting for “communications writing.”
If communications writing is disabled, operation commands for parameter
rewriting, RUN/STOP, and other operations will be rejected.
Default is communications writing enabled.
This command can be used for setting area 0 or 1.

Response MRC SRC Response code


“30” “05” “0000”

Response code: The code shown above repres5nts normal completion. For
details on the response code, refer to 5-7 Operation Commands.

5-9-8 Control Start (RUN)/Control Stop (STOP)

Command MRC SRC Command Related


code information
“30” “05” “01”

Related Contents
information ch Control
“00” 1 RUN
“01” STOP
”10” 2 RUN
“11” STOP

This command starts and stops control (RUN/STOP).


This command can be used in either setting area 0 or 1.

Response MRC SRC Response code


“30” “05” “0000”

Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-7 Operation Commands.

76
Commands and Responses Section 5-9

5-9-9 Multi-SP

Command MRC SRC CommandRelated


code information
“30” “05” “02”

Related Contents
information ch Selected SP
“00” 1 SP 0
“01” SP 1
”10” 2 SP 0
“11” SP 1

This command switches between set points that have been set in advance for
SP 0 and SP1.
“No. of multi-SP uses” must be set to 0 and “Use multi-SP” must be set to ON.
This command can be used for either setting area 0 or 1.

Response MRC SRC Response code


“30” “05” “0000”

Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-7 Operation Commands.

5-9-10 AT Execute/Stop

Command MRC SRC CommandRelated


code information
“30” “05” “03”

Related Contents
information ch Instruction details
“00” 1 Stop
“01” Execute
”10” 2 Stop
“11” Execute

This command executes or stopped autotuning.


This command can be used in setting area 0 only. If it is used in setting area
1, an operation error will be returned. An operation error will also be returned
in the following cases.
• When the “RUN/STOP” parameter for the specified channel is set to
“STOP.”
• When ON/OFF control is being used.
Before executing the command, use an operation command to enable com-
munications writing.

Response MRC SRC Response code


“30” “05” “0000”

Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-7 Operation Commands.

77
Commands and Responses Section 5-9

5-9-11 Write Mode


CommandRelated
Command MRC SRC code information
“30” “05” “04”

Related information Contents


”00” or “10” Backup mode
”01” or “11” RAM write mode

This command selects backup mode and RAM write mode.


Default is RAM write mode.
This command can be used in either setting area 0 or 1.
Before executing the command, use an operation command to enable com-
munications writing.
Write mode Description
Backup mode When operation/adjustment level setting data write has been
performed via communications, the data is written to internal
non-volatile memory. Refer to 6-3 Setup Level Configuration
and Front Panel Keys for information on operation/adjustment
level.
RAM write mode When operation/adjustment level setting data write has been
performed via communications, the data is not written to inter-
nal non-volatile memory. However, if the data is changed using
the E5ZN-SDL Setting Display Unit key operations, it is written
to internal non-volatile memory. Refer to 6-3 Setup Level Con-
figuration and Front Panel Keys for information on operation/
adjustment level.

When switching from RAM write mode to backup mode, the operation/adjust-
ment level setting data is written to internal non-volatile memory. Refer to 6-3
Setup Level Configuration and Front Panel Keys for information on operation/
adjustment level.

Response MRC SRC Response code


“30” “05” “0000”

Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-7 Operation Commands.

78
Commands and Responses Section 5-9

5-9-12 RAM Data Save


CommandRelated
Command MRC SRC code information
“30” “05” “05”

”00” or “10”

This command writes operation/adjustment level setting data to internal non-


volatile memory. Refer to 6.3 6-3 Setup Level Configuration and Front Panel
Keys for information on operation/adjustment level.
This command can be used for either setting area 0 or 1.
Before executing the command, use an operation command to enable com-
munications writing.

Response MRC SRC Response code


“30” “05” “0000”

Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-7 Operation Commands.

5-9-13 Software Reset


CommandRelated
Command MRC SRC code information
“30” “05” “06”

”00” or “10”

This command triggers a software reset, which returns the Temperature Con-
troller to its initial state when it was turned ON.
This command can be used in either setting area 0 or 1.
Before executing the command, use an operation command to enable com-
munications writing.

Response The Temperature Controller does not return a response to this command.

79
Commands and Responses Section 5-9

5-9-14 Move to Setting Area 1

Command MRC SRC CommandRelated


code information
“30” “05” “07”

”00” or “10”

Use this command to move to setting area 1.


Use this command in setting area 0. If the Temperature Controller is in setting
area 1 when the command is received, the command is ignored.
If the set value of the “initial setting/communication protection” parameter is 2
(indicating that moving to initial setting or communications setting level is dis-
abled) when the Temperature Controller receives the command, the Tempera-
ture Controller returns an error.
Before executing this command, use an operation command to enable com-
munications writing.

Response MRC SRC Response code


“30” “05” “0000”

Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-7 Operation Commands.

5-9-15 Move to Protect Level


CommandRelated
Command MRC SRC code information
“30” “05” “08”

”00” or “10”

This command moves the Temperature Controller to the protect level. Refer to
6-3 Setup Level Configuration and Front Panel Keys for information on protect
level.
This command can be used in setting area 0 only. If the Temperature Control-
ler is in setting area 1 when the command is received, it returns an error.
Before executing the command, use an operation command to enable com-
munications writing.

Response MRC SRC Response code


“30” “05” “0000”

Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-7 Operation Commands.

80
Commands and Responses Section 5-9

5-9-16 Auto/Manual

Command MRC SRC CommandRelated


code information
“30” “05” “09”

Related Contents
information ch Operation mode
“00” 1 Auto
“01” Manual
”10” 2 Auto
“11” Manual

This command selects automatic/manual operation. It can be used when the


“PID/OnOff” parameter is set to PID.
This command can be used in either setting area 0 or 1.
Before executing the command, use an operation command to enable com-
munications writing.

Response MRC SRC Response code


“30” “05” “0000”

Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-7 Operation Commands.

5-9-17 PV Hold

Command MRC SRC CommandRelated


code information
“30” “05” “0A”

“00” or “10”

This command saves the present value when the command was executed in
the variable area.
This command can be used for setting area 0. If it is used in setting area 1, an
operation error will be returned.
Before executing the command, use an operation command to enable com-
munications writing.

Response MRC SRC Response code


“30” “05” “0000”

Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-7 Operation Commands.

81
Commands and Responses Section 5-9

5-9-18 Parameter Initialize


CommandRelated
Command MRC SRC code information
“30” “05” “0B”

”00” or “10”

This command returns all settings to the default values.


This command can be used for setting area 0. If it is used in setting area 1, an
operation error will be returned.
Before executing the command, use an operation command to enable com-
munications writing.

Response MRC SRC Response code


“30” “05” “0000”

Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-7 Operation Commands.

5-9-19 Read Controller Attribute

Command MRC SRC


“05” “03”

This command reads the model name and communication buffer size of the
Temperature Controller.
The command can be used regardless of what state the Temperature Control-
ler is in.

Response MRC SRC Response code Model name Buffer size


“05” “03” “0000” “0048”

Model name No. of control Control output Auxiliary Heater


points output burnout alarm
E5ZN-2QNH0 2 Pulse voltage Transistor out- Supported
output put (sinking)
E5ZN-2QPH0 2 Pulse voltage Transistor out- Supported
output put (sourcing)
E5ZN-2TNH0 2 Transistor out- Transistor out- Supported
put put (sinking)
E5ZN-2TPH0 2 Transistor out- Transistor out- Supported
put put (sourcing)

The model name is expressed in 10-byte ASCII.


A fixed value of “0048H” (72 bytes) for the buffer size is returned.
Response Code
Response Error name Description
code
“1001” Command length over The command is too long.
“2203” Operation error An error occurs in EEPROM.
“0000” Normal completion The command is successfully executed.

82
Commands and Responses Section 5-9

5-9-20 Read Controller Status

Command MRC SRC


“06” “01”

This command reads the operation status of the Temperature Controller.


The command can be used regardless of what state the Temperature Control-
ler is in.

Response MRC SRC Response code Operation


status
Related
information
“06” “01” “0000”

Operation status Description


“00” Control operating for all channels (No errors in setting area 0,
executing RUN.)
“01” Control has stopped for one channel (Errors other than errors
in setting area 0, not executing RUN.)

Related Information
7 6 5 4 3 2 1 0 Bit position
0 0 0 0 0

Value of bit
Status
0 1
Current exceeded Not Detected
detected
Current hold Not Detected
detected
Input error Not Detected
detected

If the Temperature Controller is in setting area 1 when the command is


received, it returns a response with “unknown” related information.
Response Code
Response Error name Description
code
“1001” Command length over The command is too long.
“2203” Operation error An error occurs in EEPROM.
“0000” Normal completion The command is successfully executed.

83
Commands and Responses Section 5-9

5-9-21 Echoback Test

Command MRC SRC Data to be tested


“08” “01” 0 to 23 bytes

This command performs an echoback test.


The command can be used regardless of the state of the Temperature Con-
troller.
Data to be checked must not exceed the communications data length.
Communication data length Description
7 bits 20H to 7EH converted to ASCII code
8 bits 20H to 7EH or A1H to FEH converted to ASCII code

Response MRC SRC Response code Data to be tested


“08” “01” “0000” 0 to 23 bytes

Response Code
Response Error name Description
code
“1001” Command length over The command is too long.
“2203” Operation error An error occurs in EEPROM.
“0000” Normal completion The command is successfully executed.

84
Variable Area Map Section 5-10

5-10 Variable Area Map


The variable area of the Temperature Controller is mapped in terms of vari-
able types and addresses as described below.
Variable type C0: Read-only data for setting area 0, including process val-
ues and status
Variable type C1: Setting data for setting area 0
Variable type C3: Setting data for setting area 1
Variable type C5: Setting data for setting area 0
Variable type C7: Setting data for setting area 1
Allocations for each variable are listed below.
A dash (-) in the “ch” column indicates data that is used by both channels.
Variable Address ch Monitor value Description
type
C0 0000 1 Process value Temperature: According to specified range for each sensor.
Analog:
Scaling lower limit - 5% FS to scaling upper limit + 5% FS
0001 Status Refer to page 86.
0002 Internal set point Lower value of set point limit to upper value of set point limit
0003 Heater current value 00000000H to 00000226H (0.0 to 55.0)
monitor
0004 MV monitor for heating Standard: FFFFFFCEH to 0000041AH (-5.0 to 105.0)
Heating/cooling: 00000000H to 0000041AH (0.0 to 105.0)
0005 MV monitor for cooling 00000000H to 0000041AH (0.0 to 105.0)
0006 PV hold value Temperature: According to specified range for each sensor
Analog:
Scaling lower limit - 5% FS to scaling upper limit + 5% FS
Value stored in internal non-volatile memory (RAM) when the
“PV hold” operation command was executed.
0100 2 Process value Temperature: According to specified range for each sensor
Analog:
Scaling lower limit - 5% FS to scaling upper limit 5% + FS
0101 Status Refer to page 86.
0102 Internal set point Lower value of set point limit to upper value of set point limit
0103 Heater current value 00000000H to 00000226H (0.0 to 55.0)
monitor
0104 MV monitor for heating Standard: FFFFFFCEH to 0000041AH (-5.0 to 105.0)
Heating/cooling: 00000000H to 0000041AH (0.0 to 105.0)
0105 MV monitor for cooling 00000000H to 0000041AH (0.0 to 105.0)
0106 PV hold value Temperature: According to specified range for each sensor
Analog:
Scaling lower limit - 5% FS to scaling upper limit + 5% FS
Value stored in internal non-volatile memory (RAM) when the
“PV hold” operation command was executed.

85
Variable Area Map Section 5-10

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit position
0 0 0 0 0 0

Value of bit
Status
0 1
Current exceeded Not detected Detected
Current hold Refresh Hold
Indicate range Not detected Detected
exceeded.
Input error Not detected Detected
Heating output OFF ON
Cooling output OFF ON
HB output OFF ON
Alarm output 1 OFF ON
Alarm output 2 OFF ON
Alarm output 3 OFF ON

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 Bit position
0 0 0 0 0 0 0 0

Value of bit
Status
0 1
Event input OFF ON
Write mode Backup RAM write
EEPROM (See RAM = EEPROM RAM ¹ EEPROM
Setting area Setting area 0 Setting area 1
AT execute/cancel AT canceled AT executing
RUN/STOP RUN STOP
Data writing Disable Enable
Auto/manual Automatic Manual

Note: EEPROM is the internal non-volatile

86
Variable Area Map Section 5-10

Variable Address ch Setting data name Description


type
C1 0000 - Operation/adjustment 00000000H (0): No restriction at the operation/adjustment
protection levels
00000001H (1): Moving to adjustment level is disabled.
00000002H (2): Only “PV” and “PV/SP” display and change
enabled.
00000003H (3): Only “PV” and “PV/SP” display enabled.
0001 Initial setting/communica- 00000000H (0): Moving to initial level/communications setting
tion protection level enabled and moving to advanced func-
tion setting level displayed.
00000001H (1): Moving to initial level/communications setting
level enabled and moving to advanced func-
tion setting level not displayed.
00000002H (2): Moving to initial setting/communications set-
ting levels is disabled.
0002 Setting change protection 00000000H (0): OFF (Setting changes using the E5ZN-SDL
enabled.)
00000001H (1): ON (Setting changes using the E5ZN-SDL
disabled.)
0003 1 Set point Lower value of set point limit to upper value of set point limit
0004 Alarm value 1 FFFFF831H to 0000270FH (-1999 to 1999)
0005 Alarm upper limit value 1 FFFFF831H to 0000270FH (-1999 to 1999)
0006 Alarm lower limit value 1 FFFFF831H to 0000270FH (-1999 to 1999)
0007 Alarm value 2 FFFFF831H to 0000270FH (-1999 to 1999)
0008 Alarm upper limit value 2 FFFFF831H to 0000270FH (-1999 to 1999)
0009 Alarm lower limit value 2 FFFFF831H to 0000270FH (-1999 to 1999)
000A Alarm value 3 FFFFF831H to 0000270FH (-1999 to 1999)
000B Manual manipulated Standard: FFFFFFCEH to 0000041AH (-5.0 to 105.0)
value Heating/cooling: FFFFFBE6H to 0000041AH (-105.0 to 105.0)
000C Heater burnout detection 00000000H to 000001F4H (0.0 to 50.0)
000D Set point 0 Lower value of set point limit to upper value of set point limit
000E Set point 1 Lower value of set point limit to upper value of set point limit
000F Temperature input offset FFFFF831H to 0000270FH (-199.9 to 999.9)
value
0010 Upper limit temperature FFFFF831H to 0000270FH (-199.9 to 999.9)
input offset value
0011 Lower limit temperature FFFFF831H to 0000270FH (-199.9 to 999.9)
input offset value
0012 Proportional band 00000001H to 0000270FH (0.1 to 999.9)
0013 Integral time 00000000H to 00000F9FH (0 to 3999)
0014 Derivative time 00000000H to 00000F9FH (0 to 3999)
0015 Cooling coefficient 00000001H to 0000270FH (0.01 to 99.99)
0016 Dead band FFFFF831H to 0000270FH (-199.9 to 999.9)
0017 Manual reset value 00000000H to 000003E8H (0.0 to 100.0)
0018 Heating hysteresis 00000000H to 0000270FH (0.1 to 999.9)
0019 Cooling hysteresis 00000000H to 0000270FH (0.1 to 999.9)

87
Variable Area Map Section 5-10

Variable Address ch Setting data name Description


type
C1 0100 - Operation/adjustment 00000000H (0): No restriction at the operation/adjustment
protection levels
00000001H (1): Moving to adjustment level is disabled.
00000002H (2): Only “PV” and “PV/SP” display and change
enabled.
00000003H (3): Only “PV” and “PV/SP” display enabled.
0101 Initial setting/communica- 00000000H (0): Moving to initial level/communications setting
tion protection level enabled and moving to advanced func-
tion setting level displayed.
00000001H (1): Moving to initial level/communications setting
level enabled and moving to advanced func-
tion setting level not displayed.
00000002H (2): Moving to initial setting/communication set-
ting levels is disabled.
0102 Setting change protection 00000000H (0): OFF (Setting changes using E5ZN-SDL
enabled.)
00000001H (1): ON (Setting changes using E5ZN-SDL dis-
abled.)
0103 2 Set point Lower value of set point limit to upper value of set point limit
0104 Alarm value 1 FFFFF831H to 0000270FH (-1,999 to 9,999)
0105 Upper limit alarm value 1 FFFFF831H to 0000270FH (-1,999 to 9,999)
0106 Lower limit alarm value 1 FFFFF831H to 0000270FH (-1,999 to 9,999)
0107 Alarm value 2 FFFFF831H to 0000270FH (-1,999 to 9,999)
0108 Upper limit alarm value 2 FFFFF831H to 0000270FH (-1,999 to 9,999)
0109 Lower limit alarm value 2 FFFFF831H to 0000270FH (-1,999 to 9,999)
010A Alarm value 3 FFFFF831H to 0000270FH (-1,999 to 9,999)
010B Manual manipulated vari- Standard: FFFFFFCEH to 0000041AH (-5.0 to 105.0)
able Heating/cooling: FFFFFBE6H to 0000041AH (-105.0 to 105.0)
010C Heater burnout detection 00000000H to 000001F4H (0.0 to 50.0)
010D Set point 0 Lower value of set point limit to upper value of set point limit
010E Set point 1 Lower value of set point limit to upper value of set point limit
010F Temperature input offset FFFFF831H to 0000270FH (-199.9 to 999.9)
value
0110 Upper limit temperature FFFFF831H to 0000270FH (-199.9 to 999.9)
input offset value
0111 Lower limit temperature FFFFF831H to 0000270FH (-199.9 to 999.9)
input offset value
0112 Proportional band 00000001H to 0000270FH (0.1 to 999.9)
0113 Integral time 00000000H to 00000F9FH (0 to 3999)
0114 Derivative time 00000000H to 00000F9FH (0 to 3999)
0115 Cooling coefficient 00000001H to 0000270FH (0.01 to 99.99)
0116 Dead band FFFFF831H to 0000270FH (-199.9 to 999.9)
0117 Manual reset value 00000000H to 000003E8H (0.0 to 100.0)
0118 Heating hysteresis 00000001H to 0000270FH (0.1 to 999.9)
0119 Cooling hysteresis 00000001H to 0000270FH (0.1 to 999.9)

88
Variable Area Map Section 5-10

Variable Address ch Setting data name Description


type
C3 0000 - Input type Platinum-resistance thermometer input type:
00000000H (0): Pt (-200 to 850°C or -300 to 1,500°F)
00000001H (1): Pt (-199.9 to 500.0°C or -199.9 to 900.0°F)
00000002H (2): Pt (0.0 to 100°C or 0.0 to 210.0°F)
00000003H (3): JPt (-199.9 to 500.0°C or -199.9 to 900.0°F)
00000004H (4): JPt (0.0 to 100.0°C or 0.0 to 210.0°F)
Thermocouple input type:
00000000H (0): K (-200 to 1,300°C or -300 to 2,300°F)
00000001H (1): K (-20.0 to 500.0°C or 0.0 to 900.0°F)
00000002H (2): J (-100 to 850°C or -100 to 1,500°F)
00000003H (3): J (-20.0 to 400.0°C or 0.0 to 750.0°F)
00000004H (4): T (-200 to 400°C or -300 to 700°F)
00000005H (5): E (0 to 600°C or 0 to 1,100°F)
00000006H (6): L (-100 to 850°C or -100 to 1,500°F)
00000007H (7): U (-200 to 400°C or -300 to 700°F)
00000008H (8): N (-200 to 1,300°C or -300 to 2,300°F)
00000009H (9): R (0 to 1,700°C or 0 to 3,000°F)
0000000AH (10): S (0 to 1,700°C or 0 to 3,000°F)
0000000BH (11): B (100 to 1,800°C or 300 to 3,200°F)
0000000CH (12): Non-contact temperature sensor (K10 to
70°C)
0000000DH (13): Non-contact temperature sensor (K60 to
120°C)
0000000EH (14): Non-contact temperature sensor (K115 to
165°C)
0000000FH (15): Non-contact temperature sensor (K160 to
260°C)
00000010H (16): 0 to 50 mV
00000011H (17): T (-199.9 to 400.0°C or -199.9 to 700.0°F)
00000012H (18): U (-199.9 to 400.0°C or -199.9 to 700.0°F)
0001 1 Scaling upper limit value Scaling lower limit + 1 to 0000270FH (scaling lower limit + 1 to
9,999)
0002 Scaling lower limit value FFFFF831H to scaling upper limit -1 (-1,999 to scaling upper
limit - 1)
0003 Decimal point position 00000000H to 00000001H (0 to 1)
0004 - Temperature units 00000000H (0): °C
00000001H (1): °F
0005 1 Set point upper limit Temperature: Set point lower limit + 1 to input range upper limit
value Analog: Set point lower limit + 1 to scaling upper limit
0006 Set point lower limit value Temperature: Input range lower limit to set point upper limit - 1
Analog: Scaling lower limit to set point upper limit -1
0007 PID/OnOff 00000000H (0): ON/OFF
00000001H (1): 2-PID control
0008 Heating control period 00000001H to 00000063H (1 to 99)
0009 Cooling control period 00000001H to 00000063H (1 to 99)
000A Direct/reverse operation 00000000H (0): Reverse operation
00000001H (1): Direct operation

89
Variable Area Map Section 5-10

Variable Address ch Setting data name Description


type
C3 000B 1 Alarm 1 type 00000000H (0): No alarm function
00000001H (1): Upper and lower limit alarm
00000002H (2): Upper limit alarm
00000003H (3): Lower limit alarm
00000004H (4): Upper and lower limit range alarm
00000005H (5): Upper and lower limit alarm with standby
sequence
00000006H (6): Upper limit alarm with standby sequence
00000007H (7): Lower limit alarm with standby sequence
00000008H (8): Absolute value upper limit alarm
00000009H (9): Absolute value lower limit alarm
0000000AH (10): Absolute value upper limit alarm with
standby sequence
0000000BH (11): Absolute value lower limit alarm with standby
sequence
000C Alarm 2 type Same as for alarm 1 type
000D Alarm 3 type Same as for alarm 1 type
000E - Control output 1 alloca- 00000000H (0): Heating control output for ch1
tion 00000001H (1): Cooling control output for heating/cooling
control for ch1
00000002H (2): Alarm 1 and HB alarm OR output for ch1
00000003H (3): Alarm 2 output for ch1
00000004H (4): Alarm 3 output for ch1
00000005H (5): Heating control output for ch2
00000006H (6): Cooling control output for heating/cooling
control for ch2
00000007H (7): Alarm 1 and HB alarm OR output for ch2
00000008H (8): Alarm 2 output for ch2
00000009H (9): Alarm 3 output for ch2
000F Control output 2 alloca- Same as for control output 1 allocation
tion
0010 Auxiliary output 1 alloca- Same as for control output 1 allocation
tion
0011 Auxiliary output 2 alloca- Same as for control output 1 allocation
tion
0012 Operation after power ON 00000000H (0): Stop
00000001H (1): Continue (Continues the operation status
from before the power supply was stopped.)
0013 Communications data 00000007H (7): 7
length 00000008H (8): 8
0014 Communications stop bit 00000001H (1): 1
00000002H (2): 2
0015 Communications parity 00000000H (0): None
00000001H (1): Even
00000002H (2): Odd
0016 Communications 00000000H to 0000270FH (0 to 9,999)
response transmission
wait time
0017 No. of multi-SP uses 00000000H (0): No multi-SP
00000001H (1): Switch between SP0/1
0018 Event input function 00000000H (0): Non
00000001H (1): RUN/STOP
0019 Use multi-SP 00000000H (0): OFF
00000001H (1): ON

90
Variable Area Map Section 5-10

Variable Address ch Setting data name Description


type
C3 001A 1 SP ramp setting 00000000H (0): OFF
00000001H to 0000270FH (1 to 9,999)
001B - Standby sequence 00000000H (0): Condition A
restart 00000001H (1): Condition B
001C 1 Alarm 1 open for alarm 00000000H (0): Closed
00000001H (1): Open
001D Alarm 1 hysteresis 00000001H to 0000270FH (0.1 to 999.9)
001E 1 Alarm 2 open for alarm 00000000H (0): Closed
00000001H (1): Open
001F Alarm 2 hysteresis 00000001H to 0000270FH (0.1 to 999.9)
0020 Alarm 3 open for alarm 00000000H (0): Closed
00000001H (1): Open
0021 Alarm 3 hysteresis 00000001H to 00002702FH (0.1 to 999.9)
0022 - Use heater burnout 00000000H (0): OFF
00000001H (1): ON
0023 Heater burnout latch 00000000H (0): OFF
00000001H (1): ON
0024 1 Heater burnout hystere- 00000001H to 000001F4H (0.1 to 50.0)
sis
0025 - a 00000000H to 00000064H (0.00 to 1.00)
0026 1 MV upper limit Standard: Manipulated variable lower limit + 0.1 to 0000041AH
(manipulated variable lower limit + 0.1 to 105.0)
Heating/cooling: 00000000H to 0000041AH (0.0 to 105.0)
0027 MV lower limit Standard: FFFFFFCEH to manipulated variable upper limit -
0.1 (-5.0 to manipulated variable upper limit - 0.1)
Heating/cooling: FFFFFBE6H to 00000000H (105.0 to 0.0)
0028 Input digital filter 00000000H to 0000270FH (0.0 to 999.9)
0029 - Additional PV display 00000000H (0): OFF
00000001H (1): ON
002A Temperature input offset 00000000H (0): OFF
display add 00000001H (1): ON
002B 1 Alarm 1 latch 00000000H (0): OFF
00000001H (1): ON
002C Alarm 2 latch 00000000H (0): OFF
00000001H (1): ON
002D Alarm 3 latch 00000000H (0): OFF
00000001H (1): ON
002E - Cold junction compensa- 00000000H (0): OFF
tion method 00000001H (1): ON

91
Variable Area Map Section 5-10

Variable Address ch Setting data name Description


type
C3 0100 - Input type Platinum-resistance thermometer input type:
00000000H (0): Pt (-200 to 850°C or -300 to 1,500°F)
00000001H (1): Pt (-199.9 to 500.0°C or -199.9 to 900.0°F)
00000002H (2): Pt (0.0 to 100°C or 0.0 to 210.0°F)
00000003H (3): JPt (-199.9 to 500.0°C or -199.9 to 900.0°F)
00000004H (4): JPt (0.0 to 100.0°C or 0.0 to 210.0°F)
Thermocouple input type:
00000000H (0): K (-200 to 1,300°C or -300 to 2,300°F)
00000001H (1): K (-20.0 to 500.0°C or 0.0 to 900.0°F)
00000002H (2): J (-100 to 850°C or -100 to 1,500°F)
00000003H (3): J (-20.0 to 400.0°C or 0.0 to 750.0°F)
00000004H (4): T (-200 to 400°C or -300 to 700°F)
00000005H (5): E (0 to 600°C or 0 to 1,100°F)
00000006H (6): L (-100 to 850°C or -100 to 1,500°F)
00000007H (7): U (-200 to 400°C or -300 to 700°F)
00000008H (8): N (-200 to 1,300°C or -300 to 2,300°F)
00000009H (9): R (0 to 1,700°C or 0 to 3,000°F)
0000000AH (10): S (0 to 1,700°C or 0 to 3,000°F)
0000000BH (11): B (100 to 1,800°C or 300 to 3,200°F)
0000000CH (12): Non-contact temperature sensor (K10 to
70°C)
0000000DH (13): Non-contact temperature sensor (K60 to
120°C)
0000000EH (14): Non-contact temperature sensor (K115 to
165°C)
0000000FH (15): Non-contact temperature sensor (K160 to
260°C)
00000010H (16): 0 to 50 mV
00000011H (17): T (-199.9 to 400.0°C or -199.9 to 700.0°F)
00000012H (18): U (-199.9 to 400.0°C or -199.9 to 700.0°F)
0101 2 Scaling upper limit value Scaling lower limit + 1 to 0000270FH (scaling lower limit + 1 to
9,999)
0102 Scaling lower limit value FFFFF831H to scaling upper limit -1 (-1,999 to scaling upper
limit - 1)
0103 Decimal point position 00000000H to 00000001H (0 to 1)
0104 - Temperature units 00000000H (0): °C
00000001H (1): °F
0105 2 Set point upper limit Temperature: Set point lower limit + 1 to input range upper limit
Analog: Set point lower limit + 1 to scaling upper limit
0106 Set point lower limit Temperature: Input range lower limit to set point upper limit - 1
Analog: Scaling lower limit to set point upper limit -1
0107 PID/ OnOff 00000000H (0): ON/OFF
00000001H (1): 2-PID control
0108 Heating control period 00000001H to 00000063H (1 to 99)
0109 Cooling control period 00000001H to 00000063H (1 to 99)
010A Direct/reverse operation 00000000H (0): Reverse operation
00000001H (1): Direct operation

92
Variable Area Map Section 5-10

Variable Address ch Setting data name Description


type
C3 010B 2 Alarm 1 type 00000000H (0): No alarm function
00000001H (1): upper and lower limit alarm
00000002H (2): Upper limit alarm
00000003H (3): Lower limit alarm
00000004H (4): upper and lower limit range alarm
00000005H (5): upper and lower limit alarm with standby
sequence
00000006H (6): Upper limit alarm with standby sequence
00000007H (7): Lower limit alarm with standby sequence
00000008H (8): Absolute value upper limit alarm
00000009H (9): Absolute value lower limit alarm
0000000AH (10): Absolute value upper limit alarm with
standby sequence
0000000BH (11): Absolute value lower limit alarm with standby
sequence
010C Alarm 2 type Same as for alarm 1 type
010D Alarm 3 type Same as for alarm 1 type
010E - Control output 1 alloca- 00000000H (0): Heating control output for ch1
tion 00000001H (1): Cooling control output for heating/cooling
control for ch1
00000002H (2): Alarm 1 and HB alarm OR output for ch1
00000003H (3): Alarm 2 output for ch1
00000004H (4): Alarm 3 output for ch1
00000005H (5): Heating control output for ch2
00000006H (6): Cooling control output for heating/cooling
control for ch2
00000007H (7): Alarm 1 and HB alarm OR output for ch2
00000008H (8): Alarm 2 output for ch2
00000009H (9): Alarm 3 output for ch2
010F Control output 2 alloca- Same as for control output 1 allocation
tion
0110 Auxiliary output 1 alloca- Same as for control output 1 allocation
tion
0111 Auxiliary output 2 alloca- Same as for control output 1 allocation
tion
0112 Operation after power ON 00000000H (0): Stop
00000001H (1): Continue (Continues the operation status
from before the power supply was stopped.)
0113 Communications data 00000007H (7): 7
length 00000008H (8): 8
0114 Communications stop bit 00000001H (1): 1
00000002H (2): 2
0115 Communications parity 00000000H (0): None
00000001H (1): Even
00000002H (2): Odd
0116 Communications 00000000H to 0000270FH (0 to 9,999)
response transmission
wait time
0117 No. of multi-SP uses 00000000H (0): No multi-SP
00000001H (1): Switch between SP0/1
0118 Event input allocation 00000000H (0): Non
00000001H (1): RUN/STOP
0119 Use multi-SP 00000000H (0): OFF
00000001H (1): ON

93
Variable Area Map Section 5-10

Variable Address ch Setting data name Description


type
C3 011A 2 SP ramp setting 00000000H (0): OFF
00000001H to 0000270FH (1 to 9,999)
011B - Standby sequence 00000000H (0): Condition A
restart 00000001H (1): Condition B
011C 2 Alarm 1 open for alarm 00000000H (0): Closed
00000001H (1): Open
011D Alarm 1 hysteresis 00000001H to 0000270FH (0.1 to 999.9)
011E 2 Alarm 2 open for alarm 00000000H (0): Closed
00000001H (1): Open
011F Alarm 2 hysteresis 00000001H to 0000270FH (0.1 to 999.9)
0120 Alarm 3 open for alarm 00000000H (0): Closed
00000001H (1): Open
0121 Alarm 3 hysteresis 00000001H to 0000270FH (0.1 to 999.9)
0122 - Use heater burnout 00000000H (0): OFF
00000001H (1): ON
0123 Heater burnout latch 00000000H (0): OFF
00000001H (1): ON
0124 2 Heater burnout hystere- 00000001H to 000001F4H (0.1 to 50.0)
sis
0125 - a 00000000H to 00000064H (0.00 to 1.00)
0126 2 MV upper limit value Standard: Manipulated variable lower limit + 0.1 to 0000041AH
(manipulated variable lower limit + 0.1 to 105.0)
Heating/cooling: 00000000H to 0000041AH (0.0 to 105.0)
0127 MV lower limit value Standard: FFFFFFCEH to manipulated variable upper limit -
0.1 (-5.0 to manipulated variable upper limit - 0.1)
Heating/cooling: FFFFFBE6H to 00000000H (105.0 to 0.0)
0128 Input digital filter 00000000H to 0000270FH (0.0 to 999.9)
0129 - Additional PV display 00000000H (0): OFF
00000001H (1): ON
012A Temperature input offset 00000000H (0): OFF
display add 00000001H (1): ON
012B 2 Alarm 1 latch 00000000H (0): OFF
00000001H (1): ON
012C Alarm 2 latch 00000000H (0): OFF
00000001H (1): ON
012D Alarm 3 latch 00000000H (0): OFF
00000001H (1): ON
012E - Cold junction compensa- 00000000H (0): OFF
tion method 00000001H (1): ON
C5 0000 1 Remote PV Temperature: According to specified range for each sensor
Analog:
Scaling lower limit - 5% FS to scaling upper limit + 5% FS
0100 2 Remote PV Temperature: According to specified range for each sensor
Analog:
Scaling lower limit - 5% FS to scaling upper limit + 5% FS

94
Variable Area Map Section 5-10

Variable Address ch Setting data name Description


type
C7 0000 - Remote PV mode 00000000H (0): OFF (normal mode)
00000001H (1): ON (remote PV mode)
0001 - Remote PV communica- 00000000H to 0000270F (0 to 9,999) ms
tions wait time
0100 - Remote PV mode 00000000H (0): OFF (normal mode)
00000001H (1): ON (remote PV mode)
0101 - Remote PV communica- 00000000H to 0000270F (0 to 9,999) ms
tions wait time

95
Variable Area Map Section 5-10

96
SECTION 6
Using the E5ZN-SDL

6-1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
6-1-1 Outline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
6-1-2 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
6-1-3 System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
6-2 Names of Parts on the Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
6-2-1 Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
6-2-2 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
6-2-3 Using the Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
6-2-4 Main Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
6-3 Setup Level Configuration and Front Panel Keys . . . . . . . . . . . . . . . . . . . . . . 102
6-4 Initial Setup Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
6-5 Using Copy Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
6-5-1 Parameter Copy Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
6-6 List of Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108

97
Introduction Section 6-1

6-1 Introduction
6-1-1 Outline
The E5ZN-SDL Setting Display Unit is used to set and display parameters for
E5ZN Temperature Controllers.
Using the E5ZN-SDL simplifies the initial settings and maintenance of the
E5ZN.

6-1-2 Preparation
The E5ZN-SDL uses serial communications to display the settings for the
E5ZN Temperature Controller.
Connect the E5ZN-SDL to the E5ZN-SCT24S-500. There is no connection
terminal on the E5ZN-SCT18S-500.
Input power
supply
24 VDC
19
20
+ -

8 7 6 5
B (+)
4 21
RS-485
communications
with the E5ZN

9 3 A (-)
22
10 11 1 2
P2CF-11 or P3GA-11 E5ZN-SCT24S-500

Note 1. Connections between terminals 4 and 9, 7 and 11, and 8 and 10 are made inside
the E5ZN-SDL. Refer to the following connection diagram.
2. Do not connect anything to terminals 1, 2, 5, or 6.

E5ZN-SCT24S-500 Do not
use.
6 7
-

(+) 5 Input
power
24V DC

21 (RS-485)
B
4 8 +

22 A
(-)
3 9
2 10 +
Do not
use. 1 11 -

98
Introduction Section 6-1

6-1-3 System Configuration


Unit No. setting Unit No. settings Unit No. settings

E5ZN-2 E5ZN-2 E5ZN-2

Channel 1

Channel 2

Channel 1

Channel 2

Channel 1

Channel 2
100 to 125 9
terminator Side
(1/2 W) Communi- Communi- Communi- connector
cations cations cations
E5ZN-SDL

RS-485
E5ZN-SCT24S-500 E5ZN-SCT18S-500 E5ZN-SCT18S-500

• The RS-485 connection can be either one-to-one to one-to-N. Up to 16


units can be connected in one-to-N systems
• Keep the total cable length to 500m maximum.
• Attach a terminator to both ends of the transmission path.
Note Communications with the E5ZN-SDL will be cut if the E5ZN-2 connection to the E5ZN-
SCT24S-500 is broken
The E5ZN Temperature Controller and the E5ZN-SDL are connected by serial
communications. When connecting multiple E5ZN Temperature Controllers,
set a different unit number for each one.
The E5ZN-SDL recognizes the E5ZN Temperature Controllers by the unit
numbers. Use the UNIT Key on the E5ZN-SDL to set the unit number of the
E5ZN Temperature Controller to be set and displayed on the E5ZN-SDL.
The E5ZN-2 Temperature Controller has two channel input channels.
Use the CH Key to set the E5ZN-SDL channel number to be displayed.

99
Names of Parts on the Front Panel Section 6-2

6-2 Names of Parts on the Front Panel


6-2-1 Front Panel
Temperature unit

SUB1
SUB2
SUB3 PV
Operation SUB4
indicators No.1 display
OUT1
OUT2 SV
STOP
CMW No. 2
UNIT/CH display UNIT/CH

Up key
Level key
UNIT Down key
COPY CH
E5ZN-SDL

Mode Key UNIT Key COPY Key CH Key

6-2-2 Display

No.1 Display Displays the type of process value or parameter for the E5ZN Temperature
Controller.

No. 2 Display Displays the process value, read value for the parameter, and the input value
when settings are changed for the E5ZN Temperature Controller.

Temperature Unit The temperature unit is displayed when the display unit parameter for the
E5ZN Temperature Controller is set to a temperature. Indication is determined
by the current set value of the “temperature unit” parameter. When this
parameter is set to °C, “c” is displayed, and when set to °F, “f” is displayed.

Operation Indicators
1,2,3... 1. SUB1 (auxiliary output 1)
Lit when the auxiliary output 1 function is ON.
SUB2 (auxiliary output 2)
Lit when the auxiliary output 2 function is ON.
SUB3 (auxiliary output 3)
Not used with the E5ZN Temperature Controller. Always not lit.
SUB4 (auxiliary output 4)
Not used with the E5ZN Temperature Controller. Always not lit.
2. OUT1 (control output 1)
Lit when the control output 1 function is ON.
OUT2 (control output 2)
Lit when the control output 2 function is ON.
3. STOP (stop)
Lit when operation for the selected channel is stopped. Lit when the “RUN/
STOP” parameter is set to STOP. Not lit at all other times.
4. CMW (Communications writing control)
Lit when communications writing is enabled and not lit when writing is dis-
abled.

100
Names of Parts on the Front Panel Section 6-2

5. UNIT/CH display
Displays the E5ZN Temperature Indicator unit number and channel num-
ber that will be set and displayed on the E5ZN-SDL.
When facing the front panel, the unit number (0 to F) is displayed on the
left and the channel number (1 to 2, U) is displayed on the right.
When the channel number is “U,” the setting and display is used by both
channels.

6-2-3 Using the Keys

Level Key Press this key to select the setting levels.

Mode Key Press this key to select parameters within each level.

Up Key Each press of this key increments values displayed on the No. 2 display. Hold-
ing down this key continuously increments values.
Alternatively, the display moves to the next setting item.

Down Key Each press of this key decrements values displayed on the No. 2 display.
Holding down this key continuously decrements values.
Alternatively, the display moves back one setting item.

Level Key + Mode Key This key combination sets the E5ZN to the “protect level.” For details on the
protect level, refer to 6-3 Setup Level Configuration and Front Panel Keys.

UNIT Key Each press of this key increments the unit number.
Select the E5ZN Temperature Controller unit number to set for the E5ZN-SDL.

CH Key Each press of this key changes the channel number.


The channel number cannot be selected when the channel number display for
the E5ZN Temperature Controller is “U” because the setting is used by both
channels.

COPY Key Press this key to read all E5ZN Temperature Controller set values to the
E5ZN-SDL or to write all set values to the E5ZN from the E5ZN-SDL.

6-2-4 Main Functions

Display The process value and set values for the E5ZN Temperature Controller as
well as other data and control outputs, auxiliary outputs, and other status
information can be displayed.

Settings The parameters and control operations for the E5ZN Temperature Controller
can be changed.

Copy All settings for the E5ZN Temperature Controller can be read and saved to the
E5ZN-SDL. Also, all the settings for the E5ZN Temperature Controller that
were saved in the E5ZN-SDL can be written to the E5ZN Temperature Con-
troller.

101
Setup Level Configuration and Front Panel Keys Section 6-3

6-3 Setup Level Configuration and Front Panel Keys


Parameters are divided into groups called levels. Each of the set values
(setup items) in these levels are called a parameter. The parameters on the
E5ZN are divided into the following seven levels:

Power ON
Normal mode

Copy
mode
Operation level Adjustment level
Level Key
Less than
1 second Level + Level +
Mode Keys Mode Keys
1 second 3 seconds
Level Key Level Key min.
1 second
Level Key
3 seconds
25 The PV display flashes
min. min. 100 after one second.
Control stops.
Copy Key
Less
than
1 second Initial Communica-
setting level Level Key tions setting level
Less than Protect level
1 second
Level Key Password input
1 second min. set value “-169”
Control in progress
Copy Key Advanced function
1 second setting level Control stopped
min.

Mode/Level Control in Control


progress stopped
Normal Protect level OK -
mode Operation level OK -
Adjustment level OK -
Initial setting level - OK
Advanced function setting level - OK
Communications setting level - OK
Copy mode - OK

OK: Indicates items that can be set.


Note To move to the advanced function setting level, set the “initial setting/communications
protection” parameter in the “protect level” to “0.”
Of these levels in normal mode, the initial setting level, communications set-
ting level, and advanced function setting level can be used only when control
has stopped. Controller outputs are stopped when any of these four levels are
selected.
It is possible to enter copy mode while Controller outputs are being made, but
copy operations (e.g., upload, download) can by used only when control has
stopped.

102
Setup Level Configuration and Front Panel Keys Section 6-3

Protect Level To move the mode to this level, simultaneously press the Level and Mode
Keys for at least three seconds in the operation level or adjustment level. This
level is for preventing unwanted or accidental modification of parameters. Pro-
tected levels will not be displayed, and so the parameters in that level cannot
be modified.

Operation Level • This level is initially displayed when you turn ON the power to the E5ZN.
You can move to the protect level, initial setting level, and adjustment
level from this level.
• During operation, the process value, set point, and manipulated variable
can be monitored, and the set point, alarm value and upper and lower
limit alarms can be monitored and modified.

Adjustment Level • To move the mode to this level, press the Level Key for less than one sec-
ond.
• This level is for entering set values and offset values for control. This level
contains parameters for setting the autotuning, communications writing
enable/disable, hysteresis, multi-SP, input shift values, heater burnout
alarm (HBA) settings, PID constants, etc. You can move to the top param-
eter of the initial setting level and operation level from here.

Initial Setting Level To move the mode to this level, press the Level Key for at least three seconds
in the operation level or adjustment level. The first display flashes after one
second. This level is for specifying the input type, selecting the control
method, control period, setting direct/reverse action and alarm type. You can
move to the advanced function setting level or communications setting level
from this level. To return to the operation level, press the Level Key for at least
one second. To move to the communications setup level, press the Level Key
for less than one second.
The display will be blank “----” when you move from the initial setting level to
the operation level.

Advanced Function • To enter this level, you must enter the password “-169” in the initial setting
Setting Level level.
• You can move to the initial setting level only from this level.
• This level is for setting the MV limits, event input assignment, standby
sequence, alarm hysteresis, and other parameters.

Communications To move to this level, press the Level Key for less than one second in the initial
Setting Level setting level. When the communications settings are to used, set the commu-
nications conditions in this level. Communicating with a personal computer
(host computer) allows set points to be read and written, and manipulated
variables to be monitored.

103
Initial Setup Examples Section 6-4

6-4 Initial Setup Examples


On previous Controllers, the sensor input type, alarm type, and control period
were set on DIP switches. These hardware settings are now set using the
setup menus of the E5ZN-SDL. The Level and Mode Keys are used to switch
between setup menus, and the amount of time that you hold the keys down
determines which setup menu you move to.

Typical Usage Example


Changing parameters
: indicates that there are more parameters.
in-t Continue to press the Mode Key until the
0 in-h desired parameter is reached.
100 Mode Key
Mode Key
in-l
0 Mode Key Changing numerals

cntl °c Use the Up and Down Keys


25
cntl to change numeric data.
pid pid 0

104
Initial Setup Examples Section 6-4

Typical Example 1
Setup procedure
Input type: 0 (K thermocouple -200 to 1,300°C)
Power ON Power ON
Control method:ON/OFF control
Alarm type: 2 (upper limit)
Alarm value 1: 20°C Operation level
Set point: 100°C
E5ZN Unit No.:3 °c 25 Process
Channel No.: 1 value/set
01 0 point

Match UNIT/CH using


the UNIT and CH Keys.
Set unit No. °c 25
31 0
Set channel No. Press Level Key for at
least three seconds.
Initial setting level Control stops.
Initial setting level

Set input specifications Check input in-t Input type 0


3u 0
Mode Key In ON/
Set control specifications OFF
Use the Up and
Down Keys to cntl control onof
select ON/OFF 31 onof In PID pid
control. control
Set alarm type Mode Key

Check alarm alt1 Alarm 1 2


type
type.
31 2
Mode Key

Press Level Key for at


Operation level least one second.
Operation level
Press Up and °c 25
Set alarm values Down Keys to Process 100
set the set 31 100 value/set
point
point to 100°C.
Mode Key

Press Up and °c
Down Keys to al-1
20 Alarm 20
set alarm 31 value 1
value to 20°C.
Mode Key
Use the Up and r-5 During run run
Down Keys to
select “RUN.” 31 run During stop stop

Mode Key

Start operation
Start operation

105
Initial Setup Examples Section 6-4

Typical Example 2
Input type: 4 (T thermocouple -200 to 400°C) E5ZN unit No.:1
Control method:PID control Channel: 2
Calculate PID constants by autotuning.
Alarm type: 2 (upper limit)
Alarm value 1:30°C
Set point: 150°C
Setup procedure Power ON

Power ON Operation level

°c 25 Process value/
0 set point
01

Use the UNIT Key


to match the unit
°c 25
Set unit No. 11 0
Use the CH Key
to match the
Set channel No.
°c 25
12 0
Press Level Key for at least
three seconds.
Initial setting level Control stops.
Initial setting level
Use the Up
Set input specifications and Down in-t Input type 4
Keys to set the 12 4
input type to 4.

Set control specifications


method Use the Up and In ON/OFF onof
Down Keys to cntl control
Set pid for
check that the 12 pid In PID pid PID control.
mode is PID
control. control
Set alarm type The recommended
Check the Heating control setting for relay
control
cp period (unit: operation is 20 s and
period. 12 2 seconds) 2 for voltage/ transistor
output, 2 s.
Check alarm Alarm 1 type 2
type. alt1
12 2

Press Level Key for at


Operation level least one second.
Operation level
Press Up nd °c
Set alarm values Down Keys to 25 Process 150
value/set
set the set 12 150 point
point to

Press Up and
Down Keys to °c al-1 Alarm value 1 30
set alarm 12 30
value to 30°C.

Use the Up
PV/SP
and Down r-5 During run run
After AT execution
Keys to select 12 run During stop stop
°c 25 “RUN.”
100
During AT execution Press Level Key for
Adjustment level °c 25 less than 1 second.
Adjustment level
100 Select “ON:
AT execution Execute at To execute AT on execute AT” to
While AT is being autotuning.
executed, SP will flash 12 off execute AT and
To cancel AT off
(when PID After AT execution “OFF: stop AT” to
control is at Press Level Key for stop AT.
selected) off less than 1 second.
During AT execution
Start operation Start control after AT
at completed.
on

106
Using Copy Mode Section 6-5

6-5 Using Copy Mode


6-5-1 Parameter Copy Operations

Upload (Temperature
Controller to Setting
Display Unit) copy
0 up

UNIT
COPY CH

1,2,3... 1. Press the COPY Key for at least one second to move to the copy mode.
2. Use the Up and Down Keys to select “UP” on the No. 2 display. Press the
UNIT Key to select the unit number for the upload.
Any unit number from 0 to F and “-” (All units) can be selected.
3. Press the Level Key for at least one second to start the upload.
Note 1. “Up” will flash on the No. 2 display during the upload.
2. The mode will return automatically to the operation level when the upload has been
completed.

Download (Setting
Display Unit to
Temperature Controller) copy
0 down

UNIT
COPY CH

1,2,3... 1. Press the COPY Key for at least one second to move to the copy mode.
2. Use the Up and Down Keys to select “DOWN.”
The possible selections are “UP” and “DOWN.”
3. Press the UNIT Key to select the unit number for the download.
Any unit number from 0 to F can be selected.
However, the unit number for any units without uploaded data will not be
displayed.
Also, the selection operation will not be possible if the uploaded informa-
tion was uploaded from all units. The UNIT display will be “-”.
4. Press the Level Key for at least one second to start the download.
Note 1. “Down” will flash on the No. 2 display during the download.
2. The mode will return automatically to the operation level when the download has
been completed.
3. To download to all Temperature Controllers, use the same configuration as when
the data was uploaded. Downloading is not possible in the following circumstances.
“Down” will not be displayed when download is not possible.
• When a E5ZN has been added or deleted since the upload.
• When the same number of units are connected as when the upload was exe-
cuted, but when the unit numbers are different.
• When the platinum-resistance thermometer/thermocouple type configuration
is different.

107
List of Parameters Section 6-6

6-6 List of Parameters


Communications
setting level

len
0u 7
Mode
Key
Level Key for sbit
less than 1 s 0u 2
Mode
Key
prty
0u eUen
Mode
Key
sdwt
0u 20

Level Key for 1 s min. Level Key


Advanced function Initial setting level
setting level
Level Key
Same for ch1 and ch2 Same for ch1 and ch2
init Same for ch1 and in-t
off ch2 0
0u 0u
Mode Key Same for ch1 and ch2 Mode Key ch1
Mode Key
ch2
eU-m alfa out1 in-h in-h
0u 1 0.65 0 02 100 CH 01 100
0u 0u
Mode Key Mode Key
ch2 Mode Key ch1 Mode Key
eU in-l in-l
none ol-h ol-h out2
0u
105.0 5 02 0 CH 01 0
02 CH 01 105.0 0u
Mode Key Mode Key
Mode Key Mode Key
mspu dp dp
ol-l ol-l sub1
0u off 02 0 CH 01 0
02- 5.0 CH 01-
01 5.0 0u 2
ch2 Mode Key ch1 Mode Key
Mode Key Mode Key
sprt sprt d-u
0 inf inf sub2
02 CH 01 0 0.0 0u c
02 CH 01 0.0 0u 7
Mode Key Mode Key
Mode Key Mode Key
rest °c sl-h °c sl-h
a pUad cont
0u 02 1300 CH 01 1300
0u off 0u no
Mode Key Mode Key
Mode Key Mode Key
al1n al1n °c sl-l °c sl-l
n-o isdp aioU
02 CH 01 n-o off 02- 200 CH 01- 200
0u 0u 0
Mode Key Mode Key
Mode Key
°c alh1 °c alh1 cntl cntl
0.2 a1lt a1lt Possible by onof
02 CH 01 0.2 off 02 CH 01 onof
02 CH 01 off setting password
Mode Key (-169) Mode Key
Mode Key
al2n al2n cp cp
n-o a2lt a2lt
02 CH 01 n-o off 02 2 CH 01 2
02 CH 01 off To top of initial
Mode Key Mode Key
Mode Key setting level
°c alh2 °c alh2 c-cp
a3lt a3lt c-cp
02 0.2 CH 01 0.2 02 2 2
02 off CH 01 off CH 01
Mode Key Mode Key
Mode Key
al3n al3n oreU oreU
n-o cjc
02 CH 01 n-o 02 or-r CH 01 or-r
0u on
Mode Key Mode Key
°c alh3 °c alh3 alt1 alt1
Return to top of advanced
02 0.2 CH 01 0.2 function setting level 02 2 CH 01 2
Mode Key Mode Key
hbu alt2 alt2
0u on 02 2 CH 01 2
Mode Key Mode Key
hbl alt3 alt3
0u off 02 2 CH 01 2
Mode Key Mode Key
hbh hbh
02 0.1 CH 01 0.1

108
List of Parameters Section 6-6

Protect level

Copy mode
oapt
0u 0
Mode
Automatic return Key
or COPY Key for Level + Mode Level + Mode
1 s or less COPY Key Keys 1 s min. Keys 3 s min. icpt
1 s min. 0u 0
Mode
Key
wtpt
Power ON 0u off

1 s min. Level Key for less than 1 s

Operation level Adjustment level


3 s min. Level Key for less than 1 s
ch2 ch1 ch2 ch1
°c 25 °c 25 at at
02 01 02 off CH 01 off
Mode Key Mode Key ch2 ch1
°c 25 °c 25 c-sc
cmwt Same for ch1 c-sc
02 0 CH 01 0 and ch2 02 1.00 1.00
0u off CH 01
Mode Key Mode Key
Mode Key
m-sp m-sp °c °c
0 c-db c-db
02 CH 01 0 ct ct 0.0
02 CH 01 0.0
Mode Key 02 0.0 CH 01 0.0
Mode Key
°c sp-m °c sp-m Mode Key
02 0 CH 01 0 of-r of-r
hb hb
Mode Key 02 50.0 01 50.0
02 0.0 CH 01 0.0 CH

ct ct Mode Key
Mode Key
02 0.0 CH 01 0.0 °c hys °c hys
Mode Key °c sp-0 °c sp-0
0 02 1.0 CH 01 1.0
r-s r-s 02 CH 01 0
Mode Key
02 stop CH 01 stop Mode Key

Mode Key °c chys °c chys


°c sp-1 °c sp-1
°c al-1 °c 02 1.0 CH 01 1.0
al-1 02 0 CH 01 0
02 0 CH 01 0
Mode Key
Mode Key To top of adjustment level
°c °c °c in5 °c in5
al1h al1h
02 0 CH 01 0 02 0.0 CH 01 0.0
Mode Key Mode Key

°c al1l °c al1l °c in5h °c in5h


02 0 CH 01 0 0.0
02 CH 01 0.0
Mode Key
Mode Key
°c al-2 °c al-2
0 °c in5l °c in5l
02 CH 01 0
Mode Key
02 0.0 CH 01 0.0
°c al2h °c al2h
Mode Key

02 0 CH 01 0 °c p °c p
Mode Key 02 8.0 CH 01 8.0
°c al2l °c al2l Mode Key
02 0 CH 01 0
Mode Key
i i
°c °c 02 233 CH 01 233
al-3 al-3
02 0 CH 01 0 Mode Key

Mode Key d d
°c o °c o 02 40 CH 01 40
02 0.0 CH 01 0.0 Mode Key
Mode Key
°c c-o °c c-o
02 0.0 CH 01 0.0

To top of operation level

109
List of Parameters Section 6-6

110
SECTION 7
Parameters
7-1 Conventions Used in this Chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
7-2 Protect Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
7-2-1 Operation/Adjustment Protection (oapt), Initial Setting/
Communications Protection (icpt), Setting Change Protection (wtpt) 114
7-3 Operation Level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
7-3-1 PV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
7-3-2 PV/SP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
7-3-3 Multi-SP (Set Point 0 to 1) (m-sp) . . . . . . . . . . . . . . . . . . . . . . . . . . 116
7-3-4 Set Point During SP Ramp (sp-m) . . . . . . . . . . . . . . . . . . . . . . . . . . 116
7-3-5 Heater Current Value Monitor (ct) . . . . . . . . . . . . . . . . . . . . . . . . . 116
7-3-6 RUN/STOP (r-s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
7-3-7 Alarm Value 1 (al-1), Alarm Value 2 (al-2), Alarm Value 3 (al-3) 117
7-3-8 Alarm Upper Limit Value 1 (al 1h), Alarm Lower Limit
Value 1 (al 1l) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
7-3-9 Alarm Upper Limit Value 2 (al2h), Alarm Lower Limit Alarm
Value 2 (al2l) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
7-3-10 MV monitor for heating (o) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
7-3-11 MV monitor for cooling (c-o) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
7-4 Adjustment Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
7-4-1 AT Execute/Cancel (at) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
7-4-2 Communications Writing (cmwt) . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
7-4-3 Heater Current Value Monitor (ct) . . . . . . . . . . . . . . . . . . . . . . . . . 121
7-4-4 Heater Burnout Detection (hb) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
7-4-5 Set Point 0 (sp-0), Set Point 1 (sp-1) . . . . . . . . . . . . . . . . . . . . . . . 123
7-4-6 Temperature Input Shift (ins) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
7-4-7 Upper limit Temperature Input Shift Value (insh), Lower limit
Temperature Input Shift Value (insl) . . . . . . . . . . . . . . . . . . . . . . . 124
7-4-8 Proportional Band (p), Integral Time (i), Derivative Time (d) . . . . 124
7-4-9 Cooling Coefficient (c-sc). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
7-4-10 Dead Band (c-db) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
7-4-11 Manual Reset Value (of-r) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
7-4-12 heating hysteresis (hys), Cooling hysteresis (chys) . . . . . . . . . . . . 127
7-5 Initial Setting Level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
7-5-1 Input Type (in-t) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
7-5-2 Scaling Upper Limit (in-h), Scaling Lower Limit (in-l),
Decimal Point (dp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
7-5-3 °C/°F Selection (d-u) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
7-5-4 Set Point Upper Limit (sl-h), Set Point Lower Limit (sl-l) . . . . . 130
7-5-5 PID / ON/OFF (cntl). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
7-5-6 Heating Control period (cp), Cooling Control period (c-cp) . . . . . 131
7-5-7 Direct/Reverse Operation (oreU) . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
7-5-8 Alarm 1 Type (alt1), Alarm 2 Type (alt2), Alarm 3 Type (alt3) 132
7-5-9 Control Output 1 Assignment (out1). . . . . . . . . . . . . . . . . . . . . . . . 132
7-5-10 Control Output 2 Assignment (out2). . . . . . . . . . . . . . . . . . . . . . . . 133
7-5-11 Auxiliary Output 1 Assignment (sub1) . . . . . . . . . . . . . . . . . . . . . . 133
7-5-12 Auxiliary Output 2 Assignment (sub2) . . . . . . . . . . . . . . . . . . . . . . 134
7-5-13 Operation After Power ON (cont) . . . . . . . . . . . . . . . . . . . . . . . . . . 134
7-6 Advanced Function Setting Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
7-6-1 Parameter Initialize (init) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135

111
7-6-2 Number of Multi-SP Uses (eU-m) . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
7-6-3 Event Input Assignment (eU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
7-6-4 Multi-SP Uses (mspu) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
7-6-5 SP Ramp Set Value (sprt) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
7-6-6 Standby Sequence Reset Method (rest) . . . . . . . . . . . . . . . . . . . . . 137
7-6-7 Alarm 1 Open for alarm (al1n), Alarm 2 Open for alarm (al2n),
Alarm 3 Open for alarm (al3n) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
7-6-8 Alarm 1 Hysteresis (alh1), Alarm 2 Hysteresis (alh2),
Alarm 3 Hysteresis (alh3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
7-6-9 HBA Used (hbu) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
7-6-10 Heater Burnout Latch (hbl) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
7-6-11 Heater Burnout Hysteresis (hbh). . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
7-6-12 a (alfa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
7-6-13 MV Upper Limit (ol-h), MV Lower Limit (ol-l) . . . . . . . . . . . . . 141
7-6-14 Input Digital Filter (inf). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
7-6-15 Additional PV Display (pUad) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
7-6-16 Additional Temperature Input Shift Value Display (isdp). . . . . . . . 143
7-6-17 Alarm 1 Latch (a1lt), Alarm 2 Latch (a2lt), Alarm 3 Latch (a3lt) 143
7-6-18 Cold Junction Compensation Method (cjc) . . . . . . . . . . . . . . . . . . . 144
7-7 Communications Setting Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
7-7-1 Communications Data Length (len). . . . . . . . . . . . . . . . . . . . . . . . . 145
7-7-2 Communications Stop Bit (sbit) . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
7-7-3 Communications Parity (prty) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
7-7-4 Communications Response Wait Time (sdwt) . . . . . . . . . . . . . . . . . 146

112
Conventions Used in this Chapter Section 7-1

7-1 Conventions Used in this Chapter


Headings

Function Describes the functions of the parameter.

Communications Describes the variable type and address specified in communications com-
mands.

Settings Describes the setting range and defaults of the parameter.

Monitoring Describes the monitor values.

Example of Use Describes procedures for the E5ZN-SDL Setting Display Unit.

See Also Describes related parameters and items.

Display Conditions for Related Parameters


The parameters are displayed in the display section of the E5ZN-SDL Setting
Display Unit only when the condition for use shown at the top of the section
describing the parameter are met. Protected parameters are not be displayed
regardless, although the parameters themselves will be enabled.

Order for Parameter Display


The parameters are displayed by level.

113
Protect Level Section 7-2

7-2 Protect Level


7-2-1 oapt)
oapt
Operation/Adjustment Protection (oapt
icpt)
icpt
Initial Setting/Communications Protection (icpt
wtpt)
wtpt
Setting Change Protection (wtpt

Function These parameters specify the range of parameters to be protected. The


shaded areas indicate the defaults.

Settings Operation/Adjustment Protection


The following table shows the relationship between set values and the range
of protection.
Level Set value
0 1 2 3
Operation PV m m m m
level PV/SP ¨ ¨ ¨ m
Other ¨ ¨ ´ ´
Adjustment level ¨ ´ ´ ´

¨: Can be displayed and changed


m: Can be displayed
´: Cannot be displayed and move to other levels not possible
Parameter items are not protected when the set value is set to 0.
Initial Setting/Communications Protection
Moving to the “initial setting level,” “communications setting level” and
“advanced function setting level” can be prohibited.
Set value Initial setting level Communications Advanced function
setting level setting level
0 m m m
1 m m ´
2 ´ ´ ´

m: Moving to other levels possible


´: Moving to other levels not possible
Setting Change Protection
Changes to setups by key operation can be prohibited.
Set value Description
OFF Setup can be changed by key operation.
ON Setup cannot be changed by key operation. (The protect level can be
changed.)

Communications
Setting Variable type Address
Operation/adjustment protection C1 0000 or 0100
Initial setting/communications protection C1 0001 or 0101
Setting change protection C1 0002 or 0102

114
Operation Level Section 7-3

7-3 Operation Level


7-3-1 PV
Condition: The “additional PV display” parameter must be set to ON.

Function The process value is displayed on the No.1 display, and nothing is displayed
(blank) on the No. 2 display.

Communications
ch Variable type Address
1 C0 0000
2 C0 0100

Monitoring
Monitoring range Unit
Process Input range lower limit -10% FS to input range upper limit EU
Value +10%FS
Scaling lower limit -10% FS to scaling upper limit +10%FS

The decimal point position is dependent on the selected sensor.

See Also • Related Parameters


“Input type” (page 128)
“Set point upper limit” “Set point lower limit” (page 130)

7-3-2 PV/SP

Function The process value is displayed on the No.1 display, and the set point is dis-
played on the No. 2 display.
Monitoring range Unit
Process Input range lower limit -10%FS to input range upper limit EU
Value +10%FS
Scaling lower limit -10%FS to scaling upper limit +10%FS

Monitoring range Unit


Set Point Set point lower limit to set point upper limit EU

Communications
Monitor value/parameter ch Variable type Address
PV 1 C0 0000
2 C0 0100
SP 1 C1 0003
2 C1 0103

See Also Refer to the PV parameter.

115
Operation Level Section 7-3

7-3-3 m-sp)
m-sp
Multi-SP (Set Point 0 to 1) (m-sp
Condition: The “multi-SP uses” parameter must be set to ON.

Function Multi-SP allows you to set up to two set points (SP0 to 1) in the adjustment
level. These can be switched between by operating the keys on the front panel
or by external input signals (event input allocation).
In the parameter, enter set points 0 to 1. Default is 0.

Communications Use the multi-SP operation commands. Refer to page 77 for information.

See Also • If multi-SP cannot be selected using the event input, set the “No. of multi-
SP uses” parameter to 0 and the “multi-SP uses” parameter to ON. This
will enable SP selection.
• SP can be selected using the communications function also.

7-3-4 sp-m)
sp-m
Ramp SP Value Monitor (sp-m
Condition: The “SP ramp set value” parameter must not be set to 0.

Function This parameter monitors the SP while the ramp function is being used.
The ramp function restricts the rate of change in the width of the set point.
The set value is displayed when “SP ramp set value” parameter is set.
When the set point is out of the preset ramp, the set point is matched to the
set point set in the “PV/SP” parameter.

Communications
ch Variable type Address
1 C0 0002
2 C0 0102

Monitoring
Monitoring range Unit
SP: Set point lower limit to set point upper limit EU

See Also • Related Parameters


“PV/SP” (operation level) (page 115)
“SP ramp set value” (advanced function setting level) (page 136)
“Set point upper limit” “Set point lower limit” (initial setting level)
(page 130)

7-3-5 ct)
ct
Heater Current Value Monitor (ct
Condition: The “HBA used” parameter must be set to “ON.”
This parameter measures the heater current value from the CT input used for
detecting heater burnout.

Function Measures and displays the heater current value.

Communications
ch Variable type Address
1 C0 0003
2 C0 0103

116
Operation Level Section 7-3

Monitoring
Monitoring range Unit
00000000H to 00000226 H (0.0 to 55.0) A

When the current exceeds 55.0A in the E5ZN-SDL Setting Display Unit,
“ffff” is displayed.

See Also • Related Parameters


“Heater burnout detection” (adjustment level) (page 122)
“Heater burnout use” (advanced function setting level) (page 140)

7-3-6 r-s)
r-s
RUN/STOP (r-s
Condition: The RUN/STOP function must not be set for the event input.

Function This parameter starts and stops operation.


Default is “STOP.”

Communications Use the “RUN/STOP” operation command. Refer to page 76 for information.

Example of Use When run is selected, control is executed. When stop is selected, control is
stopped. When control is stopped, the STOP indicator will be lit.
• This parameter is not displayed when the RUN/STOP function is set to
the event input.

See Also • Related Parameters


“Event input allocation” (advanced function setting level) (page 135)

7-3-7 al-1)
al-1
Alarm Value 1 (al-1
al-2)
al-2
Alarm Value 2 (al-2
al-3)
al-3
Alarm Value 3 (al-3
Condition: The alarm type must not be set to no alarm or upper and lower
limit alarm (alarms 1 and 2 only).
These parameters set the input value “X” in the alarm.

Function • These parameters are used to set the alarm values for alarm outputs 1 to
3.
• During temperature input, the decimal point position is dependent on the
currently selected sensor, and during analog input it is dependent on the
“decimal point” parameter setting.

Communications
Setting ch Variable type Address
Alarm value 1 1 C1 0004
2 C1 0104
Alarm value 2 1 C1 0007
2 C1 0107
Alarm value 3 1 C1 000A
2 C1 010A

117
Operation Level Section 7-3

Settings
Setting range Unit Default
FFFFF831H to 00000270FH (-1999 to 9999) EU 0

The alarm type must be set to other than no alarm or upper and lower limit
alarm (alarms 1 and 2 only).

See Also • Related Parameters


“Input type” (initial setting level) (page 128)
“Scaling upper limit” “Scaling lower limit” “Decimal point” (initial setting
level) (page 129)
”Alarm 1 type” “Alarm 2 type” “Alarm 3 type” (initial setting level)
(page 132)
”Alarm 1 open for alarm” “Alarm 2 open for alarm” “Alarm 3 open for
alarm” (advanced function setting level) (page 138) “Alarm 1 hysteresis”
“Alarm 2 hysteresis” “Alarm 3 hysteresis” (advanced function setting
level) (page 139)
”Standby sequence reset method” (advanced function setting level)
(page 137)

7-3-8 al 1h)
Alarm Upper Limit Value 1 (al 1h
al 1l)
Alarm Lower Limit Value 1 (al 1l
Condition: Alarm 1 type must be set to upper and lower limits, upper and
lower limit range, or upper and lower limit with standby sequence.
These parameters independently set the upper and lower limit alarm values
when the mode for setting the upper and lower limits is selected for alarm 1
type.

Function • These parameters set the upper and lower limit values of alarm 1.
• During temperature input, the decimal point position is dependent on the
currently selected sensor, and during analog input it is dependent on the
“decimal point” parameter setting.

Communications
Setting ch Variable type Address
Alarm upper limit value 1 1 C1 0005
2 C1 0105
Alarm lower limit alarm 1 C1 0006
value 1 2 C1 0106

Settings
Setting range Unit Default
FFFFF831H to 00000270FH (-1999 to 9999) EU 0

See Also • Related Parameters


“Alarm 1 type” (initial setting level) (page 132)
”Standby sequence reset method” (advanced function setting level)
(page 137)
“Alarm 1 open for alarm” (advanced function setting level) (page 138)
“Alarm 1 hysteresis” (advanced function setting level) (page 139)

118
Operation Level Section 7-3

7-3-9 al2h)
al2h
Alarm Upper Limit Value 2 (al2h
al2l)
al2l
Alarm Lower Limit Alarm Value 2 (al2l
Condition: Alarm 2 type must be set to upper and lower limits, upper and
lower limit range, or upper and lower limit alarm with standby sequence.
These parameters independently set the upper and lower limit alarm values
when the mode for setting the upper and lower limits is selected for alarm 2
type.

Function • These parameters set the upper and lower limit values of alarm 2.
• The decimal point position is dependent on the currently selected sensor.
For analog input, it is dependent on the “decimal point position” setting.

Communications
Setting ch Variable type Address
Alarm upper limit value 2 1 C1 0008
2 C1 0108
Alarm lower limit value 2 1 C1 0009
2 C1 0109

Settings
Setting range Unit Default
FFFFF831H to 00000270FH (-1999 to 9999) EU 0

See Also • Related Parameters


“Input type” “Alarm 2 type” (initial setting level) (page 132)
“Standby sequence reset method” (advanced function setting level)
(page 137)
“Alarm 2 open for alarm” (advanced function setting level) (page 138)
“Alarm 2 hysteresis” (advanced function setting level) (page 139)

o)
7-3-10 MV Monitor for Heating (o

Function During standard control, the MV is monitored, and during heating/cooling con-
trol, the MV on the heating side is monitored.

Communications
ch Variable type Address
1 C0 0004
2 C0 0104

Monitoring
Control Monitoring range Unit
Standard FFFFFFCEH to 0000041AH (-5.0 to 105.0) %
Heating and cooling 00000000H to 0000041AH (0.0 to 105.0) %

119
Operation Level Section 7-3

c-o)
c-o
7-3-11 MV Monitor for Cooling (c-o
The control must be heating and cooling control.
This parameter is for monitoring the MV on the cooling side during operation.

Function During heating and cooling control, the MV on the cooling side is monitored.

Communications
ch Variable type Address
1 C0 0005
2 C0 0105

Monitoring
Control Monitoring range Unit
Heating and cooling 00000000H to 0000041AH (0.0 to 105.0) %

See Also • Related Parameters


“Control output 1allocation”“Control output 2 allocation” (initial setting
level) (page 132) “Auxiliary output 1 allocation” “Auxiliary output 2 alloca-
tion” (initial setting level) (page 133)

120
Adjustment Level Section 7-4

7-4 Adjustment Level


7-4-1 at)
at
AT Execute/Cancel (at
Condition: Operation in automatic mode with 2-PID control.
This parameter executes autotuning.

Function When you execute AT, the optimum PID parameters “proportional band,” “inte-
gral time,” and “derivative time” for the set point during program execution are
automatically set by changing the MV to calculate the characteristics of the
control target.

Communications Use the “AT execute/cancel” operation command. Refer to page 77 for infor-
mation.

Example of Use • Normally, this parameter is set to “off”. When you press the Up Key, the
parameter is turned ON and AT is executed.
AT cannot be executed when control has stopped or during ON/OFF con-
trol.
• When AT execution ends, the parameter setting automatically returns to
“off.”
• The SP flashes if “PV/SP” is monitored during AT.
• Channel settings cannot be changed during AT.

See Also • Related Parameters


“Proportional band” “Integral time” “Derivative time” (adjustment level)
(page 124)
“PID/OnOff” (initial setting level) (page 130)

7-4-2 cmwt)
cmwt
Communications Writing (cmwt

Function This parameter enables/disables writing of parameters to the E5ZN from the
host (e.g., personal computer) by communications.

Communications Use the “communications writing” operation command. Refer to page 76 for
information.

Example of Use Set this parameter to “on” to enable writing and to “off” to disable writing.

See Also • Related Parameters


”Communication unit No.” “Baud rate” (setting switch) (page 3)
“Data bit” “Stop bit” (communications setting level) (page 145) “Parity”
“Communications response wait time” (communications setting level)
(page 146)

7-4-3 ct)
ct
Heater Current Value Monitor (ct
Condition: The “HBA used” parameter must be set to “ON”.
This parameter measures the current value of the heater from current trans-
former (CT) input to detect heater burnout.

Function This parameter measures and displays the current value of the heater.

121
Adjustment Level Section 7-4

Communications
ch Variable type Address
1 C0 0003
2 C0 0103

Monitoring
Monitoring range Unit
00000000H to 00000226 H (0.0 to 55.0) A

“ffff” is displayed when 55.0A is exceeded in the E5ZN-SDL Setting Display


Unit.

See Also • Related Parameters


“Heater burnout detection” (adjustment level) (page 122)
“HBA used” (advanced function setting level) (page 140)

7-4-4 hb)
hb
Heater Burnout Detection (hb
Condition: The “HBA used” parameter must be set to “ON”.
This parameter sets the current value for the heater burnout alarm output to
become active.

Function • This parameter outputs the heater burnout alarm when the heater current
value falls below this parameter setting.
• When the set value is 0.0, the heater burnout alarm will be OFF. When the
set value is 50.0, the heater burnout alarm will be ON.

Communications
ch Variable type Address
1 C1 000C
2 C1 010C

Settings
Setting range Unit Default
00000000H to 000001F4H (0.0 to 50.0) A 0.0

See Also • Related Parameters


“HBA used” (advanced function setting level) (page 140)
”Heater current value monitor” (operation or adjustment level) (page 121)
“Heater burnout latch” (advanced function setting level) (page 140)
“Heater burnout hysteresis” (advanced function setting level) (page 140)

122
Adjustment Level Section 7-4

7-4-5 sp-0)
sp-0
Set Point 0 (sp-0
sp-1)
sp-1
Set Point 1 (sp-1
Condition: The “number of multi-SP uses” parameter must be set to
either 1 or 2, and the “multi-SP uses” parameter must be set to ON.
These parameters set the set points when the multi-SP function is used.

Function The values set in these parameters can be selected.


• When the set point has been changed, the set value of these parameters
currently set by multi-SP is linked and changed.
• The decimal point position is dependent on the selected sensor.
During analog input, the decimal point position is dependent on the setting of
the “decimal point position” parameter.

Communications
Setting ch Variable type Address
Set point 0 1 C1 000D
2 C1 010D
Set point 1 1 C1 000E
2 C1 010E

Settings
Setting range Unit Default
Lower set point limit to upper set point limit EU 0

See Also • Related Parameters


“Number of multi-SP uses” (advanced function setting level) (page 135)
”Event input allocation” “Multi-SP uses” (advanced function setting level)
(page 135)
“PV/SP” (operation level) (page 115)
“Input type” (initial setting level) (page 128)

7-4-6 ins)
ins
Temperature Input Shift (ins
Condition: The “additional temperature input display” parameter must be
set to ON and the “input type” parameter must not be set to temperature
input for a non-contact temperature sensor.
Sometimes an error between the set point and the actual temperature occurs.
To offset this, a value obtained by adding an input shift value to the input is
displayed as the measurement value and used for control.

Function The entire input range is shifted by a fixed rate (1-point shift). If the input shift
value is set to -1.0°C, the set point is controlled to a value obtained by sub-
tracting 1.0°C from the actual temperature.

Communications
ch Variable type Address
1 C1 000F
2 C1 010F

Settings
Setting range Unit Default
FFFFF831H to 0000270FH (-199.9 to 999.9) °C or °F 0.0

123
Adjustment Level Section 7-4

See Also • Related Parameter


“Input type” (initial setting level) (page 128)

7-4-7 insh)
insh
Upper Limit Temperature Input Shift Value (insh
insl)
insl
Lower Limit Temperature Input Shift Value (insl
Condition: The “additional temperature input display” parameter must be
set to ON and the “input type” parameter must be set to a non-contact
temperature sensor.
These parameters allow the input range to be shifted both at the upper and
lower limits (2-point shift) (as opposed to the “temperature input shift” parame-
ter, where the entire input range is shifted by a fixed rate (1-point shift)). A 2-
point shift enables more accurate offset of the input range compared with a 1-
point shift when the input shift values at the upper and lower limits differ.

Function This parameter sets input shift values for each of the upper and lower limits
(2-point shift) of the input range.

Communications
Setting ch Variable type Address
Upper limit temperature 1 C1 0010
input shift value 2 C1 0110
Lower limit temperature 1 C1 0011
input shift value 2 C1 0111

Settings
Setting range Unit Default
FFFFF831H to 0000270FH (-199.9 to 999.9) °C or °F 0.0

See Also Related Parameter


“Input type” (initial setting level) (page 128)

7-4-8 Proportional Band (p p)


i)
Integral Time (i
Derivative Time (dd)
Condition: The control must be 2-PID control.
These parameters set the PID constants for control. The PID can be automat-
ically set by executing autotuning.

Function Proportional action:P refers to control in which the MV is proportional to the


deviation.
Integral action: I gives a control action that is proportional to the time inte-
gral of the control error. With proportional control, there is
normally an offset (control error). So, proportional action
is used in combination with integral action. As time
passes, this control error disappears, and the set point
comes to agree with the control temperature (process
value).
Derivative action: D gives a control action that is proportional to the time
derivative of the control error. As proportional control and
integral control correct for errors in the control result, the
control system will be late in responding to sudden
changes in temperature. Derivative action enables control

124
Adjustment Level Section 7-4

that is proportional to a predicted process output to cor-


rect for future error.

Communications
Setting ch Variable type Address
Proportional band 1 C1 0012
2 C1 0112
Integral time 1 C1 0013
2 C1 0113
Derivative time 1 C1 0014
2 C1 0114

Settings
Setting Setting range Unit Default
Proportional band 00000001H to 0000270FH (0.1 to 999.9) EU 8.0
Integral time 00000000H to 00000F9FH (0 to 3999) Second 233
Derivative time 00000000H to 00000F9FH (0 to 3999) Second 40

See Also • Related Parameters


“AT execute/cancel” (adjustment level) (page 121)
“PID/OnOff” (initial setting level) (page 130)

7-4-9 c-sc)
c-sc
Cooling Coefficient (c-sc
Condition: The control must be either heating and cooling control or 2-
PID control.
If the heating and cooling characteristics of the control target differ enough to
prevent satisfactory control characteristics from being obtained by the same
PID parameters, adjust the proportional band (P) on the cooling side by add-
ing the cooling coefficient to control cooling.

Function In heating and cooling control, cooling side P is calculated by the following for-
mula to set the cooling coefficient:
Cooling side P = Cooling coefficient ´ P (proportional operation)

Communications
ch Variable type Address
1 C1 0015
2 C1 0115

Settings
Setting range Unit Default
00000001H to 0000270FH (0.01 to 99.99) None 1.00

See Also • Related Parameter


“Proportional band” (adjustment level) (page 124)

125
Adjustment Level Section 7-4

c-db)
c-db
7-4-10 Dead Band (c-db
Condition: The control system must be heating and cooling control.
This parameter sets the output dead band width in a heating and cooling con-
trol system. A negative setting sets an overlap band.

Function This parameter sets an area in which the control output is 0 centering around
the set point in a heating and cooling control system.

Communications
ch Variable type Address
1 C1 0016
2 C1 0116

Settings
Setting range Unit Default
FFFFF831H to 0000270FH (-199.9 to 999.9) EU 0.0

of-r)
of-r
7-4-11 Manual Reset Value (of-r
Condition: The control must be standard control or 2-PID control. The
“integral time” parameter must be set to 0.

Function This parameter sets the required manipulated variable to remove offset during
stabilization of P or PD control.

Communications
ch Variable type Address
1 C1 0017
2 C1 0117

Settings
Monitoring range Unit Default
00000000H to 000003E8H (0.0 to 100.0) % 50.0

See Also • Related Parameters


“PID/OnOff” (initial setting level) (page 130)
“Integral time” (adjustment level) (page 124)

126
Adjustment Level Section 7-4

hys)
hys
7-4-12 Heating Hysteresis (hys
chys)
chys
Cooling Hysteresis (chys
Condition: The control must be ON/OFF control.
These parameters set the hysteresis for ensuring stable operation at ON/OFF
switching.

Function • In a standard control, use the “heating hysteresis” parameter. The “cool-
ing hysteresis” parameter cannot be used.
• In a heating and cooling control, the hysteresis can be set independently
for heating and cooling. Use the “heating hysteresis” parameter to set the
heating side hysteresis, and use the “cooling hysteresis” parameter to set
the cooling side hysteresis.

Communications
Setting ch Variable type Address
heating hysteresis 1 C1 0018
2 C1 0118
Cooling hysteresis 1 C1 0019
2 C1 0119

Settings
Setting range Unit Default
00000001H to 0000270FH (0.1 to 999.9) EU 1.0

See Also • Related Parameter


“PID/OnOff” (initial setting level) (page 130)

127
Initial Setting Level Section 7-5

7-5 Initial Setting Level


7-5-1 in-t)
in-t
Input Type (in-t

Function • This parameter sets the sensor type using a corresponding code.
• When this parameter is changed, the set point limiter is changed to the
default. If the set point limits must be changed, set the “set point upper
limit” and “set point lower limit” parameters.

Communications
ch Variable type Address
Shared C3 0000 or 0100

Settings Set the code according to the following table. Shaded ranges indicate default
settings.
Sensor Input type Name Set value Input temperature range
Platinum Platinum Pt100 00000000H (0) -200 to 850 (°C) to -300 to 1,500 (°F)
resistance resistance 00000001H (1) -199.9 to 500.0 (°C) to -199.9 to 900.0 (°F)
thermometer thermometer
00000002H (2) 0.0 to 100.0 (°C) to 0.0 to 210.0 (°F)
JPt100 00000003H (3) -199.9 to 500.0 (°C) to -199.9 to 900.0 (°F)
00000004H (4) 0.0 to 100.0 (°C) to 0.0 to 210.0 (°F)
Thermocou- Thermocou- K 00000000H (0) -200 to 1,300 (°C) to -300 to 2,300 (°F)
ple input ple 00000001H (1) -20.0 to 500.0 (°C) to 0.0 to 900.0 (°F)
type
J 00000002H (2) -100 to 850 (°C) to -100 to 1,500 (°F)
00000003H (3) -20.0 to 400.0 (°C) to 0.0 to 750.0 (°F)
T 00000004H (4) -200 to 400 (°C) to -300 to 700 (°F)
00000011H (17) -199.9 to 400.0 (°C) to -199.9 to 700.0 (°F)
E 00000005H (5) 0 to 600 (°C) to 0 to 1100 (°F)
L 00000006H (6) -100 to 850 (°C) to -100 to 1,500 (°F)
U 00000007H (7) -200 to 400 (°C) to -300 to 700 (°F)
00000012H (18) -199.9 to 400.0 (°C) to -199.9 to 700.0 (°F)
N 00000008H (8) -200 to 1,300 (°C) to -300 to 2,300 (°F)
R 00000009H (9) 0 to 1,700 (°C) to 0 to 3,000 (°F)
S 0000000AH (10) 0 to 1,700 (°C) to 0 to 3,000 (°F)
B 0000000BH (11) 100 to 1,800 (°C) to 300 to 3,200 (°F)
Infrared tem- K10 to 70°C 0000000CH (12) 0 to 90 (°C) to 0 to 190 (°F)
perature K60 to 120°C 0000000DH (13) 0 to 120 (°C) to 0 to 240 (°F)
sensor
K115 to 165°C 0000000EH (14) 0 to 165 (°C) to 0 to 320 (°F)
ES1A
K160 to 260°C 0000000FH (15) 0 to 260 (°C) to 0 to 500 (°F)
Analog input 0 to 5 mV 00000010H (16) One of following ranges depending on the
results of scaling:
-1,999 to 9,999 or -199.9 to 999.9,

See Also • Related Parameters


“°C/°F selection” (initial setting level) (page 129) “Set point upper limit”
“Set point lower limit” (initial setting level) (page 130)

128
Initial Setting Level Section 7-5

7-5-2 in-h)
in-h
Scaling Upper Limit (in-h
in-l)
in-l
Scaling Lower Limit (in-l
dp)
dp
Decimal Point (dp
Condition: The input type must be set to analog input.

Function • These parameters can be used when a voltage input is selected as the
input type.
• When a voltage input is selected as the input type, scaling is performed.
Set the upper limit in the “scaling upper limit” parameter and the lower
limit in the “scaling lower limit” parameter.
• The “decimal point” parameter specifies the decimal point position of
parameters (e.g., set point) whose unit is set to EU.

Communications
Setting ch Variable type Address
Scaling upper limit value 1 C3 0001
2 C3 0101
Scaling lower limit value 1 C3 0002
2 C3 0102
Decimal point position 1 C3 0003
2 C3 0103

Settings
Setting Settings range Unit Default
Scaling upper limit Scaling lower limit +1 to 00000270FH - 100
value (Scaling lower limit +1 to 9,999)
Scaling lower limit FFFFF831H to scaling upper limit -1 - 0
value (-1999 to scaling upper limit -1)
Decimal point 00000000H to 00000001H (0 t0 1) - 0
position

See Also • Related Parameter


“Input type” (initial setting level) (page 128)

7-5-3 °C/°F Selection (d-u


d-u)
d-u
Condition: The input type must be set to temperature input.

Function • Set the temperature input unit to either °C or °F.


• The temperature input unit must be the same for both ch1 and ch2.

Communications
ch Variable type Address
Shared C3 0004 or 0104

Settings
Setting range Unit Default
00000000H to 00000001H - 0: °C
0: °C (c)
1: °F (f)

129
Initial Setting Level Section 7-5

See Also • Related Parameter


“Input type” (initial setting level) (page 128)

7-5-4 sl-h)
sl-h
Set Point Upper Limit (sl-h
sl-l)
sl-l
Set Point Lower Limit (sl-l

Function • These parameters set the upper and lower limits for the SP setting. The
SP can be set within the range defined by the upper and lower limit set
values in the “set point upper limit” and “set point lower limit” parameters.
If existing SP settings are out of the range, they will be changed to either
the upper or lower limit values (which-ever is closest).
• When the temperature input type and temperature unit are changed, the
set point upper limit and set point lower limit will be changed to the upper
and lower limits of the sensor.
• During temperature input, the decimal point position is dependent on the
currently selected sensor. During analog input, it is dependent on the
“decimal point” parameter setting.

Communications
Setting ch Variable type Address
Set point upper limit value 1 C3 0005
2 C3 0105
Set point lower limit value 1 C3 0006
2 C3 0106

Settings
Setting Settings range Unit Default
Set point Temperature: Set point lower limit +1 to Depends Input range
upper limit sensor range upper limit on °C/°F upper limit
value selection
Analog: Set point lower limit + 1 to scal- EU Scaling upper
ing upper limit limit
Set point Temperature: Sensor range lower limit to Depends Input range
lower limit set point upper limit -1 on °C/°F lower limit
value selection
Analog: Scaling lower limit to set point EU Scaling lower
upper limit - 1 limit

See Also • Related Parameters


“Input type” (initial setting level) (page 128) “°C/°F selection” (initial setting
level) (page 129)

7-5-5 cntl)
cntl
PID/OnOff (cntl

Function • This parameter selects 2-PID control or ON/OFF control as the control
system.
• The AT tuning function can be used in 2-PID control.

Communications
ch Variable type Address
1 C3 0007
2 C3 0107

130
Initial Setting Level Section 7-5

Settings
Settings range Unit Default
00000000H to00000001H - 1: 2-PID
0: ON/OFF (onof)
1: 2-PID (pid)

See Also • Related Parameters


“Manual reset” “Heating hysteresis” “Cooling hysteresis” (adjustment
level) (page 126)

7-5-6 cp)
cp
Heating Control Period (cp
c-cp)
c-cp
Cooling Control Period (c-cp
Condition: The control must be set to 2-PID control when the cooling side
control period is cooling/heating control.

Function • These parameters set the control periods. Set the control periods taking
the control characteristics and the electrical life expectancy of the relay
into consideration.
• In a standard control system, use the “heating control period” parameter.
• In a heating and cooling control system, the control period can be set
independently for heating and cooling.

Communications
Setting ch Variable type Address
Heating control period 1 C3 0008
2 C3 0108
Cooling control period 1 C3 0009
2 C3 0109

Settings
Setting Settings range Unit Default
Heating control 00000001H to 00000063H (1 to 99) Second 2
period
Cooling control 00000001H to 00000063H (1 to 99) Second 2
period

See Also • Related Parameter


“PID/OnOff” (initial setting level) (page 130)

7-5-7 oreU)
oreU
Direct/Reverse Operation (oreU

Function Direct operation increases the MV when the process value increases. Alterna-
tively, reverse operation increases the manipulated variable when the process
value decreases.

Communications
ch Variable type Address
1 C3 000A
2 C3 010A

131
Initial Setting Level Section 7-5

Settings
Settings range Unit Default
00000000H to00000001H - 0: Reverse
0: Reverse operation (or-r) operation
1: Direct operation (or-d)

See Also 3-4 Setting Output Specifications (page 25)

7-5-8 alt1)
alt1
Alarm 1 Type (alt1
alt2)
alt2
Alarm 2 Type (alt2
alt3)
alt3
Alarm 3 Type (alt3

Function These parameters select alarm type for alarms 1, 2, or 3

Communications
Setting ch Variable type Address
Alarm 1 type 1 C3 000B
2 C3 010B
Alarm 2 type 1 C3 000C
2 C3 010C
Alarm 3 type 1 C3 000D
2 C3 010D

Settings
Setting Settings range Unit Default
Alarm 1 type 00000000H (0): No alarm function - 2: Upper limit
Alarm 2 type 00000001H (1): Upper and lower limit alarm alarm
Alarm 3 type 00000002H (2): Upper limit alarm
00000003H (3): Lower limit alarm
00000004H (4): Upper and lower limit range alarm
00000005H (5): Upper and lower limit alarm with standby sequence
00000006H (6): Upper limit alarm with standby sequence
00000007H (7): Lower limit alarm with standby sequence
00000008H (8): Absolute value upper limit alarm
00000009H (9): Absolute value lower limit alarm
0000000AH (10): Absolute value upper limit alarm with standby sequence
0000000BH (11): Absolute value lower limit alarm with standby sequence

See Also • Related Parameters


“Alarm 1 to 3 value” (operation level) (page 117)
“Upper limit alarm value 1” “Lower limit alarm value 1” (operation level)
(page 118) “Upper limit alarm value 2” “Lower limit alarm value 2” (opera-
tion level) (page 119)
“Standby sequence reset” (advanced function setting level) (page 137)
“Alarm 1 to 3 open for alarm” (advanced function setting level) (page 138)
“Alarm 1 to 3 hysteresis” (advanced function setting level) (page 139)
“Alarm 1 to 3 latch” (advanced function setting level) (page 143)

7-5-9 out1)
out1
Control Output 1 Allocation (out1

Function This function assigns the data to be output to the control output 1 terminals
(terminals 7 and 8.)

132
Initial Setting Level Section 7-5

Communications
ch Variable type Address
Shared C3 000E or 010E

Settings
Settings range Unit Default
00000000H (0): Heating control output for ch1 - 0: ch1 heating
00000001H (1): Cooling control output for heating/cooling control for ch1 control output
00000002H (2): Alarm 1 and HB alarm OR output for ch1
00000003H (3): Alarm 2 output for ch1
00000004H (4): Alarm 3 output for ch1
00000005H (5): Heating control output for ch2
00000006H (6): Cooling control output for heating/cooling control for ch2
00000007H (7): Alarm 1 and HB alarm OR output for ch2
00000008H (8): Alarm 2 output for ch2
00000009H (9): Alarm 3 output for ch2

out2)
out2
7-5-10 Control Output 2 Allocation (out2

Function This parameter allocates the data to be output to the control output 2 termi-
nals (terminals 1 and 2.)

Communications
ch Variable type Address
Shared C3 000F or 010F

Settings
Settings range Unit Default
Refer to the table of setting ranges for control output 1 alloca- - 5: ch2
tion. heating
control
output

sub1)
sub1
7-5-11 Auxiliary Output 1 Allocation (sub1

Function This parameter allocates the data to be output to the auxiliary output 1 termi-
nals (terminals 13 and 15.)

Communications
ch Variable type Address
Shared C3 0010 or 0110

Settings
Settings range Unit Default
Refer to the table of setting ranges for control output 1 alloca- - 2: ch1
tion. alarm 1
and HB
alarm OR
output

133
Initial Setting Level Section 7-5

sub2)
sub2
7-5-12 Auxiliary Output 2 Allocation (sub2

Function This parameter allocates the data to be output to the auxiliary output 2 termi-
nals (terminals 14 and 15.)

Communications
ch Variable type Address
Shared C3 0011 or 0111

Settings
Setting range Unit Default
Refer to the table of setting ranges for control output 1 alloca- - 7: ch2
tion. alarm 1
and HB
alarm OR
output

cont)
cont
7-5-13 Operation after Power ON (cont

Function • This parameter selects either “stop” or “continue” for the E5ZN operation
after the power has been turned ON.
• The operation after a software reset or when moving from initial setting
level to operation level depends on the “stop” or “continue” selection
made using this parameter.

Communications
ch Variable type Address
Shared C3 0012 or 0112

Settings
Setting range Unit Default
00000000H to 00000001H - 0: Stop
0: Stop (no)
1: Continue (yes)

See Also 3-10 Starting and Stopping Control (page 37)

134
Advanced Function Setting Level Section 7-6

7-6 Advanced Function Setting Level


7-6-1 init)
init
Parameter Initialize (init

Function This parameter returns all settings to their defaults.

Communications Use the “parameter initialize” operation command. Refer to page 82 for infor-
mation.

Example of Use ON (on): Initializes all parameters.


OFF (off): Turns OFF the E5ZN after returning parameter settings to their
defaults.

7-6-2 eU-m)
eU-m
Number of Multi-SP Uses (eU-m

Function • This parameter sets the multi-SP set points that are used for the event
input.
• When the number of multi-SP uses setting has been changed, the setting
must enabled by executing a software reset or by turning ON the power
again.

Communications
ch Variable type Address
Shared C3 0017 or 0117

Settings
Setting range Unit Default
00000000H to 00000001H - 0: No
0: No multi-SP multi-SP
1: SP0/1

7-6-3 eU)
eU
Event Input Allocation (eU
Condition: The number of multi-SP uses must be set to “0.”

Function • By selecting this parameter to “RUN/STOP,” an external signal can be


used to control RUN/STOP status.
• Settings are not possible when the “number of multi-SP uses” parameter
is set to 1 (2: multi-SP).
• Setting changes to event input allocations must be enabled by executing
a software reset or turning ON the power again.

Communications
ch Variable type Address
Shared C3 0018 or 0118

135
Advanced Function Setting Level Section 7-6

Settings
Setting range Unit Default
00000000H to 00000001H - 0: None
0: None (none)
1: RUN/STOP (stop)

Note The relationship with the external signal when RUN/STOP has been selected is shown
below.
External signal OFF: STOP (operation stop)
ON: RUN (operation)

See Also • Related Parameter


“Number of Multi-SP uses” (advanced function setting level) (page 135)

7-6-4 mspu)
mspu
Multi-SP Uses (mspu
Condition: The “number of multi-SP uses” parameter must be set to 0.

Function • When set to ON, this parameter enables switching between SP0 and SP1
by using communications command or E5ZN-SDL Setting Display Unit
key operations.
• Setting changes to this parameter must be enabled by executing a soft-
ware reset or by turning ON the power again.

Communications
ch Variable type Address
Shared C3 0019 or 0119

Settings
Setting range Unit Default
00000000H to 00000001H - 0: OFF
0: OFF (off)
1: ON (on)

Note To switch between set points using event input, set the “number of multi-SP uses” to
“1.”

See Also • Related Parameter


“Number of Multi-SP uses” (advanced function setting level) (page 135)

7-6-5 sprt)
sprt
SP Ramp Set Value (sprt

Function • This parameter specifies the rate of change during SP ramp operation.
Set the maximum permissible change width per unit of time (minute) as
the “SP ramp set value.” When the “SP ramp set value” is set to 0, the SP
ramp function is disabled.
• During temperature input, the decimal point position of the SP ramp set
value is dependent on the currently selected sensor, and during analog
input it is dependent on scaling.
• Setting changes to “SP ramp set value” must be enabled by executing a
software reset or by turning ON the power again.

136
Advanced Function Setting Level Section 7-6

Communications
ch Variable type Address
1 C3 001A
2 C3 011A

Settings
Setting range Unit Default
00000000H to 00000271H (0 to 9999) EU/min. 0: OFF
0: OFF

See Also • Related Parameters


“Input type” (initial setting level) (page 128)
“Scaling upper limit” “Scaling lower limit” “Decimal point” (initial setting
level) (page 129)

7-6-6 rest)
rest
Standby Sequence Reset Method (rest
Condition: The alarm 1 to 3 type must be set to an alarm with a standby
sequence.

Function • This parameter selects the conditions for enabling reset after the standby
sequence of the alarm has been canceled.
• Condition A:
Control started (including power ON) or change made in set point, alarm
value (upper/lower limit alarm value), or input shift value (upper/lower limit
temperature input shift value).
• Condition B:
Power ON
• The following example shows the reset action when the alarm type is
lower limit alarm with standby sequence.
Condition A only
SP change

Alarm point
(after change)
Alarm hysteresis

Condition A only Standby sequence


Alarm point canceled point
Standby sequence
reset point

Alarm output:
Condition A
Alarm output:
Condition B

• Setting changes to “standby sequence reset” must be enabled by execut-


ing a software reset or by turning ON the power again.

Communications
ch Variable type Address
Shared C3 001B or 011B

137
Advanced Function Setting Level Section 7-6

Settings
Setting range Unit Default
00000000H to 00000001H - 0: Condition A
0: Condition A (a)
1: Condition B (b)

See Also • Related Parameters


”Alarm 1to 3 type” (initial setting level) (page 132)
”Alarm 1 to 3 latch” (advanced function setting level) (page 143)

7-6-7 al1n)
al1n
Alarm 1 Open for Alarm (al1n
al2n)
al2n
Alarm 2 Open for Alarm (al2n
al3n)
al3n
Alarm 3 Open for Alarm (al3n

Function • These parameters set the output states for alarm 1, 2, and 3.
• When the E5ZN is set to “close for alarm,” the alarm output is normally
open. When set to “open for alarm,” the alarm output is normally closed.
The following table shows the relationship between alarm output func-
tions, alarm output, and operation indicator LEDs.
• When alarm 1 is set to “open for alarm,” the heater burnout alarm output
also are also normally closed.
Setting Alarm Output Function Alarm Output Operation
Indicator LEDs
Close for ON ON Lit
alarm OFF OFF Not lit
Open for ON OFF Lit
alarm OFF ON Not lit

• Setting changes to “alarm 1 to 3 open for alarm” must be enabled by exe-


cuting a software reset or by turning ON the power again.

Communications
Setting ch Variable type Address
Alarm 1 open for alarm 1 C3 001C
2 C3 011C
Alarm 2 open for alarm 1 C3 001E
2 C3 011E
Alarm 3 open for alarm 1 C3 0020
2 C3 0120

Settings
Setting Setting range Unit Default
Alarm 1 open for alarm 00000000H to 00000001H - 0: close for
Alarm 2 open for alarm 0: Close for alarm (n-o) alarm
Alarm 3 open for alarm 1: Open for alarm (n-c)

138
Advanced Function Setting Level Section 7-6

See Also • Related Parameters


“Alarm value 1 to 3” (operation level) (page 117)
“Upper limit alarm value 1” “Lower limit alarm value 1” (operation level)
(page 118) ”Upper limit alarm value 2” “Lower limit alarm value 2” (opera-
tion level) (page 118)
“Alarm 1 to 3 type” (initial setting level) (page 132)
“Control output 1 allocation” “Control output 2 allocation” (initial setting
level) (page 132) ”Auxiliary output 1 allocation” “Auxiliary output 2 alloca-
tion” (initial setting level) (page 133)
“Alarm 1 to 3 hysteresis” (advanced function setting level) (page 139)
“Standby sequence reset method” (advanced function setting level)
(page 137)
“Alarm 1 to 3 latch” (advanced function setting level) (page 143)

7-6-8 alh1)
alh1
Alarm 1 Hysteresis (alh1
alh2)
alh2
Alarm 2 Hysteresis (alh2
alh3)
alh3
Alarm 3 Hysteresis (alh3
Condition: The alarm type must be set to other than “no alarm.”

Function • These parameters set the hystereses of alarm outputs 1, 2, and 3.


• Setting changes to “alarm 1 to 3 hysteresis” must be enabled by execut-
ing a software reset or by turning ON the power again.

Communications
Setting ch Variable type Address
Alarm 1 hysteresis 1 C3 001D
2 C3 011D
Alarm 2 hysteresis 1 C3 001F
2 C3 011F
Alarm 3 hysteresis 1 C3 0021
2 C3 0121

Settings
Setting Setting range Unit Default
Alarm 1 hysteresis 00000001H to 00000270H Temperature 0.2
Alarm 2 hysteresis (0.1 to 999.9) input: °C/°F
Alarm 3 hysteresis Analog input:
EU

See Also • Related Parameters


“Alarm value 1 to 2” (operation level) (page 117)
“Upper limit alarm value 1” “Lower limit alarm value 1” (operation level)
(page 118) “Upper limit alarm value 2” “Lower limit alarm value 2” (opera-
tion level) (page 119)
“Alarm 1 to 3 type” (initial setting level) (page 132)
“Control output 1 allocation” “Control output 2 allocation” (initial setting
level) (page 132) “Auxiliary output 1 allocation” “Auxiliary output 2 alloca-
tion” (initial setting level) (page 133)
“Alarm 1 to 3 open for alarm” (advanced function setting level) (page 138)
“Standby sequence reset method” (advanced function setting level)
(page 137)
“Alarm 1 to 3 latch” (advanced function setting level) (page 143)

139
Advanced Function Setting Level Section 7-6

7-6-9 hbu)
hbu
HBA Used (hbu

Function • This parameter sets use of the heater burnout alarm.


• Setting changes to “HBA used” must be enabled by executing a software
reset or by turning ON the power again.

Communications
ch Variable type Address
Shared C3 0022 or 0122

Settings
Setting range Unit Default
00000000H to 00000001H - 1: Used
0: Not used (off)
1: Used (on)

hbl)
hbl
7-6-10 Heater Burnout Latch (hbl
Condition: The “HBA used” parameter must be set to “ON”.

Function • When this parameter is set to ON, the heater burnout alarm is held until
either of the following conditions is satisfied:
a) Heater burnout detection is set to 0.0 A.
b) The power is turned OFF then back ON again (power is reset).
• When switching to setting area 1, the output is turned OFF.
• Setting changes to “heater burnout latch” must be enabled by executing a
software reset or by turning ON the power again.

Communications
ch Variable type Address
Shared C3 0023 or 0123

Settings
Setting range Unit Default
00000000H to 00000001H - 0: Disabled
0: Disabled (off)
1: Enabled (on)

See Also • Related Parameter


“HBA used” (advanced function setting level) (page 140)

hbh)
hbh
7-6-11 Heater Burnout Hysteresis (hbh
Condition: The “heater burnout latch” parameter must be set to OFF.

Function • This parameter sets the hysteresis when HBA is detected.


• Setting changes to “heater burnout hysteresis” must be enabled by exe-
cuting a software reset or by turning ON the power again.

Communications
ch Variable type Address
1 C3 0024
2 C3 0124

140
Advanced Function Setting Level Section 7-6

Settings
Setting range Unit Default
00000001H to 000001F4H (0.1 to 50.0) A 0.1

See Also • Related Parameter


“HBA used” (advanced function setting level) (page 140)

7-6-12 a (alfa
alfa)
alfa
Condition: The control must be 2-PID control.

Function • Normally, use this parameter at its default.


• This parameter sets the 2-PID constant a.
• Setting changes to “a” must be enabled by executing a software reset or
by turning ON the power again.

Communications
ch Variable type Address
Shared C3 0025 or 0125

Settings
Setting range Unit Default
00000000H to 00000064H (0.00 to 1.00) - 0.65

See Also • Related Parameter


“PID/OnOff” (initial setting level) (page 130)

ol-h)
ol-h
7-6-13 MV Upper Limit (ol-h
ol-l)
ol-l
MV Lower Limit (ol-l
Condition: The control must be 2-PID control.

Function • The “MV upper limit” and “MV lower limit” parameters set the upper and
lower limits of the manipulated variable. When the manipulated variable
calculated by the E5ZN exceeds the upper or lower limit value, the upper
or lower limit will be used as the output level.
• MV Upper Limit
The setting ranges during standard control and heating and control output
2 control are different.
The manipulated variable at the cooling side during heating and cooling
control is expressed as a negative value.
• MV Lower Limit
The setting ranges during standard control and heating and cooling con-
trol are different.
The manipulated variable at the cooling side during heating and cooling
control is expressed as a negative value.
• Setting changes to “MV upper and lower limit” must be enabled by exe-
cuting a software reset or by turning ON the power again.

141
Advanced Function Setting Level Section 7-6

Communications
Setting ch Variable type Address
MV upper limit value 1 C3 0026
2 C3 0126
MV lower limit value 1 C3 0027
2 C3 0127

Settings
Setting Setting range Unit Default
MV upper For Standard Control: % 105.0
limit value (MV lower limit + 1)H to 0000041AH
(MV lower limit + 0.1 to 105.0)
For Heating and Cooling Control: % 105.0
00000000H to 0000041AH
(0.0 to 105.0)
MV lower For Standard Control: % -5.0
limit value FFFFFFCEH to (MV upper limit - 1)H
(-5.0 to MV upper limit -1)
For Heating and Cooling Control % -105.0
FFFFFBE6H to 00000000H
(-105.0 to 0.0)

See Also • Related Parameter


“PID/OnOff” (initial setting level) (page 130)

inf)
inf
7-6-14 Input Digital Filter (inf

Function • Sets the time constant of the input digital filter. The following figure shows
the effect on data after passing through the digital filter:

PV before passing through filter


A
PV after passing through filter

0.63 A

Time constant

Input digital filter

• Setting changes to “input digital filter” must be enabled by executing a


software reset or by turning ON the power again.

Communications
ch Variable type Address
1 C3 0028
2 C3 0128

Settings
Setting range Unit Default
00000000H to 00000270H (0.0 to 999.9) Second 0.0

142
Advanced Function Setting Level Section 7-6

pUad)
pUad
7-6-15 Additional PV Display (pUad

Function • This parameter enables displaying only the PV. It is added to the top of
the operation level of the E5ZN-SDL Setting Display Unit. It is used to
give the option of displaying the PV and SP, or just the PV only.
• Setting changes to “additional PV display” must be enabled by executing
a software reset or by turning ON the power again.

Communications
ch Variable type Address
Shared C3 0029 or 0129

Settings
Setting range Unit Default
00000000H to 00000001H - 0: Not added
0: Not added (off)
1: Added (on)

isdp)
isdp
7-6-16 Additional Temperature Input Shift Value Display (isdp

Function • This parameter stops the display of the temperature input shift value in
the E5ZN-SDL Setting Display Unit operation level. The shift function is
enabled even when this parameter is set to “no display. “
• Setting changes to “temperature input shift value display/not display”
must be enabled by executing a software reset or by turning ON the
power again.

Communications
ch Variable type Address
Shared C3 002A or 012A

Settings
Setting range Unit Default
00000000H to 00000001H - 0: No display
0: No display (off)
1: Display (on)

a1lt)
a1lt
7-6-17 Alarm 1 Latch (a1lt
a2lt)
a2lt
Alarm 2 Latch (a2lt
a3lt)
a3lt
Alarm 3 Latch (a3lt
Condition: The alarm type must be set to other than “no alarm.”

Function • When these parameters are set to ON, the latch function is added to the
alarm functions. This means that once the alarm function has turned ON,
the alarm output function is held ON until the power is turned OFF. The
latch is canceled if setting area 1 is switched to.
• When alarm output function is set to “open for alarm,” the closed output is
held, and when set to “close in alarm,” the open output is held.
• Setting changes to “alarm 1 to 3 latch” must be enabled by executing a
software reset or by turning ON the power again.

143
Advanced Function Setting Level Section 7-6

Communications
Setting ch Variable type Address
Alarm 1 latch 1 C3 002B
2 C3 012B
Alarm 2 latch 1 C3 002C
2 C3 012C
Alarm 3 latch 1 C3 002D
2 C3 012D

Settings
Setting Setting range Unit Default
Alarm 1 latch 00000000H to 00000001H - 0: OFF
Alarm 2 latch 0: OFF (off)
Alarm 3 latch 1: ON (on)

See Also • Related Parameters


“Alarm value 1 to 3” (operation level) (page 117)
“Upper limit alarm value 1” “Lower limit alarm value 1” (operation level)
(page 118) ”Upper limit alarm value 2” “Lower limit alarm value 2” (opera-
tion level) (page 119)
“Alarm 1 to 3 type” (initial setting level) (page 132)
“Standby sequence reset method” (initial setting level) (page 137)
“Alarm 1 to 3 open for alarm” (advanced function setting level) (page 138)
“Alarm 1 to 3 hysteresis” (advanced function setting level) (page 139)

cjc)
cjc
7-6-18 Cold Junction Compensation Method (cjc
Condition: Input type must be thermocouple or non-contact temperature
sensor.

Function • Specifies whether cold junction compensation is to be performed inter-


nally by the Controller or to be performed externally when the input type
set value is No. 0 to 15, 17 or 18.
• The cold junction compensation external setting is valid when the temper-
ature difference is measured using two thermocouples or two ES1As.
• Setting changes to “cold junction compensation method” must be enabled
by executing a software reset or by turning ON the power again.

Communications
ch Variable type Address
Shared C3 002E or 012E

Settings
Setting range Unit Default
00000000H to 00000001H - 1: Internally
0: External (off)
1: Internal (on)

See Also • Related Parameter


“Input type” (initial setting level) (page 128)

144
Communications Setting Level Section 7-7

7-7 Communications Setting Level


7-7-1 len)
len
Communications Data Length (len

Function Setting changes to “communications data length” must be enabled by execut-


ing a software reset or by turning ON the power again.

Communications
ch Variable type Address
Shared C3 0013 or 0113

Settings
Setting range Unit Default
00000007H to 00000008H (7 or 8) Bit 7

7-7-2 sbit)
sbit
Communications Stop Bit (sbit

Function Setting changes to “communications stop bit” must be enabled by executing a


software reset or by turning ON the power again.

Communications
ch Variable type Address
Shared C3 0014 or 0114

Settings
Setting range Unit Default
00000001H to 00000002H (1 or 2) Bit 2

7-7-3 prty)
prty
Communications Parity (prty

Function Setting changes to “communications parity” must be enabled by executing a


software reset or by turning ON the power again.

Communications
ch Variable type Address
Shared C3 0015 or 0115

Settings
Setting range Unit Default
00000000H to 00000002H - 1: Even
00000000H (0): None (none)
00000001H (1): Even (eUen)
00000002H (2): Odd (odd)

145
Communications Setting Level Section 7-7

7-7-4 sdwt)
sdwt
Communications Response Wait Time (sdwt

Function Setting changes to “communications response wait time” must be enabled by


executing a software reset or by turning ON the power again.

Communications
ch Variable type Address
Shared C3 0016 or 0116

Settings
Setting range Unit Default
00000000H to 0000270FH (0 to 9999) ms 20

146
SECTION 8
Troubleshooting
This section describes the troubleshooting procedure and possible errors and remedies when the E5ZN is not operating
properly. When performing troubleshooting, follow the order in which information is provided in this section.

8-1 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148


8-2 Communications Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
8-3 Temperature Sensing Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
8-4 Temperature Control Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
8-5 Output Errors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
8-6 HB Alarm Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155

147
Troubleshooting Procedure Section 8-1

8-1 Troubleshooting Procedure


If the E5ZN has an error, refer to the following items to find the possible cause
of the error and take corrective measures.
1,2,3... 1. Indicators
Check the operating status of the E5ZN using the indicators.
If the ERROR indicator is lit, turn the E5ZZ OFF and ON. If the ERROR
indicator is not lit after the E5ZN is turned ON, it may mean that the E5ZN
is being influenced by noise. Find the source of the noise and provide ad-
equate protection against it.
2. Switch, Selectors, and Wiring
Check if the switch and selector settings of the E5ZN, the wiring of the
E5ZN and devices connected to the E5ZN are correct.
a) Power Supply
• Check that the power supply connected to the E5ZN is turned ON.
• Check whether the supply voltage at the power supply terminals is
within the allowable voltage range of the E5ZN.
b) Switch and Selectors
Check that the switch and selectors of the E5ZN are correctly set ac-
cording to the system.
c) Wiring
• Check that the terminal block wiring is correct.
• Check that the polarity of each wire connected to the E5ZN is correct.
• Check if any wire is disconnected.
• Check if a wire or cable is cut or short-circuited.
d) Communications Conditions
Check that the communications conditions of the E5ZN are compatible
with the host connected to the E5ZN.
Check the above items and remedy any problems listed above. If the error
persists after error processing, perform further checks through communi-
cations.
3. Checking through Communications
• Check the end code and error code with the response returned from
the E5ZN.
• Check the status of the E5ZN with the Status Read Command.
• Check if the functions used with the E5ZN have any operating restric-
tions.
• Check if the set data items of the communication commands used for
the E5ZN are correct.
Troubleshoot problems on the basis of the data read with the E5ZE.
4. Troubleshooting Based on Error Symptoms
If the cause of the error is still unknown after checking all the previously
mentioned items, find the cause by isolating the symptoms of the error
while referring to the tables in 8-2 Communications Errors, and correct the
problem accordingly.

148
Communications Errors Section 8-2

8-2 Communications Errors


Communications Not Possible or No Response
Probable cause Remedy
Communications Baud rate of the E5ZN is different from that of the Set the same rate.
conditions host.
Communications method of the E5ZN is different Match the communications method of the E5ZN
from that of the host. to the host's communications conditions.
Connections Excessive number of E5ZN Units are connected Do not connect an excessive number of E5ZN
in parallel. Units.
• The number of E5ZN Units that can be con-
nected to the host for RS-485 communications
is 16 max.
Transmission path is too long. The transmission path must be within the permis-
sible range.
• The maximum RS-485 transmission path is
500 m in total.
Same unit number has been allocated more than Make sure that different numbers are assigned to
once on the same transmission path. all the E5ZNUnits that communicate with the host.
Communications data error due to ambient noise. • Move the communications cable away from the
source of noise.
• Use shielded communication cables.
• Use an Optical Interface.
• Write a program that makes it possible for the
host to detect a response error for any com-
mand that the host transmits and to re-transmit
it again.
Mistake in the use of the Optical Interface and Refer to the datasheets of the Optical Interface
RS-232C/RS-485 Converter Units. and RS-232C/RS-485 Converter Units used.
Terminators incorrectly attached to RS-485. Attach terminators only to the devices at each end
of the communications path.
Program System begins communications without any inter- Write a program so that the system starts com-
val after the E5ZN Units are turned ON. munications with an interval of 4 s min. after the
E5ZN Units are turned ON.
Unstable signal of the E5ZN, which is generated Initialize the reception buffer of the host at the fol-
when the E5ZN is turned ON or OFF, is read as lowing stages.
data by the host. • Before the host transmits the first command.
• After the E5ZN is turned OFF.
Host sends commands to the E5ZN before receiv- Write a program enabling the host to read the
ing any response from the E5ZN. response after the host sends any command.
Interval between the time the host receives a The interval between the time the host receives a
response and sends a command is too short. response and sends a command must be 5 min-
utes minimum.
Program of the host is incorrect. • Correct the program.
• Check the command with the line monitoring
function.
• Run a sample program with the host.
Settings Unit numbers set with the selectors are different The unit numbers must coincide.
from those set using the commands of the host.

149
Temperature Sensing Errors Section 8-3

8-3 Temperature Sensing Errors


Temperature Sensing Not Possible or Abnormal
Probable cause Remedy
Connections Polarity or wiring of a temperature sensor is incor- Correct the wiring of the temperature sensor.
rect.
Temperature sensor is not an applicable one. Replace the temperature sensor with an applica-
ble one.
Leads of a temperature sensor are disconnected, Replace the temperature sensor.
short-circuited, or deteriorated.
Temperature sensors are not used. Use temperature sensors.
Thermocouple does not use applicable compen- • Replace the thermocouple with another ther-
sating conductors. mocouple with long leads.
• Connect applicable compensating conductors
for the thermocouple.
Thermocouple is connected to the E5ZN with a Connect a thermocouple-dedicated device
device using a metal that is different in type from between the thermocouple and the E5ZN.
the metal of the thermocouple or that of the com-
pensating conductors.
A screw of the terminal block of the E5ZN is loos- Tighten the screw.
ened and improper contact is resulting.
Leads or compensating conductors of a thermo- • Use sufficiently thick compensating conduc-
couple are too long and leads or compensating tors.
conductors have resistance. • Change the location of the thermocouple so
that the length of the leads or compensating
conductors can be shortened.
The resistance of the conductors for the 3 termi- Use conductors that are the same in resistance
nals is different from the resistance of the temper- for the two B terminals and the A terminal.
ature sensor connected to the E5ZN.
Installation Noise is affecting the E5ZN. • Separate the E5ZN from the source of the
noise.
• Connect a surge absorber or noise filter to the
device generating the noise.
Inductive noise generated from power lines is • Separate the leads from the power lines.
affecting the leads of a temperature sensor. • Wire the leads in a separate conduit or duct.
• Do not wire the leads alongside power lines.
• Shorten the leads.
• Shield the leads.
Thermal response of a temperature sensor con- Locate the tip of the protective tubing of the tem-
nected to the E5ZN is slow because the tempera- perature sensor at the temperature controlling
ture sensor is located far from the temperature position.
controlling position of the E5ZN.
Ambient operating temperature of the E5ZN is not The ambient operating temperature range of the
within the allowable ambient operating tempera- E5ZN must be between -10 and 55°C.
ture range of the E5ZN.
Ambient operating temperature of the E5ZN is not Shield the E5ZN.
within the allowable ambient operating tempera-
ture range of the E5ZN.
E5ZN is affected by heat radiation from Peripheral Install the E5ZN in a location where it will not be
Devices and the temperature of the terminal block affected by heat radiation.
of the E5ZN is not even.
Terminal block of the E5ZN is affected by wind. Protect the terminal block of the E5ZN against
wind.

150
Temperature Sensing Errors Section 8-3

Probable cause Remedy


Settings Selector settings for the input type of temperature Correct the input type setting.
sensor are incorrect.
Celsius-Fahrenheit designation of the E5ZN is Correct the °C/°F selection switch setting.
incorrect.
The process value appears to be incorrect due to Set the input shift to 0.0.
the input shift setting.
Data setting unit is incorrect. Change the program of the host.
Program of the host is incorrect.
Operation Temperature sensor input terminals of the E5ZN Connect a thermocouple to the temperature sen-
thermocouple input model have been short-cir- sor input terminals.
cuited.
Temperature sensor connected to the E5ZN has Turn OFF the power to the E5ZN, and then turn
been replaced or the switch or selector settings of ON again.
the E5ZN have been changed while the power is
ON.

Simple Method for Checking Temperature Sensors


Platinum Resistance Thermometer
1,2,3... 1. Connect a 100-W resistor between the A and B temperature sensor input
terminals and short-circuit the B terminals.
2. If the temperature sensed by the E5ZN is 0.0°C or 32.0°F, the E5ZN is op-
erating normally.
Thermocouple
1,2,3... 1. Short-circuit the temperature sensor input terminals of the E5ZN.
2. If the E5ZN senses the temperature of the terminal block of the E5ZN, the
E5ZN is operating normally.

151
Temperature Control Errors Section 8-4

8-4 Temperature Control Errors


Temperature Does Not Rise
Probable cause Remedy
Connections Process value of the E5ZN is abnormal. Refer to 8-3 Temperature Sensing Errors for
appropriate troubleshooting.
Load is not connected to the control output termi- Connect a load.
nal of the E5ZN.
Polarity or wiring of a load is incorrect. Correct the wiring of the load.
A screw of the terminal block of the E5ZN is loos- Tighten the screw.
ened and improper contact is resulting.
Power is not supplied to heaters. Supply power to the heaters.
Heaters are burnt out or have deteriorated. Replace the heaters.
Heat capacity of the heater is too small. • Replace the heater with one having a larger
heat capacity.
• If more than one heater is used and some are
burnt out, replace the heaters.
Overheating prevention device for the E5ZN is The set value of the overheating prevention
operating. device must be larger than the set value of the
E5ZN.
Settings E5ZN is in reverse operation mode, instead of Correct the operation mode setting.
direct operation mode, or vice versa.
PID constants of the E5ZN are incorrect. • Execute autotuning.
• Set the PID constants of the E5ZN to appropri-
ate values.
E5ZN has not started temperature control. Start the temperature control.
Control output value of the E5ZN does not Set the MV limit value of the E5ZN to an appropri-
increase because of the restrictions of the MV ate value.
limit value.
Cooling fan is operating. Turn OFF the cooling fan.

Process Value Exceeds Set Point


Probable cause Remedy
Connections Process value of the E5ZN is abnormal. Refer to 8-3 Temperature Sensing Errorsfor
appropriate troubleshooting.
Load is connected to the incorrect control point of Correct the wiring of the load.
the E5ZN and is controlling the heaters with the
control output of the incorrect control point.
Relay driven by control output has contact weld. Replace the relay.
SSR is short-circuited. Replace the SSR.
SSR leakage current is flowing into the heaters. Connect a bleeder resistance to the SSR to pre-
vent operation with the SSR leakage current.
Settings E5ZN is in reverse operation mode, instead of Correct the operation mode setting.
direct operation mode, or vice versa.
PID constants of the E5ZN are incorrect. • Execute autotuning.
• Set the PID constants of the E5ZN to the val-
ues suitable to the system.
Control output value of the E5ZN does not Set the MV limit value of the E5ZN to an appropri-
increase because of the restrictions of the set MV ate value.
limit value.
E5ZN is outputting in manual mode. Interrupt the manual mode of the E5ZN.
Operation Controlled object is radiating heat. Execute heating and cooling control.
Controlled object is influenced by large overshoot- Refer to the following table regarding overshoot-
ing. ing and undershooting for appropriate trouble-
shooting.

152
Temperature Control Errors Section 8-4

Overshooting or Undershooting
Probable cause Remedy
Connections Process value of the E5ZN is abnormal. Refer to 8-3 Temperature Sensing Errors for
appropriate troubleshooting.
General-purpose temperature sensor with slow Change to a sheath-type temperature sensor.
thermal response characteristics is being used to
sense a controlled object with quick thermal
response characteristics.
Settings E5ZN has a narrow proportional band and small • Increase the P constant keeping within the
P constant. range where the response delay caused by the
P constant can be allowed.
• Execute autotuning.
E5ZN has a short integral time or small I constant. • Increase the I constant keeping within the
range where the response delay caused by the
I constant can be allowed.
• Execute autotuning.
E5ZN has a short derivative time or small D con- • Increase the D constant keeping within the
stant. range where the D constant will not have an
undesirable influence on temperature stability.
• Execute autotuning.
E5ZN is executing ON and OFF control. Execute P or PID control.
Control period is too long when the E5ZN controls Shorten the control period.
the temperature of an object with quick thermal
response characteristics.
Dead band instead of an overlap band is set with Set the overlap band of the E5ZN.
the E5ZN in heating and cooling control opera-
tion.

Hunting
For troubleshooting problems with connections and settings, refer to the same
probable causes and remedies as provided for overshooting and undershoot-
ing.
Probable cause Remedy
Operation Heat capacity of a heater controlling the tempera- Use a heater with a heat capacity suited to the
ture of an object is too large for the object. object.
Heat capacity of a controlled object changes due Take appropriate measures to prevent the periodi-
to periodical external disturbances. cal external disturbances.
E5ZN is executing autotuning. Hunting will not occur if autotuning is completed.

153
Output Errors Section 8-5

8-5 Output Errors


Control Output or Alarm Output Does Not Turn ON
Probable cause Remedy
Connections Process value of the E5ZN is abnormal. Refer to 8-3 Temperature Sensing Errorsfor
appropriate troubleshooting.
Polarity of the load or connected terminals are Correct the wiring.
wired incorrectly.
Load exceeding the output ratings of the E5ZN is • Connect a load that does not exceed the out-
connected. put ratings to the E5ZN.
• Request repair of the E5ZN if it is malfunction-
ing.
Load power supply is not connected to transistor Provide a power supply satisfying the output rat-
output. ings of the E5ZN and suitable for the load.
Polarity of the load power supply for transistor Correct the wiring.
output is incorrect.
Settings Operation after power ON has been stopped. • Send A Control Operation run command from
the host after turning the E5ZN ON.
• Set operation after power ON to “continue.”
E5ZN has not started control operation. Sent a Control Operation RUN command from the
host.
Control point designation is incorrect. Set the correct control point numbers.
Set point of the E5ZN is set incorrectly. Correct the set point settings.
Incorrect multi-SP is designated. Set the correct multi-SP.
The same multi-SP is selected for all channels Specify a setting other than “event input” for multi-
because event input is designated for multi-SP. SP so that different multi-SP can be designated
for each channel.
When designating multi-SP with event input, the Set the E5ZN so that the ON or OFF status of the
ON or OFF status of the input is not kept on hold. input is kept on hold while designating the multi-
SP with the event input.
E5ZN attempts multi-SP designation with commu- Correct the multi-SP designation method setting.
nications when multi-SP event input designation
is selected.
Alarm mode of the E5ZN is set to 0 (no alarm Set the correct alarm mode.
function).
Alarm mode of the E5ZN is set to alarm with Use alarms without a standby sequence.
standby sequence.
Deviation value and absolute value are incorrect Set the correct alarm mode.
for the alarm mode set.

154
HB Alarm Errors Section 8-6

8-6 HB Alarm Errors


HB Alarm Errors: Heater Burnout Detection Function Not Possible
Probable cause Remedy
Connections Current Transformer is not connected. Connect a Current Transformer to the E5ZN.
Current Transformer is wired to an incorrect chan- Wire the Current Transformer to the correct chan-
nel of the E5ZN. nel.
Heaters are controlled directly with an alarm out- Change the wiring so that the CT input is con-
put. nected to the correct control output.
Settings E5ZN has not started control operation. Start the control operation.
Control output is ON for less than 190 ms. The HB alarm will operate if the control output is
turned ON for 190 ms or more.
HB alarm is not set in output allocations. Set “Alarm 1 and HAB OR output” in output
assignments.
Heaters are turned ON after the E5ZN starts con- Turn ON the heaters before starting the E5ZN
trol operation. control operation.
Heater burnout detection current value of the Set the heater burnout detection current value to
E5ZN is set to 0.0 or 50.0 A. an appropriate value between 0.1 and 49.9 A.
Heater burnout detection current value of the Determine the heater burnout detection current
E5ZN is set to the rated current. value from the actual current consumption of the
heaters.
Heater burnout detection current value obtained Reset the heater burnout detection current value
from the actual current consumption of the heat- by considering the voltage range of the power
ers is incorrect. supply for the heaters and any error in measure-
ment of the current.
Operation Total current consumption of the heaters con- Set the heater current to 50.0 A maximum.
nected to the E5ZN exceeds 50.0 A.
Heaters connected are supplied with DC. The HB alarm do not operate under this condition.
Pure metal heaters are being used. Determine the heater burnout detection current
value from the actual current consumption of the
heaters.

155
HB Alarm Errors Section 8-6

156
Appendix A
Specifications

Ratings
Supply voltage 24 VDC
Operating voltage 85% to 110% of rated supply voltage
range
Power consumption Approx. 3 W
Sensor input Thermocouple: K, J, T, E, L, U, N, R, S, B
Platinum resistance thermometer: Pt100, JPt100
Non-contact temperature sensor: K10 to 70°C, K60 to 120°C, K115 to 165°C, K160 to 260°C
Voltage input: 0 to 50 mV
Control output Pulse voltage 12 VDC ± 15%, max. load current 21 mA
output (PNP) Short-circuit proof
Transistor out- Max. operational voltage 30 VDC, max. load current 100 mA
put Max. residual voltage 1.5 V, max. leakage current 0.4 mA
Auxiliary output Sink type Max. operational voltage 30 VDC, max. load current 50 mA
Source type Max. residual voltage 1.5 V, max. leakage current 0.4 mA
Event input Contact ON: 1 kW max., OFF: 100 kW min.
Non-contact ON: Max. residual voltage 1.5 V, OFF: Max. leakage current 0.1 mA
No. of input/control 2 input points, 2 control points
points
Setting method Communications or E5ZN-SDL Setting Display Unit
Control method 2-PID or ON/OFF control
Other functions Heater burnout alarm function, multi-SP with event input or RUN/STOP selection
Ambient tempera- -10 to 55°C (with no condensation or icing)
ture
Ambient humidity 25% to 85%
Storage temperature -25 to 65°C (with no condensation or icing)
Altitude 2,000 m or less
Inrush current 13 A max.
Recommended fuse T4A, 125 V, time lag, low shut-off capacity
Installation environ- Installation Category II, Pollution Class 2 (UL3121-1, CSA C22-2 No. 1010-1 compliant)
ment

HBA
Max. heater current Single-phase AC 50 A
Input current readout accuracy ±5%FS±1 digit max.
Heater burnout alarm setting range 0.1 to 49.9 A (0.1 A units)
0.0 A: Heater burnout alarm output turns OFF.
50.0 A: Heater burnout alarm output turns ON.
Min. detection ON time (See note.) 190 ms

Note When the control output ON time is less than 190 ms, heater burnout detection and heater current measurement are
not performed.

157
Specifications Appendix A

Characteristics
Indication accuracy Thermocouple:
(±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max. (See note.)
Platinum resistance thermometer:
(±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.
Analog input: ±0.5%FS±1 digit max.
CT input: ±0.5%FS±1 digit max.
Hysteresis 0.1 to 999.9 EU (in units of 0.1 EU)
Proportional band 0.1 to 999.9 EU (in units of 0.1 EU)
(P)
Integral time (I) 0 to 3,999 s (in units of 1 second)
Derivative time (D) 0 to 3,999 s (in units of 1 second)
Control period 1 to 99 s (in units of 1 second)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position dependent on input type)
Sampling period 500 ms
Insulation resistance 20 MW min. (at 500 VDC)
Dielectric strength 600 VAC 50 or 60 Hz 1min
Vibration resistance 10 to 55 Hz, 10 m/s2 for 2 hrs. each in X, Y and Z directions
Shock resistance 150 m/s2 max. 3 times each in 3 axes, 6 directions
Protective structure Temperature Controller Module IP00
Terminal Unit IP00
Memory protection EEPROM (non-volatile memory) (number of writes: 100,000)
Weight Temperature Controller Module Approx. 90 g
Basic Terminal Unit Approx. 100 g
Expansion Terminal Unit Approx. 80 g

Note The indication of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of -100°C
or less, and U and L thermocouples at any temperature is ±2°C ±1 digit maximum. The indication of B thermocou-
ples at a temperature of 400°C or less is unrestricted.
The indication of R and S thermocouples at a temperature of 200°C or less is ±3°C ±1 digit maximum.

Ratings/Specifications for Setting Display Unit (Sold Separately)


Supply voltage 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consumption Approx. 1 W
Indication method 7-segment digital display and single-light indicator
Ambient temperature -10 to 55°C (with no condensation or icing)
Ambient humidity 25% to 85%
Storage temperature -25 to 65°C (with no condensation or icing)
Altitude 2,000 m or less
Recommended fuse T4A, 125 V, time lag, low shut-off capacity
Communications method RS-485 (half duplex)
Communications format Fixed
Insulation resistance 20 MW min. (at 500 VDC)
Dielectric strength 1500 VAC, 50 or 60 Hz 1min
Vibration resistance 10 to 55 Hz, 20 m/s2 for 2 hrs. each in X, Y and Z directions
Shock resistance 300 m/s2 max. 3 times each in 3 axes, 6 directions
Protective structure Front panel: IP50, Rear case: IP20, Terminal section: IP00
Memory protection EEPROM (non-volatile memory) (number of writes: 100,000)
Weight Approx. 100 g, Adapter: approx. 10g

158
Specifications Appendix A

Current Transformer (CT)


Specifications
Item Specifications
Model E54-CT1 E54-CT3
Max. continuous current 50 A 120 A (See note.)
Dielectric strength 1000 VAC (for 1 minute)
Vibration resistance 50 Hz 98m/s2 {10G}
Weight Approx. 11.5 g Approx. 50 g
Accessory None Armature (2)
Plug (2)

Note The maximum continuous current of the E5ZN is 50 A.

External Dimensions (Unit: mm)


E54-CT1
21
15 2.8

7.5

a.
di
8
5.
25

10.5

3
40 a.
di
.5
o,3
Tw
10

30

E54-CT3
2.36 dia.
30
9

a.
di
12
40 ´ 40

4
h
pt
de
3
M
2-
15
30

159
Specifications Appendix A

160
Appendix B
Error Displays

When an error has occurred, the E5ZN-SDL Setting Display Unit indicates the error codes.
This section describes how to check error codes on the display, and the actions you must take to remedy the
problem.

s.err Input Error


Meaning
The input value has exceeded the control range.
Note Control range
Platinum resistance thermometer, thermocouple input:
Temperature setting lower limit -20°C to temperature setting upper limit 20°C
(temperature setting lower limit -40°F to temperature setting upper limit 40°F)
ES1A input:
Same as input indication range
Analog input:
-5% to 105% of scaling range
Action
Check the wiring of inputs for mistakes in wiring, disconnections, short-circuits, and the input type.
If no abnormality is found in the wiring and input type, turn the power OFF then back ON again. If the display
remains the same, the E5ZN must be repaired. If the display is restored, then a probable cause can be electri-
cal noise affecting the control system. Check for electrical noise.
Operation at Error
After the error occurs, the error is displayed, and control output functions turn OFF.
Alarm outputs function as if the upper limit value has been exceeded.
An error message is displayed when “process value” or “PV/SP” are displayed.

<<<<,
<<<< >>>> Display range over
Meaning
Though this is not an error, this is displayed when the process value exceeds the display range when the con-
trol range is larger than the display range (-1999 to 9999).
• When less than “-1999” <<<<
• When larger than “9999” >>>>
Action
Control continues, allowing normal operation. An error message is displayed when “process value” or “PV/SP”
are displayed.

e111 Memory error


Meaning
Internal memory operation for the E5ZN-SDL Setting Display Unit is in error.
Action
First, turn the power OFF then back ON again. If the display remains the same, the E5ZN must be replaced. If
the display is restored, then a probable cause can be electrical noise affecting the control system. Check for
electrical noise.
Operation at Error
Key operations are not possible.

161
Error Displays Appendix B

ffff Current value exceeded


Meaning
This error is displayed when the heater current value exceeds 55.0A.
Action
Control continues, allowing normal operation. An error message is displayed when the heater current value
monitor is displayed.

---- Disabled Status


Meaning
This error is displayed when one of the following errors has occurred in the connection with the E5ZN.
• The connection cable is disconnected.
• The power supply to the E5ZN-SDL has been turned OFF while in copy mode.
• A memory error has occurred in the E5ZN. The control output and alarm outputs will be OFF for the E5ZN
generating the error.
Action
Units that do not show this disabled status will continue control and will operate normally. The selected Unit
and the channel status will be displayed.

162
Appendix C
Sensor Input Setting Ranges/Control Ranges

Sensor Input Name Set Input temperature setting range Control range
type value
Platinum Plati- Pt100 0 -200 to 850 °C or -300 to 1,500 °F -220 to 870 °C or -340 to 1,540 °F
resis- num 1 -199.9 to 500.0 °C or -199.9 to 900.0 °F -219.9 to 520.0 °C or -239.9 to 940.0 °F
tance resis-
ther- tance 2 0.0 to 100.0 °C or 0.0 to 210.0 °F -20.0 to 120.0 °C or -40.0 to 250.0 °F
mometer ther- JPt100 3 -199.9 to 500.0 °C or -199.9 to 900.0 °F -219.9 to 520.0 °C or -239.9 to 940.0 °F
input mometer 4 0.0 to 100.0 °C or 0.0 to 210.0 °F -20.0 to 120.0 °C or -40.0 to 250.0 °F
type
Thermo- Thermo- K 0 -200 to 1,300 °C or -300 to 2,300 °F -220 to 1,320 °C or -340 to 2,340 °F
couple couple 1 -20.0 to 500.0 °C or 0.0 to 900.0 °F -40.0 to 520.0 °C or -40.0 to 940.0 °F
input
type J 2 -100 to 850 °C or -100 to 1,500 °F -120 to 870 °C or -140 to 1540 °F
3 -20.0 to 400.0 °C or 0.0 to 750.0 °F -40.0 to 420.0 °C or -40.0 to 790.0 °F
T 4 -200 to 400 °C or -300 to 700 °F -220 to 420 °C or -340 to 740 °F
17 -199.9 to 400.0 °C or -199.9 to 700.0 °F -219.9 to 420.0 °C or -239.9 to 740.0 °F
E 5 0 to 600 °C or 0 to 1,100 °F -20 to 620 °C or -40 to 1,140 °F
L 6 -100 to 850 °C or -100 to 1,500 °F -120 to 870 °C or -140 to 1,540 °F
U 7 -200 to 400 °C or -300 to 700 °F -220 to 420 °C or -340 to 740 °F
18 -199.9 to 400.0 °C or -199.9 to 700.0 °F -219.9 to 420.0 °C or -239.9 to 740.0 °F
N 8 -200 to 1,300 °C or -300 to 2,300 °F -220 to 1,320 °C or -340 to 2,340 °F
R 9 0 to 1,700 °C or 0 to 3,000 °F -20 to 1,720 °C or -40 to 3,040 °F
S 10 0 to 1,700 °C or 0 to 3,000 °F -20 to 1,720 °C or -40 to 3,040 °F
B 11 100 to 1,800 °C or 300 to 3,200 °F 0 to 1,820 °C or 0 to 3,240 °F
ES1A K10 to 12 0 to 90 °C or 0 to 190 °F -20 to 130 °C or -40 to 270 °F
Infrared 70°C
tempera- K60 to 13 0 to 120 °C or 0 to 240 °F -20 to 160 °C or -40 to 320 °F
ture sen- 120°C
sor
K115 to 14 0 to 165 °C or 0 to 320 °F -20 to 205 °C or -40 to 400 °F
165°C
K160 to 15 0 to 260 °C or 0 to 500 °F -20 to 300 °C or -40 to 580 °F
260°C
Analog 0 to 16 One of the following ranges depending -5% to 105% of setting range
input 50 mA on the results of scaling:
-1,999 to 9,999 or -199.9 to 999.9

• Default is 0.
• The applicable standards for each of the above input ranges are as follows:
• K, J, T, E, N, R, S, B: JIS C1602-1995, IEC 584-1
• L: Fe-CuNi, DIN 43710-1985
• U: Cu-CuNi, DIN 43710-1985
• JPt100: JIS C 1604-1989, JIS C 1606-1989
• Pt100: JIS C 1604-1997 IEC 751

163
Sensor Input Setting Ranges/Control Ranges Appendix C

164
Appendix D
ASCII Table

Upper
Lower 0 1 2 3 4 5 6 7
0 NUL DLE SPACE 0 @ P ‘ p
1 SOH DC1 ! 1 A Q a q
2 STX DC2 “ 2 B R b r
3 ETX DC3 # 3 C S c s
4 EOT DC4 $ 4 D T d t
5 ENQ NAK % 5 E U e u
6 ACK SYN & 6 F V f v
7 BEL ETB ‘ 7 G W g w
8 BS CAN ( 8 H X h x
9 HT EM ) 9 I Y i y
A LF SUB * : J Z j z
B VT ESC + ; K [ k {
C FF FS , < L \ l |
D CR GS - = M ] m }
E SO RS . > N ^ n ~
F SI US / ? O _ o DEL

165
ASCII Table Appendix D

166
Index

Symbols AT execute/cancel, 67, 121


AT execute/stop, 77
°C/°F, 23 auto/manual, 54, 67
°C/°F selection, 129 automatic mode, 54
autotuning, 30

Numerics auxiliary output, 26


auxiliary output 1 allocation, 133
1-point shif, 40
auxiliary output 2 allocation, 134
2-PID control, 24
auxiliary outputs, 15
2-point shift, 40, 41
2-point temperature input shift, 43
3-position control, 28 B
baud rate, 3

A BCC, 61, 62

α, 141
additional PV display, 143 C
additional temperature input shift value display, 143 calculating the detection current value, 36
address, 64 characteristics, 158
adjustment level, 103 cold junction compensation method, 144
advanced function setting level, 103 command frame, 61
alarm 1 hysteresis, 139 communications data length, 145
alarm 1 latch, 143 communications parity, 145
alarm 1 open for alarm, 138 communications procedure, 60
alarm 1 type, 132 communications response wait time, 146
alarm 2 hysteresis, 139 communications setting level, 103
alarm 2 latch, 143 communications stop bit, 145
alarm 2 open for alarm, 138 communications writing, 52, 67, 76, 121
alarm 2 type, 132 CompoWay/F, 5, 60
alarm 3 hysteresis, 139 connector cover, 9
alarm 3 latch, 143 control output, 15
alarm 3 open for alarm, 138 control output 1 allocation, 132
alarm 3 type, 132 control output 2 allocation, 133
alarm hysteresis, 44 control period, 25
alarm latch, 44 control start, 48
alarm lower limit alarm value 2, 119 control stop, 48
alarm lower limit value 1, 118 cooling coefficient, 47, 125
alarm type, 32 cooling control output, 26
alarm upper limit alarm value 2, 119 cooling control period, 25, 131
alarm upper limit value 1, 118 copy mode, 102, 107
alarm value, 32, 34 CT, 15
alarm value 1, 117 current transformer (CT), 35, 159
alarm value 2, 117
alarm value 3, 117
ASCII table, 165

167
Index

D I
dead band, 28, 47, 126 initial setting level, 103
decimal point, 46, 129 initial setting/communications protection, 52, 114
derivative time, 31, 124 input digital filter, 142
DIN track, 11 input type, 22, 128
direct operation, 25 integral time, 31, 124
direct/reverse operation, 131
download, 107
L
levels, 102
E list of parameters, 108
echoback test, 63, 84 lower limit alarm, 32
end code, 62 lower limit temperature input shift value, 40, 42, 124
end plates, 10 lower limit values, 34
error displays, 161
ETX, 61, 62
event input, 5, 16, 48
M
event input allocation, 48, 135 manual mode, 54
external dimensions, 8 manual reset value, 126
manual setup, 31
move to protect level, 67, 80
F move to setting area 1, 67, 80
FINS, 60 MRC, 63
FINS-mini command text, 61 MRES, 63
FINS-mini response tex, 62 multiple reads of monitor values/setting data, 72
frame, 61 multiple writes of setting data, 75
front panel, 100 multi-SP, 48, 67, 77, 116
multi-SP use, 48, 136
MV lower limit, 141
H MV monitor for cooling, 120
HBA, 157 MV monitor for heating, 119
HBA used, 140 MV upper limit, 141
heater burnout, 35
heater burnout alarm, 15, 26, 35, 45
heater burnout detection, 35
N
heater burnout hysteresis, 140 no. of multi-SP uses, 48, 135
heater burnout latch, 140 node no., 61, 62
heater current monitor, 35
heater current value monitor, 116, 121
heating and cooling control, 28, 47
O
heating control output, 26 ON/OFF control, 24, 28
heating control period, 131 one-point shift, 41
hysteresis, 28 open for alarm, 45
operation after power ON, 134
operation after turning ON the power supply, 37

168
Index

operation commands, 63, 67 set point lower limit, 130


operation display, 3 set point upper limit, 130
operation level, 103 setting change protection, 53, 114
operation/adjustment protection, 52, 114 setting display unit, 17, 98, 158
output allocations, 26 setting switches, 3
shifting input, 40
SID, 61
P side connector, 8
parameter initialize, 67, 82, 135 software reset, 67, 79
PID constants, 30 solderless terminals, 13
PID parameters, 31 SP ramp, 51
PID/OnOff, 130 SP ramp set value, 51, 136
power supply, 14 SRC, 63
proportional band, 31, 124 SRES, 63
protect level, 73, 103 standby sequence, 44
PV, 115 standby sequence reset method, 137
PV hold, 56, 67, 81 starting control, 37
PV hold value, 56 stopping control, 37
PV/SP, 115 STX, 61, 62
sub-address, 61, 62

R
RAM data save, 67, 79 T
ramp SP value monitor, 116 temperature input shift, 123
ratings, 157 terminal arrangement, 13
read controller attribute, 63, 82 terminator, 17
read controller status, 63, 83 twisted-pair cable, 16
read from multiple variable area, 63 two-point shift, 42
read from variable area, 63, 65
read monitor value, 70
read setting data, 71
U
response frame, 62 unit number, 3
reverse operation, 25 upload, 107
RUN/STOP, 37, 67, 117 upper limit alarm, 32
upper limit temperature input shift value, 40, 42, 124
upper limit values, 34
S using the keys, 101
scaling, 46
scaling lower limit, 46, 129
scaling upper limit, 46, 129
V
sensor input setting ranges/control ranges, 163 variable area, 64
set point 0, 123 variable area map, 85
set point 1, 123 variable type, 64
set point during SP ramp, 51
set point limits, 50

169
Index

W
wiring, 14
write mode, 78
write protect level setting data, 73
write setting data, 74
write to multiple variable area, 63
write to variable area, 63, 66

170
Revision History
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.

Cat. No. H113-E1-1

Revision

The following table outlines the changes made to the manual during each revision. Page numbers refer to the
previous version.
Revision code Date Revised content
1 January 2001 Original production

171
172
Authorized Distributor:

Cat. No. H113-E1-1 Note: Specifications subject to change without notice Printed in Japan
0101-1M (0101) (A)

You might also like