You are on page 1of 4

CONNECTIONS: VALVES: DAMPERS: SEPARATION: SIGNALS:

= PIPELINE = 2-WAY ON-OFF VALVE = ON-OFF DAMPER = ANALOGUE


= STRAINER GENERAL
= 2-WAY VALVE ANGLE TYPE = DIGITAL
= INSTRUMENT CONNECTION =NON-RETURN DAMPER
= 3-WAY VALVE M
= STRAINER WITH PIT FOR DRAINING
= T-BRANCH
= 2-WAY VALVE WITH DIAPHRAGM =CONTROL DAMPER WITH = DRAIN MESH
= CROSSING WITH CONNECTION ACTUATOR ELECTRICAL MOTOR
= 2-WAY VALVE WITH CILINDER = SAFETY DAMPER = PUMP INLET FILTER
= CROSSING WITHOUT CONNECTION ACTUATOR
= INTERRUPTION OF M
= REVERSE OSMOSIS
= 2-WAY VALVE WITH ELECTRICAL
CONNECTION LINE MOTOR ACTUATOR SAFETY DEVICES:
STORAGE:
JOINTS,COUPLINGS,ETC.: = NON RETURN VALVE = FLAME ARRESTOR

= BREATHER VALVE = FLAME ARRESTOR


= CLOSED TANK
IDENTIFICATION LETTERS FOR INSTRUMENTATION:
= FLANGE EXPLOSION PROOF
= THREADED
First letters Succeeding letters
= WELDED = CONTROL VALVE = BREATHER
= QUICK RELEASE COUPLING = VESSEL DISHED ENDS Column 1 Column 2 Column 3 Column 4 Column 5

= CONTROL VALVE ANGLE TYPE Measured/Initiating Variable Readout/Passive Output/Active Function


= QUICK RELEASE COUPLING Variable Modifier Function Function Modifier
WITH AUTOMATIC CLOSING ACTUATORS: = VESSEL SPHERICAL ENDS A Analysis Alarm
= CONTROL VALVE 3-WAY
User's
CONNECTION ACCESSORIES: = MANUAL B Burner, Combustion User's Choice User's Choice
Choice
= SUPPORTING LEGS C User's Choice Control Close
= DRAIN,FUNNEL = SELF-OPERATING BACK-PRESSURE
CONTROL VALVE D User's Choice Difference, Differential Deviation
= DRAINPAN = FLOAT E Voltage Sensor, Primary Element
= SELF-OPERATING PRESSURE F Flow, Flow Rate Ratio
= VENT = INSULATED
REDUCING CONTROL VALVE G User's Choice
Glass, Gauge, Viewing
Device
= SPRING
= PRESET CONTROL VALVE H Hand High
= SIPHON = BARREL I Current Indicate
= SAFETY VALVE
J Power Scan
= DIAPHRAGM
= SLOPE = SAFETY VALVE K Time, Schedule Time Rate of Change Control Station
= GAS CYLINDER
SPRING LOADED L Level Light Low
= WALL PENETRATION M User's Choice Middle, Intermediate
= SAFETY VALVE = CILINDER
SPRING LOADED ANGLE TYPE = BAG User's
N User's Choice User's Choice User's Choice
Choice
= WALL PENETRATION 0 User's Choice Orifice, Restriction Open
= BREATHER VALVE = SOLENOID
TUBED = CONTAINER P Pressure Point (Test Connection)
WITH SAFETY FUNCTION M
Q Quantity Integrate, Totalize Integrate, Totalize
= WALL PENETRATION = BUTTERFLY VALVE = ELECTRICAL MOTOR
SEALED ENERGY STORAGE: R Radiation Record Run
S Speed, Frequency Safety Switch Stop
SUPPLEMENTARY VALVE SYMBOLS FLUID TRANSPORT: T Temperature Transmit
PIPELINE COMPONENTS: = EXPANSION VESSEL U Multivariable Multifunction Multifunction
= VALVE NEEDLE TYPE = PUMP GENERAL
= COMPENSATOR Vibration,
= VALVE GLOBE TYPE V Mechanical Valve, Damper, Louver
= FLEXIBLE PIPE = VALVE BALL TYPE = DIAPHRAGM PUMP Analysis

= VALVE GATE TYPE


PROCESS CONTROL: W Weight, Force Well, Probe
= ORIFICE = EJECTOR PUMP Accessory Devices,
= VALVE DIAPHRAGM TYPE X Unclassified X-axis Unclassified Unclassified
= FIELD MOUNTED Unclassified
= SILENCER = VALVE NORMALLY CLOSED M Event, State,
NC Y Y-axis Auxiliary Devices
Presence
= VALVE NORMALLY OPEN = FIELD MOUNTED EXTENDED FORM
= VIEWING GLASS NO = PUMP INTEGRATED MOTOR Driver, Actuator,
Z-axis, Safety
Z Position, Dimension Unclassified final control
= VALVE LOCKING DEVICE = LOCAL CONTROL SYSTEM Instrumented System
element
= HOSEREEL
= INTERLOCKING DEVICE AIR TRANSPORT:
= LOCAL CONTROL SYSTEM EXTENDED FORM
= RUPTURE DISC = KEY
= FAN GENERAL
= CENTRAL CONTROL SYSTEM
= LOUVRE MISCELLANEOUS: = FAN IMPELLER TYPE
= CENTRAL CONTROL SYSTEM EXTENDED FORM
= BOUNDARY LINE
= VACUUM PUMP
DNXX DNXX = POINT OF MEASUREMENT
= PIPEREDUCER
= LIMIT GENERAL = TEMPERATURE MEASUREMENT
= BLINDFLANGE
ENERGY TRANSFER:
= LEVEL MEASUREMENT
= OPEN PIN = HEAT EXCHANGER GENERAL
INSULATION: DESIGNATION LEVEL 1 = LEVEL MEASUREMENT ULTRASONIC
= SPRAY NOZZLE
= PIPE INSULATED = CLOSED PIN
DESIGNATION LEVEL 2 = LEVEL MEASUREMENT VIBRATING
= ELECTRICAL TRACING
= PLATE HEAT EXCHANGER
DOC REF = FLOW MEASUREMENT ORIFICE
= CONNECTION REFERENCE
TYPES & APPLICATION OF FLAGS: LINE REF
= ELECTRIC HEATER = FLOW MEASUREMENT FLOW NOZZLE
=AAANN
= FLAG FOR NON REVERSIBLE FLOW = FLOW MEASUREMENT VENTURI NOZZLE
AANNN = BUND
= CONDENSER . . . . . . . .
=AAANN
= FLOW MEASUREMENT VORTEX
AANNN = FLAG FOR REVERSIBLE FLOW . . . . . . . .
= DRIP TRAY = FLOW MEASUREMENT ULTRA SONIC . . . . . . . .
. . . . . . . .

= VIBRATION MEASUREMENT GENERAL 01 06/10/2020 ABO For Review Second Issue RBL MMA DDE
00 30/06/2020 ABB For Review First Issue RBL MMA DDE
Rev. Rev. Date By Purpose of issue Comment / change log Checked IDC Approved
= LIMIT SWITCH MECHANICAL TYPE Reference Item designation
. HKN=T001AXG10
Contractors doc-id
= LIMIT SWITCH PROXIMITY TYPE .
HKN-FAB-DS-DIA-4006
. Employers doc-id
. HKN-EFI-00146
TO/FROM CONTROL SYSTEMS . DCC
M - Mechanical engineering, FB030 Piping & Instrument Diagram (P&ID)
Company Name of the project
C AUXILIARY SCADA EFI HOLLANDSE KUST NOORD
Document title

LT LEVEL TRANSMITTER HAZARDOUS DRAIN SYSTEM - PIPING & INSTRUMENTATION DIAGRAM (P & ID) - AXG10
Logo Scale
NTS
Format
LI LEVEL INDICATOR A1
Revision Sheet
01 1 OF 4
NOZZLE TABLE F0 F1 F2 LINE SIZE SERVICE PIPE SPEC. INSULATION NOTES
N1 DN100 N7 DN100 T001 AXG10 WP001 DN100 DH AP01 N
1. TANK AND CONNECTING VALVES TO BE INSULATED.
N2 DN100 N8 DN100 T001 AXG10 WP002 DN50 DH AP01 N 2. OIL/WATER SEPARATOR AND OIL IN WATER ANALYZER ARE LOCATED IN A DRIP TRAY.
T001 AXG10 WP003 DN50 DH AP01 N 3. OIL UPON HIGH OIL-IN-WATER THREE WAY VALVE TO SWITCH TO OFF SPEC WATER
N3 DN25 N9 DN50 LINE TO SUMP TANK AND TO SWITCH TO WATER OVERBOARD LINE WHEN OIL-IN-WATER
T001 AXG10 WP004 DN50 DH AP01 N CONTENT IS WITHIN 15 PPM. DRAIN TRANSFER PUMP ARE NOT
N4 DN25 N10 DN50
T001 AXG10 WP005 DN80 DH AP01 N
TRIPPED ON HIGH OIL-IN-WATER.
N5 DN100 N11 DN50 4. INCREASE PIPE SECTION FUNCTIONS AS BREAK TANK AT THE INLET OF
T001 AXG10 WP006 DN50 DH AP01 N OIL/WATER SEPARATOR. PUMP DISCHARGE LINES TO TO ENTER AT THE TOP
N6 DN100 N12 DN50 OF THE PIPE SECTION, TO AVOID REVERSE FLOW FROM ONE PUMP TO THE
T001 AXG10 WP007 DN100 DH AP01 H/E
OTHER PUMP.
T001 AXG10 WP008 DN100 DH AP01 H/E 5. OIL SENSOR IS DESIGNED FOR PARTIAL FLOW. INLET BRANCH TO BE IN VERTICAL LINE
SECTION INSIDE LIQUID POCKET, AND TO PENETRATE INSIDE THE
T001 AXG10 WP009 DN100 DH AP01 N DISCHARGE PIPE TO A DISTANCE OF ONE QUARTER THE DIAMETER OF THAT PIPE.
FROM DRAIN
T001 AXG10 WP010 DN80 DH AP01 N 6. THREE MANWAYS PROVIDE FULL ACCESS FROM THE TOP.
TRANSFER PUMP
7. VACUUM BREAKER VENT OIL-IN-WATER ANALYZER TO BE ENDING AT THE SAME
WP015 T001 AXG10 WP011 DN100 DH AP01 N ELEVATION AS VACUUM BREAKER ON MAIN WATER OVERBOARD LINE.
T001 AXG10 WP012 DN100 DH AP01 N

T001 AXG10 WP013 DN100 DH AP01 N

T001 AXG10 WP014 DN80 DH AP01 N

T001 AXG10 WP015 DN80 DH AP01 N

SLOPE

TO ATM @ SAFE
LOCATION GENERAL NOTES
FROM DRAIN OUTDOOR
1. SLOPES SHOULD BE BETWEEN 0.5% TO 1%.
TRANSFER PUMP
WP014
SLOPE

NOTE 4
ON ON
SLOPE C
INDICATION INDICATION OVERFLOW
WP001 NOTE 7
C C
BQ SET @
15 PPMV
WP008

N2 N3 N4 N5 N6

SLOPE
M1 M2 M3 N7 SLOPE
N1 NOTE 6 NOTE 6 NOTE 6
WP013 N8
WP007 SLOPE TO DUMP CAISSON
OIL IN WATER
ANALYZER
WP011
NOTE 3

M
NOTE 1

OIL/WATER
SEPARATOR C
N9 OFF-SPEC WATER TO
SUMP TANK
SLOPE OIL/WATER COMPARTMENT

WP012

ELECTRIC HEATER ELECTRIC HEATER

WP001
N12 N11 N10

NC WP002.QM001 NC WP003.QM001 NC WP005.QM001

WP006
SLOPE
WP002

WP003

WP004

. . . . . . . .
. . . . . . . .
TO SUMP TANK . . . . . . . .
SLOPE SLOPE SLOPE SLOPE SLOPE OIL COMPARTMENT . . . . . . . .
01 06/10/2020 ABO For Review Second Issue RBL MMA DDE
WP002 WP002 WP005 WP005 WP009
00 30/06/2020 ABB For Review First Issue RBL MMA DDE
Rev. Rev. Date By Purpose of issue Comment / change log Checked IDC Approved
Reference Item designation
. HKN=T001AXG10
Contractors doc-id
.
HKN-FAB-DS-DIA-4006
. Employers doc-id
NOTE 2 . HKN-EFI-00146
DCC
.
M - Mechanical engineering, FB030 Piping & Instrument Diagram (P&ID)
TO SUMP TANK Company Name of the project
OIL/WATER
EFI HOLLANDSE KUST NOORD
SLOPE COMPARTMENT Document title
HAZARDOUS DRAIN SYSTEM - PIPING & INSTRUMENTATION DIAGRAM (P & ID) - AXG10
WP010 Logo Scale
NTS
Format
A1
Revision Sheet
01 2 OF 4
F0 F1 F2 LINE SIZE SERVICE PIPE SPEC. INSULATION NOTES
T001 AXG10 WP009 DN100 DH AP01 N

T001 AXG10 WP010 DN80 DH AP01 N 1. PIPING ROUTING INTERNAL IS PREFERRED.


2. ALL DRIP TRAY CONNECTIONS SHALL BE FITTED WITH FIRE TRAPS.
T001 AXG10 WP016 DN80 DH AP01 N 3. RODDING POINT.
T001 AXG10 WP017 DN80 DH AP01 N 4. BUNDED AREA SIZED TO CONTAIN 110% SPILLAGE OF A SINGLE PIECE OF
CRANE HYDRAULIC EQUIPMENT IN THE ROOM + FIRE WATER MEDIA AND ARE PROVIDED WITH FIRE
POWER PACK T001 AXG10 WP018 DN80 DH AP01 N PROTECTION GRATING.
T001 AXG10 WP019 DN200 DH AP01 N

T001 AXG10 WP020 DN100 DH AP01 N

T001 AXG10 WP021 DN100 DH AP01 N


DRIPTRAY
T001 AXG10 WP022 DN100 DH AP01 N
TO ATK @ SAFE T001 AXG10 WP023 DN100 DH AP01 N
LOCATION OUTDOOR
T001 AXG10 WP024 DN100 DH AP01 N

T001 AXG10 WP025 DN100 DH AP01 N

WP016
T001 AXG10 WP026 DN40 DH AP01 N

T001 AXG10 WP027 DN80 DH AP01 N

SLOPE
T001 AXG10 WP028 DN80 DH AP01 N GENERAL NOTES
T001 AXG10 WP029 DN80 DH AP01 N
1. SLOPES SHOULD BE BETWEEN 0.5% TO 1%.
WP017 T001 AXG10 WP030 DN80 DH AP01 N

T001 AXG10 WP031 DN40 DH AP01 N

T001 AXG10 WP032 DN40 DH AP01 N


FROM DIESEL GENERATORS
& DIESEL TANKS SLOPE

WP018

CHANGE ROOM GREY WATER


WORKSHOP WASH (++AZA10.304) MESS
BASIN (++AZA10.308)
(++AZA10.409)

WP018

WP031

WP032
STORAGE OF OIL
DRUMS IN MAIN
WP017

TRANSFORMER ROOM
(++AZA10.207)
FIRE FIGHTING SLOPE
ROOM
(++AZA10.204)

DRIPTRAY

WP026
SLOPE

WP028

WP029
COOLER COOLER

SLOPE

SLOPE
TRANSFORMER TRANSFORMER
A B SLOPE
(++AZA10.254) (++AZA10.255)
WP027
NOTE 3
DRIPTRAY SLOPE

WP030
NOTE 3
WP020

WP021

WP022

WP023

WP024

WP025

EARTHING AND EARTHING AND


SLOPE

SLOPE

SLOPE

SLOPE

SLOPE

SLOPE

MAIN MAIN
TRANSFORMER TRANSFORMER AUX AUX
ROOM B ROOM A TRANSFORMER TRANSFORMER

WP031
SLOPE
(++AZA10.208) (++AZA10.207) ROOM A ROOM B
(++AZA10.201) (++AZA10.205)

NOTE 4 NOTE 4 NOTE 4 NOTE 4

SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE OPENING SIZE 1500 SQ.CM

WP019 WP019 WP019 WP019 WP019 WP019


WP027

NOTE 3

. . . . . . . .
. . . . . . . .
TO SUMP TANK . . . . . . . .
SLOPE SLOPE OIL COMPARTMENT
WP019

. . . . . . . .
01 06/10/2020 ABO For Review Second Issue RBL MMA DDE
WP027 WP027
00 30/06/2020 ABB For Review First Issue RBL MMA DDE
OFF-SPEC WATER FROM Rev. Rev. Date By Purpose of issue Comment / change log Checked IDC Approved
OIL/WATER SEPARATOR SLOPE Reference Item designation
. HKN=T001AXG10
Contractors doc-id
.
WP009 HKN-FAB-DS-DIA-4006
. Employers doc-id
. HKN-EFI-00146
DCC
.
M - Mechanical engineering, FB030 Piping & Instrument Diagram (P&ID)
Company Name of the project
FROM DRIPTRAY
EFI HOLLANDSE KUST NOORD
OIL/WATER SEPARATOR SLOPE TO SUMP TANK Document title
OIL/WATER HAZARDOUS DRAIN SYSTEM - PIPING & INSTRUMENTATION DIAGRAM (P & ID) - AXG10
WP010 WP010 COMPARTMENT Logo Scale
SLOPE NTS
Format
A1
WP019 Revision Sheet
01 3 OF 4
F0 F1 F2 LINE SIZE SERVICE PIPE SPEC. INSULATION NOTES
T001 AXG10 WP012 DN100 DH AP01 N
1. DIP PIPE ENDS ABOVE TANK BOTTOM.
T001 AXG10 WP014 DN80 DH AP01 N 2. DRAIN BOTTOM IN BUNDLE AREA, DISCHARGING DIRECTLY INTO SUMP TANK
T001 AXG10 WP015 DN80 DH AP01 N
UNDERNEATH. TO BE TEMPORARY PLUGGED DURING TANK INSPECTION.
3. DIP PIPE TO BE AT LOWEST POINT IN THE SUMP TANK COMPARTMENT ABOVE SUMP.
T001 AXG10 WP019 DN200 DH AP01 N 4. TANK TO BE INSULATED (WINTERIZATION).
5. PERISTALTIC PUMP, AFTER PUMPING, THE PUMP WILL OPERATE WITH REVERSED
T001 AXG10 WP027 DN80 DH AP01 N
FLOW VIA THE AUXILIARY SCADA TO DRAIN OFF THE DISCHARGE LINE. FOR
T001 AXG10 WP033 DN50 DH AP01 N MAINTENANCE PURPOSES, THE PUMP SHALL BE STARTED/STOPPED IN REVERSE
DIRECTION ONCE A WEEK.

GENERAL NOTES
1. SLOPES SHOULD BE BETWEEN 0.5% TO 1%.
OUTDOOR INDOOR

SLOPE TO OIL/WATER SEPARATOR


WP015
WP015

SLOPE TO OIL/WATER SEPARATOR


WP014
WP014

OUTDOOR INDOOR

PT PT
C C

L L
WP015

WP014
SLOPE

SLOPE
C C C C
N2 N2

VENT
M
DRAIN DRAIN
M M
TRANSFER TRANSFER SLOPE
VF
PUMP PUMP BUNKER
STATION
NOTE 5 WP015.MA001 WP014.MA001 NOTE 5

N1 N1 DRIP PAN

SLOPE SLOPE
TRANSFER BUNKERING
PUMP SKID

WP033
INDOOR OUTDOOR

FROM HAZARDOUS FROM HAZARDOUS


WP014
WP015

DRAIN SYSTEM SLOPE DRAIN SYSTEM


SLOPE

WP019 WP009 C WP027

SLOPE
SLOPE FROM OIL/WATER SEPARATOR
C
TO ATM @
SAFE LOCATION THERMOSTAT WP012

THERMOSTAT
ON ON
INDICATION INDICATION
RADAR RADAR
HH HH
LI LT H C C LI LT H C C
L L
C NO
LL LL
C M NO NO

SLOPE
NOTE 2
LEAK_DETECT. NOZZLE TABLE

N1 N2 N3 N4 N5 N6 N7 N8 N9 N10 N11 N12 N13 N14 N15 N16 N17 N18 N1 DN50 N10 DN100

N2 DN-- N11 DN50

N3 DN80 N12 DN50 . . . . . . . .


. . . . . . . .
NOTE 4 OIL/WATER OIL N4 DN50 N13 DN80 . . . . . . . .
COMPARTMENT COMPARTMENT
SUMP TANK N5 DN50 N14 DN80 . . . . . . . .
01 06/10/2020 ABO For Review Second Issue RBL MMA DDE
N6 DN80 N15 DN80 00 30/06/2020 ABB For Review First Issue RBL MMA DDE
Rev. Rev. Date By Purpose of issue Comment / change log Checked IDC Approved
N7 DN50 N16 DN50 Reference Item designation
NOTE 1 NOTE 1 NOTE 1 NOTE 1 NOTE 3 NOTE 3 NOTE 1 NOTE 1 NOTE 1 . HKN=T001AXG10
N8 DN80 N17 DN80 .
Contractors doc-id
HKN-FAB-DS-DIA-4006
. Employers doc-id
N9 DN50 N18 DN100 . HKN-EFI-00146
DCC
.
M - Mechanical engineering, FB030 Piping & Instrument Diagram (P&ID)
Company Name of the project
EFI HOLLANDSE KUST NOORD
Document title
HAZARDOUS DRAIN SYSTEM - PIPING & INSTRUMENTATION DIAGRAM (P & ID) - AXG10
Logo Scale
NTS
Format
A1
Revision Sheet
01 4 OF 4

You might also like