= VIBRATION MEASUREMENT GENERAL 01 06/10/2020 ABO For Review Second Issue RBL MMA DDE
00 16/06/2020 ABO For Review First Issue RBL MMA DDE
= LIMIT SWITCH MECHANICAL TYPE Rev. Rev. Date
Reference
By Purpose of issue
Item designation
Comment / change log Checked IDC Approved
. #HKN=T001 AXD30
= LIMIT SWITCH PROXIMITY TYPE .
Contractors doc-id
HKN-EFI-00403
. Employers doc-id
LT LEVEL TRANSMITTER Fresh Water System - Piping and instrumentation diagram (P&ID)
Logo Scale
NTS
Format
LG
LEVEL GAUGE A1
Revision Sheet
01 1 OF 3
F0 F1 F2 LINE SIZE SERVICE PIPE SPEC. INSULATION NOTES
T001 ADX30 WP001 DN32 WF AP01 N
1. TO PREVENT LEGIONELLA GROWTH, A CIRCULATION LINE IS INSTALLED AND
T001 ADX30 WP002 DN32 WF AP01 N DEAD ENDS SHALL BE MINIMIZED.
T001 ADX30 WP003 DN32 WF AP01 N 2. DOING POINT FOR CLEANING OF SYSTEM.
3. FEMALE CAMLOCK CONNECTION DN80.
T001 ADX30 WP004 DN25 WF AP01 N
WP001.QM001 - QM001
NOTE 2
SLOPE
WP011
WP003.QM001
LT
NC M C
NC
NC WP001.QM001 - MA001
DN100
WP003
NC
FRESH WATER TANK
DN50
LG
M1 M2
SLOPE
DN50
NC DN32 DN32
NC
DRIPTRAY C
C
C
SLOPE
(TYP.7) PT
MAIN L
C
C
SWITCH
WP001
BOARD
WP011
WP001.QM005
WP001.QM006
WP001.QM003
WP001. MA001
M
NC TO FRESH WATER
WP001.QM002 WP001.QM004 WP001.QM007 UV WP001.QM008
N2
DISTRIBUTION
WP001 NOTE 1
N1 STERILIZER NO POCKETS
WP001.QM001
WP002.QM001
WP001.HN001
NC NC
N5
DRIPTRAY . . . . . . . .
. . . . . . . .
C . . . . . . . .
. . . . . . . .
01 06/10/2020 ABO For Review Second Issue RBL MMA DDE
SLOPE
WP002
.
HKN-EFI-00403
. Employers doc-id
BUNKER WP011
. HKN-FAB-DS-DIA-4012
CONNECTION DCC
NC NC .
CAMLOCK DN80 M - Mechanical engineering, FB030 Piping & Instrument Diagram (P&ID)
(TYP.1) Company Name of the project
SLOPE SLOPE TO DUMP CAISSON
WP014 EFI HOLLANDSE KUST NOORD
WP011.QM002 Document title
WP014
Fresh Water System - Piping and instrumentation diagram (P&ID)
Logo Scale
NTS
Format
A1
Revision Sheet
01 2 OF 3
NOTES
1. TO PREVENT LEGIONELLA GROWTH, A CIRCULATION LINE IS INSTALLED AND DEAD
ENDS SHALL BE MINIMIZED, CONNECT VALVE DIRECT ON TEE.
2. REFER TO P & ID HAZARDOUS DRAINAGE SYSTEM.
3. VENT TO BE LOCATED AT HIGHEST POINT.
4. BRANCH-OFF LINE TO TAPPING POINT TO BE MAXIMUM 1 LITER VOLUME BRANCH-OFF
ON TOP OF MAIN DISTRIBUTION RING WITH AN EA-TYPE CHECK VALVE AT THE
HIGHEST POINT.
5. CIRCULATION LOOP TO RUN THROUGH CHILLER ROOM ++AZA10.402 TO INSTRUMENT
BOARD WITH FRESH WATER MAKE-UP TO HVA/C CHILLED WATER SYSTEM LOOP.
NOTE 3
WP002.VE004
TO FRESH WATER
TANK
WP001 NOTE 1 NO POCKETS WP001
GENERAL NOTES
TO DECK WASH
SYSTEM 1. SLOPES SHOULD BE BETWEEN 0.5% TO 1%.
WP010
HKN-FAB-EG-DIA-4129
TO DECK WASH
SYSTEM
WP009
HKN-FAB-EG-DIA-4129
NOTE 4 NOTE 4
WP001
NOTE 3
WP018.QM001
WP019.QM001
WP008.VE001
MIN.
WP008 WP008 WP008
WP008.QM002
WP019
SLOPE
SLOPE
WP018
WP001.QM011
NC
WP008
ELECTRIC
INLINE HEATER
NOTE 2
WORKSHOP
ROOM
(++AZA10.409) WP008.QM001
WP008
MIN.
WP009.QM001
NC
WP001
NOTE 3
WP002.VE002
WP004 C
WP007.QM002 - MA001
M
TO CHILLED WATER
MIN. SYSTEM LOOP
WP007
HKN-FAB-EG-DIA-4079
WP007.QM001 WP007.QM002 - QM001 WP007.QM003
NOTE 3
C
WP006.QM002 - MA001
M TO CHILLED WATER
MIN. SYSTEM LOOP
WP006
HKN-FAB-EG-DIA-4079
WP006.QM001 WP006.QM002 - QM001 WP006.QM003
NOTE 4 NOTE 4 NOTE 4
NOTE 3
WP015.QM001
WP016.QM001
WP017.QM001
WP004.VE001 C
WP005.QM002 - MA001
WP004 WP004 WP004 M TO CHILLED WATER
MIN. SYSTEM LOOP
WP005
HKN-FAB-EG-DIA-4079
WP005.QM001 WP005.QM002 - QM001 WP005.QM003
SLOPE
WP015
SLOPE
WP017
WP016
SLOPE
WP004
WP004.QM003
WP004
. . . . . . . .
MIN.
NOTE 2 NOTE 2
ELECTRIC . . . . . . . .
INLINE HEATER . . . . . . . .
WP001.QM010
CHANGE MESS . . . . . . . .
ROOM ROOM NC 01 06/10/2020 ABO For Review Second Issue RBL MMA DDE
(++AZA10.304) (++AZA10.308)
00 16/06/2020 ABO For Review First Issue RBL MMA DDE
WP004.QM001 Rev. Rev. Date By Purpose of issue Comment / change log Checked IDC Approved
WP004
Reference Item designation
NOTE 5 . #HKN=T001 AXD30
WP005.QM002
MIN. .
Contractors doc-id
NC HKN-EFI-00403
. Employers doc-id
WP005 . HKN-FAB-DS-DIA-4012
DCC
.
M - Mechanical engineering, FB030 Piping & Instrument Diagram (P&ID)
Company Name of the project
EFI HOLLANDSE KUST NOORD
Document title
Fresh Water System - Piping and instrumentation diagram (P&ID)
FROM FRESH WATER PUMP Logo Scale
WP001 NOTE 1 NTS
Format
NO POCKETS A1
Revision Sheet
01 3 OF 3