LOGICAL PROGRAMMING
This document is MABE’s property, and cannot be used by others for any purpose, without prior written consent
INDEX
1 GENERAL................................................................................................................................................ 4
1.1 SCOPE................................................................................................................................................................4
1.2 REFERENCE DOCUMENTATION..................................................................................................................4
1.3 GENERAL CONSIDERATIONS......................................................................................................................4
1.3.1 Events activation and deactivation............................................................................................... 4
1.3.2 Nested events.............................................................................................................................. 5
1.3.3 Timers reset................................................................................................................................. 5
2 LOGICAL TABLES.................................................................................................................................. 5
2.1 AREA 9-305: DIESEL TANK AREA (SHEET 2 OF C&E MATRIX)............................................................5
2.2 AREA 9-202: ELECTRICAL BUILDING & CONTROL ROOM (SHEET 3-6 OF C&E MATRIX)...........11
2.3 AREA 9-401: ADMINISTRATION BUILDING (SHEET 7-8 OF C&E MATRIX)......................................28
2.4 AREA 9-402: GUARD HOUSE (SHEET 9 OF C&E MATRIX)...................................................................34
2.5 AREA 9-402: WAREHOUSE & WORKSHOP (SHEET 10 OF C&E MATRIX).........................................37
2.6 AREA 9-301 & 302: FIRE FIGHTING PUMP HOUSE (SHEET 11 OF C&E MATRIX)............................42
2.7 AREA 9-202: COMPRESSOR AIR STATION (SHEET 12 OF C&E MATRIX).........................................42
2.8 AREA 9-305: WASTE WATER TREATMENT PLANT (SHEET 13 OF C&E MATRIX)..........................43
2.9 AREA 9-303: DEMI WATER TREATMENT PLANT (SHEET 14 OF C&E MATRIX).............................43
2.10 AREA 9-302: AUXILIARIES ELECTRICAL ROOM (SHEET 15 OF C&E MATRIX)..............................43
2.11 AREA 9-202: COAL CONVEYOR FROM COAL STORAGE AREA TO BOILERS (SHEET 16 OF
C&E MATRIX).............................................................................................................................................................49
2.12 AREA 9-901: COAL STORAGE ELECTRICAL ROOM (SHEET 17 OF C&E MATRIX).........................54
2.13 AREA 9-305: WASTE WATER ELECTRICAL BUILDING (SHEET 18 OF C&E MATRIX)...................61
2.14 AREA 9-303: DEMI WATER TREATMENT BUILDING (SHEET 19 OF C&E MATRIX).......................63
2.15 AREA 1-501: STEAM TURBINE AND GENERATOR BEARING - LINE 1 (SHEET 21 OF C&E
MATRIX).......................................................................................................................................................................64
2.16 AREA 1-601: COOLING TOWER ELECTRICAL ROOM - LINE 1 (SHEET 22 OF C&E MATRIX) .75
2.17 AREA 1-501: STEAM TURBINE LUBE OIL AND LUBE OIL PIPING & STEEL STRUCTURAL
PROTECTION - LINE 1 (SHEET 23 OF C&E MATRIX)..........................................................................................78
2.18 AREA 1-501: TURBINE BUILDING AREA PLAN AT +100,00 TO +106,00 - LINE 1 (SHEET 24 OF
C&E MATRIX).............................................................................................................................................................83
2.19 AREA 1-501: TURBINE BUILDING AREA PLAN AT +106,00 TO +112,00 - LINE 1 (SHEET 25 OF
C&E MATRIX).............................................................................................................................................................88
2.20 AREA 1-501: TURBINE BUILDING AREA PLAN AT +112,00 & ABOVE - LINE 1 (SHEET 26 OF
C&E MATRIX).............................................................................................................................................................88
2.21 AREA 1-701: COAL BUNKER - LINE 1 (SHEET 27 OF C&E MATRIX)...................................................92
2.22 AREA 1-201: MEDIUM VOLTAGE SWITCHROOM - LINE 1 (SHEET 28 OF C&E MATRIX)............116
2.23 AREA 1-801: FGD ELECTRICAL ROOM - LINE 1 (SHEET 29 OF C&E MATRIX)..............................119
2.24 AREA 1-701: COAL BURNERS - LINE 1 (SHEET 30 OF C&E MATRIX)..............................................126
2.25 AREA 1-201: MAIN & AUXILIARY TRANSFORMERS - LINE 1 (SHEET 31 OF C&E MATRIX)......126
2.26 AREA 1-701: STEAM GENERATOR BOILER - LINE 1 (SHEET 32 OF C&E MATRIX).......................131
REVISAR
MODIFICADO
ACRECENTADO/NOVO
OWNER ID Code
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
1 GENERAL
1.1 SCOPE
The Fire Detection & Alarm System is composed by Fire Panels and Field Devices. Every field device can
generate events (Alarm/Trouble/Monitor), as well as all the switches the exist on the Fire Panels. Output
field devices and LEDs can be activated depending on the logical programming.
The logical programming tables show all the actions that are taken by the Fire Panels according to the events
generated by the system inputs (field devices / swiches).
The SAT procedure (refer to document M004-KK-VD-020-0806) contains the descriptions of how to
perform the Site Acceptance Test for the supplied F&G systems.
Each logic sequence is executed when a specific event becomes active. When this event is no more active,
the logic sequence is canceled.
The events return to a normal condition (leave the active state) on different ways, as described below:
Event Type Description
Alarm Alarm events are latched. This means that this kind of event, once activated,
remains in the active state until the Fire Panel is reseted.
Trouble/monitor Trouble and monitor events are unlatched. This means that this kind of event is
active while the real condition is active. When the monitored input or the trouble
is normalized, the event also returns to the normal condition
automatically.
Switch for remote This kind of switch is configured as “Momentary”. This means that it is active while
activation of pressed only. If it is kept pressed for 5 seconds, it generates an “alarm test” event
extinguishing (by software) that is latched. Therefore, after a remote activation of extinguishing
system system, the Fire Panel shall be reseted to return to a
normal condition.
Switch for This king of switch is configured as “Toggle”. This means that its state is
extinguishing toggled every time the switch is pressed. Therefore, pressing a switch,
system exclusion excludes the extinguishing system until the same switch is pressed again.
OWNER ID Code
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
Some output sequences are activated by a combination of events connected by operators (e.g.: AND
condition). In these cases, the output sequences are activated only if all event conditions are true.
For example, in areas with FM200 extinguishing systems, the “MANUAL START OF EXTINCTION
SYSTEM” only generates the output sequences if the “AMI SELECTOR” is not in inhibit position.
Timers are active and counting only when the input events are true (output sequence is activated). When the
input events are not true, the output sequence is cancelled and all timers are reseted.
For example, in areas with FM200 extinguishing systems, if the “MANUAL STOP BUTTON” is pressed
(during the “30 seconds” count down before solenoid activation), all timers are reseted. When “MANUAL
STOP BUTTON” is released, the timer starts counting again from the beginning.
2 LOGICAL TABLES
EVENT:
Alarm (1 oo N of the following devices)
Device TAG Address Text on Fire Panel LCD
MANUAL ALARM BUTTON – oh 90AYE16_AA001 02010409 AM TQ DIESEL-AREA TANQUE DIESEL
MANUAL ALARM BUTTON-ok 90AYE16_AA002 02010432 AM TQ DIESEL-AREA TANQUE DIESEL
ACTIONS:
Activate the following devices
Device TAG Address Text on Fire Panel LCD
HORN/STROBE ALARM-ok 90AYC16_AA001 02010438 MCSIR TQ DIESEL-AREA TANQUE DIESEL
HORN/STROBE ALARM-ok 90AYC16_AA002 02010430 MCSIR TQ DIESEL-AREA TANQUE DIESEL
CUMULATIVE ALARM-ok 90CYE22EU141-YG01 01010404 REPETICAO ALARME DCS-TANQUES/BOMBAS DIESEL
LED ON MIMIC PANEL - Diesel Tank Area-ok -------- --------
EVENT:
Alarm (1 oo N of the following devices)
Device TAG Address Text on Fire Panel LCD
LINEAR HEAT DETECTOR-ok 90SGY16_AA007 02010425 DLHS TQ PERIMETRAL-AREA TANQUE DIESEL
LINEAR HEAT DETECTOR-ok 90SGY16_AA008 02010424 DLHS TQ PERIMETRAL-AREA TANQUE DIESEL
LINEAR HEAT DETECTOR-nok 90SGY16_AA009 02020426 DLHS TQ IMERSO-AREA TANQUE DIESEL
LINEAR HEAT DETECTOR-nok 90SGY16_AA010 02020427 DLHS TQ IMERSO-AREA TANQUE DIESEL
LINEAR HEAT DETECTOR-nok 90SGY16_AA011 02020428 DLHS TQ IMERSO-AREA TANQUE DIESEL
ACTIONS:
Activate the following devices
Device TAG Address Text on Fire Panel LCD
HORN/STROBE ALARM-ok 90AYC16_AA001 02010438 MCSIR TQ DIESEL-AREA TANQUE DIESEL
HORN/STROBE ALARM-ok 90AYC16_AA002 02010430 MCSIR TQ DIESEL-AREA TANQUE DIESEL
CUMULATIVE ALARM-ok 90CYE22EU141-YG01 01010404 REPETICAO ALARME DCS-TANQUES/BOMBAS DIESEL
LED ON MIMIC PANEL - Diesel Tank Area-ok -------- --------
OWNER ID Code
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
LINEAR HEAT DETECTOR-ok 90SGY16_AA004 02020421 DLHS BOMBAS DIESEL-AREA TANQUE DIESEL
LINEAR HEAT DETECTOR-ok 90SGY16_AA005 02020420 DLHS BOMBAS DIESEL-AREA TANQUE DIESEL
LINEAR HEAT DETECTOR-ok 90SGY16_AA006 02020423 DLHS BOMBAS DIESEL-AREA TANQUE DIESEL
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
POWER SUPPLY TROUBLE 90CYE26_GR001 02020381 FALHA FONTE TQ DIESEL-TRATAM AGUA RESIDUAL
SIGNAL TO SOLENOID VALVE 90SGF12_AA151 02020387 MCSOL ESPUMA TQ DIES-TRATAM AGUA RESIDUAL
PRESSURE SWITCH 90SGF12_CP101 02020380 PRESS ESPUMA TQ DIES-TRATAM AGUA RESIDUAL
MANUAL START OF EXTINCTION SYSTEM 90SGY16_AA020 02020415 AD ESPUMA BOMB DIESEL-AREA TANQUE DIESEL
HORN/STROBE BEGINNING EXTINCTION 90SGY16_AA023 02020406 MCEXT TQ DIESEL-AREA TANQUE DIESEL
ACTIONS:
Activate the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL - 07040138 ESPUMA BOMBAS DIESEL-LED AMARELO
2.2 AREA 9-202: ELECTRICAL BUILDING & CONTROL ROOM (SHEET 3-6
OF C&E MATRIX)
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
SMOKE DETECTOR - ABOVE CEILING-ok 90SGY10_AA092 01010064 DFEF SL CONTROLE-PR ELETR E SL CONTR
SMOKE DETECTOR - ABOVE CEILING-ok 90SGY10_AA093 01010037 DFEF SL SUP OPERAD-PR ELETR E SL CONTR
SMOKE DETECTOR - ABOVE CEILING-ok 90SGY10_AA094 01010039 DFEF SL OPER TECNICA-PR ELETR E SL CONTR
SMOKE DETECTOR - ABOVE CEILING-ok 90SGY10_AA095 01010041 DFEF SL ENG LOG DOC-PR ELETR E SL CONTR
SMOKE DETECTOR - BELOW FLOOR-ok 90SGY10_AA102 01010006 DFEP SL CONFIGURACAO-PR ELETR E SL CONTR
SMOKE DETECTOR - BELOW FLOOR-ok 90SGY10_AA103 01010013 DFEP SL CONFIGURACAO-PR ELETR E SL CONTR
SMOKE DETECTOR - BELOW FLOOR-ok 90SGY10_AA104 01010005 DFEP SL CONFIGURACAO-PR ELETR E SL CONTR
SMOKE DETECTOR - BELOW FLOOR-ok 90SGY10_AA105 01010014 DFEP SL CONFIGURACAO-PR ELETR E SL CONTR
SMOKE DETECTOR - BELOW FLOOR-ok 90SGY10_AA106 01010022 DFEP SL CONTROLE-PR ELETR E SL CONTR
SMOKE DETECTOR - BELOW FLOOR-ok 90SGY10_AA107 01010015 DFEP SL CONTROLE-PR ELETR E SL CONTR
SMOKE DETECTOR - BELOW FLOOR-ok 90SGY10_AA108 01010021 DFEP SL CONTROLE-PR ELETR E SL CONTR
SMOKE DETECTOR - BELOW FLOOR-ok 90SGY10_AA109 01010020 DFEP SL CONTROLE-PR ELETR E SL CONTR
SMOKE DETECTOR - BELOW FLOOR-ok 90SGY10_AA110 01010016 DFEP SL CONTROLE-PR ELETR E SL CONTR
SMOKE DETECTOR - BELOW FLOOR-ok 90SGY10_AA111 01010017 DFEP SL CONTROLE-PR ELETR E SL CONTR
SMOKE DETECTOR - BELOW FLOOR-ok 90SGY10_AA112 01010019 DFEP SL CONTROLE-PR ELETR E SL CONTR
SMOKE DETECTOR - BELOW FLOOR-ok 90SGY10_AA113 01010018 DFEP SL CONTROLE-PR ELETR E SL CONTR
ACTIONS:
Activate the following devices
Device TAG Address Text on Fire Panel LCD
HORN/STROBE ALARM-ok 90AYC10_AA012 01010131 MCSIR SL PAINEL DCS-PR ELETR E SL CONTR
HORN/STROBE ALARM-ok 90AYC10_AA013 01010129 MCSIR SL CONFIGURACAO-PR ELETR E SL CONTR
HORN/STROBE ALARM-ok 90AYC10_AA014 01010158 MCSIR SL CONTROLE-PR ELETR E SL CONTR
HORN/STROBE ALARM-ok 90AYC10_AA015 01010166 MCSIR SL CONTROLE-PR ELETR E SL CONTR
HORN/STROBE ALARM-ok 90AYC10_AA016 01010139 MCSIR CORR SL PNL DCS-PR ELETR E SL CONTR
CUMULATIVE ALARM-ok 90CYE22EU111-YG01 01010386 REPETICAO ALARME DCS-PR ELETR CONTR PAV 2
TRIP SIGNAL-ok 90CYE22EU206-YG01 01010145 TRIP HVAC 6-PR ELETR E SL CONTR
LED ON MIMIC PANEL - Electrical Control
Building - 2nd Floorok -------- --------
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
Regra 45
CBABORT_ELBDGCTRRM_LV_1- ok 418 MONITOR 01010418 45 MFCP_01 (01) m1_3-SDDC1_L56 (6)
CBABORT_ELBDGCTRRM_LV_2-ok 424 MONITOR 01010424 45 MFCP_01 (01) m1_3-SDDC1_L56 (6)
ROTOLO DE SAÍDA
AND_CBSMOKE_ELBDGCTRRM_ -ok LV_1 10 AND 45 N/A DISABLE
-
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
HORN/STROBE LEAVE THE LOCAL 90SGK10_AA007 01040414 MCABA SL BAIXA TENSAO-PR ELETR E SL CONTR
HORN/STROBE LEAVE THE LOCAL 90SGK10_AA008 01040422 MCABA SL BAIXA TENSAO-PR ELETR E SL CONTR
HORN/STROBE LEAVE THE LOCAL 90SGK10_AA030 01040427 MCABA SL UPS AC/DC-PR ELETR E SL CONTR
Wait for 30 seconds
Activate the following devices
Device TAG Address Text on Fire Panel LCD
HORN/STROBE BEGINNING EXTINCTION 90SGK10_AA025 01040426 MCEXT SL UPS AC/DC-PR ELETR E SL CONTR
SIGNAL TO SOLENOID VALVE 90SGK10_AA155 01040134 MCSOL SL UPS AC/DC-PR ELETR E SL CONTR
OWNER ID Code
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
HORN/STROBE LEAVE THE LOCAL-ok 90SGK10_AA008 01040422 MCABA SL BAIXA TENSAO-PR ELETR E SL CONTR
HORN/STROBE BEGINNING EXTINCTION-ok 90SGK10_AA025 01040426 MCEXT SL UPS AC/DC-PR ELETR E SL CONTR
HORN/STROBE LEAVE THE LOCAL-ok 90SGK10_AA030 01040427 MCABA SL UPS AC/DC-PR ELETR E SL CONTR
Activate the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL-ok - 07050131 PRED. ELETR UPS-LED VERMELHO
Activate the following devices
Device TAG Address Text on Fire Panel LCD
CUMULATIVE ALARM 90CYE22EU110-YG01 01040385 REPETICAO ALARME DCS-PR ELETR CONTR PAV 1
LED ON MIMIC PANEL - Electrical Control
Building - 1st Floor-ok -------- --------
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
HORN/STROBE LEAVE THE LOCAL 90SGK10_AA007 01040414 MCABA SL BAIXA TENSAO-PR ELETR E SL CONTR
HORN/STROBE LEAVE THE LOCAL 90SGK10_AA008 01040422 MCABA SL BAIXA TENSAO-PR ELETR E SL CONTR
AMI SELECTOR - IN MANUAL 90SGK10_AA027 01040416 CMMAN SL BAIXA TENSAO-PR ELETR E SL CONTR
HORN/STROBE LEAVE THE LOCAL 90SGK10_AA030 01040427 MCABA SL UPS AC/DC-PR ELETR E SL CONTR
AMI SELECTOR - IN INHIBIT 90SGK10_AA037 01040415 CMINI SL BAIXA TENSAO-PR ELETR E SL CONTR
SIGNAL TO SOLENOID VALVE 90SGK10_AA153 01040132 MCSOL SL BAIXA TENSAO-PR ELETR E SL CONTR
PRESSURE SWITCH 90SGK10_CP103 01040138 PRESS EXT SL B TENSAO-PR ELETR E SL CONTR
ACTIONS:
Activate the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL - 07050130 PRED. ELETR BX TENSAO-LED AMARELO
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
POWER SUPPLY TROUBLE 90CYE10_GR002 01040139 FALHA FONTE SL COMBAT-PR ELETR E SL CONTR
MANUAL STOP BUTTON 90SGK10_AA009 01050137 BA SL PAINEL DCS-PR ELETR E SL CONTR
MANUAL START OF EXTINCTION SYSTEM 90SGK10_AA013 01050136 AD SL PAINEL DCS-PR ELETR E SL CONTR
HORN/STROBE BEGINNING EXTINCTION 90SGK10_AA017 01050132 MCEXT SL PAINEL DCS-PR ELETR E SL CONTR
HORN/STROBE LEAVE THE LOCAL 90SGK10_AA021 01050133 MCABA SL PAINEL DCS-PR ELETR E SL CONTR
AMI SELECTOR - IN MANUAL 90SGK10_AA029 01050135 CMMAN SL PAINEL DCS-PR ELETR E SL CONTR
AMI SELECTOR - IN INHIBIT 90SGK10_AA038 01050134 CMINI SL PAINEL DCS-PR ELETR E SL CONTR
SIGNAL TO SOLENOID VALVE 90SGK10_AA151 01040130 MCSOL SL PAINEL DCS-PR ELETR E SL CONTR
PRESSURE SWITCH 90SGK10_CP101 01040136 PRESS EXT PAINEL DCS-PR ELETR E SL CONTR
ACTIONS:
Activate the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL - 07050134 PRED. ELETR P. DCS-LED AMARELO
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
EVENT:
Trouble/Monitor (1 oo N of the following
devices)
Device TAG Address Text on Fire Panel LCD
POWER SUPPLY TROUBLE 90CYE10_GR002 01040139 FALHA FONTE SL COMBAT-PR ELETR E SL CONTR
MANUAL STOP BUTTON 90SGK10_AA010 01050156 BA SL CONFIG-PR ELETR E SL CONTR
MANUAL START OF EXTINCTION SYSTEM 90SGK10_AA014 01050155 AD SL CONFIG-PR ELETR E SL CONTR
HORN/STROBE BEGINNING EXTINCTION 90SGK10_AA018 01050151 MCEXT SL CONFIG-PR ELETR E SL CONTR
HORN/STROBE LEAVE THE LOCAL 90SGK10_AA022 01050152 MCABA SL CONFIG-PR ELETR E SL CONTR
AMI SELECTOR - IN MANUAL 90SGK10_AA034 01050154 CMMAN SL CONFIG-PR ELETR E SL CONTR
AMI SELECTOR - IN INHIBIT 90SGK10_AA035 01050153 CMINI SL CONFIG-PR ELETR E SL CONTR
SIGNAL TO SOLENOID VALVE 90SGK10_AA154 01040133 MCSOL SL CONFIG-PR ELETR E SL CONTR
PRESSURE SWITCH 90SGK10_CP104 01040137 PRESS EXT SL CONFIG-PR ELETR E SL CONTR
ACTIONS:
Activate the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL - 07050138 PRED. ELETR CONFIG-LED AMARELO
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
EVENT:
Trouble/Monitor (1 oo N of the following
devices)
Device TAG Address Text on Fire Panel LCD
POWER SUPPLY TROUBLE 90AYE18_GR001 03020141 FALHA FONTE SL COMBAT-PR ADMINISTRATIVO
MANUAL STOP BUTTON 90SGK18_AA001 03020137 BA SL ELETRICA-PR ADMINISTRATIVO
MANUAL START OF EXTINCTION SYSTEM 90SGK18_AA002 03020136 AD SL ELETRICA-PR ADMINISTRATIVO
HORN/STROBE BEGINNING EXTINCTION 90SGK18_AA003 03020132 MCEXT SL ELETRICA-PR ADMINISTRATIVO
HORN/STROBE LEAVE THE LOCAL 90SGK18_AA004 03020133 MCABA SL ELETRICA-PR ADMINISTRATIVO
AMI SELECTOR - IN MANUAL 90SGK18_AA005 03020135 CMMAN SL ELETRICA-PR ADMINISTRATIVO
AMI SELECTOR - IN INHIBIT 90SGK18_AA006 03020134 CMINI SL ELETRICA-PR ADMINISTRATIVO
SIGNAL TO SOLENOID VALVE 90SGK18_AA151 03020140 MCSOL SL ELETRICA-PR ADMINISTRATIVO
PRESSURE SWITCH 90SGK18_CP101 03020142 PRESS EXT SL ELETRICA-PR ADMINISTRATIVO
SMOKE DETECTOR - BELOW FLOOR 90SGY18_AA029 03020016 DFEP SL ELETRICA-PR ADMINISTRATIVO
SMOKE DETECTOR - BELOW FLOOR 90SGY18_AA030 03020015 DFEP SL ELETRICA-PR ADMINISTRATIVO
ACTIONS:
Activate the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL - 07040148 PREDIO ADMINISTRATIVO-LED AMARELO
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
Workshop-ok
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
2.6 AREA 9-301 & 302: FIRE FIGHTING PUMP HOUSE (SHEET 11 OF
C&E MATRIX)
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
EVENT:
Trouble/Monitor (1 oo N of the following
devices)
Device TAG Address Text on Fire Panel LCD
POWER SUPPLY TROUBLE 10CYE19_GR001 01030379 FALHA FONTE SL COMBAT-SL AUXILIAR ELETRICA
SIGNAL TO SOLENOID VALVE 90SGK13_AA152 01030383 MCSOL SL BAIXA TENSAO-SL AUXILIAR ELETRICA
PRESSURE SWITCH 90SGK13_CP102 01030382 PRESS EXT SL B TENSAO-SL AUXILIAR ELETRICA
MANUAL STOP BUTTON 90SGK19_AA002 01030391 BA SL PAINEL DCS-SL AUXILIAR ELETRICA
MANUAL START OF EXTINCTION SYSTEM 90SGK19_AA004 01030390 AD SL PAINEL DCS-SL AUXILIAR ELETRICA
HORN/STROBE BEGINNING EXTINCTION 90SGK19_AA006 01030386 MCEXT SL PAINEL DCS-SL AUXILIAR ELETRICA
HORN/STROBE LEAVE THE LOCAL 90SGK19_AA008 01030387 MCABA SL PAINEL DCS-SL AUXILIAR ELETRICA
AMI SELECTOR - IN MANUAL 90SGK19_AA010 01030389 CMMAN SL PAINEL DCS-SL AUXILIAR ELETRICA
AMI SELECTOR - IN INHIBIT 90SGK19_AA012 01030388 CMINI SL PAINEL DCS-SL AUXILIAR ELETRICA
ACTIONS:
Activate the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL - 07040144 SLELEC AUX PAINEL DCS-LED AMARELO
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
LOGIC NUMBER: 11.11 – laços 11.11 ,11.12.11.3 e 11.14 reunidos em uma laço unico na programação – pag 102
EVENT:
Activation of the following switch
Device TAG Address Text on Fire Panel LCD
SWITCH ON REPEATER PANEL-ok - 07060007 ESTEIRA CARVAO 1-BOTAO DISPARO REMOTO
ACTIONS:
Blink fast the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL-ok - 07060141 ESTEIRA CARVAO 1-LED VERMELHO
Wait for 5 seconds
Start Alarm Test of the following devices
Device TAG Address Text on Fire Panel LCD
LINEAR HEAT DETECTOR-ok 90SGY11_AA001 02030188 DLHS ESTEIRA 1Zona1-TRANSPORTADORA CARVAO
LOGIC NUMBER: 11.15 – laços 11.15 – 11.18 unidos na programaçao ; adicionados pontos 124,125,127,127 – pag 102
,
OWNER ID Code
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
EVENT:
Activation of the following switch
Device TAG Address Text on Fire Panel LCD
SWITCH ON REPEATER PANEL- ok - 07060008 ESTEIRA CARVAO 1-INIBICAO REMOTA
ACTIONS:
Activate the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL-ok - 07060144 ESTEIRA CARVAO 1-LED AMARELO
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
ACTIONS:
Activate the following devices
Device TAG Address Text on Fire Panel LCD
HORN/STROBE ALARM-ok 90AYC26_AA001 02020388 MCSIR SL LAB AGUA-TRATAMENTO AGUA DEMI
CUMULATIVE ALARM-ok 90CYE22EU143-YG01 01040406 REPETICAO ALARME DCS-TRATAMENTO AGUA DEMI
LED ON MIMIC PANEL - Demi Water Treatment
Plant-ok -------- --------
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
SIGNAL TO SOLENOID VALVE 10SGC17_GX100 04030196 MCSOL ROLAM 1 TURBINA-PREDIO TURBINA Un1
SIGNAL TO SOLENOID VALVE 10SGC17_GX104 04030192 MCSOL N2 BANCO PRINC-PREDIO TURBINA Un1
HORN/STROBE BEGINNING EXTINCTION 10SGY17_AA001 04030137 MCEXT TURBINAS P112-PREDIO TURBINA Un1
HORN/STROBE BEGINNING EXTINCTION 10SGY17_AA002 04030175 MCEXT TURBINAS P112-PREDIO TURBINA Un1
ACTIONS:
Activate the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL - 07080130 ROL1 TURB PRINC UN1-LED AMARELO
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
HORN/STROBE ALARM-nok 10AYC13_AA002 01020145 MCSIR SL BAIXA TENSAO-SL ELET TOR RESFR Un1
HORN/STROBE ALARM-ok 10AYC13_AA003 01020128 MCSIR SL TRAFOS-SL ELET TOR RESFR Un1
HORN/STROBE ALARM-ok 10AYC13_AA004 01020144 MCSIR SL AR CONDIC-SL ELET TOR RESFR Un1
TRIP SIGNAL-ok 10CYE44EU152-YG01 01020133 TRIP HVAC 2-SL ELET TOR RESFR Un1
CUMULATIVE ALARM-ok 90CYE22EU119-YG01 01040394 REPETICAO ALARME DCS-SL ELET TOR RESFR Un1
LED ON MIMIC PANEL - Unit 1 - Cooling Tower
Electrical Building-ok -------- --------
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
ACTIONS:
Activate the following devices
Device TAG Address Text on Fire Panel LCD
HORN/STROBE LEAVE THE LOCAL 10SGK13_AA004 01020137 MCABA SL BAIXA TENSAO-SL ELET TOR RESFR Un1
Wait for 30 seconds
Activate the following devices
Device TAG Address Text on Fire Panel LCD
HORN/STROBE BEGINNING EXTINCTION 10SGK13_AA003 01020136 MCEXT SL BAIXA TENSAO-SL ELET TOR RESFR Un1
SIGNAL TO SOLENOID VALVE 10SGK13_AA151 01020129 MCSOL SL B TENSAO-SL ELET TOR RESFR Un1
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
2.17 AREA 1-501: STEAM TURBINE LUBE OIL AND LUBE OIL PIPING &
STEEL STRUCTURAL PROTECTION - LINE 1 (SHEET 23 OF C&E
MATRIX)
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
HORN/STROBE ALARM-ok 10AYC18_AA011 04040387 MCSIR SL BAIXA TENSAO-SL BAIXA TENSAO Un1
SIGNAL TO SOLENOID VALVE-ok 10SGC16_AA151 04030227 MCSOL TUB LUBRF TURB-QUEIMADOR CARVAO Un1
HORN/STROBE BEGINNING EXTINCTION-ok 10SGY16_AA007 04030177 MCEXT TUB LUBRF TURB-PREDIO TURBINA Un1
HORN/STROBE BEGINNING EXTINCTION-ok 10SGY16_AA008 04030139 MCEXT TUB LUBRF TURB-PREDIO TURBINA Un1
CUMULATIVE ALARM-ok 90CYE22EU118-YG01 01040393 REPETICAO ALARME DCS-PR TURBINA Un1
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
HORN/STROBE ALARM-ok 10AYC18_AA010 04040379 MCSIR SL BAIXA TENSAO-SL BAIXA TENSAO Un1
HORN/STROBE ALARM-ok 10AYC18_AA011 04040387 MCSIR SL BAIXA TENSAO-SL BAIXA TENSAO Un1
CUMULATIVE ALARM-ok 90CYE22EU118-YG01 01040393 REPETICAO ALARME DCS-PR TURBINA Un1
LED ON MIMIC PANEL - Unit 1 - Turbine Hall--ok -------- --------
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
ACTIONS:
Activate the following devices
Device TAG Address Text on Fire Panel LCD
HORN/STROBE ALARM-ok 10AYC18_AA001 04030219 MCSIR TURBINAS P100-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA002 04030220 MCSIR TURBINAS P100-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA003 04030208 MCSIR TURBINAS P100-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA004 04030180 MCSIR TURBINAS P100-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA005 04030183 MCSIR TURBINAS P100-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA006 04030184 MCSIR TURBINAS P100-PREDIO TURBINA Un1
HORN/STROBE ALARM-nok 10AYC18_AA007 04030186 MCSIR TURBINAS P100-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA008 04030204 MCSIR TURBINAS P100-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA009 04030206 MCSIR TURBINAS P100-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA010 04040379 MCSIR SL BAIXA TENSAO-SL BAIXA TENSAO Un1
HORN/STROBE ALARM-ok 10AYC18_AA011 04040387 MCSIR SL BAIXA TENSAO-SL BAIXA TENSAO Un1
HORN/STROBE ALARM-nok 10AYC18_AA012 04030167 MCSIR TURBINAS P100-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA013 04030171 MCSIR TURBINAS P106-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA014 04030133 MCSIR TURBINAS P106-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA015 04030131 MCSIR TURBINAS P106-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA016 04030169 MCSIR TURBINAS P100-PREDIO TURBINA Un1
HORN/STROBE ALARM-nok 10AYC18_AA017 04030135 MCSIR TURBINAS P112-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA018 04030129 MCSIR TURBINAS P112-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA019 04030179 MCSIR TURBINAS P112-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA020 04030173 MCSIR TURBINAS P112-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA021 04020132 MCSIR PAINEL DCS-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA022 04020131 MCSIR PAINEL DCS-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA023 04030127 MCSIR TURBINAS P122-PREDIO TURBINA Un1
HORN/STROBE ALARM-nok 10AYC18_AA024 04030217 MCSIR TURBINAS P122-PREDIO TURBINA Un1
CUMULATIVE ALARM-ok 90CYE22EU118-YG01 01040393 REPETICAO ALARME DCS-PR TURBINA Un1
LED ON MIMIC PANEL - Unit 1 - Turbine Hall--ok -------- --------
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
2.20 AREA 1-501: TURBINE BUILDING AREA PLAN AT +112,00 & ABOVE - LINE
1 (SHEET 26 OF C&E MATRIX)
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY18_AA029 04020005 DFEP PAINEL DCS-PREDIO TURBINA Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY18_AA030 04020006 DFEP PAINEL DCS-PREDIO TURBINA Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY18_AA031 04020004 DFEP PAINEL DCS-PREDIO TURBINA Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY18_AA032 04020007 DFEP PAINEL DCS-PREDIO TURBINA Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY18_AA033 04020003 DFEP PAINEL DCS-PREDIO TURBINA Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY18_AA034 04020008 DFEP PAINEL DCS-PREDIO TURBINA Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY18_AA035 04020002 DFEP PAINEL DCS-PREDIO TURBINA Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY18_AA036 04020001 DFEP PAINEL DCS-PREDIO TURBINA Un1
SMOKE DETECTOR - AMBIENT-ok 10SGY18_AA043 04020014 DF PAINEL DCS-PREDIO TURBINA Un1
ACTIONS:
Activate the following devices
Device TAG Address Text on Fire Panel LCD
HORN/STROBE ALARM-ok 10AYC18_AA016 04030169 MCSIR TURBINAS P100-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA017 04030135 MCSIR TURBINAS P112-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA018 04030129 MCSIR TURBINAS P112-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA019 04030179 MCSIR TURBINAS P112-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA020 04030173 MCSIR TURBINAS P112-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA021 04020132 MCSIR PAINEL DCS-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA022 04020131 MCSIR PAINEL DCS-PREDIO TURBINA Un1
HORN/STROBE ALARM-ok 10AYC18_AA023 04030127 MCSIR TURBINAS P122-PREDIO TURBINA Un1
HORN/STROBE ALARM-nok 10AYC18_AA024 04030217 MCSIR TURBINAS P122-PREDIO TURBINA Un1
TRIP SIGNAL-ok 10CYE02EU153-YG01 04030166 TRIP HVAC TURBINA-PREDIO TURBINA Un1
CUMULATIVE ALARM-ok 90CYE22EU115-YG01 01040390 REPETICAO ALARME DCS-SL PAINEL DCS Un1
LED ON MIMIC PANEL - Unit 1 - DCS Electrical
Room-ok -------- --------
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
ACTIONS:
Blink fast the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL-ok - 07070141 PAINEL DCS UN1-LED VERMELHO
Wait for 5 seconds
Start Alarm Test of the following devices
Device TAG Address Text on Fire Panel LCD
MANUAL START OF EXTINCTION SYSTEM-ok 10SGK18_AA013 04020140 AD PAINEL DCS-PREDIO TURBINA Un1
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
LED ON CO2 REL. PANEL-ok 10SGJ10_CP105-YG01 04020410 LED PRESS CO2 GRP 2-2-QC1 CO2 AL CARVAO Un1
LED ON CO2 REL. PANEL-ok 10SGJ10_CP105-YG02 04040157 LED PRESS CO2 GRP 2-2-QC2 CO2 AL CARVAO Un1
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
EVENT:
Activation (1 oo N of the following devices)
Device TAG Address Text on Fire Panel LCD
WEIGHT SENSOR-ok 10SGJ10_CW102 04040191 PESO CO2 GRUPO 1-2-ALIMENT CARVAO Un1
ACTIONS:
Activate the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL-ok - 07070134 SILO CARVAO A UN1-LED AMARELO
Activate the following devices
Device TAG Address Text on Fire Panel LCD
LED ON CO2 REL. PANEL-ok 10SGJ10_CW102-YG01 04020422 LED PESO CO2 GRP 1-2-QC1 CO2 AL CARVAO Un1
LED ON CO2 REL. PANEL-ok 10SGJ10_CW102-YG02 04040169 LED PESO CO2 GRP 1-2-QC2 CO2 AL CARVAO Un1
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
WEIGHT SENSOR-ok 10SGJ10_CW111 04040216 PESO CO2 GRUPO 4-2-ALIMENT CARVAO Un1
ACTIONS:
Activate the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL-ok - 07070140 SILO CARVAO D UN1-LED AMARELO
Activate the following devices
Device TAG Address Text on Fire Panel LCD
LED ON CO2 REL. PANEL-ok 10SGJ10_CW111-YG01 04020431 LED PESO CO2 GRP 4-2-QC1 CO2 AL CARVAO Un1
LED ON CO2 REL. PANEL-ok 10SGJ10_CW111-YG02 04040178 LED PESO CO2 GRP 4-2-QC2 CO2 AL CARVAO Un1
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
SIGNAL TO SOLENOID VALVE-ok 10SGJ10_AA160 04040195 MCSOL CO2 GRUPO 2-2-ALIMENT CARVAO Un1
Wait for 600 seconds
Activate the following devices
Device TAG Address Text on Fire Panel LCD
SIGNAL TO SOLENOID VALVE-ok 10SGJ10_AA161 04040196 MCSOL CO2 GRUPO 2-3-ALIMENT CARVAO Un1
Wait for 600 seconds
Deactivate the following devices
Device TAG Address Text on Fire Panel LCD
SIGNAL TO DIRECTIONAL VALVE-ok 10SGJ10_AA153 04020463 VALV BUNKER-B-CARVOARIA Un1
SIGNAL TO DIRECTIONAL VALVE-ok 10SGJ10_AA153 04020463 VALV BUNKER-B-CARVOARIA Un1
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
SIGNAL TO SOLENOID VALVE-ok 10SGJ10_AA166 04040211 MCSOL CO2 GRUPO 4-2-ALIMENT CARVAO Un1
Wait for 600 seconds
Activate the following devices
Device TAG Address Text on Fire Panel LCD
SIGNAL TO SOLENOID VALVE-ok 10SGJ10_AA167 04040212 MCSOL CO2 GRUPO 4-3-ALIMENT CARVAO Un1
Wait for 600 seconds
Deactivate the following devices
Device TAG Address Text on Fire Panel LCD
SIGNAL TO DIRECTIONAL VALVE-ok 10SGJ10_AA155 04020465 VALV BUNKER-D-CARVOARIA Un1
SIGNAL TO DIRECTIONAL VALVE-ok 10SGJ10_AA155 04020465 VALV BUNKER-D-CARVOARIA Un1
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
SIGNAL TO SOLENOID VALVE 10SGJ10_AA159 04040192 MCSOL CO2 GRUPO 2-1-ALIMENT CARVAO Un1
Wait for 600 seconds
Activate the following devices
Device TAG Address Text on Fire Panel LCD
SIGNAL TO SOLENOID VALVE 10SGJ10_AA160 04040195 MCSOL CO2 GRUPO 2-2-ALIMENT CARVAO Un1
Wait for 600 seconds
Activate the following devices
Device TAG Address Text on Fire Panel LCD
SIGNAL TO SOLENOID VALVE 10SGJ10_AA161 04040196 MCSOL CO2 GRUPO 2-3-ALIMENT CARVAO Un1
Wait for 600 seconds
Deactivate the following devices
Device TAG Address Text on Fire Panel LCD
SIGNAL TO DIRECTIONAL VALVE 10SGJ10_AA153 04020463 VALV BUNKER-B-CARVOARIA Un1
SIGNAL TO DIRECTIONAL VALVE 10SGJ10_AA153 04020463 VALV BUNKER-B-CARVOARIA Un1
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
SIGNAL TO SOLENOID VALVE 10SGJ10_AA169 04040222 MCSOL CO2 GRUPO 5-2-ALIMENT CARVAO Un1
Wait for 600 seconds
Activate the following devices
Device TAG Address Text on Fire Panel LCD
SIGNAL TO SOLENOID VALVE 10SGJ10_AA170 04040223 MCSOL CO2 GRUPO 5-3-ALIMENT CARVAO Un1
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
DIRECTIONAL VALVE BUTTON 10SGY10_AA026 04040128 BTVALV BUNKER C-QC2 CO2 AL CARVAO Un1
AND Alarm (1 oo N of the following devices)
Device TAG Address Text on Fire Panel LCD
MANUAL START OF EXTINCTION SYSTEM 10SGY10_AA032-YG02 04040130 AD CO2 GRUPO 5-QC2 CO2 AL CARVAO Un1
ACTIONS:
Activate the following devices
Device TAG Address Text on Fire Panel LCD
CUMULATIVE ALARM 90CYE22EU114-YG01 01040389 REPETICAO ALARME DCS-CARVOARIA Un1
LED ON MIMIC PANEL - Unit 1 - Coal Bunkers -------- --------
Activate the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL - 07070137 SILO CARVAO C UN1-LED VERMELHO
Activate the following devices
Device TAG Address Text on Fire Panel LCD
SIGNAL TO SOLENOID VALVE 10SGJ10_AA168 04040221 MCSOL CO2 GRUPO 5-1-ALIMENT CARVAO Un1
Wait for 600 seconds
Activate the following devices
Device TAG Address Text on Fire Panel LCD
SIGNAL TO SOLENOID VALVE 10SGJ10_AA169 04040222 MCSOL CO2 GRUPO 5-2-ALIMENT CARVAO Un1
Wait for 600 seconds
Activate the following devices
Device TAG Address Text on Fire Panel LCD
SIGNAL TO SOLENOID VALVE 10SGJ10_AA170 04040223 MCSOL CO2 GRUPO 5-3-ALIMENT CARVAO Un1
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
ACTIONS:
Blink fast the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL-ok - 07070137 SILO CARVAO C UN1-LED VERMELHO
Wait for 5 seconds
Start Alarm Test of the following devices
Device TAG Address Text on Fire Panel LCD
MANUAL START OF EXTINCTION SYSTEM-ok 10SGY10_AA022 04020458 AD BUNKER-C-CARVOARIA Un1
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
SIGNAL TO SOLENOID VALVE 10SGJ10_AA160 04040195 MCSOL CO2 GRUPO 2-2-ALIMENT CARVAO Un1
SIGNAL TO SOLENOID VALVE 10SGJ10_AA161 04040196 MCSOL CO2 GRUPO 2-3-ALIMENT CARVAO Un1
PRESSURE SWITCH 10SGJ10_CP104 04040194 PRESS CO2 GRUPO 2-1-ALIMENT CARVAO Un1
PRESSURE SWITCH 10SGJ10_CP105 04040204 PRESS CO2 GRUPO 2-2-ALIMENT CARVAO Un1
PRESSURE SWITCH 10SGJ10_CP106 04040203 PRESS CO2 GRUPO 2-3-ALIMENT CARVAO Un1
PRESSURE SWITCH 10SGJ10_CP117 04020466 PRESS CO2 BUNKER B-CARVOARIA Un1
WEIGHT SENSOR 10SGJ10_CW104 04040193 PESO CO2 GRUPO 2-1-ALIMENT CARVAO Un1
WEIGHT SENSOR 10SGJ10_CW105 04040200 PESO CO2 GRUPO 2-2-ALIMENT CARVAO Un1
WEIGHT SENSOR 10SGJ10_CW106 04040199 PESO CO2 GRUPO 2-3-ALIMENT CARVAO Un1
HORN/STROBE BEGINNING EXTINCTION 10SGY10_AA017 04040230 MCEXT ALIMENT CARVAO-ALIMENT CARVAO Un1
HORN/STROBE BEGINNING EXTINCTION 10SGY10_AA018 04020446 MCEXT CARVOARIA-CARVOARIA Un1
HORN/STROBE BEGINNING EXTINCTION 10SGY10_AA019 04020461 MCEXT CARVOARIA-CARVOARIA Un1
MANUAL START OF EXTINCTION SYSTEM 10SGY10_AA021 04020447 AD BUNKER-B-CARVOARIA Un1
DIRECTIONAL VALVE BUTTON 10SGY10_AA025 04020380 BTVALV BUNKER B-QC1 CO2 AL CARVAO Un1
MANUAL START OF EXTINCTION SYSTEM 10SGY10_AA028-YG01 04020387 AD CO2 GRUPO 1-QC1 CO2 AL CARVAO Un1
MANUAL START OF EXTINCTION SYSTEM 10SGY10_AA029-YG01 04020384 AD CO2 GRUPO 2-QC1 CO2 AL CARVAO Un1
MANUAL START OF EXTINCTION SYSTEM 10SGY10_AA030-YG01 04020385 AD CO2 GRUPO 3-QC1 CO2 AL CARVAO Un1
MANUAL START OF EXTINCTION SYSTEM 10SGY10_AA031-YG01 04020382 AD CO2 GRUPO 4-QC1 CO2 AL CARVAO Un1
MANUAL START OF EXTINCTION SYSTEM 10SGY10_AA032-YG01 04020383 AD CO2 GRUPO 5-QC1 CO2 AL CARVAO Un1
ACTIONS:
Activate the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL - 07070136 SILO CARVAO B UN1-LED AMARELO
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
PRESSURE SWITCH 10SGJ10_CP110 04040217 PRESS CO2 GRUPO 4-1-ALIMENT CARVAO Un1
PRESSURE SWITCH 10SGJ10_CP111 04040220 PRESS CO2 GRUPO 4-2-ALIMENT CARVAO Un1
PRESSURE SWITCH 10SGJ10_CP112 04040219 PRESS CO2 GRUPO 4-3-ALIMENT CARVAO Un1
PRESSURE SWITCH 10SGJ10_CP119 04020468 PRESS CO2 BUNKER D-CARVOARIA Un1
WEIGHT SENSOR 10SGJ10_CW110 04040213 PESO CO2 GRUPO 4-1-ALIMENT CARVAO Un1
WEIGHT SENSOR 10SGJ10_CW111 04040216 PESO CO2 GRUPO 4-2-ALIMENT CARVAO Un1
WEIGHT SENSOR 10SGJ10_CW112 04040215 PESO CO2 GRUPO 4-3-ALIMENT CARVAO Un1
HORN/STROBE BEGINNING EXTINCTION 10SGY10_AA017 04040230 MCEXT ALIMENT CARVAO-ALIMENT CARVAO Un1
HORN/STROBE BEGINNING EXTINCTION 10SGY10_AA018 04020446 MCEXT CARVOARIA-CARVOARIA Un1
HORN/STROBE BEGINNING EXTINCTION 10SGY10_AA019 04020461 MCEXT CARVOARIA-CARVOARIA Un1
DIRECTIONAL VALVE BUTTON 10SGY10_AA026 04040128 BTVALV BUNKER C-QC2 CO2 AL CARVAO Un1
MANUAL START OF EXTINCTION SYSTEM 10SGY10_AA028-YG02 04040134 AD CO2 GRUPO 1-QC2 CO2 AL CARVAO Un1
MANUAL START OF EXTINCTION SYSTEM 10SGY10_AA029-YG02 04040131 AD CO2 GRUPO 2-QC2 CO2 AL CARVAO Un1
MANUAL START OF EXTINCTION SYSTEM 10SGY10_AA030-YG02 04040132 AD CO2 GRUPO 3-QC2 CO2 AL CARVAO Un1
MANUAL START OF EXTINCTION SYSTEM 10SGY10_AA031-YG02 04040129 AD CO2 GRUPO 4-QC2 CO2 AL CARVAO Un1
MANUAL START OF EXTINCTION SYSTEM 10SGY10_AA032-YG02 04040130 AD CO2 GRUPO 5-QC2 CO2 AL CARVAO Un1
ACTIONS:
Activate the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL - 07070140 SILO CARVAO D UN1-LED AMARELO
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY14_AA021 04050261 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY14_AA022 04050262 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY14_AA023 04050263 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY14_AA024 04050264 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY14_AA025 04050265 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY14_AA026 04050266 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY14_AA027 04050270 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY14_AA028 04050271 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY14_AA029 04050272 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY14_AA030 04050273 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY14_AA031 04050274 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY14_AA032 04050275 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - AMBIENT-ok 10SGY14_AA033 04050292 DF SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - AMBIENT-ok 10SGY14_AA034 04050291 DF SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY14_AA035 04050252 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY14_AA036 04050267 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY14_AA037 04050268 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR-ok 10SGY14_AA038 04050269 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
ACTIONS:
Activate the following devices
Device TAG Address Text on Fire Panel LCD
HORN/STROBE ALARM-ok 10AYC14_AA001 04050405 MCSIR SL MEDIA TENSAO-SL MEDIA TENSAO Un1
HORN/STROBE ALARM-ok 10AYC14_AA002 04050403 MCSIR SL MEDIA TENSAO-SL MEDIA TENSAO Un1
TRIP SIGNAL-ok 10CYE42EU201-YG01 04050376 TRIP HVAC 1-SL MEDIA TENSAO Un1
CUMULATIVE ALARM-ok 90CYE22EU120-YG01 01040395 REPETICAO ALARME DCS-SL MEDIA TENSAO Un1
LED ON MIMIC PANEL - Unit 1 - MV Electrical
Room-ok -------- --------
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA013 04050253 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA014 04050254 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA015 04050255 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA016 04050256 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA017 04050257 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA018 04050258 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA019 04050259 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA020 04050260 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA021 04050261 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA022 04050262 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA023 04050263 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA024 04050264 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA025 04050265 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA026 04050266 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA027 04050270 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA028 04050271 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA029 04050272 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA030 04050273 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA031 04050274 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA032 04050275 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA035 04050252 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA036 04050267 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA037 04050268 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
SMOKE DETECTOR - BELOW FLOOR 10SGY14_AA038 04050269 DFEP SL MEDIA TENSAO-SL MEDIA TENSAO Un1
AND NOT Activation (1 oo N of the following
devices)
Device TAG Address Text on Fire Panel LCD
MANUAL STOP BUTTON 10SGK14_AA001 04050401 BA SL MEDIA TENSAO-SL MEDIA TENSAO Un1
AND NOT Activation (1 oo N of the following
devices)
Device TAG Address Text on Fire Panel LCD
AMI SELECTOR - IN MANUAL 10SGK14_AA005 04050399 CMMAN SL MEDIA TENSAO-SL MEDIA TENSAO Un1
AND NOT Activation (1 oo N of the following
devices)
Device TAG Address Text on Fire Panel LCD
AMI SELECTOR - IN INHIBIT 10SGK14_AA006 04050398 CMINI SL MEDIA TENSAO-SL MEDIA TENSAO Un1
ACTIONS:
Activate the following devices
Device TAG Address Text on Fire Panel LCD
HORN/STROBE LEAVE THE LOCAL 10SGK14_AA004 04050397 MCABA SL MEDIA TENSAO-SL MEDIA TENSAO Un1
Wait for 30 seconds
Activate the following devices
Device TAG Address Text on Fire Panel LCD
SIGNAL TO SOLENOID VALVE 10SGK11_AA151 04050391 MCSOL SL MEDIA TENSAO-SL MEDIA TENSAO Un1
HORN/STROBE BEGINNING EXTINCTION 10SGK14_AA003 04050396 MCEXT SL MEDIA TENSAO-SL MEDIA TENSAO Un1
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
SIGNAL TO SOLENOID VALVE-ok 10SGK11_AA151 04050391 MCSOL SL MEDIA TENSAO-SL MEDIA TENSAO Un1
2.23 AREA 1-801: FGD ELECTRICAL ROOM - LINE 1 (SHEET 29 OF C&E MATRIX)
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
AMI SELECTOR - IN MANUAL-ok 10SGK19_AA011 04050151 CMMAN SL BAIXA TENSAO-COMPRESSOR FGD Un1
ACTIONS:
Activate the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL-ok - 07070130 FGD BX TENSAO UN1-LED AMARELO
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
HORN/STROBE BEGINNING EXTINCTION 10SGK19_AA007 04050158 MCEXT SL PAINEL DCS-COMPRESSOR FGD Un1
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
EVENT:
Alarm (1 oo N of the following devices)
Device TAG Address Text on Fire Panel LCD
LINEAR HEAT DETECTOR 10SGY21_AA001 04030389 DLHS TRAFO PRINCIPAL-TRAFOS AUXILIARES Un1
AND NOT Activation of the following switch
Device TAG Address Text on Fire Panel LCD
SWITCH ON REPEATER PANEL - 07100004 TRAFO PRINC UN1-INIBICAO REMOTA
ACTIONS:
Activate the following devices
Device TAG Address Text on Fire Panel LCD
HORN/STROBE ALARM 10AYC21_AA001 04030386 MCSIR TRAFO PRINCIPAL-TRAFOS AUXILIARES Un1
SIGNAL TO SOLENOID VALVE 10SGC13_AA151 04030392 MCSOL TRAFO PRINCIPAL-TRAFOS AUXILIARES Un1
HORN/STROBE BEGINNING EXTINCTION 10SGY21_AA002 04030387 MCEXT TRAFO PRINCIPAL-TRAFOS AUXILIARES Un1
CUMULATIVE ALARM 90CYE22EU121-YG01 01040396 REPETICAO ALARME DCS-TRANSFORMADORES Un1
LED ON MIMIC PANEL - Unit 1 - MV Step Up
Transformer Area -------- --------
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
Transformer Area
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
EVENT:
Activation of the following switch
Device TAG Address Text on Fire Panel LCD
SWITCH ON REPEATER PANEL-ok - 07100005 TRAFO AUX1 UN1-BOTAO DISPARO REMOTO
ACTIONS:
Blink fast the following LEDs
Device TAG Address Text on Fire Panel LCD
LED ON REPEATER PANEL-ok - 07100137 TRAFO AUX1 UN1-LED VERMELHO
Wait for 5 seconds
Start Alarm Test of the following devices
Device TAG Address Text on Fire Panel LCD
MANUAL START OF EXTINCTION SYSTEM-ok 10SGY20_AA005 04030379 AD TRAFO AUX 1-TRAFOS AUXILIARES Un1
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number
M004-KK-VD-020_0011
LOGICAL PROGRAMMING
CREA Number