Professional Documents
Culture Documents
WireXpert Overview :
Testing Procedure :
On the both WireXpert Local and Remote units.
Then change below settings in LOCAL unit. (For CAT 6 UTP)
1) Quick Settings
This provides quick selection using predefined TIA (CAT 5e/6/6A) and ISO (Class
D/E/EA/F/FA) configurations for UTP/FTP cables.
For CAT 6 UTP cables, touch the arrow mark in Quick setup group >Select CAT 6
This is a property of “Orange” and you are bound to maintain the confidentiality This ISO 9001:2008 document which is publish ed on intranet is subjected to be
updated as & when needed. Any hard copy of this document is regarded as an “uncontrolled” copy which may not contain up to date information.
WORK INSTRUCTIONS-(Cables) Page: 2 of 1
2) Test Settings
First change the Test limit. Press the SETUP button > Test Settings > Test
Limits to choose from a list of commonly used limits. Three recently used limits will
be on top of the list.
This is a property of “Orange” and you are bound to maintain the confidentiality This ISO 9001:2008 document which is publish ed on intranet is subjected to be
updated as & when needed. Any hard copy of this document is regarded as an “uncontrolled” copy which may not contain up to date information.
WORK INSTRUCTIONS-(Cables) Page: 3 of 1
Auto save. Chose as desired. Enable option for WireXpert to auto save every PASS
result. Option will be enabled for List Based Testing.
4) System Settings
Leave the System settings in the same way.
After changing the above settings in LOCAL unit, it is necessary to perform a set reference
measurement if the Local and Remote units are being paired for the first time. To
set reference,
I. Connect a Permanent Link adapter to the Local unit.
II. Connect a Channel adapter to the Remote unit.
III. Connect the 2 units together using the patch cord
provided in the kit.
IV. Press the TOOLS button > Set Reference
This is a property of “Orange” and you are bound to maintain the confidentiality This ISO 9001:2008 document which is publish ed on intranet is subjected to be
updated as & when needed. Any hard copy of this document is regarded as an “uncontrolled” copy which may not contain up to date information.
WORK INSTRUCTIONS-(Cables) Page: 4 of 1
This is a property of “Orange” and you are bound to maintain the confidentiality This ISO 9001:2008 document which is publish ed on intranet is subjected to be
updated as & when needed. Any hard copy of this document is regarded as an “uncontrolled” copy which may not contain up to date information.
WORK INSTRUCTIONS-(Cables) Page: 5 of 1
3) Otherwise, press the “SETUP” button > System Settings 2 > Storage > USB
4) Select “Test Results”.
5) Click “OK” to proceed.
6) Launch eXport software.
7) Go to File > Create New Project to create new project space.
8) Go to Import > USB Flash Drive and select the flash drive. Click “Import”.
9) Select database and click “Import Selected” to import or click “Import All” for all
databases.