EGYPT CABLE

ALL-ALUMINIUM ALLOY CONDUCTOR


IEC SIZES
Aluminium Alloy conductors AAAC sizes from characteristics of A2 conductors
maximum
AREA AREA Equivalent stranding & Approx Nominal
Approx weight resistance dc Current Rating
NOMINAL ACTUAL copper area wire diameter overall breaking load
Code number at 20°
temperate
mm² mm² mm² mm mm kg/km KN ohm/km tropical amp
amp
IEC 16 18.4 9.8 7/1.83 5.49 50.4 5.43 1.7896 90 60

IEC 25 28.8 15.4 7/2.29 6.86 78.7 8.49 1.1453 112 74

IEC 40 46.0 24.6 7/2.89 8.68 125.9 13.58 0.7158 150 90

IEC 63 72.5 38.7 7/3.63 10.9 198.3 21.39 0.4545 190 115

IEC 100 115 61.4 19/2.78 13.9 316.3 33.95 0.2877 250 145

IEC 125 144 76.8 19/3.10 15.5 395.4 42.44 0.2302 291 160

IEC 160 184 98.2 19/3.51 17.6 506.1 54.32 0.1798 350 180

IEC 200 230 122.8 19/3.93 19.6 632.7 67.91 0.1439 400 190

IEC 250 288 153.5 19/4.39 22 790.8 84.88 0.1151 460 205

IEC 315 363 193.4 37/3.53 24.7 998.9 106.95 0.0916 530 210

IEC 400 460 245.6 37/3.98 27.9 1268.4 135.81 0.0721 602 222

IEC 450 518 276.3 37/4.22 29.6 1426.9 152.79 0.0641 650 225

IEC 500 575 307.0 37/4.45 31.2 1585.5 169.76 0.0577 689 211

IEC 560 645 340.9 61/4.67 33 1778.4 190.14 0.0516 700 250

IEC 630 725 383.5 61/3.89 35 2000.7 213.9 0.0458 780 240

IEC 710 817 432.2 61/4.13 37.2 2245.8 241.07 0.0407 840 220

IEC 800 921 487.0 61/4.38 39.5 2540.6 271.62 0.0361 900 220