Professional Documents
Culture Documents
Substation Solutions
Contents
Introduction__________________________ 1
Preface 1
Your Electrical Network 2
Your Business and SSS Applications 2
Our Product Map (SSS & DNS) 3
Main features_________________________ 4
Safety 4
Reliability 4
Efficiency 5
Sustainability 5
Continuous innovation 5
Technical details_______________________ 6
Family 6
Technical data 7
Constructive structure 8
Design characteristics___________________ 9
Key components 9
Main compartments 10
Handling, installation
and after sales_______________________35
Inside buildings 36
Inside mobile substations 36
Inside wind turbines and wind farm substations 36
Commissioning and After Sales 37
Recycling and end-of-life 37
The quality of the products designed, manufactured and installed by Ormazabal is backed by the implementation and certification of a quality management system,
based on international standard ISO 9001:2008.
Our commitment to the environment is reaffirmed with the implementation and certification of an environmental management system as laid down in international standard
ISO 14001.
In view of the constant evolution in standards and design, the characteristics of the elements contained in this catalogue are subject to change without prior notification.
These characteristics, as well as the availability of components, are subject to confirmation by Ormazabal.
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
Introduction
Preface
MV/MV and HV/MV substations are Ormazabal is the leading provider Velatia is an international industrial
one of the most critical nodes in any of personalized solutions to electrical and technological group which operates
electrical network. utilities, to energy end users as well as in the areas of electrical networks,
renewable energy systems applications electronics and communication networks
The increasing demand for electricity, based on our own technology. as well as in the consulting, security
and for more power in these and aviation sectors, where security,
substations, requires that MV panels We encourage the development
efficiency and reliability are valued.
have to guarantee maximum reliability of the electrical sector concerning
and service continuity for rated current the challenges of the future energy Grupo Ormazabal is now called
levels. needs. We cooperate with the world's Velatia. We have combined our
leading local, regional and global forces to transform ourselves into
Following the long years of design, companies in the electrical sector with a stronger group. Made up of
development, manufacturing and a strong commitment to innovation companies with more than a hundred
commissioning experience in for personal safety, network years of experience and committed
gas insulated switchgear (GIS) in reliability, energy efficiency, and to innovation to meet the present
secondary distribution, in 2005 sustainability. and future needs of our customers,
Ormazabal introduced into the world wherever they may be.
markets the CPG system: Our highly qualified and focused
team of professionals thrilled by The solutions of the companies in
High duty, flexible and extensible innovation have developed our own Velatia seek to make the world a
single and double busbars GIS panels products and solutions during our more connected, more sustainable,
up to 36 kV. more than a century long consolidated smarter, better connected, safer,
During the recent years CPG has been history, always by establishing close more humane place.
extended to higher electrical ratings, relationship with our clients towards
e.g. up to 2500 A and up to 38 kV. achieving mutual long term benefits.
1
CPG.0 & CPG.1 MV Switchgear for
Single and double busbar panel type GIS system Substation Solutions
2
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
CGMCOSMOS CGMCOSMOS
CGM.3 GAE GA EA
[IEC - ANSI/IEEE] [HN]
Distribution transformers
Low voltage
Protection, automation and control
Conventional oil ORGANIC TPC board
Concrete enclosure for transformer substations (TS) Metallic enclosure Photovoltaic Mobile
Underground Walk-in Modular for TS substation substation
Advanced metering,
Protection, automation
sensing & analytics
and control
and communications
3
CPG.0 & CPG.1 MV Switchgear for
Single and double busbar panel type GIS system Substation Solutions
Main features
Safety Reliability
Protection for people, environment Interlocks Help to maintain uninterrupted supply
and your electrical installations. of your electrical network
CPG panels have mechanical and
Special attention paid to the personal electrical interlocks as standard in Sealed for life insulation
safety of the operators and the accordance to IEC 62271-200 to
general public, even under fault enable safe and reliable service. Insulation inside a stainless steel
conditions. gas tank provides long service
Interlocks prevent unsafe operations: life (30 years) and absence of
Internal arc • It makes impossible to close the maintenance in live parts.
The CPG panels have been designed switch-disconnector and the earthing Installation, assembly on site,
to withstand the effects of an internal (grounding) switch at the same time. extension and replacement without
arc according to IEC 62271-200 • It permits the opening of the gas handling.
(IAC class) / IEEE Std C37.20.7 access cover to the MV cables
(1D-S class). when the earthing (grounding) Suitable for any
switch is closed. environment
Gas insulated and
Optional locks, key interlocks and Resistance to harsh conditions
screened
electrical locks based on customers’ (humidity, salinity, dust, pollution…).
The breaking and making devices specifications are available. Uninterrupted supply even in case
are housed in independent sealed of flooding.
for life stainless steel gas tanks. It Indicators
provides resistance against harsh 100% Routine tested
Additional safety by using:
environmental conditions and All the switchgear is subject to 100%
protection against indirect contacts. • Switchgear position indicators:
electrical and mechanical routine tests
Visual indication on the
The whole power circuit is fully according to the relevant standards.
mimic diagram, validated
insulated, including the cable Also gas tightness test has been
by the kinematic chain test in
terminals, and entirely screened, carried out 100% of our switchgear
accordance with current standards
earthed (grounded) and installed as a routine test to guarantee the
(IEC 62271-102).
inside a metal enclosure. reliability throughout its operational
• Capacitive voltage presence / life.
absence indicators(IEC 61243-5)
• Gas tightness test
• Permanent indication (multi-
• Power-frequency test
LED) and optional contacts for
remote display and/or use of • Measurement of the resistance of
electromagnetic interlocks the main circuit
• Temperature-compensated • Mechanical endurance test
monitoring of the gas pressure • Measurement of the partial
inside each of the panel tanks. discharge
Other tests performed:
• Salt & fog tested for 500 hours
• Seismic tested as per Richter
4
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
5
CPG.0 & CPG.1 MV Switchgear for
Single and double busbar panel type GIS system Substation Solutions
Technical details
Family
CPG.0 CPG.1 CPG.1
Single busbar Single busbar Double busbar
V F S V1 F1 S1 V2 F2 S2
Circuit breaker Fuse protection Disconnector Circuit breaker Fuse protection Disconnector Circuit breaker Fuse protection Disconnector
RB C C CL CT
6
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
Technical data
Electrical characteristics IEC ANSI / IEEE
CPG.0 CPG.1 CPG.0 CPG.1
Rated Voltage Ud [kV] 24 36 24 36 27 38 27 38
Rated frequency fr [Hz] 50 / 60
Rated normal current Ir
Busbars [A] Up to 2500 Up to 12503) Up to 2000 Up to 22503) Up to 12503) Up to 20003)
Outgoing line 1)
[A] Up to 2500 Up to 1250 Up to 2000 Up to 2250 Up to 1250 Up to 2000
7
CPG.0 & CPG.1 MV Switchgear for
Single and double busbar panel type GIS system Substation Solutions
Constructive structure
CPG.0
Front view Side view
1. Gas tank/s
1.1. Vacuum circuit breaker
1.2. Three-position switch-
disconnector (CPG.0) /
Disconnectors (CPG.1)
1.3. Earthing switch (CPG.1)
1.4. Pressure relief duct
2. Busbar compartment
2.1. Main busbars
3. Base: Cable compartment
3.1. Bushings
3.2. Current transformers
3.3. Voltage transformers
3.4. Phase segregation assembly
3.5. Terminals
4. Low voltage compartment
4.1. Protection, control and
signalling devices
5. Operation interface
5.1. Circuit-breaker driving
mechanism
CPG.1 5.2. Disconnector/s driving
mechanism
Front view Side view
5.3. Earthing (grounding) switch
mechanism
5.4. Pressure switch (CPG.0)
5.5. Voltage presence/absence
indicator
5.6. Mimic diagram
CPG
ANSI / IEEE type
8
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
Design characteristics
Key components
Vacuum circuit breaker Disconnector Main busbars
(VCB) Puffer type high dutydisconnector The function of the main busbars is to
Circuit-breaker with vacuum designed and developed by connect panel-to-panel electrically.
breaking technology, compact and Ormazabal.
They are single-phase arranged
with excellent reliability, certified The switch-disconnector includes and located outside the sealed gas
in accordance to IEC 62271-100 the functions of switch-disconnector tank .It allows modularity and future
standard, including extended and earthing (grounding) switch in a extensibility without gas handling on
electrical endurance (class E2) with single three-position unit. site or moving adjacent panels.
rapid reclosing cycle and hence
maintenance-free during its whole Disconnector and earthing The upper busbar set consists of
service life. (grounding) switch: three separate cylindrical copper
conductors with solid and shielded
Circuit-breaker CPG.0 CPG.1
insulation. Every phase is connected
CPG.0 CPG.1 Mechanical endurance
M0 –
1000
M0-
1000
using a busbar segment and “T” or
“L” shaped connectors.
Breaking capacity Earthing (grounding) switch
Short-circuit
[kA] 25 25 / 31.5 63 (50
63-80 The whole set is protected against
(asymmetry) Making capacity [kA] Hz) / 65
(50 Hz)
dirt and condensation; in addition, it
/ 65-85
(60 Hz)
DC >34% >45% (60 Hz) has a metal cover to protect it against
No-load cable-
31.5 (24 kV) Electrical endurance E01) E0 1)
impacts.
charging breaking [A]
50 (36 kV)
capacity 24 kV:
Up to The busbars are prepared to
Capacitor bank
breaking capacity
[A] 400 Rated current [A]
2500
36 kV:
2000 A withstand thermal and dynamic forces
Up to of rated short-time currents (CPG.0:
Electrical endurance E2 1250
25 kA / 1 or 3 s and CPG.1 up to
Reclosing sequence O-0.3”-CO-15”-CO Short-time [kA –1 /
25
25 25-31.5 kA / 1 or 3 s) and rated
current 3 s] 31.5
Mechanical endurance M2 10000 continuous current up to 2500 A.
Up to 2500
(24 kV) Up to 2000 1)The earthing switch does not have
Rated current [A]
Up to 2000 (24-36 kV)
(36 kV)
making capacity by itself, as this is
[kA / transferred to the circuit-breaker.
Rated short-time
1s- 25 25 / 31.5
withstand current 3 s] Characteristics:
Operatiing time [ms] <45
• 3 positions (connection -
Characteristics: disconnection - earthing)
• Vacuum breaking • Independent actuation and levers
for the operations:
• Manual operation through push-button
(lockable with a padlock) • Connection - disconnection [motor driving
mechanism option]
• Motor driving mechanism
• Disconnection – earthing (grounding)
• Spring loading time <15 seconds
[motor driving mechanism option]
• Operating coils:
• 1 (CPG.0) and 2 (CPG.1) shunt trip
opening coils. 2nd optional coil.
• 1 closing coil
• 1 undervoltage coil (optional)
9
CPG.0 & CPG.1 MV Switchgear for
Single and double busbar panel type GIS system Substation Solutions
Main compartments
CPG panel system presents a Switch / CB compartment Driving mechanism
structure divided into independent
compartments: The switch compartment, sealed The driving mechanism is used
for life, houses the switching and to perform making and breaking
breaking switchgear, where the operations in the MV circuits.
insulating medium is SF6 gas.
4 The front layout of the driving
2
CPG.0 contains one single gas tank, mechanisms and the use of anti-reflex
whereas CPG.1 is characterised levers permits safe, comfortable,
by having one tank for the Circuit- simple operations with a minimum of
5 Breaker and earthing (grounding) effort.
1
switch and one tank for each feeder
The front mimic diagrams include the
disconnectors depending on whether
position indicating devices. Maximum
it corresponds to single or double
reliability verified using the kinematic
busbar.
chain test of the signalling mechanism
3 Built in stainless steel, it is designed in accordance with IEC 62271-102.
to withstand an internal arc. The gas
Features:
generated as a result of an internal
arc is cooled down and can be • Mimic diagram and pushbuttons
CPG.0 channelled towards the top of the • Position display (Kinematic chain)
panel through a relief duct located on • Switching devices
the rear side.
• Fuse tripping
4 The following elements are
• Capacitive voltage indicator
2 located inside, depending on the
functionality: • Interlocks (electrical and
mechanical)
• Disconnector and earthing
(grounding)switch. • Optimized operator interface
1 • Vacuum circuit-breaker.
5
• Fuse holders
This compartment can be connected
to the busbar and the medium
voltage cables respectively by means
3 of cable bushings at the top and
bottom.
The gas pressure is tested by means
of a temperature-compensated
CPG.1 pressure gauge, with a potential-free
contact, allowing it to be used as a
1. Gas tank/s: remote alarm.
Switch/ CB compartment/s
Features:
2. Busbar compartment
• Sealed-for-life insulation system
3. Base: Cable compartment (30 years)
4. Low voltage compartment • Internal arc tested
5. Operation interface • Stainless steel – IP65 rating
• Switching, breaking and main
circuit devices
• Outer-cone bushing plug-in type
terminal
• Pressure gauge
• Pressure relief diaphragm valve
10
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
11
CPG.0 & CPG.1 MV Switchgear for
Single and double busbar panel type GIS system Substation Solutions
Protection &
Automation
CPG switchgear is used a very wide ekorSYS Family ekorRPS-TCP
range of areas in power distribution
ekorSYS family is the generic Communications
and mostly includes comprehensive
protection and control systems to name of all the protection • Ports: RS-232, RS-485, FOC
provide the related functions for the relays, automation, control and
• Protocols:
application. communication components and
MODBUS, PROCOME, IEC-
systems that are designed, developed
CPG is suitable to utilize in 60870-5-101, IEC-60870-5-103,
and manufactured by Ormazabal.
substations with conventional DNP3.0, IEC-61850
protection relays as well as where The basic products and systems that
Protection ekorRPS-DC and
complex combination of several can be integrated into CPG panels
ekorRPS-DD
protection relays and controls are as follows:
• Phase overcurrent: (3 x 50/51)
systems are required. The devices Protection
are installed in the low-voltage • Earth overcurrent: (50N/51N)
compartment of the panels. Indicators ekorRPG • Current unbalance/ negative
and controls are integrated into Measurements sequence current: (46-46FA)
the front door of the low voltage • Current: Amperimeter Function • Breaker failure: (50BF)
compartment.
Protection Functions • 2nd harmonic restraint
Protection • Phase overcurrent: 50-51 • Ultrasensitive earth overcurrent:
• Protection functions such as • Earth overcurrent: 50N-51N (50Ns/51Ns)
Differential protection • Ultrasensitive earth leakage
• Ultrasensitive earth overcurrent
Distance protection protection: 50Ns-51Ns
(3 x 67)
Overcurrrent time protection • Thermometer (external trip): 49T
• Recloser (79) • Directional earth fault and
Earth fault protection
sensitive earth fault:
Overload protection Communications (67N), (67Ns)
Over/under voltage protection • Front port configuration:
Pver/under frequency protection DB9 RS232 • Isolated earth directional function:
Directional power protection • Rear port remote control (67NA)
Load unbalance protection RS485 (5kV) –RJ45 • Voltage restrained overcurrent:
Automatic re-starting, etc. • Protocol: MODBUS (RTU) (51V)
• Substation protection • Setup and monitoring program • Fuse failure
• Supply to MV customers ekorSOFT (optional)
• Thermal image: (49)
• Protection of switching substations
and industrial customers
• Generator set protection unit
Automation
• Automation and remote control
• Remote control
• Automatic transfer
• Fault detection
Communication
A wide range of interfaces and
protocol structures are available
for communication with the control
system depending on the device
variants used. The connection is
made using a data cable or fibre
optic cable depending on the system.
12
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
13
CPG.0 & CPG.1 MV Switchgear for
Single and double busbar panel type GIS system Substation Solutions
Type of modules
CPG.0-V
Single busbar circuit-breaker panel
Includes a vacuum circuit-breaker and a three position disconnectorin series with it. Both components are located Both
components are located inside the switch compartment.
Applications
Main transformer protection, feeder protection, busbar coupling protection, capacitor bank protection and auxiliary services
transformer protection.
14
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
Dimensions
Configuration
Panel structure
Internal arc
JJ IAC AFL 25 kA 1 s (IEC)
FF IAC AFLR 25 kA 1 s (IEC)
Gas tank
JJ Pressure gauge with potential-
free contact
JJ Voltage presence indicator
FF Auxiliary contact
FF Visual inspection device
Busbar compartment
FF Up to 2500 A – 24 kV
FF Up to 1250 A – 36 kV
FF Up to 2250 A – 27 kV
FF Up to 1250 A – 38 kV
FF Current Transformers
FF Voltage Transformers IEC
CPG.0-V
Driving mechanism
Three-position disconnector
FF Disconnector motorization
FF Earthing (grounding) switch
motorization [mm]
[in]
Vacuum circuit-breaker
JJ Motor
JJ Tripping coil
FF 2ndTripping coil
JJ Closing col
FF Undervoltage coil
JJ Opening/closing push-button
blocking
Additional interlocks
FF Electrical interlocks
FF Key lock interlocks
FF Pad locks
Cable compartment
JJ Up to 4 cables per phase
FF Toroidal-core current
transformers ANSI / IEEE
CPG.0-V
FF Plug-in voltage transformer
15
CPG.0 & CPG.1 MV Switchgear for
Single and double busbar panel type GIS system Substation Solutions
CPG.0-F
Single busbar fuse protection panel
It has a three-position switch-disconnector (closed/open/earthing-grounding), including fuse protection. The fuses are
housed in sealed fuse holders, which in turn are inside the switch compartment, reinforcing the level of insulation.
The three-pole opening switch with combined actuation by fuse blow is optionally motorisable.
Applications
Feeder/transformer disconnection, busbar coupling rise and busbar voltage metering.
16
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
Dimensions
Configuration
Panel structure
Internal arc
JJ IAC AFL 25 kA 1 s (IEC)
FF IAC AFLR 25 kA 1 s (IEC)
Gas tank
JJ Fuses combined with the
switch-disconnector
JJ Pressure gauge with
potential-free contact
JJ Voltage presence indicator
FF Auxiliary contact
FF Visual inspection device
Busbar compartment
FF Up to 2500 A – 24 kV
IEC
FF Up to 1250 A – 36 kV CPG.0-F
FF Up to 2250 A – 27 kV
FF Up to 1250 A – 38 kV
FF Current Transformers
FF Voltage Transformers [mm]
Driving mechanism [in]
Three-position disconnector
FF Disconnector motorization
Additional interlocks
FF Electrical interlocks
FF Key lock interlocks
FF Pad locks
Cable compartment
JJ Up to 4 cables per phase
FF Toroidal-core current transformers
FF Plug-in voltage transformer
Low voltage compartment
Panel height
JJ 2425 ANSI / IEEE
CPG.0-F
FF 2245
FF Protection, automation, control
and signalling devices Weight
Configuration
Kg Lbm
<550 <250
17
CPG.0 & CPG.1 MV Switchgear for
Single and double busbar panel type GIS system Substation Solutions
CPG.0-S
Single busbar Disconnector panel
Includes a three-position disconnector without load breaking capacity.
Rated current
1250 / 1600 / 1250 / 1600 /
General busbar Ir [A] 2000 / 2500
1250(*)
2250(**)
1250(*)
250 / 1600 /
Feeder Ir [A] 1250 / 1600 1250
2250
1250
Switch-disconnector Category
Mechanical endurance 2000-M1 1000
Main switch making capacity (peak value) Ima [kA] 63 (50Hz) / 65 (60 Hz) 65
Applications
Feeder/transformer disconnection, busbar coupling rise and busbar voltage metering.
18
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
Dimensions
Configuration
Panel structure
Internal arc
JJ IAC AFL 25 kA 1 s (IEC)
FF IAC AFLR 25 kA 1 s (IEC)
Gas tank
JJ Pressure gauge with
potential-free contact
JJ Voltage presence indicator
FF Auxiliary contact
FF Visual inspection device
Busbar compartment
FF Up to 2500 A – 24 kV
FF Up to 1250 A – 36 kV
FF Up to 2250 A – 27 kV
IEC
FF Up to 1250 A – 38 kV CPG.0-S
FF Current Transformers
FF Voltage Transformers
Driving mechanism
Three-position disconnector [mm]
[in]
FF Disconnector motorization
FF Earthing (grounding) switch
motorization
Additional interlocks
FF Electrical interlocks
FF Key lock interlocks
FF Pad locks
Cable compartment
JJ Up to 4 cables per phase
FF Toroidal-core current
transformers
FF Plug-in voltage transformer
Low voltage compartment
Panel height ANSI / IEEE
JJ 2245 CPG.0-S
FF 2425
FF Protection, automation, control Weight
and signalling devices Configuration
Kg Lbm
<550 <250
19
CPG.0 & CPG.1 MV Switchgear for
Single and double busbar panel type GIS system Substation Solutions
CPG.0-C
Single busbar coupling panel
It includes a vacuum circuit-breaker with two three-position disconnectors in series with it, one upstream and the
other downstream from the circuit-breaker.
These elements are located inside the switch compartments.
Applications
Longitudinal busbar coupling.
20
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
Dimensions
Configuration
Panel structure
Internal arc
JJ IAC AFL 25 kA 1 s (IEC)
Gas tank
JJ Pressure gauge with
potential-free contact
FF Auxiliary contact
Busbar compartment
FF Up to 2500 A – 24 kV
FF Up to 1250 A – 36 kV
FF Up to 2250 A – 27 kV
FF Up to 1250 A – 38 kV
FF Current Transformers
IEC
FF Voltage Transformers CPG.0-C
Driving mechanism
Three-position disconnector
FF Disconnector motorization
Vacuum circuit-breaker
JJ Motor
JJ Tripping coil
JJ Closing col
FF Undervoltage coil
JJ Opening/closing push-button
blocking
Additional interlocks:
FF Electrical interlocks
FF Pad locks
Cable compartment
JJ Lower busbar ANSI / IEEE
FF Toroidal-core current CPG.0-C
transformers
Low voltage compartment
Weight
Panel height Configuration
Kg Lbm
JJ 2245 1)
Up to 38 kV ≤ 1600 A <1300 <591
2)
Up to 27 kV 2000 A <2200 <1000
FF 2425
3)
Up to 24 kV 2500 A
<2400 <1091
FF Protection, automation, control Up to 27 kV 2250 A
and signalling devices
21
CPG.0 & CPG.1 MV Switchgear for
Single and double busbar panel type GIS system Substation Solutions
CPG.0-RB
Single busbar rise panel
Allows the lateral cable feeder incoming or outgoing for communication with the busbar of the general cubicle
assembly and its earthing (grounding).
Rated current
General busbar Ir [A] 2500 1250(*) 2250 (*) 1250 (*)
Applications
Busbar lateral feeder.
22
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
Dimensions
Configuration
Panel structure
Internal arc
JJ IAC AFL 25 kA 1 s (IEC)
FF IAC AFLR 25 kA 1 s (IEC)
Gas tank
JJ Pressure gauge with
potential-free contact
JJ Voltage presence indicator
FF Auxiliary contact
Busbar compartment
FF Up to 2500 A – 24 kV
FF Up to 1250 A – 36 kV
FF Up to 2250 A – 27 kV
FF Up to 1250 A - 38 kV IEC
FF Current Transformers CPG.0-RB
FF Voltage Transformers
Additional interlocks:
FF Electrical interlocks
[mm]
FF Key lock interlocks
[in]
FF Pad locks
Cable compartment
FF Toroidal-core current
transformers
Low voltage compartment
Panel height
JJ 2245
FF 2425
FF Protection, automation, control
and signalling devices
ANSI / IEEE
CPG.0-RB
Weight
Configuration
Kg Lbm
<500 <227
23
CPG.0 & CPG.1 MV Switchgear for
Single and double busbar panel type GIS system Substation Solutions
CPG.1-V
Single (V1) and double (V2) busbar circuit-breaker panel
It includes, in separate compartments, both a circuit-breaker with vacuum breaking technology and an earthing
(grounding)switch in series with it, and also feeder disconnectors.
Switch-disconnector Category
Mechanical endurance 1000-M1 1000
Cycles of operations (Short-circuit making current)- class 5-E3 3
63 / 80 (50 Hz)
Main switch making capacity (peak value) Ima [kA] 65 / 85 (60 Hz)
65
Applications
Main transformer protection, feeder protection, capacitor bank protection, auxiliary service transformer protection,
longitudinal coupling with MV cables.
24
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
Dimensions
Configuration
Panel structure
Internal arc
JJ IAC AFL 31.5 kA 1 s (IEC)
Gas tank
FF Voltage presence indicator
Busbar compartment
JJ Up to 2000 A - 38 kV
FF Current Transformers
FF Voltage Transformers
Driving mechanism
FF Feeder disconnector
motorization
FF Earthing (grounding) switch
motorization
Vacuum circuit-breaker
JJ Motor
IEC
CPG.1-V1 CPG.1-V2
JJ Tripping coil
JJ Closing col
FF Undervoltage coil
[mm]
JJ Opening/closing push-button [in]
blocking
Additional interlocks
FF Electrical
FF Key lock
FF Pad locks
Cable compartment
JJ Up to 4 cables per phase
25
CPG.0 & CPG.1 MV Switchgear for
Single and double busbar panel type GIS system Substation Solutions
CPG.1-F
Single (F1) and double (F2)fuse protection panel
The single busbar variant is equipped with a switchgear compartment with a three-position switch-disconnector
(closed / open / earthing), including fuse protection, whereas the double busbar variant is equipped with another
two separate switchgear compartments with feeder disconnectors.
The fuses are housed inside sealed fuse holders, these are housed inside the switchgear compartment, and
enhanceits insulation level. The combined fuse blow action enables three-pole opening of the switch.
Switch-disconnector Category
Mechanical endurance 1000-M1 1000
Cycles of operations (Short-circuit making current)- class 5-E3 3
Combined switch-relay take-overcurrent
Breaking Imaxacc.TD itransfer >800
Applications
Auxiliary service transformer protection.
26
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
Dimensions
Configuration
Panel structure
Internal arc
JJ IAC AFL 31.5 kA 1 s (IEC)
Gas tank
JJ Fuses combined with the switch-
disconnector
FF Voltage presence indicator
FF Visual inspection device
Busbar compartment
JJ Up to 2000 A – 38 kV
FF Current Transformers
FF Voltage Transformers
Driving mechanism
FF Feeder disconnector
motorization IEC
CPG.1-F1 CPG.1-F2
FF Earthing (grounding) switch
motorization
Additional interlocks
FF Electrical
[mm]
FF Key lock
[in]
FF Pad locks
Cable compartment
JJ Up to 4 cables per phase
FF Toroidal-core current
transformers
FF Plug-in voltage transformer
ANSI / IEEE
CPG.1-F1
Weight
Configuration
Kg Lbm
CPG.1-F1 1000 2425
CPG.1-F2 1300 2866
27
CPG.0 & CPG.1 MV Switchgear for
Single and double busbar panel type GIS system Substation Solutions
CPG.1-S
Single (S1) and double (S2)disconnector panel
It incorporates feeder disconnectors and earthing (grounding)switches, located in separate compartments.
Switch-disconnector Category
Mechanical endurance 1000-M1 1000
Cycles of operations (Short-circuit making current)- class 5-E3 3
Combined switch-relay (ekorRPT) take-overcurrent
Earthing (grounding) Switch IEC 62271-102 IEEE C37.74
Rated short-time withstand current (earthing circuit)
Value tk = 1 s or 3 s Ik [kA] 25/31.5
63 / 80 (50 Hz)
Peak value Ip [kA] 65 / 85 (60 Hz)
65 / 85
63 / 80 (50 Hz)
Main switch making capacity (peak value) Ima [kA] 65 / 85 (60 Hz)
65
Applications
Longitudinal busbar coupling with MV cables.busbar voltage metering with disconnection of the voltage transformers.
28
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
Dimensions
Configuration
Panel structure
Internal arc
JJ IAC AFL 31.5 kA 1 s (IEC)
Gas tank
FF Voltage presence indicator
Busbar compartment
JJ Up to 2000 A – 38 kV
FF Current Transformers
FF Voltage Transformers
Driving mechanism
FF Feeder disconnector
motorization
FF Earthing (grounding) switch
motorization
Additional interlocks
IEC
FF Electrical CPG.1-S1 CPG.1-S2
FF Key lock
FF Pad locks
Cable compartment
JJ CPG.1-S1: Up to 4 cables per [mm]
phase [in]
ANSI / IEEE
CPG.1-S1
Weight
Configuration
Kg Lbm
CPG.1-S1 1000 2425
CPG.1-S2 1200 2645
29
CPG.0 & CPG.1 MV Switchgear for
Single and double busbar panel type GIS system Substation Solutions
CPG.1-C
Longitudinal single (C) and double (CL) busbar coupling panel
Includes the following components for each busbar in separate compartments: A vacuum circuit-breaker and the
earthing (grounding)switches in series with it in a switchgear compartment and two feeder disconnectors in their
corresponding compartments.
Switch-disconnector Category
Mechanical endurance 1000-M1 1000
Cycles of operations (Short-circuit making current)- class 5-E3 3
Combined switch-relay (ekorRPT) take-overcurrent
Earthing (grounding) Switch IEC 62271-102 IEEE C37.74
Rated short-time withstand current (earthing circuit)
Value tk = 1 s or 3 s Ik [kA] 25/31.5
63 / 80 (50 Hz)
Peak value Ip [kA] 65 / 85 (60 Hz)
65 / 85
63 / 80 (50 Hz)
Main switch making capacity (peak value) Ima [kA] 65 / 85 (60 Hz)
65
Applications
Longitudinal busbar coupling.
30
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
Dimensions
Configuration
Panel structure
Internal arc
JJ IAC AFL 31.5 kA 1 s (IEC)
Gas tank
FF Voltage presence indicator
Busbar compartment
JJ Up to 2000 A – 38 kV
FF Current Transformers
FF Voltage Transformers
Driving mechanism
FF Feeder disconnector
motorization
FF Earthing (grounding) switch
motorization
Additional interlocks
FF Electrical
IEC
CPG.1-C
FF Key lock
FF Pad locks
Options
IEC ANSI/IEEE
CPG.1-CL CPG.1-C (M type)
ANSI / IEEE
CPG.1-C
(C type)
Weight
Configuration
Kg Lbm
CPG.1-C
1400 3086
CPG.1-C (type C)
CPG.1-C (type M)
2800 6172
CPG.1-CL
31
CPG.0 & CPG.1 MV Switchgear for
Single and double busbar panel type GIS system Substation Solutions
CPG.1-CT
Transversal busbar coupling panel
Includes the following components in separate switchgearcompartments:
A vacuum circuit-breaker and two earthing(grounding)switches inseries with it in the switchgear compartment, and
feederdisconnectors in its corresponding compartments.
63 / 80 (50 Hz)
Main switch making capacity (peak value) Ima [kA] 65 / 85 (60 Hz)
65
Applications
Transversal busbar coupling.
32
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
Dimensions
Configuration
Panel structure
Internal arc
JJ IAC AFL 31.5 kA 1 s (IEC)
Gas tank
FF Voltage presence indicator
Busbar compartment
JJ Up to 2000 A – 38 kV
FF Current Transformers
FF Voltage Transformers
Driving mechanism
FF Feeder disconnector
motorization
FF Earthing (grounding) switch
motorization
Additional interlocks
FF Electrical IEC
CPG.1-CT
FF Key lock
FF Pad locks
33
CPG.0 & CPG.1 MV Switchgear for
Single and double busbar panel type GIS system Substation Solutions
Each panel includes a voltage Transformers designed by Ormazabal • Busbar compartment and/or cable
presence/absence detector with whose main characteristics are: compartment
permanent light indication and an • Toroidal type
optional free auxiliary contact for
remote display of the corresponding • Encapsulated
indication. • Installed outside the switch
compartment, upstream of the
The indicator, with fixed installation,
medium voltage connectors
has been designed according to
standard IEC 61243-5 and VDE • Protected against environmental
0682 Part 415. conditions
• Simple assembly and free of
Pressure switch
errors during installation (earths)
The gas pressure in CPG.0 panels
Installation:
is tested by means of a temperature-
compensated pressure gauge, with a • Busbar compartment and/or cable
potential-free contact, allowing it to be compartment
used as a remote alarm.
Optionally in CPG.1, pressure
switches for each gas tank can be
installed.
HRC Fuses
Protection against short circuits in the
Medium Voltage network is made by
means of the fuse protection functions.
The fuse holder tubes reach a uniform
CPG.0 temperature all along the tube when
they are placed horizontally inside the
gas tank. When the cover is closed,
they are fully sealed against floods
and external pollution.
Features:
Voltage transformers • Horizontal fuse holders
• Front access
CPG.1 Characteristics:
• Phase-independent compartments
Cable connectors • Plug-in type
• Protected within the gas tank
• Single-phase
Features: • Insulation and sealing against
• Insulated
• For single-core or three core external agents (pollution,
cables. • Shieled temperature changes, adverse
• For dry cable or impregnated • Inductive operation weather conditions, including
cable. • Installed outside the switch floods)
• Shielded compartment • Internal interlocks for a safe
• Protected against environmental access to the fuse holder area
• Elbow
conditions
• Up to 4 screw-in terminals per Please, consult Ormazabal for further
phase (6 for CPG.0 2000 / information about fuse selection
2500 A)
34
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
• Handling methods:
• Lifting: Forklift truck or hand-operated
pallet jack
• Raising: Slings & lifting beams
Operating levers
Fuse protection
• Fuse holder carriage
35
CPG.0 & CPG.1 MV Switchgear for
Single and double busbar panel type GIS system Substation Solutions
For CPG.1
Inside wind turbines
and wind farm
substations
CPG panels can also be installed
inside wind turbines and wind farm
substations.
36
MV Switchgear for CPG.0 & CPG.1
Substation Solutions Single and double busbar panel type GIS system
37
www.ormazabal.com
CA-110-EN-1311