You are on page 1of 86

SEPTEMBER 2020

ASHRAE
JOURNAL THE MAGAZINE OF HVAC&R TECHNOLOGY AND APPLICATIONS ASHRAE.ORG

Optimizing
Chiller Plant
For Office, Laboratory Facility

5 Factors for Boiler Plant Optimization


Load Calculations for Commercial Kitchen

Covering HVAC and COVID-19 | Building Readiness


COVID-19
Plan for SARS-CoV-2
-CoV-2 | IEQ in Cold Climates
REASON
Up to 12%
more efficient.
R-32 systems are up to 12% more efficient
than similar R-410A systems.

T H I S I S J U S T O N E O F 3 2 G R E AT R E A S O N S
T O C H O O S E R - 3 2 R E F R I G E R A N T.
S E E T H E M A L L AT R 3 2 R E A S O N S . C O M .

WITH MORE THAN 100 MILLION UNITS


INSTALLED WORLDWIDE, R-32 IS ENDORSED BY:
CONTENTS
September 2020

FEATURES STANDING COLUMNS


Five Design Factors to Help 60 Engineers Notebook

14
Optimize a Boiler Plant Performance-Based Approach
By Kal Osman; Nicholas Lane To Laboratory Exhaust
Systems
By Nathan Ho, P.E.

Optimizing Boiler Plant 70 Refrigeration Applications


Deeper Into Vacuum
By Andy Pearson, Ph.D., C.Eng.
Filling the Knowledge Gaps:
HVAC and COVID-19 72 IEQ Applications

20
By Ed Light; James Bailey, P.E.; ASHRAE Headquarters:
Reid Lucas; Laurence Lee Building Readiness Plan for
SARS-CoV-2
By Wade H. Conlan, P.E.

HVAC and COVID-19

DEPARTMENTS
Improving IEQ to Reduce 4 Commentary
Transmission of Airborne 6 Industry News

30
Pathogens in Cold Climates 8 Letters
By Stephanie H. Taylor, M.D.; 12 Meetings and Shows
C. Michael Scofield; Patricia T. 76 Special Products
Graef, P.E., 78 InfoCenter
79 Classified Advertising
Cold Climate IEQ
80 Advertisers Index

Calculating Airflow Rates, Submissions: ashraejournal.submittable.com/submit


Archive: technologyportal.ashrae.org
Cooling Loads in Commercial

48
Letters: sfoster@ashrae.org
Kitchens Missing Issue: cservice@ashrae.org
By Iurii A. Tabunshchikov; ASHRAE® Journal (ISSN 0001-2491) PUBLISHED MONTHLY | Copyright 2020 by
ASHRAE, 1791 Tullie Circle N.E., Atlanta, GA 30329. Periodicals
Alexander N. Kolubkov; Marianna postage paid at Atlanta, Georgia, and additional mailing offices.
SUBSCRIPTIONS | $10 per single copy (plus applicable shipping).
M. Brodach; Iurii S. Avakian Subscriptions for members $8 per year, included with annual
dues, not deductible. Nonmember $90 (includes postage in
USA); $90 (includes postage for Canadian); $158 international
Airflow Rates and Cooling Loads (includes air mail). Expiration dates vary for both member and
nonmember subscriptions. Payment (U.S. funds) required
with all orders. CHANGE OF ADDRESS | Requests must be received at
subscription office eight weeks before effective date. Send both
old and new addresses for the change. ASHRAE members may
submit address changes at www.ashrae.org/address. POSTMASTER
Technology Award | Send form 3579 to: ASHRAE Journal, 1791 Tullie Circle N.E.,
Atlanta, GA 30329. Canadian Agreement Number 40037127.
Chiller Plant Optimized Without
PUBLICATION DISCLAIMER | ASHRAE has compiled this publication

52
Capital Expenditures with care, but ASHRAE has not investigated and ASHRAE
expressly disclaims any duty to investigate any product,
By Kelley Whalen; service, process, procedure, design or the like which may
be described herein. The appearance of any technical data,
Jason Brooks, P.E.; Eric Mobley editorial material or advertisement in this publication does not
constitute endorsement, warranty or guarantee by ASHRAE
of any product, service, process, procedure, design or the like.
ASHRAE does not warrant that the information in this publication
is free of errors and ASHRAE does not necessarily agree with
any statement or opinion in this publication. The entire risk of the
Optimizing Chiller Plant use of any information in this publication and its supplement is
assumed by the user.

2 SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL VO LU M E 62, N O.9


the ART of Building
Sustainability
TECHNOLOGY SUPPORTED BY A BROAD
ARRAY OF TECHNICAL SERVICES.
Does your IoT vendor
provide extensive online
technical services?

In addition to a high level of integration between HVAC, lighting, and security systems, sustainability demands
other technological and supporting elements that will endure over the long term. At Reliable Controls, we provide
nine important elements to help you create true building sustainability—now and into the future. One of these
elements demands the use of technology backed by comprehensive technical support services. With more than
30 years in the building controls industry, Reliable Controls is ideally positioned to deliver comprehensive technical
services and expertise in building automation. Whether you’re new to the industry or a skilled professional, Reliable
Controls has the resources to support your goals. Our online portal provides access to operator certification
training, engineering specifications, software manuals, hardware user guides, troubleshooting tools, and more. To
learn more about the art of building sustainability please visit reliablecontrols.com /TABS09A20
COMMENTARY
COMMENTARY
1791 Tullie Circle NE
Atlanta, GA 30329-2305
Phone: 404-636-8400
Fax: 404-321-5478 | www.ashrae.org

DIRECTOR OF ASHRAE PUBLICATIONS & EDUCATION


Mark S. Owen Always Working Toward Best Results
EDITORIAL
Editor Optimizing systems helps achieve the best results based
Sarah Foster
sfoster@ashrae.org on the conditions within which the system is operating
Managing Editor and criteria prioritized by stakeholders. A technical
Mary Kate McGowan feature (page 14) tackles optimizing a new condensing
mmcgowan@ashrae.org
boiler plant.
Assistant Managing Editor
Jeri Alger However, efficiency gains also can be realized by opti-
jalger@ashrae.org mizing existing equipment and controls. An article on page 52 dis-
Associate Editor cusses a project in Alabama where modifications to a chiller plant real-
Rebecca Matyasovski
rmatyasovski@ashrae.org ized huge savings in energy costs without any capital expenditures.
Associate Editor
Tani Palefski AS WITH OPTIMIZING SYSTEMS, building professionals need to be
tpalefski@ashrae.org
able to get results under the conditions we are all operating under.
Associate Editor
Courtney Payne “Filling the Knowledge Gaps: HVAC and COVID-19” (page 20) reviews
cpayne@ashrae.org recent research to give engineers the most up-to-date knowledge
PUBLISHING SERVICES
Publishing Services Manager needed for helping to make difficult decisions during the pandemic.
David Soltis An article that was being written just as the pandemic began is
Production “Improving IEQ to Reduce Transmission of Airborne Pathogens in Cold
Jayne Jackson
ADVERTISING
Climates” (page 30). The authors reworked it to reflect the challenges
Associate Publisher, of the COVID-19 pandemic.
ASHRAE Media Advertising
Greg Martin As I write this, COVID-19 infection rates are still high in many places.
gmartin@ashrae.org ASHRAE staff are working remotely and in the office on a staggered
Senior Coordinator—Advertising schedule as we prepare for moving to ASHRAE’s new headquarters
Production and Operations
Vanessa Johnson in October. “ASHRAE Headquarters: Building Readiness Plan for
vjohnson@ashrae.org SARS-CoV-2” (page 72) discusses the choices ASHRAE made for its own
Coordinator—Circulation Development building using guidance from ASHRAE’s Epidemic Task Force (ETF),
Austin Brafford
abrafford@ashrae.org standards, guidelines and more.
ASHRAE OFFICERS
President
Charles E. Gulledge III, P.E. THE ETF HAS UPDATED its “Building Readiness” guide (tinyurl.
President-Elect com/y5r92ohs) and continues its work to provide the best guidance
Michael Schwedler, P.E. and ASHRAE resources to building professionals. Previous ASHRAE
Treasurer Journal articles that discuss COVID-19 are available under Resources at
Farooq Mehboob, P.E.
ashrae.org/covid19.
Vice Presidents
Donald L. Brandt
K. William Dean, P.Eng. THANK YOU TO EVERYONE who has taken the time to fill out the
Malcolm Dennis Knight, P.E.
William F. McQuade, P.E. ASHRAE Journal surveys. It’s a great tool for letting us know which
Tim McGinn, P.E. articles and columns you find the most helpful. September’s survey is
Secretary & Executive Vice President located here: https://bit.ly/3k9ecVE.
Jeff H. Littleton
POLICY GROUP
2020 – 21 Chair Sarah Foster, ASHRAE Journal Editor
Publications Committee
Hugh D. McMillan III, P.E.
Washington Office
washdc@ashrae.org
Mission Statement: ASHRAE Journal reviews current HVAC&R technology of broad interest through publication of application- CELEBRATING
oriented articles. ASHRAE Journal’s editorial content ranges from back-to-basics features to reviews of emerging technologies,
covering the entire spectrum of professional interest from design and construction practices to commissioning and the service life 125
YEARS
of HVAC&R environmental systems.

4 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


Belimo
Butterfly Valves

Commissioning at your Fingertips


Easily commission and troubleshoot actuators with your smartphone.
NFC allows assisted configuration by a smartphone, even if the actuator
is not connected to power.

CESIM. Small Devices, Big Impact.


Comfort | Energy Efficiency | Safety | Installation | Maintenance
INDUSTRY NEWS

Epidemic Task Force Update


ETF Updates Building Readiness Guidance
ATLANTA—The ASHRAE Epidemic Task ing Conditions in Place (ECiP) and ments to a system’s ability to
Force’s updated Building Readi- Post-Epidemic Conditions in Place mitigate virus transmission.
ness guidance provides practical (P-ECiP); A specific building’s actual
information and checklists for • Increased ventilation and filtra- conditions will vary, and the
how buildings should operate tion; and adjustments that should be made
during and after the pandemic • Building exhaust air re-entrain- depend on factors such as local
and how to practically check op- ment. climate, system complexity and
erations. The guidance addresses: The guidance also includes use, occupancy and activities that
• Energy recovery ventilation information on tactical commis- happen in and around the build-
systems operation; sioning and systems analysis to ing.
• Building readiness modes of develop a Building Readiness Plan Download the guidance: tinyurl.
operation, such as Epidemic Operat- and how to make overall improve- com/buildingreadinessguidance.

ETF Releases School Reopening Guidance


ATLANTA—As some schools prepare to reopen while designers plan how to improve indoor air
others are occupied for the fall academic year, the quality and slow the transmission of viruses
ASHRAE Epidemic Task Force developed HVAC via HVAC systems. Download the guidance:
systems operation guidance to help mitigate the air- tinyurl.com/schoolreopeninguidance.
borne transmission of SARS-CoV-2. The guidance:
• Includes checklists such as starting up HVAC sys- Explore ASHRAE COVID-19 Resources
tems prior to occupancy and checks and verifications to ATLANTA—ASHRAE’s COVID-19 response resources web-
maintain during the academic year. page provides guidance from the Epidemic Task Force
• Addresses determining building readiness, filtra- for health-care facilities, schools and other building
tion upgrades, facility design recommendations and types. The guidance includes recommended strategies
controlling infection outbreak in school facilities. and specific “how-to” information for various chal-
A section of the guidance is designed to help lenges. Visit the page: ashrae.org/COVID19.

Industry Roundup
EPA Updates Pandemic ply for certification while comply- of their state-of-the-art, open-
Benchmarking, ing with medical experts’ recom- source, whole-building energy
Certification Guidance mendations for reducing the risk modeling tools: the EnergyPlus™
WASHINGTON, D.C.—The U.S. Environ- of exposure to the coronavirus. engine and the OpenStudio™
mental Protection Agency (EPA) Source: EPA software development kit and
has updated its guidance on graphical application. The current
benchmarking and applying for DOE Releases Updated version of the EnergyPlus engine
2020 Energy Star certification for Energy Modeling Tools includes refactored implementa-
commercial buildings affected WASHINGTON, D.C.—The U.S. Department tions of all coils and plant compo-
by the COVID-19 pandemic. The of Energy and its National Labora- nents and fixes for 76 known issues
guidance allows for people to ap- tories released updated versions and bugs. Source: U.S. DOE

6 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


The Authority in
LIFE SAFETY DAMPERS
Pottorff Provides the Perfect Solution for Any Condition!

Our Newest Release For


Corrosive and High Humidity
Environments …
STAINLESS STEEL
UL Class 1 Leakage Rated
Airfoil Blade Fire/Smoke Damper

Our FSD-151-SS features 304 stainless steel airfoil blades


and is perfect for mildly corrosive environments or areas
of high humidity. The airfoil design offers excellent air
performance. Approved for system velocities up to 2,000
fpm and system pressures of 4" w.g. at 350° F.

www.pottorff.com
LETTERS

Electrification, For example, his data about a COP This responsibility would be zero
of 5.5 seems quite impressive in only if the COP of the heat pump
Heat Pumps, and terms of the first law. But looking was 35 (0.95/0.027), which is practi-
Thermal Storage at the same example in terms of cally impossible. Conversely speak-
Referring to “Electrification, the second law, we see a different ing, the exergy-based COP (COPEX)
Heat Pumps and Thermal Storage” picture: electric power is a “high- of the heat pump is 5.5 × 0.027/0.95,
by Mark M. MacCracken, P.E., in quality” energy source of which which is much less than one
the July 2020 ASHRAE Journal, it is 95% may be used in useful works (COPEX = 0.156).
agreeable that electrification with (0.95 kWh/kWh). Of course, the author is absolutely
renewables is viable for sustained Compare such a high quality of right in looking for ways to save
decarbonization. supplied energy with the quality energy in buildings, but it would
However, the second law of ther- of temperature elevation process probably be better to compare
modynamics, which we often ignore from 26.7°C (299.85K, 80°F) to 35°C CO2 emissions savings of storing
in practice, tells us that tracing the (308.15K, 95°F) in their design case energy in the ice tanks with the
downstream path along which and where the chiller acts as a heat pump COPEX value of the heating pro-
how the so-called green electricity in winter for morning warm-up. cess by the chillers. The second
is used is as important as where and According to the ideal law may have also guided us to
how it is generated. The second law Carnot cycle, the energy qual- another option, which is using a
also tells us that once electric power ity of this temperature jump trigeneration system even if it runs
is generated from renewables (or is only 0.027 kWh/kWh on natural gas because a typical
not), it is important to keep using it (1 − 299.85K/308.15K). This means trigeneration system destroys only
as electricity as far as possible down- that the supplied unit exergy of about 0.15 kWh/kWh (therefore,
stream along the power demand 0.95 kWh/kWh is destroyed by 0.31 × 0.15 = 0.046 kg CO2/kWh)
chain. 0.92 kWh/kWh. and provides on-site heat, electric-
The key is to question whether Moreover, until the entire globe is ity (without transmission losses)
any particular power demand has electrified by renewables, an indi- and cold together using absorption
options other than electricity. For rect fossil fuel-equivalent carbon chillers.
example, comfort cooling with elec- footprint will always exist in pro- Thermal storage (but not in the
trically driven chillers has options portion to the destroyed exergy. form of ice) is indispensable in this
like absorption and or adsorption This footprint is expressed as 0.31 alternative, too. The total CO2 emis-
cooling with waste heat, but electric times the destroyed exergy, as refer- sions responsibility will include
lighting and electric public trans- enced in the natural gas boiler data the exhaust emissions of about
port do not. Indeed, industry and given in the article (the net thermal 0.307 kg CO2/kWh at a partial ther-
transport above about 400°C have efficiency is 0.75), where natural mal efficiency of 0.65, and the total
no option other than electricity. gas has about 0.2 kg CO2/kWh in CO2 emissions responsibility will
Therefore, electric power should be combustion and has unit exergy be 0.353 kg CO2/kWh. This respon-
directed first to the demand points of 0.87 kWh/kWh. This calcula- sibility rate is not too far from the
that have no option except electricity. tion comes from 0.2/(0.75 × 0.87) design case presented in the article,
For example, in the Netherlands and means that the heat pump will even if we ignore the ice-making/
state trains have the privilege, by be responsible for additional CO2 ice-melting cycle losses, grid power
all means, to run on green electric- emissions of 0.285 kW = h/kWh losses, etc. If all these are included,
ity generated from wind energy (0.31 × 0.92) even though the elec- these two cases will become even in
because they do not have any other tricity comes from renewables, terms of decarbonization.
option. In this respect, the author because the electricity is used only By the way, this letter is not
did a fine eye-opening job in his one step away from the plug by the intended to criticize the design of
article. Yet revisiting the article heat pump and then converted to a the authors, but only to underscore
seems necessary. heat of very low quality. that the second law is an important

8 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


LETTERS

tool, even in terms of the simple of energy, namely fossil fuels, of Makeshift
Carnot cycle equation, in present-
ing and comparing other feasible
which we have a limited supply
and that have sizable long-term
Negative Pressure
design alternatives beyond boilers consequences. However, the renew- Patient Rooms
and chillers. able sources of energy supplied ASHRAE’s efforts and publications
Birol Kilkis, Ph.D., Fellow ASHRAE, Cankaya, Turkey
to the Earth each day is massively regarding the response to COVID-19
beyond our needs, limited only are exactly what membership needs
The Author Responds by our ability to collect and store ASHRAE to do.
Thank for your kind words on it. If we look at the exergy of the As a practicing Florida engineer,
the article and for sharing your renewable sources, much of the we have an eleventh lesson learned
perspective on the exergy of the sys- incoming energy is radiated back to following the 10 in the July 2020
tem. Of all the questions I thought space which, as I understand it, is ASHRAE Journal article “Makeshift
the article might generate, solving an incalculable loss of exergy, or at Negative Pressure Patient Rooms
the age-old question of exergy vs. least incalculable for me. in Response to COVID-19” by Frank
energy was not one I expected. So the realization I come to is, Shadpour, P.E., Fellow ASHRAE, and
You obviously know the topic well, in respect to electrification and Stefanie Johnson.
so I won’t delve into the accuracy of renewables, exergy may not be as Stated simply, existing facili-
the calculations. important a metric, since it will ties quickly run out of conditioned
Long ago I let go of the skills for all be either used by nature or makeup air for added exhaust to
those calculations, about the time wasted away. Fossil fuels are a finite transform positive pressure ICU
I was taught 1 Btu (1 match com- resource, the creation of which took rooms into negative pressure rooms.
pletely burned as per my article) millions of years to form and con- In California outside makeup air
could lift a 1 lb weight 778 ft into the centrate into a stored form. Their has “no” humidity, and the addition
air. I still can’t comprehend that is unique “high level” and energy den- of exhaust may create a negative
the equivalent amount of energy, sity will surely be needed for things pressure building, but without the
but I accept it as fact. like aviation, for which we have associated high humidity problems
To address your observation, first yet to invent a viable carbon-free we see in more humid regions. All
let me say that the entire premise of solution. would agree that 100% exhaust is
the article was based on the goal of True, there indeed are other appli- the better solution, but when the
“electrification” and an efficient car- cations of using the “high level” of building lacks capacity for addi-
bon emissions-free building, with electrical energy we collect, and for tional makeup air, HEPA recircula-
all energy coming from carbon-free that I say let’s collect more. But to tion is a viable option allowed by the
sources. So from that respect, your preclude it from being used in a way guidelines and CDC.
solution of a much higher exergy that satisfies the need to remove Additionally, HEPA units can be in
system using combustion at the site carbon-emitting combustion from short supply and other than an Office
is a nonstarter. Besides not includ- our buildings, based on the “loss” of Statewide Health and Planning
ing all the upstream exergy losses of exergy that will be lost anyway, and Development (OSHPD) alter-
of getting and delivering that fossil doesn’t seem prudent. nate, codes do not require HEPA fil-
fuel to the site, you are ignoring the Yes, if the grid is not all carbon tration of AII room exhaust.
downstream implications of the free, there is some shifting in where In light of this, it would be of
emitted CO2. emissions occur, but the grid is interested to learn what discussion
However, your analysis highlights likely to get to low or very low car- the authors’ firm had with facility
an interesting point in the age-old bon before all buildings and cer- infection control risk assessment on
debate. Your explanation correctly tainly before transportation. Thanks the recirculation option using HEPA
points out the first and second again for your comments. filtration for temporary negative
laws of thermodynamics and then Mark MacCracken, P.E., Life Member ASHRAE,
pressure rooms.
goes on to apply it to a certain type Miami Beach, Fla. Grady Burch, P.E., Member ASHRAE, Oakland, Fla.

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 9


LETTERS

The Author Responds systems in most non-medical build- are a hazardous combination. Are
One of the facilities we worked ings play only a small role in infec- ventilation systems operating properly
with requested the recirculation of tious disease transmission, includ- and capable of providing a healthy
HEPA-filtered air from the COVID-19 ing COVID-19.” The column’s HVAC indoor environment? Verifying that
negative pressure rooms back to the recommendations have also been the HVAC system is operating as
hospital. We contacted state officials made by the CDC, ASHRAE and designed is a necessary first step.
and the hospital’s infection control OSHA and include better filtering, Michael A. Miller, P.E., Fellow/Life Member ASHRAE,
West Monroe, N.Y.
officer to obtain approval. Both par- longer operating hours and cleaning
ties did not recommend it. HVAC equipment. The Author Responds
The guidance from CDC, ASHRAE What is missing in most of the Michael, thank you for making
and WHO generally support each published materials addressing these important points, which I
other; however, the details regard- COVID-19 are evaluations of the agree with. Since I wrote the col-
ing COVID-19 remain in flux. How it existing HVAC systems. It may umn, several well-researched
spreads and proper methods of miti- be implied, but this step is sorely reports have been released demon-
gation are still being explored by sci- missing. The guidance should also strating COVID-19 transmission in
entists and engineers alike. Therefore, recommend verification that HVAC the absence of what I consider a mini-
as mentioned in the article, it is criti- systems have been properly main- mally effective HVAC system.
cal to perform any work in conjunc- tained and that actual operation I still believe the HVAC system
tion with the authorities having juris- meets the original design intent. usually plays a small role, provided
diction and to obtain prior approval. In many cases I have found that there really is one in place that is
We understand that within a cli- the operation of HVAC systems properly maintained and operated,
mate such as Southern California, is determined by personnel with with amounts of outdoor air, filtra-
high humidity is not generally a limited knowledge of the system tion and room air distribution meet-
problem. In this scenario, we closely design. Often, the staff technician ing a code or standard for the space
followed the California OSHPD becomes the decision maker to occupancy. My column, ASHRAE’s
PIN-4 and coordinated with infec- achieve energy savings and makes Epidemic Task Force (ETF) and other
tion control staff to implement the the changes to HVAC operation. published guidance from authori-
steps as included in the case study. Intervention by building occupants ties, as you state, make further HVAC
We also carefully reviewed the avail- has little effect where energy goals recommendations. Avoiding dense
able capacities within the systems, are treated with greater interest and occupancy, using social distancing
including makeup air and the effect urgency than occupant comfort, and masks remain critical.
on adjacent areas. We suggest you do health and productivity. Evaluating and correcting existing
the same and follow the guidelines It is not appropriate for HVAC systems, as you emphasize, is essen-
established by authorities having technicians to unilaterally make tial, especially for buildings restarting
jurisdiction in the state of Florida. changes to the HVAC system without after a period of shutdown. Saving
Frank Shadpour, P.E., Fellow ASHRAE, and Stefanie a review by a competent HVAC engi- energy is a lower priority than sav-
Johnson, San Diego
neer, preferably one with operations ing lives and good health at any time,
experience. There is a true need for and especially during the pandemic.
Guidance for an inspection process for HVAC ven- Reopening guidance should prioritize
tilation operations. The ill effects of equipment checks and verification of
COVID-19 Building modifying HVAC operation on peo- system performance.
Operations ple is menacing and hard to detect. Details to check include air deliv-
The May 2020 ASHRAE Journal It would be interesting to know if ery per person and correcting rooms
column “Guidance for Building other HVAC engineers have encoun- that receive minimal or no airflow.
Operations During the COVID- tered similar circumstances. The latter happens due to mistakes
19 Pandemic” by Lawrence J. Now we have the crisis of COVID-19. such as moving or adding walls
Schoen, P.E., begins, “The HVAC Locations with poor IAQ plus a virus without HVAC system changes, fire

10 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


LETTERS

dampers closed or other dampers


improperly adjusted, thermostats
set to “fan auto,” VAV box mini-
mums too low and other operational
problems.
No magic bullets exist. They do not
substitute for outdoor air dilution
ventilation, high MERV particle filtra-
tion and air distribution to all rooms
during all operating hours, including
during cleaning.
Proper system performance and
good IAQ don’t happen automatically,
and I believe it requires a partnership
and collaboration among engineers,
building operations personnel, build-
ing management and occupants.
Lawrence J. Schoen, P.E., Fellow/Life Member ASHRAE,
Columbia, Md.
column, “Designing HVAC Systems and the updated column can be
for School Gyms,” the points were downloaded here in ASHRAE’s
Errata shifted in Figure 2 during produc- Technology Portal (free for mem-
In August’s Engineer’s Notebook tion. The corrected figure is above, bers): https://tinyurl.com/y4ytzf3a.

Effective healthy air solution gets a BOOST


Our easy-to-install 100 CFM Intelli-Balance Energy
Recovery Ventilator is now even more effective.
When large gatherings in the home require greater
VOCs ventilation, the new occupant-controllable BOOST
Viruses/Bacteria

Dust/Allergens
function increases airflow on demand. With
Moisture
the flip of a switch, two ECM motors with Smart
Flow™ technology BOOST output power to provide
healthier indoor environments.

Give your homes and your sales a healthy boost.


Visit your local HVAC distributor or visit
www.intellibalance.com to learn more.

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 11


MEETINGS AND SHOWS
Because of the impact that COVID-19 is having on conferences, please check the conference’s website for the most up-to-date information.

OCTOBER
(Virtual) I2SL Annual Conference, Oct. 5–7, Chica-
IIAR Natural Refrigeration Conference & CALLS FOR PAPERS
Heavy Equipment Expo, March 28–31, Palm
go. Contact the International Institute for Sustain- Springs, Calif. Contact the International Insti- ASHRAE JOURNAL
able Laboratories at 703-841-5484, info@i2sl.org or tute of Ammonia Refrigeration at 703-312-4200, ASHRAE Journal seeks applications arti-
www.i2sl.org/conference/2020/index.html. annualmeeting@iiar.org or www.iiar.org. cles of 3,000 or fewer words. Submissions
(Virtual) SMACNA EDGE Conference, Oct. 13–15, are subject to peer reviews and cannot
Austin, Texas. Contact the Sheet Metal & Air Con- APRIL have been published previously. Submit
ditioning Contractors Association at 703-803- CxEnergy, April 20–23, Dallas/Ft. Worth, Texas.
Contact Anna Kosova, event manager, at 202-737- abstracts to https://ashraejournal.
2980, info@smacna.org or www.smacna.org/
annualconvention. 7775, Anna@Commissioning.org, or https://www. submittable.com/submit.
cxenergy.com. SCIENCE AND TECHNOLOGY
(Virtual) Solar Power International, Oct. 21–22,
Las Vegas. Contact organizers at customerservice@ MAY FOR THE BUILT ENVIRONMENT
sets.solar or www.solarpowerinternational.com. Purdue Conferences on Compressor Engi- ASHRAE’s Science and Technology for the
(Virtual) RETA Conference, Oct. 27–29, Orlando, neering, Refrigeration, Air-Conditioning, and Built Environment seeks papers on origi-
Fla. Contact the Refrigerating Engineers and Tech- High Performance Buildings, May 23–27, West nal, completed research not previously
nicians Association at 541-497-2955, info@reta.com Lafeyette, Ind. Contact Brian Barrett at 765-494- published. Papers must discuss how the
or www.reta.com. 6078, barret71@purdue.edu or https://tinyurl.com/ research contributes to technology. Pa-
Purdue2020.
NOVEMBER pers should be about 6,000 words. Ab-
(Cancelled) NAFA Annual Convention, Nov. 3–5, JUNE stracts and papers should be submitted
Clearwater, Fla. Contact the National Air Filtration THERMAG IX International Conference on Ca- on Manuscript Central at www.ashrae.
Association at 608-310-7542, nafa@nafahq.org or loric Cooling, June 6–10. College Park, Md. En- org/manuscriptcentral. Contact Jeffrey
www.nafahq.org. dorsed by ASHRAE. Contact organizers at https:// D. Spitler, Ph.D, P.E., at spitler@okstate.
(Virtual) ABX, Nov. 4–5, Boston. Contact organiz- ceee.umd.edu/events/thermag-ix. edu.
ers at 972-536-6444, info@abexpo.com or www.
abexpo.com. AUGUST ASHRAE TECHNICAL, CONFERENCE OR
Ventilation 2021: 13th International Industrial TOPICAL CONFERENCE PAPERS:
(Virtual) Greenbuild, Nov. 4–7, San Diego, Calif. Ventilation Conference for Contaminant Con-
Contact organizers at 866-815-9824, info@
For more information, contact
trol, Aug. 15–18, Toronto, Canada. Contact ASHRAE
greenbuildexpo.com or www.greenbuildexpo.com. hblauridson@ashrae.org or tel: 678-539-
at 800-527-4723, meetings@ashrae.org or www.
ashrae.org/ventilation2021. 1121.
(Virtual) CTBUH 2020, Nov. 17. Contact the
Council on Tall Buildings and Urban Habitat at
312-283-5645, info@ctbuh.org or https://2020. OCTOBER IEA Heat Pump Conference, Sept. 21–24, Jeju Is-
ctbuhconference.com. ACEEE National Conference on Energy Efficien- land, South Korea. Endorsed by ASHRAE. Con-
cy as a Resource, Oct. 18–20, Philadelphia. Con- tact Phetradico Communication and Publishing at
DECEMBER tact the American Council for an Energy-Efficient info@heatpumpsnl.com or http://hpc2020.org.
HARDI Annual Conference, Dec. 5–8, Atlanta. Economy at 202-507-4000 or https://www.aceee.
Contact the Heating, Air-conditioning, & Refrig- org/2021-eer-conference. OCTOBER
eration Distributors International at 614-345-4328, (Virtual) Fourth International Conference on Ef-
ficient Building Design, Oct. 1–2, Beirut, Leba-
hardimail@hardinet.org or www.hardinet.org. OUTSIDE NORTH AMERICA non. Contact ASHRAE at 800-527-4723, meetings@
FEBRUARY ashrae.org or www.ashrae.org/Beirut.
2021
FILTECH 2021, Feb. 23–25, Cologne, Germany BuildSim Nordic, Oct. 13–14, Oslo, Norway. En-
JANUARY Contact organizers at 49 (0)2132 935760, info@ dorsed by ASHRAE. Contact Matthias Hassse
ASHRAE Winter Conference, Jan 23–27, Chica- filtech.de or https://filtech.de. at matthias.haase@sintef.no or http://www.
go. Contact ASHRAE at 800-527-4723, meetings@ ACREX India, Feb. 25–27, Bangalore, India. Con- ibpsa-nordic.org.
ashrae.org or www.ashrae.org/chicago. tact organizers at (011) 41635655, info@ishraehq.in Chillventa, Oct. 13–15, Nuremberg, Germa-
AHR Expo, Jan. 25–27, Chicago. Cosponsored by or www.acrex.in. ny. Contact organizers at +49 9 11 86 06-49 06 or
ASHRAE. Contact the International Exposition https://www.chillventa.de/en.
Company at 203-221-9232, info@ahrexpo.com or SEPTEMBER
PLEA Conference, Sept. 1–3, A Coruña, Spain. European Heat Pump Summit, Oct. 26–27,
www.ahrexpo.com.
Contact the Passive and Low Energy Architec- Nuremberg, Germany. Contact organizers at www.
hp-summit.de/en.
FEBRUARY ture Association at info@plea-arch.org or www.
IAQA Annual Meeting & Expo, Feb. 17–19, Austin, plea2020.org. 15th Conference on Advanced Building Skins,
Texas. Contact the Indoor Air Quality Association at Oct. 26–27, Bern, Switzerland. Contact organiz-
Mostra Convegno Expocomfort, Sept. 8–11, Milan,
844-802-4103, info@iaqa.org or www.iaqa.org. ers at 49 89 20000-4161, info@abs.green or https://
Italy. Contact Organizers at +39 02 4351 70.1, info.
abs.green.
mce@reedexpo.it or www.mcexpocomfort.it/en/
MARCH
Home.
ACEEE Hot Water Forum, March 2–4, San Diego. NOVEMBER
Contact the American Council for an Energy-Ef- CIBSE ASHRAE Technical Symposium, Sept. Indoor Air 2020, Nov. 1–5, Seoul, Korea. En-
ficient Economy at 202-507-4000 or www.aceee. 14–15, Glasgow, Scotland. Contact the Char- dorsed by ASHRAE. Contact organizers at +82-2-
org/2021-hot-water-forum. tered Institution of Building Services Engineers 566-5950, 6031, info@indoorair2020.org or http://
at symposium@cibse.org or https://cibse.org/ indoorair2020.org/.
2021 ASHRAE Virtual Design and Construc-
tion Conference, March 8–10, Orlando. Con- symposium.
Outlook 2020, Nov. 8–10, Sydney, Australia. En-
tact ASHRAE at 800-527-4723, meetings@ IAQ 2020: Indoor Environmental Quality Perfor- dorsed by ASHRAE. Contact the Australian Insti-
ashrae.org or www.ashrae.org/conferences/ mance Approaches, Sept. 13–15, Athens, Greece. tute of Refrigeration Air Conditioning and Heating
topical-conferences/2021-virtual-design-and- Contact ASHRAE at 800-527-4723, meetings@ (AIRAH) at 03 8623 3000, conferences@airah.org.
construction-conference. ashrae.org or www.ashrae.org/IAQ2020. au or www.airah.org.au/Outlook2020.

12 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


Hurst announces AIA partnership for Online
Specifications Tool
Hurst has just added to its list of accomplishments with the addition of a Fire-tube Boilers
Specifications Section in the nation’s top industry specifications system, AIA Product
MasterSpec®. Adding this tool to our arsenal of online specification capabilities enables
architects and engineers all over the world to access, evaluate and specify our products
easily, and save valuable time. Subscribers to MasterSpec® can pick and choose the Basis
of Design content and documentation needed for their project and accelerate the process.
Hurst Boiler on MasterSpec®
In order to help designers with a specification description that fully explains our products
and how they should be installed, among other details, Hurst has included complete
product specification entries encompassing a broad spectrum of our Fire-tube Boiler
Product Line. The Product MasterSpec® section, 235239 Fire-Tube Boilers, will now
help designers quickly add necessary descriptions, specs and easily access CAD files and
PDF drawings when specifying Hurst’s products, providing them with a tool that saves
them time and money.
ers more than 950 copyrighted sections, which allows designers,
architects, and engineers to select expertly written specification content for thousands of
products without having to waste time writing detailed explanations that already exist.
For more information about
Hurst Boiler’s new specification section on MasterSpec® go here:
https://www.hurstboiler.com/boilers/boiler_auxiliary_equipment/masterspec

HURST
TECHNICAL FEATURE

Five Design Factors


To Help Optimize
A Boiler Plant
BY KAL OSMAN; NICHOLAS LANE, ASSOCIATE MEMBER ASHRAE

When designing boiler plants for today’s facilities, engineers need heat and hot water
solutions that save installation time, lower construction costs and deliver superior
performance to save energy and increase return on investment (ROI). The best solu-
tions to satisfy these parameters are systems with the highest efficiencies and smallest
footprints.
Condensing boilers are one piece of this design puzzle. (54°C) or lower when the exhaust O2 is approximately
They match output to the building load under all cir- 5%. If the O2 is higher, the exhaust condensing dew
cumstances to improve plant efficiency by eliminating point will be lower, requiring lower exhaust and return
many of the temperature and flow requirements asso- water temperatures to achieve the same condensing
ciated with non-condensing units. They are normally ability.
equipped with a modulating blower, modulating gas Other considerations affect boiler plant efficiency.
valve and mesh burner capable of firing at very low Engineers need to consider five important factors to
rates. In addition, these boilers are generally made reap the greatest ROI:
from materials that can withstand the corrosive nature • Design for plant function;
of exhaust gas condensate associated with low return • Piping design;
water temperatures, which significantly improves con- • Boiler selection;
densing boiler efficiency (Figure 1).1 • Boiler controller; and
These boilers rely on proper air/fuel mixture, a highly • Remote access.
efficient heat exchanger and low oxygen content in the
exhaust to increase the condensing dew point of the Design for Plant Function
exhaust gases.2 Thus, the boiler can condense at 130°F Plant designs can range from space heating only to

Kal Osman is director of product management (boilers) at AERCO. Nicholas Lane is a systems engineer at AERCO.

14 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


TECHNICAL FEATURE

systems with multiple functionality, such as FIGURE 1 Thermal efficiency of a condensing boiler at different firing rates at 5% O2.
indirect hot water (DHW), reheat, etc. For com- 100
bination plants where there will be multiple 99 Boiler Firing Rate
98
temperature setpoints, three design options are 97
100%
5% O2 5%
available: 96
95

Efficiency (%)
94
Temperature Priority 93
5% O2
Temperature priority designs (Figure 2) allow 92
91
the temperature to be raised to satisfy the needs 90
of the higher of the two temperatures. There are 89 15% O2 9% O2 5% O2
two notable disadvantages—one side will sacri- 88
87
fice its temperature to satisfy the other (thereby 86
reducing comfort) and overall plant efficiency 85
will decrease. Even if additional valves and 70 80 90 100 110 120 130 140 150 160 170
Return Water Temperature with 20 Degree Rise (°F)
controls are used to improve temperature con-
trol, overall plant efficiency is lowered because
FIGURE 2 Combination plant application with single setpoint temperature control.
the whole system supply and return temperatures are
Boiler Pump System Pump System Supply
increased.

Two Independent Plants


Another option is to have two independent plants,
Four-Port
each with its own boilers, pumps, controls and piping. Buffer
This approach requires a larger plant size and brings Tank
additional learning curve requirements. Furthermore,
if N + 1 redundancy is desired, an additional boiler is Boiler Indirect Water Heater
necessary for both plants, increasing major equipment
System Return
costs.

Single Plant with Smart Controller This design adds a layer of security, as well. For
The most efficient approach is one plant with a example, if the DHW boiler cannot meet its load, the
smart controller that can meet temperature and load controller will direct the swing valves to divert its
requirements without the large oversizing associated designated boilers from space heating to DHW. As per
with two independent plants and dedicated controls. ASHRAE, it is assumed that both space heating and
It also significantly improves the overall plant effi- DHW peak loads may not happen concurrently.3 This
ciency without sacrificing comfort and temperature offers a major benefit in reducing the number of boil-
control. ers required to meet plant peak load, shrinking the
What makes all this possible is the swing boiler con- footprint.
cept, which allows certain boilers to be assigned for Another benefit is that the boiler system condenses
space heating while others are for DHW. In normal oper- more because the high and low temperature supply
ation, each boiler is equipped with its own integrated are separated. Models with dual returns can lever-
controller. The integrated controller of the master/ age this by allowing boilers to condense significantly
manager boiler manages all the slave/client boilers and more when the lower temperature return water is
swing valves. This controller is mounted on the front of fed into a special inlet designed to reduce flue gas
the boiler and manages all the boilers’ electronic inputs temperatures further. When combined with a low-
and outputs, allowing boilers with swing valves to be mass boiler and its faster adaptation to plant load
easily switched from space heating to DHW or vice versa, changes, the footprint of the plant becomes even
depending on load requirements. more compact.

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 15


TECHNICAL FEATURE

Piping Design FIGURE 3 Piping design concepts.


Primary-secondary piping has been used much lon- Variable Primary Primary Secondary
ger, as it was developed to help protect non-condensing
boilers from thermal shock and condensation. Initially, Pump Pump
both primary and secondary loops had fixed speed
pumps. Through the years, variable speed pumps were
Pump
introduced into the system loop. Though this improved
system efficiency, its full potential was not realized
because the difference in flow between the two loops Coil Coil
under low loads caused reverse flow in the connecting
common pipe, decoupling the two loops. The result was
a short-circuiting boiler loop that reduced plant supply
and return DT temperature control and was slower to
respond to load changes. should require half the flow. That in turn, based on the
Variable-primary piping (Figure 3) leverages the affinity laws, equates to reducing the pump energy use.
abilities of condensing boilers and ECM/variable speed
pumps to modulate to meet the system load through Boiler Selection
flow reduction in boilers. System DT is improved, which Plant square footage plays a role in the type of boiler
in turn reduces return water temperature to improve selected. Most condensing fire-tube boilers are low-
boiler efficiency and lower pumping electrical energy. mass and have smaller footprints, making it easier to fit
In variable-primary piping, engineers design a bypass through doors, stairs and elevators. If width is too large
line between the supply and return before the boilers to or height is taller than a door or an elevator, walls may
help improve whole-building efficiency. This allows the need to be demolished and rebuilt and/or cranes may be
pump to flow some of the building return to mix with needed, adding installation time and cost.
the boiler supply back to the building. In these cases, the Turndown is another criterion. Smaller ratios produce
boiler plant will be running at low firing rates, and the short cycling at low-load conditions, which are common
flow through the plant will be very low. This allows the in mild weather. These “shoulder months” are crucial, as
boilers to condense more. they represent the majority of the heating season (Table 1).4
Another factor is if the boiler is fire- or water-tube. Figure 4 shows the operation of two 3,000 MBH
Generally speaking, fire-tube boilers have lower pres- (900 kW) boilers in a facility located in New York City. As
sure drop across the heat exchanger (HX), making indicated, the plant operates at less than 10% of load for
them ideal for variable-primary piping. Conversely, 10% of the year. Boilers with a turndown ratio of 15:1 can
water-tube boilers tend to have higher pressure drop reduce output to as little as 7% of its capacity, which will
and minimum flow requirements, so primary-second- lower energy costs during the shoulder months, com-
ary piping is typically used. pared to units with turndown ratios of 5:1 and 10:1.

Design DT Proper Boiler Material


Commercial heat and hot water systems are normally Unlike non-condensing units, condensing boilers must
designed with 20°F to 30°F (11°C to 17°C) temperature withstand continuous exposure to the acidic exhaust
drop across the heating plant water supply and return. gases associated with natural gas combustion. Stainless
Since condensing boiler efficiency can significantly steel has been the material of choice for this corrosive
improve if the return water temperature is dropped, it is environment. Boilers made of other materials, such as
best to design for a higher DT. copper, cupronickel or cast iron, normally have an addi-
Increasing the building DT to a minimum of 40°F tional stainless steel heat exchanger at the end to handle
(22°C) helps improve the boiler plant efficiency and the condensation. Under certain circumstances, how-
saves on pump energy since it is correlated to flow. In ever, some condensation may take place in the first non-
fact, a change in DT from 20°F to 40°F (11°C to 22°C) stainless steel heat exchanger, which can significantly

16 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


C H I CAG O
JAN 25-27, 2021

T H E E V E N T F O R H VAC R

Register now at ahrexpo.com


Your health and safety are our top priorities. Learn more at ahrexpo.com/covid.
TECHNICAL FEATURE

TABLE 1 ASHRAE weather data vs. Btu load: New York, N.Y. FIGURE 4 Approximately 10% of the time the plant shall be running below 10%
TEMPERATURE ANNUAL HOURS AT OPERATING LOAD PLANT EFFICIENCY
load. *Data is based on New York City climate zone using ASHRAE bin data.
TEMPERATURE (BTU/H) FIRING RATE 1,000
900

Annual Hours at Temperature


–10°F to –5°F 0.3 5,500,000 96% 89.6%
800
–5°F to –0°F 0.8 5,133,333 90% 89.6% 700
600
0°F to 5°F 7.1 4,766,667 84% 89.6%
500
5°F to 10°F 23.6 4,400,000 77% 90.1% 400
10°F to 15°F 51 4,033,333 71% 90.7% 300
200
15°F to 20°F 90.2 3,666,667 64% 91.2% 100
20°F to 25°F 201.6 3,300,000 58% 91.7% 0
6 13 19 26 32 39 45 51 58 64 71 77 84 90 96
25°F to 30°F 355.2 2,933,333 51% 92.2% Plant Firing Rate (%)
30°F to 35°F 600.9 2,566,667 45% 92.7%
35°F to 40°F 815.4 2,200,000 39% 93.2%
150 psi to 160 psi—ideal for high-rise buildings.
40°F to 45°F 764 1,833,333 32% 93.6%
45°F to 50°F 921.3 1,466,667 26% 94.6%
Boiler Controller
50°F to 55°F 887.5 1,100,000 19% 95.2%
Building management systems (BMS) are common
55°F to 60°F 846.6 733,333 13% 95.5%
options to control many building elements, specifically
60°F to 65°F 765.2 366,667 6% 96.0% HVAC equipment. Integration of boiler plant compo-
nents into the building automation system (BAS)/BMS
reduce equipment life and increase downtime. allows communication over multiple BAS protocols,
including BACnet and Modbus. Boilers and equipment
Different Return Temperatures and Dual Returns with multiple integrated BAS protocols and transmis-
Many facilities combine different heating systems sion options gives the controls contractor the ability to
to provide the optimum solution. Often, the systems choose the one that provides the best equipment control
require dissimilar supply temperatures, as well as dif- and monitoring without the additional complications
ferent return temperatures. Depending on the system, it associated with gateways.
is important to factor the low-temperature return loops.
Some loop temperatures can be reduced further by feed- Outdoor Reset
ing the return of a high-temperature loop into the sup- Boiler controls can also be used for outdoor reset and
ply of a low-temperature loop. In these cases, the lower to establish setback schedules for ongoing operational
return water temperatures significantly improve boiler benefits. Reset helps more efficiently meet heating
plant efficiency. loads while maintaining a comfortable environment. An
These benefits can be optimized by designing plants outdoor air temperature sensor determines the boiler
with dual return boilers. Normally, the lower inlet return supply temperature. When the outdoor air temperature
is used for the lower temperature return to significantly drops, the boiler supplies higher temperature water to
improve overall plant efficiency by as much as 7%. meet high load requirements. As the warmer weather
arrives, less energy is needed for space heating and
Building Height and Boiler Pressure Rating lower temperature water is supplied to the heating coils.
When designing boilers for high-rise buildings, it is Return water temperatures are also lowered. The result
important to consider the whole system’s operating is higher boiler efficiency.
pressure. Using equipment or components below the
required pressure may complicate system design and Parallel Modulation
add significant costs by requiring additional pumps, It requires less energy for a group of modulating boil-
valves, heat exchangers or pressure reducing stations. ers, each firing in parallel at “part load,” to heat a build-
A better approach is to design a plant using boilers and ing than for a single boiler operating at “full fire” to carry
all the required components with pressure ratings of the entire workload. In low-mass and mid-mass boilers,

18 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


TECHNICAL FEATURE

operating at lower inputs with the same HX surface area plant warranty and optimized performance.
results in a more efficient heat transfer. This is converse
to more traditional non-condensing, high-mass boiler Summary
plants that fire to 100% before bringing on the next unit. Designing a heating and hot water plant for maxi-
mum efficiency and performance requires engineers
Backup Manager to consider several factors from the outset. Recognizing
In a multiboiler plant, one unit serves as the “manager” the specific needs of the facility, selecting the proper
while the others are “clients.” Advanced controls establish high-efficiency condensing boiler to best meet the load
the next in command if the “manager” is offline due to requirements, integrating advanced controls and incor-
maintenance, repair or other issues. Advanced control- porating the optimized loop design early in the process
lers can make this shift automatically to eliminate short will save installation time, lower construction and oper-
cycling and ensure optimal operating efficiency. ation costs and deliver superior performance.

Remote Access References


1. AERCO. 2013. “Benchmark 2000 Efficiency
Arming the facility owner and maintenance personnel Curves.”
with remote monitoring reduces the time spent physi- 2. 2016 ASHRAE Handbook—HVAC Systems and
Equipment, Chap. 32, Figure 7, “Relationship of
cally monitoring the system. When it is combined with Dew Point, Carbon Dioxide, and Combustion
maintenance and service alerts, the maintenance team Efficiency for Natural Gas.” https://bit.ly/3k9ecVE
3. 2019 ASHRAE Handbook—HVAC Applications, Rate this Column
is immediately notified of issues that may improve per-
Chap. 51, Figure 25, “Sizing Factor for Combination Heating and
formance or reduce tenant complaints. The staff is also Water-Heating Boilers.”
made aware so it can provide maintenance to help keep 4. ASHRAE. 2013. “Weather Data Viewer, version 5.0 (CD-ROM).”

HEPA Filter Units Provide


Cleaner, Safer Indoor Air
AJ Manufacturing has been supplying HEPA filtration units for hospitals and
other critical environments for years. Now, that same clean air technology
is available to help fight the spread of airborne pathogens like Covid-19 in
any building.
Our Criti-Clean Ultra FFUs are now available in traditional ceiling-mounted
models, as well as a portable unit that can be used in any room with a
standard electrical outlet. We offer two proven HEPA filtration options:
Air supply units provide a continual supply of filtered air to a room.
Reverse-flow units remove potentially contaminated air from a room,
creating a negative pressure environment (often used for isolation areas)
Criti-Clean Ultra Portable FFU
All Criti-Clean Ultra FFUs Feature:
• The industry’s highest output, up to 1200 CFM ceiling/1100 CFM portable
• Energy efficiency (only 42 watts at 90 FPM velocity/450 CFM)
• Quiet performance (only 45 DBA at 90 FPM, 58 DBA at 1100 CFM)
• Computer controlled, variable speed ECM motor
• All type 304 stainless steel construction
• HEPA filter (99.99% @ 0.3 micron)

Contact us today
to learn more!
Download
ajmfg.com • 816-231-5522 Brochure Criti-Clean Ultra Ceiling-Mounted FFU

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 19


TECHNICAL FEATURE

Filling the Knowledge Gaps

HVAC and COVID-19


BY ED LIGHT, CIH, MEMBER ASHRAE; JAMES BAILEY, P.E., MEMBER ASHRAE; REID LUCAS, ASSOCIATE MEMBER ASHRAE; LAURENCE LEE, CIH

Many HVAC-related factors could be significant with respect to the spread of


COVID-19. Increased ventilation, advanced filtration, humidification and improved
mechanical hygiene are being included in measures intended to reduce its spread.
ASHRAE has issued general guidance for HVAC operation during the COVID-19
pandemic based on the very limited information available at this time,1 but there is
considerable uncertainty over where these measures are effective. This paper summa-
rizes what is known about the virus responsible for COVID-19 (SARS-CoV-2) and simi-
lar viruses regarding the role of HVAC in both the spread and control of infection. It
also identifies critical information gaps and recommends research priorities.
Scientific publications were reviewed (including 2020 relationship, health risk is related to concentration
preprints of COVID-19 research) and papers previously in air and duration of exposure. These factors are not
published on related viruses such as SARS (2003 pan- known for SARS-CoV-2.
demic). The authors considered this information based CDC and WHO guidelines for COVID-19 response
on their experience as mechanical engineers special- assume that the important routes of COVID-19 trans-
izing in HVAC design and operation and as industrial mission are direct contact with the patient, short-range
hygienists specializing in indoor air quality. It should droplet exposure and transfer from surfaces where
be noted that this subject is rapidly evolving as efforts to aerosols have settled (fomites).2 Based on this assump-
control the pandemic continue. tion, recommended response measures by public health
agencies are generally limited to social distancing,
Significance of Airborne Transmission face coverings, handwashing and surface sanitizing.
Transmission of respiratory infections through the However, increasing evidence suggests that smaller
air is classified as direct contact (within a few meters) aerosols remain suspended in the air, where they
or airborne (i.e., beyond a few meters). SARS-CoV-2 is expose occupants (airborne transmission).
infectious until it degrades (inactivated), but it has not A group of Australian and Chinese researchers con-
been established how long the virus remains infectious cluded that there is now sufficient evidence of airborne
in air. Because viruses generally have a minimum dose transmission of COVID-19 to justify improving ventila-
at which they cause infection and show a dose-response tion and filtration where this would reduce SARS-CoV-2

This peer-reviewed article does not represent official ASHRAE guidance. For more information on ASHRAE resources on COVID-19, visit ashrae.org/COVID19.
Photo: spatesphoto – stock.adobe.com
20 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020
TECHNICAL FEATURE

exposure,3 and ASHRAE has adopted that position.4 • Waiters did have brief contact with infected custom-
Environmental epidemiology provides the most direct ers, but that was insufficient to cause infection.
way to establish the significance of airborne trans- This study concluded that SARS-CoV-2 was trans-
mission in the spread of COVID-19 and the efficacy of mitted by a combination of close contact (i.e., drop-
measures to limit airborne exposure. Environmental let exposure within 2 m [7 ft]) and aerosol exposure
epidemiological studies require collaboration between beyond that distance (extended short-range airborne).
engineers and health scientists to consider the location Poor ventilation resulting in little dilution of the virus
and timing of cases and environmental conditions asso- was considered a very important factor. This study
ciated with these. cannot be used to draw general conclusions on the
The following epidemiological studies suggest airborne prevalence of airborne transmission due to the atypi-
transmission of COVID-19. cal HVAC configuration. Lack of customer infection
Poorly Ventilated Restaurant. A detailed engineer- in adjacent zones suggests that SARS-CoV-2 was suf-
ing evaluation was performed of conditions at the ficiently isolated to prevent disease transmission. Lack
time of a COVID-19 outbreak at a restaurant in China. of waiter infection suggests that brief contact was not
After mapping case locations, conditions experienced sufficient to transmit COVID-19.5
by both infected and unaffected customers and staff Poorly Ventilated Bus. One hundred twenty-six peo-
were characterized. The role of different transmission ple traveled to a religious event in China in two buses,
routes was evaluated by comparing factors influencing each with a recirculating air-conditioning system (no
exposure of the two groups. Findings from this study outside air). An infected individual from Wuhan was on
included: one of the buses. All passengers mixed with the infected
• Ten of the 73 restaurant customers were infected. individual at a three-day religious event, along with 172
• Those 10 were seated at three adjacent tables on one other attendees who had not been in the buses. Thirty
side of the dining room, approximately 1 m to 5 m (3 ft to persons subsequently contracted COVID-19, and they
16 ft) from a customer who had just arrived from Wuhan were classified as follows:
before community spread in the rest of China. • No passengers on the bus without the infected indi-
• HVAC consisted of five fan coil units (FCU) with no vidual had COVID-19.
outside air and exhaust fans (off at the time). • Seven attendees who had not been in the buses
• Measured ventilation rates (infiltration only) were contracted COVID-19 but were in close contact with the
an order of magnitude below ASHRAE Standard 62.1- infected individuals during the event.
2019. • Twenty-three riders on the bus with the passenger
• Modeling of airflow patterns established that a from Wuhan were infected. By location, there were
“bubble” was formed by each FCU, dividing the room more cases in individuals sitting beyond 2 m (7 ft) of the
into five separate zones containing contaminants re- infected passenger.6
leased in that zone. Poorly Ventilated Conference Center. Also in China,
• Modeling results also suggested that discharge from 30 people attended a three-day event with an infected
the FCUs directed air in the breathing zone between individual from Wuhan in a building with poor ventila-
customers. tion (HVAC cycled on only 15 minutes per four hours).
• The three impacted tables were within the same It was not determined who had been in close proxim-
zone. ity to the infected individual, and thus within droplet
• Air from the contaminated zone did not mix signifi- range. Fifteen attendees were subsequently infected.
cantly with the rest of the room, and no customers were Investigators concluded that some infections were due
infected in those areas. to airborne exposure after comparing the infection
• Surveillance videos showed that close contact be- rate to similar outbreaks and that ineffective dilution
tween individuals and fomite contact were not signifi- because of poor ventilation appeared to be a major
cant. contributor.6
Ed Light, CIH, is president, James Bailey, P.E., is vice president and Reid Lucas is a controls specialist at Building Dynamics in Savage, Md. Laurence Lee, CIH, is owner and founder
of Pacific Industrial Hygiene in Kirkland, Wash.

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 21


TECHNICAL FEATURE

Well Ventilated Cruise Ship. Epidemiological inves- Two Wuhan Hospitals. Airborne SARS-CoV-2 was
tigation of the 696 COVID-19 cases aboard the Diamond sampled at two Chinese hospitals and nearby outdoor
Princess provided an opportunity to evaluate the role locations. Investigators classified some samples by parti-
of a recirculating HVAC system that was reported to cle size and estimated surface deposition rates. Findings
be operating with ventilation rates consistent with included:
ASHRAE standards. Infection cases were classified • Virus was detected in the air at most sites with pa-
into three categories: (a) individuals interacting with- tients present.
out restriction (i.e., passengers prior to quarantine); • Concentrations were lower in the temporary
(b) passengers quarantined in their cabin with no hospital, where air infiltration was greater than in the
COVID-positive individuals present; and (c) pas- permanent hospital.
sengers quarantined in their cabins where they were • Elevated airborne concentrations were found in a
directly exposed to an infected person. Infections only bathroom (potential fecal contribution).
occurred in categories (a) and (c). Passengers quaran- • Deposition tests associated particle settling with
tined in cabins free of infected individuals continued fomite contamination.
to be exposed to recirculated air from spaces with • Airborne virus settled on surfaces beyond the im-
infection. The lack of cases in category (b) suggests that mediate area surrounding the source and subsequently
circulation and dilution of air through the HVAC sys- resuspended, contributing to airborne exposure.
tem did not cause infection.7 • Elevated air concentrations were measured in a
Korean Call Center. All 1,145 occupants of an office/ staff changing area with used personal protective equip-
apartment building were tested for COVID-19, and a ment (PPE) (suggesting resuspension of settled virus).
cluster of cases was found on one floor, a densely occu- • Concentrations were lower in the staff changing
pied call center. There, 44% of the employees tested area after more rigorous sanitizing was instituted.
positive, and 94% of those were located on one side of • Particle size distribution varied, with >1 micron
the building. Only five cases were found on the rest of (droplets) dominating at one site, <1 micron (airborne)
the floor, where the majority of employees worked. Any dominating at another, and a third site equally divided
contact between occupants of the affected side of the between droplets and small particles.
floor with the other employees was very brief. Uniform Investigators concluded that their findings supported
spread throughout the affected area suggests there was airborne transmission.10
airborne transmission beyond direct contact. No infor- Nebraska Hospital. This study also detected
mation was provided to determine the relationship SARS-CoV-2 in the air more than 2 m (7 ft) from the
between case location and HVAC zoning.8 patient, including in the adjacent hall.11 SARS-CoV-2
Other COVID-19 studies sampled SARS-CoV-2 in air was not detected in the air around infected patients in
and on surfaces but did not correlate this with infection Singapore and Iranian hospitals. Insufficient informa-
patterns. While measured contaminant concentrations tion was provided to determine if negative results were
established airborne exposure away from the infected due to methodological limitations.12,13
individual, it was not determined if this exposure trans- A similar virus to SARS-CoV-2 was artificially gener-
mitted the infection to others. ated and measured for infectivity. Infectious virus was
Oregon Hospital. Surfaces were tested for SARS-CoV-2 detected after three hours in the air and three days on
inside a recirculating HVAC system with COVID-19 surfaces.14 Another study found airborne virus infec-
patients in some rooms. Sites with positive samples tious after 12 hours.15
included the prefilter receiving mixed air (return and Sampling studies represent occupant exposure, but
outside) and supply air dampers after filtration. These not necessarily disease transmission. Most analyses cited
recently reported results establish, for the first time, above were by polymerase chain reaction (PCR), which
that the virus can be transmitted through the HVAC measures total SARS-CoV-2 RNA, including viruses that
system. Analysis did not determine if the virus was still have been inactivated and can no longer cause infection.
infectious (airborne virus inactivates over time), and air Methods are also available that measure only infectious
quality was not tested.9 virus.

22 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


Highest Reliability and Preventative
Maintance for Mission Critical
ebm-papst supplies the latest technologies in air moving, controls, and now preventive maintenance. Our EC solutions are ultra
high efficiency with powerful performance – ranging from fractional HP to 18HP. Key features include the following:

• Solutions for low harmonic distortion available


• Measure and lock out application system resonant frequencies
• Compact design allows for easy installation – even fits into a typical freight elevator
• Easily accessible and controlled by DCIM/BMS with internal diagnostic functionality
• One supplier for entire system of air mover, motor, drive
• True Plug n Play - no commissioning needed, just wire and go
• Industry leading range of speeds 8%-100%, Highly efficient even at low speeds
• Standard controls: 0-10V, 4-20mA, ModBus

For more information, contact sales@us.ebmpapst.com


TECHNICAL FEATURE

Research on Similar Viruses the index case. Some of these were within 3 m (10 ft) of
To understand the spread of COVID-19, it is instructive the index case, but others were further away.
to review research on similar viruses. During the severe • Eleven people were infected in the room across the
acute respiratory syndrome (SARS) pandemic in 2003, hall. Because the return grilles for each zone were near
public health agencies and some researchers concluded each other in the hall, air mixed between zones.
that respiratory infections were primarily spread by • Approximately six people were infected in the two
direct exposure to droplets at close range. Other inves- rooms further down the hall. They return from the same
tigators, however, concluded that the disease was also hall, but airborne virus would be more dilute.16
being spread by airborne transmission. SARS in Apartment Building. In Hong Kong, a major
SARS in Hong Kong Hospital. Infections spread from SARS outbreak was clustered within certain areas of an
one patient (index case) to patients and medical stu- apartment building. The location of infected individuals
dents in a ward with four rooms, each a separate HVAC was mapped and compared to environmental condi-
zone. Outside air was provided by a central system and tions. Investigators found the disease pattern consistent
mixed with recirculated air from a fan coil unit (FCU) with airborne transmission. One suggested that sewer
in each room. Air was returned to each FCU from a hall gas was a contributor. Others concluded infection sites
running adjacent to the rooms. A model of air distribu- occurred with typical air distribution in high-rise apart-
tion and bioaerosol was developed to estimate relative ment buildings.17,18
concentrations of airborne virus by location. Simulated SARS in Airliner. A study of how respiratory infec-
exposures generally correlated with actual cases of tions spread on an airliner mapped the location
infection as follows: of passengers who developed infection in relation
• Twenty-one people were infected in the zone with to their distance from the index case (individual

C 1
ASS SIMPLE
S AS...
S...
Ma
g
ne

The LPD-Mag is the industry’s tA


ttr
acts Debris
first strainer solution to iron
oxide build-up within the water
system. Overtime, your steel
piping system can produce and
recirculate materials that are 2
D e b r i s C i rc l

hazardous to the health of your


system and those utilizing it.
The LPD-Mag helps to attract
and remove these particles from
e

n
ex
i

th t
your system. eC or
o ll e c ti o n V

3
Easi
ly
Bl

ow
d

n e
www.Metraflex.com/LPD-M | 312-738-3800 Dow ov
n & Rem

24 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


TECHNICAL FEATURE

already infected). Passengers were classified as either rate.21,22 At least one investigator has suggested that
within 2 m (7 ft) or further away. An equal number of proper ventilation could play a key role in containing the
infected passengers were seated near the index case spread of COVID-19.23
compared to those seated further away. The same Although window opening has been suggested as an
paper examined three flights with clusters of H1N1 option to reduce the risk of COVID-19 transmission, no
(swine flu). Each flight showed different case pat- studies related to this were available.
terns, one with nearby passengers dominating and
the other two with similar numbers of nearby and Air Distribution
distant cases.19 The authors’ field evaluation of wall-mounted fan
Overall, these findings suggested that the spread of coil units has identified situations where supply air
SARS included airborne transmission.16 blows directly on occupants, potentially transmitting
virus from an infected individual to other occupants.
HVAC Operations Our examination of airflow patterns reported in the
Ventilation Guangzhuo restaurant outbreak study5 suggests that
The studies cited above establish that SARS-CoV-2 this could have been a contributing factor. Air blowing
can be airborne beyond the immediate vicinity of directly on surfaces can also resuspend settled aerosols
an infected individual and that concentrations can containing virus.10 Air distribution also determines
be diluted by increasing ventilation.20 SARS (2003 whether infectious droplets disperse or concentrate
pandemic) investigators suggested that increased air locally. Relative pressurization can also contain or
exchange may have reduced disease spread, but they spread contamination. No data were found relating air-
lacked information to support a minimum ventilation flow patterns to COVID-19 transmission.

ArmaFlex is a trademark of the Armacell Group © 2020

TIME IS OF THE ESSENCE

ArmaFlex Ultra ®
with FlameDefense™ technology — the first elastomeric
insulation Classified by UL to UL 723 at 25/50. In an
emergency, it gives you time.

www.armacell.us

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 25


TECHNICAL FEATURE

Filtration humidity.26 However, COVID-19 also spread during ini-


Newly reported surface sampling inside recirculat- tial stages of the pandemic in humid areas.27
ing HVAC systems in an Oregon hospital provides an Continuing high rates of COVID-19 in the United States
indicator of filter efficiency. The amount of virus col- this summer further suggest that humidity is not an
lected on the prefilter, final filter and supply air damper important factor. The National Academy of Sciences con-
allows for comparison of virus in mixed air before and cluded that differences in humidity only explain a small
after prefilters (MERV 10) and after discharge from the fraction of the overall variation in COVID-19 transmis-
final filters (MERV 15). The amount of virus collected on sion rates.28
surfaces decreased by approximately 70% after passing
through the prefilters but did not decrease further after Wastewater
the final filters.9 SARS-CoV-2 has been found in feces, urine, sewage,
A modeling study of influenza spread found that toilet surfaces and air in restrooms. The release of drop-
higher efficiency air filters could lower flu infection lets containing virus from these sources is likely, but no
risk.24 Although COVID-19 response measures now monitoring results were found.
include installation of filters with higher MERV ratings,
there have been no studies to determine whether fil- Mechanical Hygiene
ter rating makes any difference in transmission of the SARS-CoV-2 on surfaces inside HVAC systems was
disease. recently documented where hospital systems recircu-
Experience suggests that, with appropriate design and lated air in zones with COVID-19 patients. The virus was
positioning, HEPA filtration units within a space could detected on prefilters receiving mixed air, the surface of
potentially reduce SARS-CoV-2 exposure by directly final filters receiving air after prefiltration and supply
capturing air in the vicinity of infected patients or by air dampers after the final filters.9 In an earlier study,
removing airborne virus near susceptible individuals. the surface of an exhaust outlet in a Singapore hospital
However, designers must also be aware that discharge tested positive.12
air could also blow virus between occupants and resus-
pend settled virus from surfaces. Preliminary Conclusions
Further study is needed to determine whether HVAC
Air Disinfection systems actually transmit COVID-19 infection and if
Ultraviolet (UV) light systems for infection control can HVAC modifications can help control its spread. Review
either be in the space (upper-room) or HVAC system (in- of available information revealed very little detail in this
duct). These systems are occasionally used in hospitals regard.
to help control airborne infectious agents but are rarely Airborne Transmission. Limited sampling has estab-
used in non-healthcare facilities. lished that SARS-CoV-2 is airborne and can expose (but
Upper-room UV was found in one study to prevent the not necessarily infect) occupants well beyond 2 m (7 ft).
spread of measles, mumps and chicken pox. However, Recent findings further establish that the virus can cir-
the authors also noted that it might not be effective in culate through some HVAC systems. While several out-
the protection of susceptible individuals against other breaks of COVID-19 infection have suggested airborne
pathogens.25 No studies were found related to the use of transmission, these have generally been in areas with
UV to control SARS-CoV-2. poor ventilation, raising the possibility that dilution
by code-required building ventilation inhibits disease
Humidity Control transmission.
Coronaviruses survive under dry conditions, and occu- Ventilation. Increasing outdoor air dilutes the concen-
pants can be more susceptible to respiratory infection at tration of airborne SARS-CoV-2. Minimum acceptable
lower relative humidity (RH). Humidification has been ventilation rates have not been established for operation
suggested as a means of controlling flu. Comparison of of buildings where infected occupants may be present.
initial COVID-19 cases by region or country suggested It is not known whether increasing ventilation rates
that infection rates might be greater in areas with higher above ASHRAE minimums actually reduces disease

26 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


TECHNICAL FEATURE

transmission. Natural ventilation has not been evaluated implement cost-effective measures to operate build-
with respect to COVID-19. ings during the pandemic. While basic research can
Air Distribution. Studies suggest that how air is take years, valuable data could be compiled much
discharged and circulates within a space could be an faster using available epidemiology and by testing
important factor determining whether exposure is suffi- buildings.
cient to cause disease. For example, wall-mounted FCUs Environmental Epidemiology. Studies can suggest
can discharge air into the breathing zone, potentially the relative role played by the various routes of dis-
directing virus to other occupants. Relative pressuriza- ease transmission and evaluate the efficacy of control
tion can also contain or spread contamination. No field measures. To accomplish this, engineers and health
data were available showing the impact of air distribu- scientists collaborate to compile exposure factors
tion on COVID-19 exposure. (i.e., ventilation, airflow patterns, filtration, occupant
Filtration. Recently reported results of surface density and spacing) to determine their relationship
sampling inside recirculating HVAC systems provide with case location and timing. If outbreak investiga-
an indicator of filter efficiency. Data suggest that a tions, contact tracing and evaluation of widespread
MERV 10 prefilter reduced the amount of deposited testing could include the collection of environmental
SARS-CoV-2 by approximately 70% and that a MERV information, findings would help support the selec-
15 final filter may not have removed additional virus. tion of HVAC response measures. Critical questions
Insufficient field data are available to guide filter that could be addressed by epidemiological studies
selection for COVID-19. Filtration within the space include:
(i.e., portable HEPA units) could reduce virus expo- • What do infection patterns suggest with respect to
sure in localized areas with appropriate design and the significance of airborne and fecal transmission as
placement. the cause of infection?
UV Disinfection. Although UV light has the potential • How do ventilation, air distribution and humidity
to reduce virus exposure in some situations, there are affect infection rates?
insufficient data to support widespread application. • How effective are various filtration and air disinfec-
Humidity Control. It has been demonstrated that tion measures in reducing exposure?
coronaviruses survive longer and occupants are Field Studies. Valuable information can be produced
more susceptible to respiratory infection in drier by sampling for contaminants in occupied buildings
conditions. Although COVID-19 initially spread in for airborne and surface SARS-CoV-2 (both total RNA
areas with drier (i.e., winter) conditions, there was copies and infectious virus). Comparison of data col-
also community spread in humid areas (i.e., tropi- lected in buildings with varying systems, uses and
cal climates and southern hemisphere summer). infection rates would provide valuable information to
Continuing high rates of COVID-19 in the United guide response efforts. Field measurements of particu-
States this summer further suggest that humidity is lar value include:
not an important factor. Available information does • Concentrations of SARS-CoV-2 in air with recircu-
not support humidification when the RH is below 40% lating HVAC systems in spaces with and without infected
as a control for COVID-19. individuals;
Sewage. SARS-CoV-2 has been found in feces and • Both air and surface SARS-CoV-2 in ducts and air
urine, making sewer gas and sewage a potential source units recirculating air from spaces with infected indi-
of exposure. Studies are needed to develop effective viduals;
strategies to avoid infecting occupants. • SARS-CoV-2 concentrations over time after removal
Mechanical Hygiene. SARS-CoV-2 has been detected of infected occupants;
on surfaces inside recirculating HVAC systems. It is not • SARS-CoV-2 in air over time in relation to opening
known if this can contaminate the airstream. windows;
• SARS-CoV-2 concentration in air associated with
Recommendations for Expedited Research different ventilation rates and filter efficiencies;
Research is urgently needed to identify and • Pilot testing of space conditioning measures, such

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 27


TECHNICAL FEATURE

as portable HEPA filtration and UV light; and 13. Faridi, S., S. Niazi, K. Sadeghi. 2020. “A field indoor air
¥ SARS-CoV-2 exposure associated with sewage and measurement of SARS-CoV-2 in the patient rooms of the largest
hospital in Iran.” Science of The Total Environment 725(July): 138401.
sewer gas. https://doi.org/10.1016/j.scitotenv.2020.138401.
14. van Doremalen, N., B. Bushmaker. 2020. “Aerosol and surface
Acknowledgments stability of SARS-CoV-2 as compared with SARS-CoV-1” New England
Journal of Medicine 382:1564 – 1567. https://tinyurl.com/vdbkzo9.
Thanks to William Bahnfleth, Ph.D., P.E., chair,
15. Fears, A., W. Klimstra, P. Duprex. 2020. “Comparative
ASHRAE Epidemic Task Force; Shelly Miller, Ph.D., dynamic aerosol efficiencies of three emergent coronaviruses and
P.E., University of Colorado; Lew Harriman, P.E., the unusual persistence of SARS-CoV-2 in aerosol suspensions.”
retired; Lidia Morawska, Ph.D., Queensland Institute Preprint. medRxiv. https://doi.org/10.1101/2020.04.13.20063784.
of Technology; Steve Taylor, P.E., Taylor Engineering; 16. Li, Y., X. Huang, T. Yu, et al. 2004. “Role of air distribution in
SARS transmission during the largest nosocomial outbreak in Hong
and to Larry Schoen, P.E., Schoen Engineering; and Kong.” Indoor Air 15(2):83 – 95.
Bernard Fontaine, CIH, The Windsor Consulting 17. Li, Y., S. Duan, I. Yu., et al. 2004. “Multi-zone modeling of
Group, for providing additional information and probable SARS virus transmission by airflow between flats in Block
suggestions. E, Amoy Gardens.” New England Journal of Medicine 15(2):96 – 111.
https://tinyurl.com/y44qlmjg.
18. McKinney, K., Y.Y. Gong, T.G. Lewis. 2006. “Environmental
References transmission of SARS at Amoy Gardens.” J Environ Health
1. ASHRAE. 2020. “ASHRAE Position Document on Airborne 68(9):26 – 30. https://tinyurl.com/yy9cb726.
Infectious Diseases.” https://tinyurl.com/rmm5mft.
19. Hertzberg, V., H. Weiss. 2016. “On the 2-row rule for
2. National Academies of Sciences, Engineering, and Medicine. infectious disease transmission on aircraft.” Annals of Global Health
2020. “Rapid Expert Consultation on Social Distancing for the 82(5):8198 – 23. https://tinyurl.com/yxh5wedv.
COVID-19 Pandemic.” The National Academies Press. https://doi.
org/10.17226/25753. 20. Dai, H., B. Zhao. 2020. “Association of infected probability of
COVID-19 with ventilation rates in confined spaces: A Wells-Riley
3. Marawski, L., J. Cao. 2020. “Airborne transmission of SARS- equation-based investigation.” Preprint. medRxiv. https://tinyurl.
CoV-2: The world should face the reality.” Environment International com/y84ofn7f.
139(June):105730. https://doi.org/10.1016/j.envint.2020.105730.
21. Yu, I, Y. Li, T. Wong. 2004. “Evidence of airborne transmission
4. ASHRAE.2020. “Coronavirus (COVID-19) Response Resources of the severe acute respiratory syndrome virus.” New England Journal
from ASHRAE and Others.” www.ashrae.org/COVID19. of Medicine 350(17):1731 – 9. https://tinyurl.com/yynhdj8v.
5. Li, Y., H. Qian, J. Hang, et al. 2020. “Evidence for probable 22. Luongo, J., K. Fennelly, J. Keen. 2016. “Role of mechanical
aerosol transmission of SARS-CoV-2 in a poorly ventilated ventilation in the airborne transmission of infectious agents in
restaurant.” Preprint. medRxiv. https://tinyurl.com/y4he3e9j. buildings.” Indoor Air 26(5):666 – 78. https://tinyurl.com/y3yqsf25.
6. Shen, Y., H. Dong, X. Chen. 2020. “Airborne transmission 23. Buonanno, G., L. Stabile, L. Morawska. 2020. “Estimation of
of COVID-19: epidemiologic evidence from two outbreak airborne viral emission: quanta emission rate of SARS-CoV-2 for
investigations.” Preprint. ResearchGate. https://tinyurl.com/ infection risk assessment.” Environment International 141(August).
y88nunaq. https://tinyurl.com/yy4vb5za.
7. Xu, P., H. Qian, T. Miao, et al. 2020. “Transmission routes of 24. Azimi, P., B. Stephens. 2013. “HVAC filtration for controlling
COVID-19 virus in the Diamond Princess Cruise Ship.” Preprint. infectious airborne disease transmission in indoor environments:
microBEnet. https://tinyurl.com/yy6hk55q. predicting risk reductions and operational costs.” Building and
8. Park, S., K. Young-Man., S. Yi, et al. 2020. “Coronavirus Environment 70(December):150 – 160. https://tinyurl.com/y6y9g79x.
disease outbreak in a Korean call center.” Emerging Infectious Diseases 25. Wells, W., M. Wells, T. Wilder. 1942. “The environmental
Journal 26(8). control of epidemic contagion. I. an epidemiologic study of radiant
9. Horve, P., L. Dietz, M. Fretz, et al. 2020. “Identification of disinfection of air in day schools.” American Journal of Epidemiology
SARS-CoV-2 RNA in Healthcare Heating, Air Conditioning Units.” 35(1):97 Ð 121. https://doi.org/10.1093/oxfordjournals.aje.a118789.
Preprint. medRxiv. https://tinyurl.com/ybj3g4ya. 26. Kardis, G., R. Thompson 2020. “Climate-Informed HVAC
10. Li, Y., Z. Ning, Y. Chen, et al. 2020. “Aerodynamic analysis of Increases in Relative Humidity May Fight Pandemic Viruses.
SARS-CoV-2 in two Wuhan hospitals.” Nature 52:557 – 560. https:// Preprint. SMITHGROUP. https://tinyurl.com/y3e3gkny.
doi.org/10.1038/s41586-020-2271-3.
27. Mecenas, P., R. Bastos, A. Vallinoto, et al. 2020. “Effects of
11. Santarpia, J., D. Rivera, et al. 2020. “Aerosol and Surface temperature and humidity on the spread of COVID-19: a systematic
Transmission Potential of SARS-CoV-2.” Preprint. MedRxiv. review.” Preprint. medRxiv. https://tinyurl.com/
https://doi.org/10.1101/2020.03.23.20039446. yxe4wb7c.
12. Ong, S., Y. Tan, P. Chia, et al. 2020. “Air, Surface 28. Droegemeier. K. 2020. “Rapid expert
Environmental, and Personal Protective Equipment Contamination consultation on SARS-CoV-2 survival in relation
by Severe Acute Respiratory Syndrome Coronavirus 2 (SARS-CoV-2) to temperature and humidity and the seasonality
from a Symptomatic Patient.” JAMA 323(16):1610 – 1612. https:// for the COVID-19 pandemic.” National Academy https://bit.ly/3k9ecVE
tinyurl.com/tk9z6dv. of Science. https://tnyurl.com/wvrgsz6. Rate this Column

28 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


Greenheck — Never Compromise on Air Quality.
Engineered and Manufactured to Support Safety, Health, and Comfort.

Widest Product Line in Air Movement, Control and Conditioning Equipment

■ Fast lead times Greenheck delivers the leading air quality solutions today’s
■ Easy installation
uncertain environment demands. From schools and hospitals
to offices, restaurants and warehouses, our comprehensive
■ Superior performance
line of air movement, control, and conditioning equipment © 2020 Greenheck

■ Energy efficient offers top performance, energy efficiency, and simple


installation. All supported by local mechanical reps you
■ Local sales support
can trust—and backed by the Greenheck brand.

FANS | ENERGY RECOVERY | PACKAGED VENTILATION | MAKE-UP AIR | KITCHEN VENTILATION | LAB EXHAUST | DAMPERS | LOUVERS | COILS

CONTACT YOUR LOCAL


greenheck.com GREENHECK REP TODAY
TECHNICAL FEATURE

Improving IEQ
To Reduce Transmission
Of Airborne Pathogens
In Cold Climates
BY STEPHANIE H. TAYLOR, M.D.; C. MICHAEL SCOFIELD, FELLOW/LIFE MEMBER ASHRAE; PATRICIA T. GRAEF, P.E., FELLOW/LIFE MEMBER ASHRAE

Winter indoor environments in cold climates often stabilize at a low relative humid-
ity (RH) due to high outdoor air ventilation rates required for schools and high-occu-
pancy office buildings. Indoor environmental quality (IEQ) is heavily impacted due to
the low RH. Recent studies have concluded that low indoor RH and reduced outdoor
air ventilation result in reduced student and worker productivity and increased
short-term sick leave.1,2 The variable air volume (VAV) design discussed in this article
uses adiabatic hydration (humidification) of all outdoor air during cold-dry ambient
conditions.

A 45°F (7°C) dew-point (DP) minimum supply to cooler/humidifier (AC/H) in a central station air-han-
core building VAV terminals will reduce fan energy dling unit (AHU).
and room air change rate. Other studies have linked
artificially high air change rate with room air turbu- Air Hydration for Human Health and Well-Being
lence within the human breathing zone, which may During the winter in cold climates, people spend at
lead to the projection of flu virus and other airborne least 85% of their time indoors,4 so it is not surprising
pathogens further from the primary human host and that the indoor environment exerts a powerful influ-
result in infecting other room occupants.3 Air-to-air ence on occupants. Existing ASHRAE guidance refers to
heat exchangers are used to recover heat from build- managing indoor air to accommodate occupant comfort.
ing exhaust air that was generated by people, lights However, new data clearly show that occupant health, a
and plug loads inside the building. Low-cost humidi- more pressing consideration than comfort for most of
fication is provided to the building using an adiabatic us, is impacted by IEQ.5
This peer-reviewed article does not represent official ASHRAE guidance. For more information on ASHRAE resources on COVID-19, visit ashrae.org/COVID19.

30 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


TECHNICAL FEATURE

FIGURE 1 Relative humidity of 40% to 60% is optimal for human health. Courtesy of Dr. Stephanie Taylor.

Virus (Lipid Membrane) High Infectivity of Pathogens Low Infectivity High Infectivity of Pathogens
Influenza, Coronavirus, RSV,
Parainfluenza., Measles, Rubella,
Herpes
Virus (Non-Lipid Membrane)

Bacteria (Gram Neg.)


Legionella (Aerosolized)

Bacteria (Gram Pos.)

Mycoplasma (No Cell Wall)

Human Illness from Infections Healthiest Humans Human Illness from Infections
Adult In-Patients (Acute Care)
Elderly Patients in Long-Term Care
Preschool Children
Poor Human Functioning Poor Human Functioning
Employee Productivity
Employee Sleep Quality

Student Learning

10 20 30 40 50 60 70 80 90
Relative Humidity (%)

Indoor RH, especially in temperate climate winters, and fungi, on and within our bodies.6
can stabilize at dry levels of 20% or lower when cold This information directly challenges our long-held
outdoor air is brought into a building and heated to hygiene theory that microbes are disease-causing germs
temperatures comfortable to lightly clothed people. that need to be eradicated as quickly as possible. We now
New research findings are revealing the magnitude of know that most microbes in our personal ecosystems,
occupant health problems associated with low indoor called our microbiome, are not only beneficial to our
RH. While many of these health issues have been noted health, but are essential to human survival.
in the past,2 they are now receiving additional attention When humans occupy a building, they shed their
because new data are reinforcing the significance of this microbes from direct contact, skin flakes and expired
relationship. droplets into the built environment. Accumulated
Much of the new information about dry air and health occupant microbes combine with those from outdoor
arises from a greater understanding of the coexistence sources, giving rise to dynamic microbial communi-
of microbes with humans. New medical diagnostic tests ties known as the building microbiome.7 This building
implement tools used to sequence the human genome microbiome is further shaped by ongoing occupant
in 2003. These tests can probe deeply into the causes shedding, ventilation strategies and surface materials
of acute infections, chronic inflammation and autoim- (Figure 1). In addition:
mune disorders. These genetic analysis tests have given ¥ When indoor air is less than 40% RH, the effective,
rise to revolutionary information about the coexistence natural immunological defenses of human airways, eyes
of vast numbers of microbes, meaning bacteria, viruses and skin are impaired. The loss of moisture from these
Stephanie H. Taylor M.D., is a Harvard Medical School Incite Health Fellow in Boston. Mike Scofield, P.E., is president, Conservation Mechanical Systems, Sebastopol, Calif., and is a
consultant to California Hydronics Corp., San Francisco. Patricia T. Graef, P.E., is retired and lives in Fort Myers, Fla.

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 31


TECHNICAL FEATURE

tissues leaves occupants significantly FIGURE 2 In ambient RH of 50%, the respiratory system is optimally protected from Influenza A disease.8
more vulnerable to infectious, inflamma-
tory and allergic diseases8 (Figure 2).
• A dry air-environment with low RH Improved Mucociliary
carries more infectious bioaerosols than Clearance
hydrated air. Airborne pathogens stay
Enhanced Protection
buoyant and viable for longer periods of Induced by Interferon
time in dry atmospheres, and they can
be spread more readily within the indoor Decreased Inflammation
human breathing zone.9 and Tissue Damage Enhanced
Tissue
• For reasons still not completely Repair
understood, when ambient RH is low, the
viruses and bacteria in aerosolized drop- • Legionnaires’ disease outbreaks have focused the
lets are more virulent to a secondary host. 10 public’s attention on hazards associated with building
• Humans have a vast surface area that loses signifi- water and HVAC systems.
cant water to the environment through breathing and Nevertheless, we now know more clearly than ever that
skin exposure.11 In dry air, this insensible water losses dry interior environments are harmful to our health,
result in mild dehydration that stresses brain func- productivity and learning.
tioning,12 impairs natural respiratory tract immunity Adding water vapor to hydrate indoor air to 40% to 60%
(discussed above), decreases skin health and wound RH benefits occupants in several ways. First, balanced
healing13 and overstimulates blood clotting, which is air-hydration directly supports healthy and functional
associated with poorer outcomes of heart attacks and skin and mucosal barriers8 necessary to resist invading
strokes.14 pathogens and facilitate appropriate immune system
In summary, dry indoor air is harmful to occupant responses to microbes. In addition, properly hydrated
health by causing skin and mucus membrane water air reduces skin production of unhealthy stress hor-
losses and by creating building conditions that foster the mones,16 improves cognitive abilities, which increase
survival and transmission of pathogenic microbes. Thus, employee productivity and student learning17 and sup-
ventilation choices clearly link human health to the built ports healthy eye physiology. Additionally, RH of 40% to
environment. Despite these findings of harm, under- 60% fosters a building microbiome with communities of
standing and remediating dry indoor environments has diverse microorganisms, which are beneficial to human
been largely overlooked by both building and clinical health.
professionals. The reasons for this are several-fold: Despite the health benefits from balanced indoor air
• While the temperature of surrounding air is imme- hydration, there are building-related concerns about
diately evident to nerve endings in our skin, the degree providing indoor humidification. Water in buildings,
of dryness is not felt and, therefore, is not experienced even in the form of vapor, generally has a bad reputa-
as discomfort. 15 tion because poorly insulated building envelopes or cold
• Acute infections from pathogens that we now know surfaces can allow unintended condensation to occur.
are transmitted via airborne infectious aerosols in dry Building owners and managers worry about this con-
air have historically been incorrectly attributed to con- densation and associated mold growth.
tact transmission routes alone. While liquid water will support mold growth, water in
• Chronic illnesses associated with dry air often arise the vapor form will not because fungal organisms are not
slowly and, therefore, are not immediately associated hygroscopic when the RH is between 40% and 60%.18 The
with low humidity indoor environments. effective and rational solution to inhibit mold growth,
• Providing humidification requires dedicated HVAC therefore, is to adequately insulate cold building surfaces
equipment (humidifiers) that must be run (using water and use vapor barriers to prevent high water activity in
and energy) and maintained (by human attention) for interstitial spaces. The result should not be an overdry
safety. indoor environment that compromises occupant health.

32 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


TECHNICAL FEATURE

Wet
-B ulb 200
FIGURE 3 The Sea Level Psychrometric Chart shows the boundary of Climate Tem
Zones 1, 2 and 3 for the 22 cities listed in Table 1. All ambient conditions in p erat
ure—
Climate Zone 1 require supplemental heat to produce a 45°F dew-point (DP) °F
180
building delivery with 100% outdoor air. Climate Zone 2, between 23°F dry bulb
(DB) and 45°F wet bulb (WB) are ambient conditions where a high sensible
efficiency heat wheel may be used to deliver a 45°F DP off the adiabatic cooler/
humidifier (AC/H) without supplemental heating. In Figure 4, Dampers A and 80 160
B modulate to produce a 45°F WB mixed-air condition delivered to the AC/H
with all outdoor air. Climate Zone 3 contains all the ambient conditions between

Humidity Ratio—Grains of Moisture Per Pound of Dry Air


45°F WB and 55°F WB when the heat wheel is off and bypassed on the supply 140
side with Damper B open and Damper A closed. In Climate Zone 3 all outdoor air
is cooled and hydrated to a leaving air condition that is allowed to float between
45°F DP to 55°F DP. Sensible cooling is produced with a cooling energy efficiency 120
ratio (EER) ranging between 80 to 100 with refrigeration off. 70

RH
60%
100

RH
60 80

40%
45°F DP
Room Target Range 70°F – 75°F DB
40% – 60% RH 60
50

45°F DP/DB/WB Room Load 45°F DP


40 40
Hum Adiaba 55°
idifi tic FW
45° cati B
Seattle Winter Design 30 FW on Outdoor Air Hydration
23°F DB/22.1°F WB Climate Zone 2 B
Climate Zone 3 20
Supplemental Heat Heat Recovery 5°F DP
Climate Zone 1
10 23°F 30 40 50 60 70°F 75°F 80 90 100 110 120
Dry-Bulb Temperature (°F)

A Wet-Bulb Heat Recovery Economizer ASHRAE Research Project RP-1515 demonstrated that,
For more than three decades, air-to-air heat exchang- with good aspirating ceiling diffusers, the turndown of
ers have been used to recover building generated heat a VAV terminal to 10% flow will not lose flow control and
and comply with the minimum winter ventilation will not result in “dumping” of cold air into the space.
requirements of ASHRAE Standard 62.1.19 These con- On the contrary, overcooling complaints in the buildings
ventional systems use the VAV 55°F (13°C) air delivery tested went down, eliminating cold room issues while
setpoint of the building. Figure 3 demonstrates a novel saving fan energy.20
method to deliver 70°F (21°C) air at 40% relative humid- In many northern hemisphere cold climates, high-rise
ity using heat recovery and adiabatic cooling/humidifi- buildings with south-facing glass experience design
cation (AC/H). cooling loads in January and February due to the low
Since VAV systems operate at their lowest flow rates angle of the sun and the radiant energy on the south-
on the coldest days, heat recovery from the building facing side of the building.21 A 45°F (7°C) DB delivery
is required to furnish the code-minimum outdoor air to these VAV terminals will provide comfortable indoor
to the building. The code minimum airflow rate may environments with reduced fan energy during these
be more than that needed at 45°F (7°C) DB to meet the peak cooling loads.
cooling load in core conference rooms and north-facing When we can hold indoor RH in winter at a minimum
perimeter zones (in the northern hemisphere). VAV ter- of 40%, room thermostat setpoints may be reduced
minal reheat will be required for those mixing boxes. to 70°F (21°C) or lower, saving heating energy. This

34 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


TECHNICAL FEATURE

TABLE 1 Bin weather data distribution for 22 northern U.S. cities, listing the total annual hours and percent of annual hours where heat recovery and adiabatic cooling and
humidification may be used to furnish 100% outdoor air, without supplemental heating energy (Climate Zones 2 and 3 in Figure 3), to produce a 45°F to 55°F dew-point
(DP) building delivery condition. The building duty cycle is assumed to be 24/7/365, and the VAV fan turndown is 50% of full flow during cold ambient conditions.
CITY, STATE ELEVATION CLIMATE ZONE 1 CLIMATE ZONE 2 CLIMATE ZONE 3
(FT) PREHEAT REQUIRED FOR 100% HUMIDIFICATION WITHOUT PREHEAT WITH 100% HUMIDIFICATION OF 100% OUTDOOR AIR WITHOUT
OUTDOOR AIR OUTDOOR AIR AND HEAT RECOVERY PREHEAT OR REFRIGERATION
WET-BULB RANGE 45F TO 55F
HOURS % HOURS % HOURS %

Boise, ID* 2,996 225 2.6% 4,214 48.1% 3,050 34.8%


Chicago, IL 658 692 7.9% 4,272 48.8% 1,304 14.9%
Des Moines, IA 938 903 10.3% 3,797 43.3% 602 6.9%
Boston, MA 133 619 7.1% 3,879 44.3% 1,419 16.2%
Detroit, MI 583 709 8.1% 3,824 43.7% 1,287 14.7%
Grand Rapids, M 841 721 8.2% 3,851 44.0% 1,276 14.6%
St. Paul, MN 834 1,404 16.0% 3,236 36.9% 1,166 13.3%
Billings, MT* 3,567 822 9.4% 4,618 52.7% 1,968 22.5%
Great Falls, MT* 3,525 1,016 11.6% 4,820 55.0% 2,224 25.4%
Buffalo, NY 590 520 5.9% 4,050 46.2% 1,331 15.2%
Bismarck, ND* 1,647 1,772 20.2% 3,297 37.6% 1,822 20.8%
Grand Forks, ND 911 2,138 24.4% 3,159 36.1% 1,192 13.6%
Cleveland, OH* 1,208 504 5.8% 3,804 43.4% 1,340 15.3%
Columbus, OH 824 472 5.4% 3,386 38.7% 1,248 14.2%
Harrisburg, PA 308 242 2.8% 3,642 41.6% 1,302 14.9%
Pittsburgh, PA* 1,137 491 5.6% 3,575 40.8% 1,365 15.6%
Rapid City, SD* 3,276 961 11.0% 4,320 49.3% 1,989 22.7%
Sioux Falls, SD* 1,418 1,351 15.4% 3,280 37.4% 1,789 20.4%
Seattle, WA* 47 18 0.2% 3,814 43.5% 2,747 31.4%
Spokane, WA* 2,462 291 3.3% 4,718 53.9% 3,026 34.5%
Madison, WI 858 1,018 11.6% 3,612 41.2% 1,187 13.6%
Casper, WY* 5,338 827 9.4% 4,841 55.3% 2,539 29.0%
22 Northern Cities Average 9.2% 44.6% 19.3%
*Western cities and cities at high altitude.
Reference Ecodyne. 1980. Climate Data Handbook. McGraw-Hill.

is because the skin evaporation rate for humans is The psychrometric chart in Figure 3 shows the heat
lower at 40% RH compared to 20% RH. The percep- recovery process (red line) provided by a high-efficiency
tion of comfort is better for the zone occupant at lower sensible heat wheel. The adiabatic process (blue line) of
indoor temperatures and lower VAV box flow rates. a high saturation efficiency AC/H provides the outdoor
Cold-climate buildings often include a radiant heat- air hydration to the 45°F (7°C) DP. The high efficiency
ing system around the building perimeter to treat of the adiabatic device is critical. With a 95% wet-
cold exterior walls and to raise the room mean radiant bulb depression efficiency (WBDE) adiabatic device,
temperature (MRT). This separate heating system will the leaving DB can be accurately measured and will
also allow exterior space zones to reduce the room set always be within 1°F (0.6°C) of the leaving DP condi-
temperature. tion. Commercial grade DP (enthalpy) sensors are not

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 35


866.951.1753 | b i g a s s f a n s.c o m
More powerful than the big bad wolf
THI S IS POWERFO I L X3.0 : A f an t ha t r ei gns sup r eme in size a n d
performance. Its patented airfoil system and maintenance-free
NitroSeal Drive gearbox keep employees happily productive with
c o ol a nd c om forti ng a i rfl o w. Po w er f o il X3 .0. R ule t h e a ir.

EXCEPTIONALLY
ENGINEERED
TECHNICAL FEATURE

recommended for this FIGURE 4 VAV unit schematic and description of components and controls.
application because when
EA
installed in an air duct after Damper C
a humidifier, they require
frequent maintenance and
calibration.22

AFS
RA

PF
With normal room load

Heat Wheel
VAV-EAF Damper D
lines in high-occupancy
buildings, such as class-
rooms, the room target of

CW Coil
HW Coil

AC/H

AFS
SA

FF
40% to 60% room RH can be
maintained. PF
Damper B VAV-SAF
VAV Central Station
Damper A
Air-Handling Unit OA
OA
Figure 4 shows a schematic
layout of a VAV central sta- Heat Wheel Air-to-air heat exchanger selected at 75% sensible Dampers A and B: These dampers modulate to deliver a
effectiveness at full cfm flow. More humid climates with many 45°F DP to the building during ambient conditions in Climate
tion air-handling unit, ambient hours above a 55°F dew point (DP) would select an Zone 2 (Figure 3) by mixing all outdoor air to produce a 45°F WB
which positions the heat enthalpy heat wheel. mixed-air condition delivered to the AC/H.
AC/ H: An adiabatic cooler/humidifier selected at 90% or higher Dampers A and C: Shut-off dampers for night and weekend
wheel between the build- wet-bulb depression efficiency (WBDE) at full cfm flow. Delivery building shutdown.
ing return air (RA) and the air dry bulb (DB) should be within 1°F of the delivery DP after Damper D: This damper is open during morning warm-up and
adiabatic humidification when the VAV flow is 50% of full flow prehumidification (Figure 5) of the building after night or weekend
outdoor air (OA). The heat during cold ambient conditions. Hydration of cold-dry winter shutdown with Dampers A, B and C closed and the heat wheel off.
wheel is sized for full cool- outdoor air is shown in Figure 3.
AFS: Airflow sensors for building pressurization and verification
ing airflow requirements HW Coil: Hot water coil is the heating source for maintaining of ASHRAE Standard 62.1-2019.
a minimum 45°F DP delivery condition to the building during
and selected at a 75% sensi- extreme cold ambient conditions (see Climate Zone 1, Table 1). PF and FF: Pre and final filters.
ble effectiveness. As airflow CW Coil: Chilled water cooling coil to maintain a minimum 55°F VAV-SAF and VAV-EAF: Variable air volume supply air fan and
delivered DB temperature to the building, after heat recovery of exhaust air fan for the air-handling unit (AHU).
requirements are reduced the outdoor air, at ambient conditions above 55°F DP and above
during cold outdoor con- 55°F wet bulb (WB).
ditions, the effectiveness
of the sensible heat wheel opens to provide enough sensible cooling to hold the
increases to 87% at 50% of rated airflow. This is due to delivery setpoint at 55°F (13°C) DB.
the reduced mass flow through the fixed surface and For humid climates with a significant number of
increased “dwell time.” hours above 55°F (13°C) DP, it is advantageous to use
During cold outdoor conditions, with Damper C open an enthalpy heat wheel (total heat wheel) as well as an
and Damper D closed, Dampers A and B modulate to airside economizer and minimum outdoor air. ASHRAE
deliver 45°F (7°C) DB off the AC/H using 100% outdoor Standard 62.1-2019 can be met by modulating Dampers
air. The hot water coil (HW) adds supplemental heat A and D with Damper B closed when the outdoor air
during extreme cold conditions below 23°F (–5°C) DB. temperature is above 75°F (24°C) DB. An outdoor airflow
When Damper A is closed and Damper B is 100% open, sensor (AFS) is needed at Damper A. The total enthalpy
the heat wheel is bypassed, and the supply-side static wheel is activated to lower the temperature and humid-
pressure penalty for heat recovery is eliminated. As the ity of the warm outdoor ventilation air.
supply air temperatures off the AC/H start to rise above The AFS is used to verify ASHRAE Standard 62.1-2019
45°F (7°C), the VAV 100% outdoor air supply fan speeds minimum required outdoor ventilation air to the build-
up to satisfy the interior cooling load at the higher deliv- ing, which also maintains building positive pressure.
ery temperature. When the delivery temperature to the The AC/H is selected for design airflow and a 90%
building exceeds 55°F (13°C), the refrigeration system minimum WBDE. The maximum static pressure pen-
is enabled, and the chilled water cooling coil (CW) valve alty should be 0.14 in. w.g. (35 Pa). This selection will

38 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


TECHNICAL FEATURE

210
200

FIGURE 5 The Prehumidification and Morning Warm-Up Psychrometric 85 190


process using building recirculated air to recharge moisture capaci- 180
tance before building occupancy after night or weekend building
shutdown. Reheat may be provided, as needed, at the air-handling unit Wet- 170
or at the VAV terminal box. B ulb T
80 emp 160
eratu
re—°
F 150

Humidity Ratio—Grains of Moisture Per Pound of Dry Air


140
75
130
120
70
110
100
65
90
60 80
Reheat 55°F DP 70
55
55° 60
50 FW
B
50
45
Hum Adiaba Hydration
40 idifi tic 40
cati
35 on
30
30 RH
25 20% 19°F DP 20
Preheat 10

20 25 30 35 40 45 50 55 60°F 65 70 75 80°F 86°F 90 95 100 105 110 115 120


Dry-Bulb Temperature (°F)

increase to a 95% WBDE at 50% of design airflow, while humidity to drop to 20% or lower, especially after week-
the static pressure will decrease to 0.05 in. w.g. (12 Pa). end or holiday shutdown periods. Morning warm-ups
The marriage of the heat wheels and AC/H in a VAV should include building prehumidification prior to
design results in significant energy savings because building occupancy.
effectiveness increases and the parasitic losses decrease The AC/H component may be used with recirculated
with reduced air mass flow. The building owner benefits building air to prehumidify the building. Figure 5 shows
from the increased energy exchange efficiency and out- the psychrometric process for humidification of the
door air hydration during cold weather. building return air. In Figure 4, Dampers A, B and C are
closed, and the heat wheel is off with Damper D open
Morning Building Prehumidification and the VAV supply fan on. The reheat after the AC/H
And Warm-Up Control Strategy may be provided by a coil downstream of the AC/H in the
In cold climates, it is customary for buildings with day- AHU or by the VAV terminal reheat coils in each zone of
time-only duty cycles to schedule a “morning warm-up” the building.
cycle after night, holiday or weekend shutdowns, when A column from the September 2017 issue of ASHRAE
indoor temperatures are allowed to drop to 60°F (16°C) Journal entitled “It’s All Relative”23 explains the mecha-
or lower to save energy. Moisture migration from the nism by which vapor may be stored inside buildings
building during shutdown often allows indoor relative on hygroscopic materials. Water vapor molecules are

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 39


TECHNICAL FEATURE

stacked in the vapor state on these indoor “storage FIGURE 6 Adiabatic evaporative cooler humidifier section that illustrates the oper-
surfaces” and are released to the room when there is a ation of the device. Water is stored in the tank below the media or in a remote
drop in room relative humidity. This “building capaci- reservoir. The pump circulates the water over the evaporative media. Air passes
through the channels of the media where evaporation occurs. The media is made
tance for moisture storage” may be replenished after from a porous substrate that provides an extended surface for efficient evapora-
night shutdown during the morning prehumidification tion. Water that is not evaporated returns to the sump where it can be filtered
and recirculated over the media. A portion of the water is discharged to drain to
control cycle. The daytime release of the water vapor keep contaminants from concentrating in the water or depositing on the media.
molecules indoors will allow the building to maintain a The float valve makes up water that was used for evaporation and bleedoff.
much more stable indoor relative humidity level during Distribution Header
building occupancy.

Key to Control:
Rigid Media Adiabatic Evaporative Cooler/Humidifier
The rigid media evaporative cooler/humidifier AC/H
is a very simple device that can consistently cool and
humidify the air very close to the saturation line over Evaporative
Media
a wide range of airflows. The media efficiency changes
little with variations in water flow, so there is no need
to modulate the amount of water supplied to the
media to maintain downstream conditions. Earlier
discussions explained how conditions are controlled Float Fill
by dew point. Figure 6 is an illustration of the wet sec- Valve
tion of a wetted media AC/H that shows all the critical Bleed Line
components. Submersible Pump
Since all evaporation of water occurs from the surface Overflow
of the media, there is no excess, unevaporated water Drain
carried downstream. Only water vapor is added to the
air. Contaminants in the water, such as minerals, stay in
the recirculated water and are flushed out by continuous • Monthly, verify that the makeup valve is adjusted
bleed and/or regular flush and dump cycles. and functioning properly.
During operation, the AC/H naturally cools the water • Monthly, check the water conductivity or total dis-
down to the wet-bulb temperature of the air. For this solved solids to ensure there is sufficient bleedoff.
design, the wet-bulb temperature is between 45°F (7°C) • Annually, calibrate the conductivity controller if one
to 55°F (13°C). Legionella bacteria is dormant when the is installed.25
water temperature is below 77°F (25°C). When the water
temperature is 77°F (25°C) to 108°F (42°C), it is favorable Bin Weather Analysis of 22 Northern U.S. Cities
for Legionella bacteria growth.24 Figure 3 shows the heat recovery/humidification psy-
Maintenance of the AC/H is simple: chrometric chart split into three cold weather climate
• If necessary, use nonoxidizing biocides approved by zones for ambient wet-bulb (WB) conditions below 55°F
the media manufacturer and the authority having juris- (13°C). The control sequence for the VAV-AHU when
diction. Oxidizing biocides such as chlorine will destroy ambient WB is 45°F (7°C) to 55°F (13°C) would be to
the media. allow the AC/H to generate a range of saturated delivery
• The media, water distribution and sump should be DP conditions from 45°F (7°C) to 55°F (13°C). The refrig-
flushed quarterly. eration is off in Climate Zones 1 to 3. In Climate Zone 3,
• Monthly inspection of the media, water distribution all outdoor air would be furnished to the AC/H through
and sump will warn the team if more frequent cleaning Damper B with Dampers A and D closed. The heat wheel
is necessary. Quarterly cleaning is usually sufficient if would be off, and the supply-side parasitic loss would be
the air has been filtered and the water is of good quality. shunted out of the system. The AC/H cooling in Climate

40 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


ASHRAE eLearning
The Complete HVAC&R Learning Experience

No Travel Required • Learn When Convenient


Access When Needed • Track Performance

CORPORATE PROGRAMS AVAILABLE

For the complete course catalog visit ashrae.org/elearning


or contact elearning@ashrae.org
From the depths of outer space
to sustainability for the human race.
At Mitsubishi Electric, the innovative thinking that we put into manufacturing satellites for space is the same
thinking we put into the sustainability of our HVAC systems. From heating and cooling in the most extreme
Canadian climates to the utmost flexibility in HVAC design, we’ve been raising the bar for close to 100 years.
Because we believe that “amazing” should apply to everything you do.

The Mitsubishi Electric Advantage


• Excellent for LEED, Passive House, and
Zero Carbon Building-Design Certifications
• Bring your vision to life with the ultimate
HVAC design flexibility
• Strong Canadian customer support team

Learn more at
www.mitsubishielectric.ca/en/hvac/professionals

PCA M-Series City Multi


Indoor Unit Outdoor Unit N-Generation
TECHNICAL FEATURE

Zone 3 has energy efficiency ratios (EERs) that approach by 33.3% compared to a 55°F (13°C) supply air tem-
100. perature delivery. Since there are 6,561 hours/year
Building ventilation rates would be far in excess of in Climate Zone 2 and 3, fan energy savings would be
the ASHRAE Standard 62.1-2019 minimum outdoor significant.
air requirements of 15 cfm/person (7 L/s per person) at Using the same Seattle bin condition of 47°F (8°C)
the higher VAV delivery temperatures. Room RH in the ADB/45°F (7°C) MCWB and assuming a 50% VAV flow
range of 40% to 60% would be maintained. Table 1 shows of 20,000 cfm (9439 L/s) over the 2,747 hours/year in
for the northern cities that an average of 44.6% of annual Climate Zone 3, given a central plant cooling energy
hours land in Climate Zone 2. The heat wheel is able to consumption at 0.8 kW/ton (0.2 kW/kW) of cooling,
transfer the heat required to maintain the 45°F (7°C) DP we can estimate sensible cooling energy avoidance in
delivery off the AC/H unit with 100% outdoor air through Climate Zone 3 at 40,289.33 kWh/year. At the Seattle
the modulation of Dampers A and B to reach the 45°F electrical energy cost of $0.108 per kWh, avoided cooling
(7°C) WB condition. energy is estimated to be $4351.24 per year.
Only 9.2% of the average annual hours reside in Assuming that the average VAV supply fan flow is
Climate Zone 1, requiring additional heating by the hot 50% of full VAV flow for all ambient conditions in
water coil to meet the 45°F (7°C) DP condition for a tar- Climate Zones 1, 2 and 3, the boiler energy avoided
get value of 40% RH in the building. through heat recovery is estimated at 71,263 therms
Clearly, western U.S. climates and arid climates at when a boiler and piping loss factor of 0.8 is applied.
higher altitudes benefit the most from this VAV design The approximate value of the annual avoided energy
strategy for hydration of outdoor air. at a Seattle energy cost of $1.127/therm would be
$80,313.40. If the factory cost for heat recovery and
Seattle Simple Payback Through adiabatic humidification components is increased by
Humidification Cost Avoidance 25% to reflect the sales representative and mechanical
The factory-installed cost of a high-performance heat contractor’s markup, the simple payback for a deliv-
wheel and a 12 in. (305 mm) deep rigid media AC/H ered heat wheel and AC/H would be 1.06 years. Other
is estimated to be $68,000 ($1.70/supply cfm) for a west coast cities such as Vancouver, Portland and San
40,000 cfm (18 878 L/s) custom AHU costing $267,350. Francisco will reflect similar paybacks for avoided
For Seattle, hours per year at each average dry bulb humidification energy.
(ADB) and mean coincident wet-bulb (MCWB) condi- More difficult to assess in Climate Zone 3 is the value
tions, were used to estimate humidification energy to a building owner of increasing the outdoor air venti-
avoidance provided by the heat wheel in Climate Zones lation rate above the minimum code requirement of 15
1, 2 and 3. cfm/person (7 L/s/person) required by ASHRAE Standard
Not included in this energy avoidance are the fan 62.1-2019. Studies have attempted to assign a value to
energy savings in Climate Zone 2 and 3 when the VAV increased worker productivity and the reduction in
delivery temperature to the building is below the short-term sick leave absence due to better outdoor air
conventional 55°F (13°C) DB setpoint. If the VAV ter- ventilation.1
minal boxes in the building are set to satisfy the room As a check against the bin hour method tabulation
cooling load at 55°F (13°C) delivery temperature, shown in Table 1, Seattle TMY2 hour-by-hour typical
temperatures lower than 55°F (13°C) will result in year points may be overlaid on the psychrometric chart
reduced fan flow into and out of each core zone where (Figure 7). There are zero hours in Climate Zone 1, 3,836
the cooling load is fairly constant. A typical or aver- hours in Climate Zone 2 and 3,231 in Climate Zone 3 or
age ambient condition for Climate Zones 2 and 3 in a total of 80.7% of the annual Seattle hours. Hydration
Seattle is the bin temperature of 47°F (8°C) ADB/45°F and sensible cooling of 100% outdoor air are produced at
(7°C) MCWB. The VAV box delivery to the core zones a very low energy cost for Climate Zones 2 and 3. Central
would be approximately 45°F (7°C) DB at 45°F (7°C) refrigeration plants may be shut down for Climate Zones
DP. If the room target temperature is 75°F (24°C) 2 and 3 climate conditions, the majority of which occur
DB, then the airflow to that zone would be reduced in the spring, winter and fall.

42 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


AIRFLOW MEASUREMENT SOLUTIONS

A MEASURABLE DIFFERENCE FOR OVER 35 YEARS!


Outdoor Air Delivery Monitoring
Contact EBTRON for the Demand Control Ventilation Systems
name of your local Fan & Fan Array Airflow Measurement
representative and a copy
Building Pressure Solutions
of our condensed
product catalog today!
Hospital & Medical Facility Airflow Measurement
Laboratory & Clean Room Pressurization

EBTRON, Inc. | 1663 HWY 701 S., Loris, S.C. 29569 | Internet: EBTRON.com | Phone: 800 2 EBTRON | email: sales@ebtron.com
TECHNICAL FEATURE

Wet 200
-B ulb
Tem
FIGURE 7 Seattle TMY2, hour by hour, typical year ambient conditions p erat
ure—
overlay on Figure 3. In Climate Zone 1 there are zero annual hours. °F 180
There are 3,836 hours per year between 23°F DB and 45°F WB. There
are 3,231 annual hours from 45°F WB to 55°F WB, or a total of 80.7%
of the year, that the adiabatic cooler/humidifier can furnish beneficial
outdoor air humidification without the assistance of the hot water coil 80 160
in the central station unit and provide energy-efficient sensible cooling
without refrigeration.

Humidity Ratio—Grains of Moisture Per Pound of Dry Air


140

120
70

100

RH
60%

RH
60 80

40%
Room Target Range 70°F – 75°F DB
DB 40% – 60% RH
60
50
45°F DP/DB/WB Room Load
Adia 45°F DP 40
Seattle Winter Design 40 bati
cH 55°
23°F DB/22.1°F WB umi FW
30 dific B Outdoor Air Hydration
ati o
23°F n
20 Heat Recovery 20

20°F DP
Climate Zone 1 Climate Zone 2 Climate Zone 3
10 20 30 40 50 60 70 80 90 100 110 120
Dry-Bulb Temperature (°F)

During the spring and fall outdoor air often contains refrigerant. Water vapor released to the atmosphere
large amounts of airborne pollens that can cause aller- returns to the earth as rain, sleet or snow.
gies in susceptible humans. Pollen ranges in size from
10 microns to 100 microns and should be removed Conclusions
from the outdoor air before it is supplied to the Through the 50 years that VAV systems have been used
building. in the HVAC industry for commercial building air-con-
When wet, the 12 in. (305 mm) deep rigid media ditioning systems, the use of airside economizers to save
pads in the AC/H have 90% or better removal efficiency heating and cooling energy have often compromised
of pollen spores larger than 10 microns in diameter. the fresh air fraction being furnished to meet code or
AC/Hs are often referred to as “wet scrubbers.” ASHRAE Standard 62.1 and have wasted energy.26 Dry
The use of air-to-air heat exchangers (sensible heat indoor conditions in winter have led to an increase
wheels) and rigid media AC/Hs are key to the success in respiratory infections and the spread of airborne
of this system including ease of control, environ- pathogens such as the influenza virus. IEQ and VAV had
mental health, energy savings and low maintenance. become two mutually exclusive acronyms.
Refrigerant 718, better known by its chemical formula This VAV design offers the hydration of all outdoor
H2O, has zero global warming potential (GWP), is inex- air in cold climates and offers resiliency in the face of
pensive, nonflammable, nontoxic and is a sustainable climate change. In the future, more and more annual

44 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


MANUFACTURED
IN ROCKMART, GA

hours are expected to move from Zone 1 into Zones 2 and


3 shown in Figure 3. If the building being analyzed has
less than a 24/7/365 duty cycle, daytime ambient condi-
tions in cold climates will have more ambient hours in
Zones 2 and 3.
There appears to be a direct correlation between low
WE DONÕT PUT
indoor RH and artificially high air change rates with the YOUR EGGS IN
spread of airborne pathogens in winter. If we can cost ONE BASKET
effectively maintain a 40% to 60% indoor RH in win-
ter while simultaneously reducing supply and return/
exhaust VAV fan energy costs, why not do it? Quoting
another ASHRAE Journal author from a recent column,
“...but for most building types, we have yet to find any
that perform better on a life-cycle cost basis than a ‘well
designed’ VAV system.”27 When it comes to your steam generation needs,
keeping all your eggs in one basket by relying
on a single firetube boiler can be a huge risk,
COVID-19 Pandemic and ASHRAE because if your boiler goes down, chances
Best Practices for Mitigation are you will lose production. Miura’s Modular,
After the substantial completion of this article On-Demand steam solution is like having every
egg in its own basket. Plus, Miura provides N+1
and prior to its publication, an ASHRAE Epidemic redundancy with less total installed horsepower,
Task Force was formed that is chaired by William P. providing cost savings and unparalleled
Bahnfleth, Ph.D., P.E., Presidential Member/Fellow reliability and efficiency.
ASHRAE. At that time, the SARS-CoV-2 virus had
shown itself to be an airborne pathogen easily spread
indoors by an infectious aerosol. The Epidemic Task
Force recommends the following steps to mitigate the
spread of COVID-19 indoors.
• Air-handling systems that permit building air recir-
culation should increase outdoor air ventilation above
code minimums, and consider installing MERV 13 filters
if they are not in place.
• Control indoor relative humidity between 40% to
60% RH. Miura’s LX-300 in M.I. configuration
• Flush the building prior to occupancy with all offers a range of advantages.

outdoor air to remove any residual infectious aerosols


indoors.
The authors would like to point out that all three of
these remedial actions are addressed in this article. The Turn-Key Boiler Room Solutions
section entitled “Morning Building Prehumidification
Full Steam in Under Five Minutes
and Warm-Up Control Strategy” would need to be
accomplished with all outdoor air in lieu of recirculated Optimum In-Service Efficiency
air. Online Monitoring Systems

Acknowledgments us.info@miuraz.com
The authors would like to thank United Metal Products 888.309.5574
of Tempe, Ariz., for their assistance in providing cus- miuraboiler.com
tom air-handling unit costs for the direct evaporative

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 45


TECHNICAL FEATURE

cooling/humidification and sensible heat wheel air-to- human exposure to humidity in occupied buildings.” ASHRAE
Transactions 91(1):611 – 621.
air heat recovery systems under consideration. 3. Pantelic, J., K.W. Tham. 2013. “Adequacy of air change rate
as the sole indicator of an air distribution system’s effectiveness
References to mitigate infectious disease transmission caused by a cough
release in the room with overhead mixing ventilation: a case study.”
1. Seppänen, O., W.J. Fisk, O.H. Lee. 2006. “Ventilation and
HVAC&R Research 19(8):947 – 961.
performance in office work.” Indoor Air 16(1):28 – 36.
4. Klepeis, N.E., C.W. Nelson, W.R. Ott, J.P. Robinson, et al. 2001.
2. Sterling, E.M., A. Arundel, T.D. Sterling. 1985. “Criteria for “The National Human Activity Pattern Survey (NHAPS): A resource
for assessing exposure to environmental
pollutants.” Journal of Exposure Analysis and
Environmental Epidemiology 11(3):231 – 252.
5. Taylor, S., M. Tasi. 2018. “Low indoor-
air humidity in an assisted living facility is
correlated with increased patient illness and
cognitive decline.” Proceedings ISIAQ 744:1 – 8.
6. Gilbert, J.A., M.J. Blaser, J.G.
Caporaso, J.K. Jansson, et al. 2018. “Current
understanding of the human microbiome.”
Nature Medicine Review 24(4):392 – 400.
7. Gilbert, J.A., B. Stephens. 2018.
“Microbiology of the built environment.”
Nature Reviews, Microbiology 16(8):661 – 670.
8. Kudo, E., E. Song, L.J. Yockey, T. Rakib,
et al. 2019. “Low ambient humidity impairs
barrier function and innate resistance against
influenza infection.” Proceedings of the National
Academy of Science 116(22): 10905–10910.
9. Reiman, J.M., B. Das, G.M.Sindberg,
M.D Urban, et al. 2018. “Humidity as a non-
pharmaceutical intervention for influenza
A.” PLoS ONE 13(9).
10. Lowen, A.C., J. Steel. 2014. “Roles
of humidity and temperature in
shaping influenza seasonality.” Journal of
Virology 88(14):7692 – 7695.
11. Taylor, A.S., C. Machado-Moreira. 2013.
“Regional variations in transepidermal
water loss, eccrine sweat gland density,
sweat secretion rates and electrolyte
composition in resting and exercising
humans.” Extreme Physiology & Medicine. 2. 4.
https://doi.org/10.1186/2046-7648-2-4.
12. Pross, N. 2017. “Effects of dehydration
on brain functioning: a life-span
perspective.” Annals of Nutrition and
Metabolism 70(suppl 1):30 – 36.
13. Junker, J., et al. 2013. “Clinical impact
upon wound healing and inflammation in
moist, wet, and dry environments.” Advances
in Wound Care 2(7): 348 – 356.
14. Galson, S.K. 2008. “Prevention of
deep vein thrombosis and pulmonary
embolism.” Public Health Reports
123(4):420 – 421.
15. Sunwoo, Y., C. Chou, J. Takeshita,
M. Murakami, et al. 2006. “Physiological
and subjective responses to low relative
humidity in young and elderly men.” Journal
of Physiological Anthropology 25(3):229 – 238.
16. Zhu, G., Z. Janjetovic, A. Slominski.
2014. “On the role of environmental

46 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


TECHNICAL FEATURE

humidity on cortisol production by epidermal keratinocytes.” “Survival of a Pseudomonas fluorescens and Enterococcus
Experimental Dermatology 23(1):15 – 17. faecalis aerosol on inert surfaces.” International Journal
17. Zimmerman, E. 2017. “Influence of temperature, relative of Food Microbiology 55(1 – 3):229 – 34.
humidity and carbon dioxide levels on student well-being and Taylor, S. 2014. ”Infectious microorganisms do
performance.” Maturaarbeit Schlussbericht G4f Betreuung (personal not care about your existing policies.” Engineered
commuication). https://bit.ly/3k9ecVE
Systems (11):42.
Rate this Column
18. Block, S. 1953. “Humidity requirements for mold growth.” Appl Tang J.W. 2009. “The effect of environmental
Microbiol 1(6):287 – 293. ncbi.nlm.nih.gov/pmc/articles/PMC 1056928. parameters on the survival of airborne infectious agents.” Journal of
19. Scofield, C.M., J.R. Taylor. 1986, “Building ventilation: a heat the Royal Society Interface 6(Suppl 6):S737 – S746.
pipe economy cycle.” ASHRAE Journal (10).
20. Paliaga, G., et al. 2019. “Eliminating
overcooling discomfort while saving
energy.” ASHRAE Journal 61(4):64.
21. Arens, E., et al. 2018. “Sunlight and
indoor thermal comfort.” ASHRAE Journal
(7):12 – 21.
Helping Leaders Create
22. Harriman, L. 2009. “Humidity Control
and Design.” Atlanta: ASHRAE.
23. Lstiburek, J. 2017. “Magic and mystery
Healthy Working Environments
of the water molecule: it’s all relative.”
ASHRAE Journal 59(9):68 – 74.
24. ASHRAE Guideline 12-2020, Minimizing
for Hard-Working People
the Risk of Legionellosis Associated with Building
Water Systems.
25. 2016 ASHRAE Handbook-HVAC Systems
& Equipment, Chap. 41, “Evaporative Air-
Cooling Equipment.”
26. Koenigshofer, D. J. Roberts. 2018. “Do
OA economizers make ‘cents’ in hospitals.”
ASHRAE Journal (11):12 – 21.
27. Taylor, S. 2018, “Making VAV great
again.” ASHRAE Journal 60(8):64 – 71.

Bibliography
Adams, R.I., A.C. Bateman, H.M. Bik, J.F.
Meadow. 2015. “Microbiota of the indoor
environment: a meta-analysis.” Microbiome
3:49.
Cox, C.S. 1998. “The Microbiology of Air.”
In: L. Collier, A. Balows, M. Sussman (Eds.)
Topley & Wilson’s Microbiology and Microbial
Infections. 9th Edition. London; Arnold,
Oxford University Press, pp. 339 – 350. ESC-SERIES
Kembal, S.W., E. Jones, J. Kline, D. Semi-Custom Evaporative Cooling Technology
Northcutt, et al. 2012. “Architectural design
influences the diversity and structure of the ✔ 12 Two-Stage Models Ranging from 2,400 to 56,000 CFM
built environment microbiome.” International ✔ Indirect, Indirect/Direct, and Direct with Heat Exchanger Options Available
Society for Microbial Ecology Journal 6:1469 – 1479.
Kramer A., I. Schwebke, G. Kampf. ✔ Available with Indirect Fired or Hot Water Heating Section
2006. “How long do nosocomial pathogens
persist on inanimate surfaces? A systematic
review.” BMC Infectious Diseases 6(1):130.
Lowen, A.C., S. Mubareka, J. Steel, P.
Palese. 2007. “Influenza virus transmission
is dependent on relative humidity and
temperature.” PLoS Pathogens 3(10):e151.
Noti, J.D., F.M. Blachere, C.M. McMillen,
W.G. Lindsley, et al. 2013. “High humidity
leads to loss of infectious influenza virus from
simulated coughs.” PLoS One 8(2):e57485. www.cambridgeair.com • 800.899.1989
Popkin, B.D, K.E. Anci, I.H. Rosenberg. S-Series HTHV Heaters • M-Series Make-Up Air • ESC-Series Evaporative Cooling
2010. “Water, hydration and health.” To learn more  www.cambridgeair.com
Nutrition Reviews 68(8):439 – 458.
Robine, E., D. Derangere, D. Robin. 2000.

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 47


TECHNICAL FEATURE

Calculating Airflow
Rates, Cooling Loads
In Commercial Kitchens
BY IURII A. TABUNSHCHIKOV, FELLOW ASHRAE; ALEXANDER N. KOLUBKOV; MARIANNA M. BRODACH; IURII S. AVAKIAN, ASSOCIATE MEMBER ASHRAE

This article describes the method of calculation for airflow rate and cooling loads
of ventilation and air-conditioning systems in commercial kitchens that takes into
account full heat gains and moisture loads. The accuracy of this method is not abso-
lute but is sufficient for designing ventilation and air-conditioning system air condi-
tioning systems that successfully handle peak loads and provide desired air tempera-
ture and humidity in an occupied zone. Unlike the simplified method, in which only
sensible heat is considered, this calculation method considers total loads and provides
the most accurate result. This method is described in Reference 1.

In general terms, the calculation algorithm is as fol- where


lows: find heat and moisture loads, find airflow rates, Q 1 = Total heat gains from kitchen appliances, kW
set the supply air temperature and calculate the indoor Q 2 = Total heat gains from people, kW
air parameters of the kitchen. If the result is not in the Q 3 = Heat gains from electrical lighting, kW
desired range, set another supply air temperature and/ Q 4 = Solar heat gains through windows and walls, kW
or increase the exhaust airflow rate and repeat all calcu- Q 5 = Total heat gains from outdoor air, kW
lations of the indoor air parameters.
Let’s look at these steps in detail. Q 1 can be found by using Tables 5A through 5F in
Reference 2 for hooded and unhooded appliances dur-
Calculation of Heat and Moisture Loads ing its idle (ready-to-cook) and cooking conditions. In
Equation 1 describes total heat gains in the kitchen (kW): estimating appliance load, probabilities of simultaneous
use must be considered.2 References 3 and 4 recommend
Q tot = Q 1 + Q 2 + Q 3 + Q 4 + Q 5 (1) multiplying the heat gain from cooking appliances by the
Iurii A. Tabunshchikov is president of ABOK and professor at Moscow Institute of Architecture (State Academy), Moscow. Alexander N. Kolubkov is vice president of ABOK and
director of LLC PPF “AK,” Moscow. Marianna M. Brodach is vice president of ABOK and professor at Moscow Institute of Architecture (State Academy). Iurii S. Avakian is certified
ABOK specialist and chief HVAC specialist at LLC “APEX project bureau,” Moscow.

48 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


TECHNICAL FEATURE

reduction factor called the simultaneous coefficient, TABLE 1 Recommended values for simultaneous coefficient.3
which is the quotient of the number of appliances in use KITCHEN TYPE SIMULTANEOUS COEFFICIENT K SIM
and the total number of appliances (Table 1). Hotel 0.6 – 0.8
Equation 2 describes total moisture emission in the Hospital 0.5 – 0.7
kitchen (kg/h): Cafeteria 0.5 – 0.7
School 0.6 – 0.8
W = W1 + W2 + W3 (2)
Restaurant 0.6 – 0.8
Industrial 0.6 – 0.8
where
W1 = Moisture emission from people, kg/h
W2= Moisture emission from kitchen appliances, where
which are not equipped with exhaust hoods, kg/h L ad = Volume airflow rate from the adjacent spaces,
W3 = Moisture emission from outdoor air, kg/h m3/h
ρad = Density of the air that comes from the adjacent
W2 can be found by using Tables 5A through 5F from spaces, kg/m3
Reference 2 or Table A1 from Reference 5, in which the The supply mass flow rate Msup (kg/h) is estimated from
data about specific moisture emissions from different the air-balance equation for the kitchen as compensa-
types of kitchen appliances is provided. tion the exhaust air:

Calculation of the Exhaust Airflow Rate M sup = M ex − M ad (5)


Exhaust mass flow rate is described by Equation 3 as the
sum of exhaust airflow rates of exhaust hoods and gen- Calculation of the Air Parameters in the
eral exhaust ventilation of the room (in the presence of Occupied Zone of the Kitchen
it) (kg/h): This algorithm of calculations is also described in
Reference 1. To calculate supply airflow rate in a com-
M ex = ∑ ( Loi ρi ) + Lgv ρgv (3) mercial kitchen, we first need to find the process line
of the air parameters in this kitchen. The process line ε
where (kJ/kg) is a quotient of total heat gains in the kitchen Q tot
Loi = Exhaust volume airflow rate in the i th kitchen and total moisture emission W:
exhaust hood or ventilated ceiling (can be
found by the calculation method described in 3600Qtot (6)
ε=
W
Reference 3), m3/h
Lgv = Volume airflow rate, exhausted by general Calculation of ε for the commercial kitchen cannot be
exhaust ventilation from the upper zone of the precise, but using Equation 6 is an acceptable rough esti-
kitchen, m3/h mation. According to Reference 4, the value of ε varies from
ρi = Density of the air, exhausted by the i th kitchen 5000 kJ/kg to 7000 kJ/kg (2,150 Btu/lb to 3,009 Btu/lb) dur-
exhaust hood or ventilated ceiling, kg/m3 ing the maximum load of the kitchen equipment, depend-
ρgv = Density of the air, exhausted by the general ing upon the type of catering enterprise. To estimate the
exhaust ventilation from the upper zone of the ε value, it is acceptable to take the average value from this
kitchen, kg/m3 range, which omits calculating moisture emissions.
The value of enthalpy (kJ/kg) of air in the occupied zone of
Calculation of the Supply Airflow Rate the kitchen is estimated from the energy balance equation:
The amount of air exhausted from the kitchen should
be at least 10% higher than the airflow supplied to the hoz =
(3600Q tot + M sup hsup + M ad had ) (7)
kitchen.3 The mass flow rate (kg/h) that comes from the M ex
adjacent spaces is defined as following: where
Mad = Lad ρad (4) hoz = Enthalpy of the supply air, kJ/kg

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 49


TECHNICAL FEATURE

had = Enthalpy of the air of adjacent spaces, kJ/kg Conclusions


This calculation method takes into account the latent
Enthalpy of the mixture of supply air and air from the heat in the kitchen. This allows for achieving not only
adjacent spaces (kJ/kg) is estimated from the same kind the desired temperature value, but also the desired air
of equation: humidity value in the working area. The calculation

hmix =
(M h
sup sup + M ad had ) (8)
algorithm requires passing through a bigger number
of operations, but they can be easily turned into a com-
M ex puter spreadsheet.

To find hsup, the designer must choose the supply air References
temperature (usually 3°C to 5°C [5°F to 9°F] below the 1. ABOK. 2019. “R NP ABOK: Recommendations for the Design
of Ventilation and Air-Conditioning Systems of Public Catering
designed indoor air temperature) and then find the Enterprises/Public Catering Enterprises. Ventilation and Air
value of hsup by using the Mollier chart or by calcula- Conditioning,” pp. 7 – 17. (In Russian.)
tion taking into account the cooling process (in the 2. 2017 ASHRAE Handbook—Fundamentals.
presence of it). Indoor air parameters can be found by 3. Halton. 2007. “Halton Kitchen Design Guide.”
using the Mollier chart. From the point that character- 4. TSNIIEP of Engineering Equipment. 1975. “Recommendations
for the Calculation of Ventilation and Air
izes the supply air parameters (knowing the ε value), a Conditioning Systems in the Hot Shops of
designer should draw the process line of the indoor air. Catering.” Moscow:Gosgrazhdanstroy. (In
At the point of intersection of the process line and the Russian.)
5. Association of German Engineers.
line of the calculated indoor air enthalpy, the rest of 2006. “VDI 2052, Ventilation Equipment for https://bit.ly/3k9ecVE
the parameters of the indoor air can be found. Rate this Column
Kitchens.”

50 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


2020 ASHRAE TECHNOLOGY AWARD CASE STUDIES

Chiller Plant
Optimized
Without Capital
Expenditures

All savings in the 640,000 ft2 (55,700 m2) tower were gained from
modifications to existing equipment and controls that increased
efficiency. Since 2005, the EUI has been reduced 39%.

BY KELLEY WHALEN, MEMBER ASHRAE; JASON BROOKS, P.E., MEMBER ASHRAE; ERIC MOBLEY, ASSOCIATE MEMBER ASHRAE

52 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


HONORABLE MENTION | 2020 ASHRAE TECHNOLOGY AWARD CASE STUDIES

The ADTRAN East Tower in Huntsville, Ala., used several


optimization methods to radically reduce energy use
without costly equipment replacements. The project was
completed without any capital expenditures; all results
were gained strictly from modifications to the existing
equipment and controls to increase efficiency. These
methods saved over $71,326 annually in energy costs
with a simple payback of 1.86 years.
The chiller plant consists of three and engineering calculations on
440 ton (1547 kW) chillers, three trended and measured data, sav-
490 ton (1723 kW) cooling towers, ings were determined (see Cost
three constant volume chilled water Effectiveness section).
pumps, three condenser constant In addition to these savings,
water pumps, two heat exchangers, changes have been implemented,
four auxiliary pumps, and one water achieving the following:
heater. • Increased business continuity
from changes that make it unneces-
Energy Efficiency sary for ADTRAN to run more than
At the beginning of the proj- two chillers, which also creates
ect, ADTRAN was consuming another layer of redundancy in the
28,390,000 kWh annually on a system if a chiller goes down.
campus level, which is comprised of • Proper cooling of the East Tower
three towers that occupy 1.04 mil- D-Wing, which has historically had
lion ft2 (96 619 m2). The East Tower, issues with cooling, through chang-
which accounts for 640,000 ft2 ing the system to allow more water
(59 458 m2) of the total footprint flow.
(slightly over 60%) consumes about Given that this project was com-
60% of that total use. Changes pleted without any capital expendi-
implemented in this project are tures, all results were gained strictly
saving ADTRAN over 950,000 kWh
annually in energy consumption
from just targeting the chilled water
plant that serves the East Tower. Building at a Glance
The savings are based on mea-
surement and verification of data ADTRAN East Tower
gathered over several years of build- Chilled Water System Optimization
ing automation system (BAS) data
and actual power meter data from Location: Huntsville, Ala.

ADTRAN and the engineering com- Owner: ADTRAN


pany’s power loggers for over 10 Principal Use: Office building, laboratory spaces, data
months. Using regression analysis centers, electronics testing

Gross Square Feet: 640,000


Kelley Whalen is facilities supervisor–energy management,
HVAC & Electrical at ADTRAN. Jason Brooks, P.E., is direc- Conditioned Square Feet: 640,000
tor, engineering, and Eric Mobley is energy engineer at Substantial Completion/Occupancy: December 2018
Sain Engineering Associates, Inc.

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 53


2020 ASHRAE TECHNOLOGY AWARD CASE STUDIES

from modifications to the existing equipment and con- FIGURE 1 EUI history.
trols that increased efficiency. 140
135 134
130 130 EUI
Existing Operation Before This Retrocommissioning Project 125 121
Trend (kBtu/ft2)
In 2005, ADTRAN created an energy program, and 120 118 118
115
since then hundreds of ECMs and many retrocommis- 110 109 108 110 107 110
104 103
sioning (RCx) projects had already taken care of the low- 105
100
hanging fruit. 95 94
89
Below are highlights of activities that took place under 90
85 82
this retrocommissioning project: 80
• Trended over 300 points pertaining to the plant in 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019
Since 2005 baseline, EUI has been reduced 39%. (Revised 1/8/20)
one-minute time intervals, capturing over 131 million
readings using the BAS, which aided in analysis of the
plant’s current operation and aided in monitoring as from the building automation system, allowing the sys-
changes were made. tem to have better response times to changing building
• Installed four power loggers/analyzers capturing conditions.
over two million power consumption readings over 10 • Tested all new programming through various
months. This data is used for measurement and veri- scenarios, temperatures, flows, modes of operation and
fication of savings calculations. Virtually all the equip- building loads to ensure that the sequences would work
ment in the building was monitored including chillers, across all situations.
pumps, cooling towers and air-handlers. Space temper- As this project was specific to the East Tower, the fol-
atures and water temperatures are also trended. lowing descriptions detail the previous operation of
• Developed equations to calculate plant energy use for some of the key pieces of equipment and the associated
individual equipment and total plant energy consump- changes made to them.
tion, which allowed for the modeling of the plant’s energy • Chiller Operation. If the chilled water supply tem-
use to aid in decision-making and savings calculations. perature (CHWST) got 2.5°F (1.38°C) above the CHWST
These equations were developed using regression analysis setpoint of 38°F (3.3°C) for 30 minutes, an additional
of power data from the loggers versus an independent chiller is enabled and starts until the difference between
variable (such as speed for pumps) from the BAS. the CHWST and chilled water return temperatures
• Performed functional testing, evaluated all existing (CHWRT) gets below the setpoint. The chiller add se-
plant programming, monitored the chilled water system quence was modified so that the ∆T required for another
and reviewed several years of historical building data. chiller to come on varies with time of day (see Innova-
• Modified chilled water flow and condenser wa- tion section). A CHWST reset was also added based off
ter flow to maximize the amount of cooling capacity building load. A reset was programmed previously, but
delivered to air-handling units with the highest cooling it was not able to operate correctly due to the decreased
demand, which allowed those units to meet their cooling flow from the chillers. This was rectified in this project.
demand, a feat the units previously could not achieve. • Cooling Tower Operation. The cooling towers
• Simulated the building and chiller plant in multiple were staged so that once one of them reached its max
iterations of models with various configurations to help speed, the next tower would turn on and ramp up. The
visualize the effects that various changes would have on condenser water setpoint was set to 78°F (25.5°C). The
the system. cooling towers staging was modified so they ramp to-
• Developed new energy saving sequences of opera- gether to take advantage of the power savings associated
tion by reprogramming 30 inefficient existing programs with the fan laws. The condenser water setpoint was
while measuring the actual plant energy consumption programmed to track the wet-bulb temperature with an
reductions. offset so that the cooling towers would output the coldest
• Modified control setpoints so they are automatically water possible to increase the efficiency of the chillers.
calculated based on real-time building inputs received • Heat Exchanger (HX) 2 operation. The auxiliary

54 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


KEEP YOUR
OPERATIONS
FLOWING.
Glycol and Hot or Chilled Water · Cooling Towers · Energy Sub-Metering

At Badger Meter, we know hydronic system applications are rigorous and have strict flow measurement
requirements. Flow meters are essential to maintain long-term accuracy, reliability and repeatability within
those applications. We offer a wide variety of metering technologies—from ultrasonic, electromagnetic to
positive displacement flow meters. Badger Meter has the proven tools and expertise to help you manage
your critical resources and keep your operations flowing.

Discover how our flow meters can


improve operational efficiencies in
your hydronic system applications:

www.badgermeter.com/HVAC
2020 ASHRAE TECHNOLOGY AWARD CASE STUDIES

pumps for the HX2 and self-contained


unit (SCU) loop, used to run continuously
without regard for if the HX2 leaving water
temperature was below its setpoint. Pump 8
operation was changed to have a mini-
mum speed of 15%. The programming was
changed to shut the pump off if the leaving
water temperature from HX2 dropped 10°F
(5.5°C) below its setpoint. Pump 8 will not
cut on again until the HX2 leaving water
temperature raises 5°F (2.7°C) above its
setpoint. Pump 10 operation was changed
so that it runs at a constant 20% instead of
35%.
• HX1 operation. Used only when the
The East Tower chiller plant.
chiller plant has the waterside econo-
mizer mode enabled, which occurs when the closed as the discharge air temperature dropped below
outside air temperature is below waterside economizer its setpoint.
mode enabled setpoint. Once the waterside econo- These programming modifications allows an addi-
mizer is enabled, the chillers are shut off and isolation tional 45,000 cfm (21 238 L/s) of cool outside air,
valves on the condenser and chilled water side close which will reduce CO2 levels and increase indoor
to isolate the chillers. Next, the cooling tower fans air quality during early morning operation of the
ramp to a speed of 100%. The cooling tower attempts to building.
produce condenser water at temperatures of near 35°F See the Maintenance and Operation section for discus-
(1.6°C). With the changes made to the airside econo- sion on occupant comfort.
mizer operation, the plant can stay inside waterside
economizer mode for much longer stretches of time. Innovation
• Airside Economizer Operation. See indoor air To address the single setpoint that added a chiller regard-
quality section. less of time of day or day of the week, the add sequence was
changed to take into account the load pattern through-
Indoor Air Quality out the day. From Figure 2, it is observed that the load of
The original operation of the air handlers would the building varies throughout the day.
allow for the units to go into economizer mode if it was Monday thru Friday 4 a.m. to 8 a.m.: A second chiller
Monday through Friday between 7 a.m. and 5 p.m. and will be added if the CHWST exceeds the chilled water
the air handler was in cooling mode with a return air supply setpoint by 3.5°F (1.9°C), the third at 7.0°F
dew-point temperature greater than the outside air dew- (3.9°C). The time from 4 a.m. to 8 a.m. shows a sharp
point temperature but less than 50°F (10°C), outside air increase in the rate of change of the building load due to
dry-bulb between 65°F (18.3°C) and 40°F (4.4°C) and the equipment turning on (Figure 2).
chilled water valve greater than 10% open. The updated Monday thru Friday 8 a.m. to 5 p.m: A second chiller
sequence was modified to allow for airside economizer will be added if the CHWST exceeds the chilled water
operation if the air handler is occupied and in airside supply setpoint by 4.5°F (2.5°C), the third at 7.5°F
economizer mode, regardless of time of day and day of (4.1°C). The time from 7 a.m. to 5 p.m. shows a gradual
week, and the outside air dry bulb is less than 68°F (20°C). increase in the rate of change. This is partly due to the
In addition, instead of having the air handler come out typically increasing outside air temperature.
of economizer mode when the outside air temperature All other times: A second chiller will be added if the
is below 40°F (4.4°C), the sequence was modified so CHWST exceeds the chilled water supply setpoint by
that the outside air damper for the unit would modulate 6.5°F (3.6°C) the third at 8.5°F (4.7°C). These times were

56 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


2020 ASHRAE TECHNOLOGY AWARD CASE STUDIES

observed to be the lowest load times and the FIGURE 2 Building load.
most constant load times. 8 am to 5 pm
4 am to 8 pm
350
Maintenance and Operation 330
Preventing the second chiller and third Chiller/Building Load (Tons)
310
chiller from coming on not only signifi-
cantly reduces energy cost, it also reduces 290

Chiller Load (Tons)


the run hours, operations and maintenance 270
cost, extending the life of the chillers by sev- 250
eral years. Due to the cost of a chiller being
230
approximately $1 million each, extending
the life of the chiller plant postpones this 210
investment for several years. 190
Other O&M savings are from the reduced 170
number of work orders, many of which were
150
from the facility having cold and hot spots. 12 am 6 am 12 pm 6 pm 12 am
After all measures were implemented, the
amount of work orders was reduced by
TABLE 1 Total savings.
nearly 50% from an average of 80 work orders per year
TASK ANNUAL COST ENERGY
for 2015, 2016, and 2017 to 47 work orders in 2018. This SAVINGS ($) SAVINGS (KWH)
allows additional time for the staff to perform preventa-
Chiller Plant/Waterside Equipment Optimization $33,101 441,347
tive maintenance, which further helps with operations
and occupant comfort. Airside Equipment Modifications $38,225 509,660
During this process, trends and reports were created for Annual Savings for this Project $71,326 951,007
all the equipment in the plant, which have continued to be
available to the staff. These trends and reports aid ADTRAN Greenhouse Gas Emissions
in analytics and diagnostics of equipment conditions. • 143 passenger vehicles driven for one year.
• 1,642,527 miles (2 643 390 km) driven by an average
Cost Effectiveness passenger vehicle.
Implemented changes are saving ADTRAN over $71,326
annually in energy costs with a simple payback of 1.86 CO2 Emissions
years based off on a project cost of $133,000. • 75,593 gallons (286 151 L) of gasoline consumed.
In addition to these savings, other implemented • 65,991 gallons (249 803 L) of diesel consumed.
changes have achieved a cost avoidance equal to • 734,422 pounds (333 128 kg) of coal burned.
approximately $1 million from not having to buy a • 8.9 tanker trucks’ worth of gasoline.
fourth chiller since only two chillers are required. • 80.4 homes’ energy use for one year.
Table 1 details the total savings. • 117 homes’ electricity use for one year.
• 3.7 railcars’ worth of coal burned.
Environmental Impact • 1,555 barrels of oil (247 225 L) consumed.
All reduction of global climate change gases (i.e. car- • 85,661,940 number of smartphones charged.
bon dioxide emissions), elimination of CFCs, reduction
in waste discharge and other environmentally favor- Greenhouse Gas Emissions Avoided
able items has been calculated using the United States • 234 tons (212 281 kg) of waste re-
Environmental Protection Agency (EPA) Greenhouse Gas cycled instead of landfilled.
Equivalence Calculator. The calculation is based on a • 33.5 garbage trucks of waste re-
950,000 kWh reduction. The calculator can be found at cycled instead of landfilled. https://bit.ly/3k9ecVE
https://tinyurl.com/j3glbf8. • 29,312 trash bags of waste recycled. Rate this Column

58 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


Sizes to Fit All Environments
Demanding conditions call for reliable equipment.
Patterson-Kelley’s newest stainless steel condensing boiler family just got bigger! The PK
Storm® line up now includes 4 new model sizes, 2500, 3000, 3500 and 4000. With a mechani-
cal turndown of 10:1 and the NURO Control maximizing system efficiencies, The Storm pro-
vides an innovative and intuitive heating solution for any application. And now, with 8 sizes
in the family to choose from, there just might be a Storm in your forecast.

Patterson-Kelley, LLC www.pattersonkelley.com • 877.728.5351


ENGINEERS NOTEBOOK
COLUMN

Nathan Ho

Performance-Based
Approach to Laboratory
Exhaust Systems
BY NATHAN HO, P.E., MEMBER ASHRAE

Laboratory facilities serve as a critical nexus for innovation and discovery, but they
often come with the potential for high operational cost (HVAC energy consumption)
and high risk (air quality performance). A prescriptive approach to designing labora-
tory exhaust stacks has been common. It will likely have a place in the future based on
the need for broadly applicable minimum design criteria that can be enforced consis-
tently through code adoption and inspectors. However, achieving superior energy
performance and acceptable air quality requires a performance-based approach to
laboratory exhaust stack design.

Examples of Prescriptive Design Criteria from exterior walls or roofs, 30 ft (9 m) from combus-
A performance approach begins with an understanding tible walls or openings into the building that are in the
of the origins and limitations of prescriptive design crite- direction of the exhaust discharge and 10 ft (3 m) above
ria. Local code and recognized industry standards often adjoining grade. (Emphasis is the author’s.)
serve as the basis of prescriptive criteria a designer would Other product-conveying outlets shall terminate not
use to design a laboratory exhaust stack. Let us exam- less than 10 ft (3 m) from a property line, 3 ft (914 mm)
ine the California Mechanical Code, California Energy from exterior walls or roofs, 10 ft (3 m) from openings
Code and the American National Standards Institute/ into the building and 10 ft (3 m) above adjoining grade.”
American Industrial Hygiene Association Standard for (Emphasis is the author’s.)
Laboratory Ventilation (ANSI/AIHA Z9.5) as examples.
2019 California Energy Code2
2019 California Mechanical Code1 “140.9 (c) Prescriptive Requirements for Covered
“502.2.2 Product Conveying Ducts. Ducts conveying Processes, Prescriptive Requirements for Laboratory
explosive or flammable vapors, fumes or dusts shall and Factory Exhaust Systems.
terminate not less than 30 ft (9 m) from a property line, Nathan Ho, P.E., is an associate principal and engineering group leader with P2S Inc., in Irvine,
10 ft (3 m) from openings into the building, 6 ft (2 m) Calif. He is the chair of ASHRAE SPC 110.

60 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


COLUMN ENGINEER’S NOTEBOOK

3. Fan System Power Consumption. All newly installed FIGURE 1 Results vs. effort qualitative comparison of analysis methods.
fan exhaust systems serving a laboratory or factory Accurate
greater than 10,000 cfm (4719 L/s) shall meet subsection
A and either B, C or D: Wind Tunnel Validation
A. System shall meet all discharge requirements in ANSI
Z9.5-2012.” (Emphasis is the author’s.)

Results
Computational
Fluid Dynamics
ANSI/AIHA Z9.5-2012, Laboratory Ventilation3 2019 ASHRAE
Handbook—HVAC
“5.4.6 Exhaust Stack Discharge. In any event the dis- Applications
charge shall be a minimum of 10 ft (3 m) above adjacent Calculation Method

roof lines and air intakes and in a vertical up direction. Conservative Effort and Resources Required
Exhaust stack discharge velocity shall be at least
3,000 ft per minute (fpm) (15.2 m/s) [emphasis is the areas sensitive to air quality, such as outdoor air intakes,
author’s] unless it can be demonstrated that a specific operable windows and populated areas, are critical vari-
design meets the dilution criteria necessary to reduce ables that must be evaluated holistically to achieve opti-
the concentration of hazardous materials in the exhaust mum design outcomes.
to safe levels at all potential receptors. Many laboratory projects are developed as renova-
The air intake or exhaust grilles shall not be located tions; as such, the site topography and areas sensitive to
within the architectural screen or mask unless it is dem- air quality are typically fixed variables, and the options
onstrated to be acceptable.” of locations to install the laboratory exhaust systems are
A relationship exists between codes and standards. often limited. Therefore, stack height and exit momen-
Often, codes are mostly sections of existing industry tum are usually the remaining variables a design team
standards with modifications made by the authority can explore and evaluate. This column presents a basic
having jurisdiction. Therefore, to identify the design framework for a design process and a case study high-
parameters to address with a performance approach to lighting the results of this process when applied to a
laboratory exhaust stack design, it is necessary to under- laboratory renovation project.
stand the context and limitations of the referenced stan- Figure 1 presents three conventional methods to evalu-
dard. It is also essential to keep in mind that the pre- ate laboratory exhaust plume dispersion performance
scriptive criteria for stack height and exit velocity have and qualitatively ranks what a designer can anticipate
substantial disclaimers, such as the one in Appendix 3 of concerning the accuracy vs. effort trade-off between
ANSI/AIHA Z9.5-2012. each method. The designer should exercise extreme
caution when using computational fluid dynamics
ANSI/AIHA Z9.5-2012 Appendix 3, Selecting Laboratory Stack Designs3 (CFD) to model exhaust plumes for laboratory pollutant
“The 10 ft (3.05 m) minimum stack height called for in sources, as CFD models can both over- and underpredict
the body of this standard is primarily intended to pro- concentration levels by orders of magnitude, leading to
tect maintenance workers from direct contamination potentially unsafe designs.4 The author agrees with the
from the top of the stack. However, the minimum height 2019 ASHRAE Handbook—HVAC Applications, Chapter 46
of 10 ft (3.05 m) is not enough by itself to guarantee that recommendation to use a wind-tunnel analysis to vali-
harmful contaminants would not be re-ingested. (Emphasis date the results from a CFD analysis.
is the author’s.) Figure 2 describes a process this author has used to
Similarly, a minimum 3,000 fpm (15.3 m/s) exit veloc- collaborate with design team stakeholders to achieve
ity is specified in the body of this standard, but this exit optimum laboratory exhaust system design based on
velocity does not guarantee that re-ingestion will not occur.” the project priorities and values. Step 5 is optional,
(Emphasis is the author’s.) but recommended by the author to achieve optimum
It has been the author’s experience that stack height, design results; wind tunnel validation can yield substan-
exhaust plume exit momentum and physical location tially more accurate performance results with higher
with respect to building massing, site topography and confidence than computational modeling or manual

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 61


COLUMN ENGINEER’S NOTEBOOK

calculation results. The following case study is an exam- FIGURE 2 Collaborative design input cycle to optimize design of lab exhaust system.
ple of how all five steps of the collaborative design pro-
cess were used on a project.

Case Study—Institutional Research Laboratory in Southern


California: Prescriptive vs. Performance Design
A research-focused higher education institution set Collaborative Effort
out to renovate a historic building to provide a modern Owner, Mechanical Engineer,
Wind Consultant, Architect,
laboratory facility for a newly recruited principal inves- Structural Engineer etc.
tigator and her team. Given the potential for growth
of the research, the laboratory program required a
highly flexible HVAC system that could provide stable,
responsive and reliable operation on day one, while also
being capable of supporting rapid growth. This institu-
tion decided to use a design-build delivery to mitigate 1 Identify primary design variables and objectives.
potential construction budget and schedule risks and 2 Collaborate with owner and design team to determine project priorities to optimize
provided the criteria as part of the bridging documents balance between variables. Develop early design concept based on this input.
(Table 1). 3 Perform preliminary analysis of design concept performance based on the
2019 ASHRAE Handbook—HVAC Applications, Chapter 46 Calculation Method or
The university requested a wind study to inform the Computational Analysis. If preliminary results are not compatible with project
design of the HVAC system and provide the university requirements, return to Step 2 and iterate as necessary.

with metrics on air quality to mitigate the risk of odor 4 Produce detailed design layout and evaluate constructibility.

or air quality concerns. The wisdom of this decision 5 Confirm feasibility of design concept and execute wind tunnel validation of performance.
Use results to finalize hardware and controls design. Iterate process as necessary to
became immediately apparent upon inspection of the achieve optimum project solution.
project site shown in Figure 3.
A typical first cost vs. energy effi- TABLE 1 Project background information and owner design criteria.
ciency discussion took place within PROJECT BACKGROUND INFORMATION UNIVERSITY DESIGN CRITERIA
the design-build team. Our team
1954 five-story building with three stories above grade. Centralized laboratory exhaust system.
agreed to compare a code-driven
prescriptive lab exhaust design to Continuously renovated to suit changing research needs. N + 1 fan redundancy, minimum three fans total.
a performance laboratory exhaust Organic addition of fume hoods over time. Motorized isolation dampers and backdraft dampers.
design (Table 2). The code-driven Perform study of wind and air quality conditions to
New lab renovation requires additional lab exhaust inform
prescriptive lab exhaust design uses infrastructure and new rooftop air-handling unit. design of laboratory exhaust stacks and rooftop
air-handling unit outdoor air intake.
bypass air to enable variable air
volume (VAV) laboratory ventilation
FIGURE 3 Rooftop topography and existing conditions.
controls within the building while
maintaining a constant volume
discharge.
The performance laboratory
exhaust design is capable of elimi- Proposed New Lab Exhaust Existing Lab Exhaust Fans
nating bypass air and achieving VAV And AHU Area On Adjacent Roof
discharge to minimize exhaust fan Existing Lab Exhaust
energy consumption along with Fans on Same Roof
reduced sound power, operational
Existing Lab Exhaust Fans
complexity and wear on fan bear- On Adjacent Roof
ings. See Figures 4 and 5 for screen
shots of our model for the prescrip-
tive exhaust system design option

62 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


PETRA OFFERS A WIDE RANGE OF HVAC PRODUCTS TO MEET DIFFERENT SPECIFICATIONS AND REQUIREMENTS
COLUMN ENGINEER’S NOTEBOOK

TABLE 2 Exhaust system design features: prescriptive vs. performance. FIGURE 4 Prescriptive exhaust system design concept, viewed from the south.
PRESCRIPTIVE EXHAUST SYSTEM FEATURES PERFORMANCE EXHAUST SYSTEM FEATURES
Separate exhaust stacks terminating at Clustered exhaust stacks terminating at
10 ft above the finished roof. 24 ft above the finished roof.
No discharge nozzles on stacks to
Discharge nozzles to achieve target exit promote fully developed turbulent airflow
velocity of 3,000 fpm. profile at exit of stack.a
Bypass air to maintain constant discharge No bypass air.
air volume at the exit of each stack.
“Hidden” outdoor air intake. “Hidden” outdoor air intake. FIGURE 5 Prescriptive exhaust system design concept, viewed from the north.
aMany numerical distribution models use the Briggs plume rise formulas that were based on fully developed
turbulent flow profiles at the stack exit.5 It has been speculated that using a nozzle on the discharge of the
stack could compromise the stack’s ability to achieve fully developed turbulent flow profiles at their point of
discharge.

and Figures 6 and 7 for the performance exhaust system


design option.
Visual inspection of the existing rooftop conditions
suggested that existing-to-remain nearby laboratory
exhaust fans may render the rooftop air unsuitable as FIGURE 6 Performance exhaust system design concept, viewed from the south.
a source of outdoor air for the new air-handling unit.
Therefore, our team decided to “hide” the outdoor air
intake from the existing rooftop exhaust fans to pas-
sively enhance the air quality of the outdoor air brought
in through the air-handling unit. Per the 2019 ASHRAE
Handbook—HVAC Applications,4 a conservative dilution
factor of 2.0 may be anticipated when the air intake is
“hidden” from the line of sight of an emissions source.
FIGURE 7 Performance exhaust system design concept, viewed from the north.
To provide an objective analysis of exhaust stack design,
the air-handling unit outdoor air intake was kept identi-
cal in both design options evaluated.
The prescriptive-based and performance-based
exhaust stack design options were both located as far
from the roof edge as practical to minimize the effects
of the wake zone formed by wind passing over the edge
of the roof. Exhaust stacks that terminate within the
“recirculation region” of a wake zone will tend to require
substantially more power for their exhaust plume to
escape the roof (Figure 8). Pollutant Dispersion from Building Exhaust Stacks,” to
Laboratory exhaust plume dispersion performance passively enhance the exhaust plume momentum by
tends to be strongly influenced by stack height and the clustering the exhaust stacks. Per ASHRAE RP-1167, ter-
momentum of the exhaust stream exiting the stack. minating stacks within a range of ~1.3 diameters of the
Discussions with the facility owner confirmed that a stack centerline with similar discharge velocities from
maximum stack height of 24 ft (7 m) above the roof was multiple active stacks will yield conditions where the
aesthetically acceptable. So our team used this height plume from each active stack will tend to merge, com-
to minimize the exhaust stream momentum required bining momentum.6
to achieve adequate exhaust contaminant dilution. Our The laboratory exhaust airflow demand profile in
team then applied the knowledge gained from ASHRAE Table 3 was determined for this project and used as the
research project RP-1167, “The Effect of Ganging on basis for the project’s wind study. These parameters

64 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


COLUMN ENGINEER’S NOTEBOOK

are essential because they establish FIGURE 8 Figure 6, “Design Procedure for Required Stack Height to Avoid Contamination,” from Chapter 46 of
upper and lower boundaries on the the 2019 ASHRAE Handbook—HVAC Applications.4
laboratory exhaust system operation Undisturbed Z1 Roof Recirculation Region
Flow
for analysis. Designers can eliminate Z2 High-Turbulence Region
Z3 Roof Wake Boundary
bypass air if the volumetric airflow
rate for acceptable plume dilution
Building Wake
is less than the absolute minimum Recirculation
volumetric airflow rate required 1.5R Region
by the laboratory exhaust system
5:1
as determined by the wind-tunnel UH HC 10:1 hs A
analysis (Table 3). XC
LC H
H
Wind Tunnel Analysis Results
The owner’s design require-
ment stipulated that the laboratory L Lr
exhaust system shall use a minimum
of three fans with an operational TABLE 3 Facility exhaust airflow demands for various operational scenarios.

redundancy of N + 1; N is the number of fans required OPERATIONAL SCENARIO MIN. EA FLOW MAX. EA FLOW

to meet the design load. Our design team determined Day 1 10,060 cfm 13,125 cfm
that a capacity of 26,000 cfm (12 271 L/s) was needed to Day 1 + Shell Spaces 11,455 cfm 17,300 cfm
meet the demand of the project. Therefore, a laboratory Day 1 + Shell Spaces + Spare Capacitya 11,455 cfm 26,000 cfm
exhaust system composed of three 13,000 cfm (6136 L/s) aTotal overall system capacity provided is 39,000 cfm including redundant fan.

capacity fans with individual exhaust stacks terminating


at 10 ft (3 m) above the finished roof were studied under performance. The resultant air quality would have
this option to represent an exhaust stack design that been significantly compromised using a prescriptive
prescriptively complied with local code requirements. approach.
Our team then sought to determine at what height
Prescriptive Design Performance Observations would an exit velocity of 3,000 fpm (15.2 m/s) yield our
The 2019 ASHRAE Handbook—HVAC Applications4 pub- target dilution criteria. We discovered through addi-
lishes a general use laboratory exhaust dilution value of tional wind tunnel testing that a 20 ft (6 m) stack would
400 µg/m3 per g/s as an evaluation benchmark for loca- be needed, which is twice as tall as the minimum pre-
tions sensitive to air quality. Our wind tunnel validation scriptive criteria required by local code (Figures 9 and 10).
testing determined that a minimum exhaust stack exit
velocity of 16,552 fpm (84.1 m/s) would be required to Evaluating the Impact of Stack Height and Volumetric Flow on Performance
achieve this criterion at the outdoor air intake of the The results from the single stack, single fan scenario
new air-handling unit. When compared to the com- show there is a strong correlation between stack height
monly referenced prescriptive approach of 3,000 fpm and associated minimum exit velocity to achieve accept-
(15.2 m/s) for exhaust stack exit velocity, these results able exhaust plume dispersion performance (Table 4).
highlight ANSI/AIHA Z9.5’s disclaimer that the use of This relationship has diminishing returns with the most
their prescriptive criteria does not guarantee that re- significant potential reduction in minimum exit veloc-
ingestion will not occur. Designers should carefully con- ity achieved up to a height of 22 ft (6.7 m) and rapidly
sider these disclaimers when applying broad, general- diminishing reductions beyond ~22 ft (6.7 m) for this
ized rules for their applications. specific project. While it has been the author’s experi-
For this project, a prescriptively designed exhaust ence that this trend of diminishing returns is generally
stack would have operated with an exit velocity that is applicable, the height and rate of performance gains are
essentially an order of magnitude slower than the proj- particular to each project and should be evaluated for
ect conditions require to achieve acceptable dilution each project.

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 65


COLUMN ENGINEER’S NOTEBOOK

FIGURE 9 Single Fan Operation: Stack height vs. exit velocity required to achieve FIGURE 10 Single Fan Operation: Stack height vs. exit velocity required to achieve
target dilution criteria. target dilution criteria (20+ ft height with higher y-axis resolution).
18,000 Single Fan (10,060 cfm) 3,500
16,000 Single Fan (10,060 cfm)
Single Fan (13,000 cfm)
Stack Exit Velocity (fpm)

14,000 3,000 Single Fan (13,000 cfm)

Stack Exit Velocity (fpm)


12,000
10,000 2,500
8,000
2,000
6,000
4,000 1,500
2,000
0 1,000
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 20 21 22 23 24 25
Exhaust Stack Height (ft) Exhaust Stack Height (ft)

Airflow moving over the edge of a building tends to TABLE 4 Stack height vs. reduction in exit velocity required to achieve target dilu-
create a “wake zone” of turbulent airflow downstream of tion criteria for a single stack in operation.
the building edge. Exhaust stacks that terminate within
AVERAGE VELOCITY REDUCTION PER
a wake zone experience a substantial exhaust plume STACK HEIGHT
FOOT INCREASE
STACK EXIT AIRFLOW RATE

dispersion performance penalty as the turbulent air will


10 ft to 20 ft 1,351 fpm per ft 13,000 cfm
locally recirculate the exhaust plume back toward the
surface of the roof. Significant exhaust plume momen- 20 ft to 21 ft 474 fpm per ft 10,060 cfm
tum is required to overcome the forces exerted by the
21 ft to 22 ft 375 fpm per ft 10,060 cfm
turbulent air within the wake zone. The single stack, sin-
gle fan scenario results demonstrate the influence of the 22 ft to 25 ft 184 fpm per ft 10,060 cfm
building wake zone. Lower stack heights within the wake
zone recirculation region require significantly higher TABLE 5 Airflow rate increase vs. exit velocity reduction to achieve target dilution
criteria for a single stack in operation.
exit velocities than taller stack heights that terminate
above the wake zone recirculation region. STACK HEIGHT
AVERAGE VELOCITY REDUCTION PER STACK EXIT AIRFLOW RATE
1,000 CFM INCREASE RANGE TESTED
While it may be possible to compensate for lower
stack heights by increasing exhaust plume momen- 20 ft 55 fpm per 1,000 cfm 13,000 to 14,000 cfm
tum through increased exit velocity, the designer will
eventually need to consider increasing mass flow rate
at the stack discharge. The stack discharge exit veloc- that was achieved by clustering the exhaust stacks
ity tends to be practically limited to “near” 3,000 fpm together (Figure 11). The data show that it is possible to
(15.2 m/s) due to sound power emitted from the stack achieve a reduction in volumetric airflow required at
and fan power considerations. Both sound power and the exit of each stack when clustering stacks as a design
fan power tend to escalate quickly, as exhaust stack pres- strategy. In this case, two clustered stacks running at
sure drop is primarily a function of velocity squared. 6,250 cfm (2950 L/s) each with a stack height of 20 ft
Our team tested adding 1,000 cfm (472 L/s) to the dis- (6 m) require an exit velocity of 2,865 fpm (14.6 m/s)
charge flow rate to the 20 ft (6 m) stack scenario and compared to the 3,040 fpm (15.4 m/s) needed for a
found that increasing the flow rate from 13,000 cfm single stack running at 13,000 cfm (6136 L/s) at the same
(6136 L/s) to 14,000 cfm (6607 L/s) decreased the mini- stack height of 20 ft (6 m).
mum required exit velocity by a very modest 55 fpm Our analysis of the two fans in operation scenario
(0.3 m/s) (Table 5). evaluated stack exit airflow rates of less than the Day
1 minimum airflow load to determine how low each
Performance Design: Multiple Stack Operation stack could operate. This was used to inform the fan
Our team’s wind tunnel validation testing was able to staging strategy to optimize fan power performance
quantify the benefit to plume dispersion performance (Figure 12).

66 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


COLUMN ENGINEER’S NOTEBOOK

FIGURE 11 Clustered Stack Design: Stack height vs. discharge velocity with two FIGURE 12 Exhaust system fan power.
fans running.
25 1 EF Running
3,000 Two Fans (6,250 cfm Per Fan) 2 EFs Running
Stack Exit Velocity (fpm)

Total Exhaust Fan Power (bhp)


2,500 Two Fans (13,000 cfm Per Fan) 20
3 EFs Running
2,000
15
1,500
1,000 10
500
20 21 22 23 24 25 26 5
Exhaust Stack Height (ft)
0
9,000 11,000 13,000 15,000 17,000 19,000 21,000 23,000 25,000 27,000
Building Exhaust Airflow (cfm)
We ran similar tests to evaluate the impact of increasing
height and volumetric airflow rate on stack performance
for the clustered stack design (Tables 6 and 7). Similar to testing, we were able to model the range of different
the single stack scenario, raising the stack height yields exhaust fan operational scenarios to determine the
a more significant impact on plume dispersion perfor- aggregate system fan power required (Figure 12). Using
mance compared to increasing volumetric airflow rate. these exhaust system power curves, we can decide on
ideal staging points to stage up or down between the
Performance Design: Optimizing VAV Fan Power three fans provided in this system for energy efficiency
With exhaust stack minimum airflow requirements and develop appropriate hysteresis to help promote
established based on our wind tunnel validation stable system operation.

ASHRAE Learning Institute


Your Cost-Effective Training Solution

ASHRAE Learning Institute (ALI) takes a proactive role


in training professionals with up-to-date requirements
for the design, construction, and renovation of new and
existing buildings and their systems.

ALI offers a variety of instructor-led courses, developed


by industry experts in the areas of:

• Commissioning • HVAC&R Applications


• Energy Efficiency • Standards & Guidelines
• Environmental Quality

Never stop learning. See how ASHRAE Learning


Institute can assist with your training needs.

Visit ashrae.org/ali for the complete list of


instructor-led training.

68 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


COLUMN ENGINEER’S NOTEBOOK

TABLE 6 Stack height vs. reduction in exit velocity required for two clustered FIGURE 13 Performance exhaust stack design installed.
stacks in operation.

AVERAGE VELOCITY
STACK HEIGHT EXIT AIRFLOW RATE PER STACK
REDUCTION PER FOOT INCREASE

20 ft to 21 ft 497 fpm/ft 6,250 cfm

21 ft to 22 ft 379 fpm/ft 6,250 cfm

22 ft to 23 ft 294 fpm/ft 6,250 cfm

23 ft to 24 ft 233 fpm/ft 6,250 cfm

24 ft to 25 ft 189 fpm/ft 6,250 cfm

25 ft to 26 ft 154 fpm/ft 6,250 cfm

TABLE 7 Airflow rate increase vs. exit velocity reduction for two clustered stacks across different appli- FIGURE 14 Close-up of cluster stack
in operation. cations and could result from performance design option
installed
AVERAGE VELOCITY REDUCTION STACK EXIT AIRFLOW
in higher contaminant
STACK HEIGHT
PER 1,000 CFM INCREASE RATE RANGE TESTED concentrations than
are acceptable. Using
20 ft 80 fpm per 1,000 cfm 6,250 to 13,000 cfm
a performance-based
design approach will
TABLE 8 Prescriptive vs. performance design results summary.
give greater confidence
PRESCRIPTIVE EXHAUST SYSTEM RESULTS PERFORMANCE EXHAUST SYSTEM RESULTS in achieving higher
performance and
10 ft stack height. 24 ft stack height.
acceptable air quality.
16,552 fpm minimum exit velocity 2,049 fpm minimum exit velocity Laboratory exhaust sys-
required per stack when in use. required for single-stack operation. tem performance tar-
1,462 fpm minimum exit velocity
gets can be quantified
13,000 cfm minimum volumetric airflow required per stack for two-stack opera- and achieved through
rate required per fan when in use. tion; less if all three stacks are running
in parallel. design team collabora-
tion and modeling of stack dispersion performance
10,060 cfm minimum volumetric airflow with the performance-based approach. Design strate-
rate required for single stack operation.
gies using taller stack heights and clustering exhaust
6,250 cfm minimum volumetric airflow stacks can result in substantial improvement of labora-
rate required for two-stack operation; less
if all three stacks are running in parallel. tory exhaust dilution performance.

Prescriptive vs. Performance Design Results Summary References


Table 8 summarizes the final results between the 1. IAPMO. 2019. “2019 California Mechanical Code.”
2. ICC. 2019. “2019 California Energy Code.”
prescriptive vs. performance-based approach design 3. ANSI/AIHA/ASSP Z9.5-2012, Laboratory Ventilation.
options for the project evaluated within this case study. 4. 2019 ASHRAE Handbook—HVAC Applications.
Figures 13 and 14 show images from the performance- 5. Briggs, G.A. 1984. “Plume rise and buoyancy effects.”
“Atmospheric Science and Power Production,” D.
based approach design option installed. Richardson, Editor. U.S. Department of Energy,
DOE/TIC-27601.
Conclusions 6. Petersen, R.L., J.D. Reifschneider, 2008.
“The effect of ganging on pollutant dispersion
A laboratory exhaust system prescriptive-based from building exhaust stacks.” ASHRAE https://bit.ly/3k9ecVE
design approach does not yield consistent results Transactions 114(1):458 – 470. Rate this Column

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 69


REFRIGERATION APPLICATIONS
Column
Andy Pearson

Deeper into Vacuum


BY ANDY PEARSON, PH.D., C.ENG., FELLOW ASHRAE

In last month’s column I wrote about the process of pulling a vacuum on refrigerating
systems and highlighted some good practice points for care of the vacuum pump and
how it is connected to the system for best effect. Here are some more tips for maxi-
mizing the benefit and avoiding some horrible pitfalls.
Don’t use a gauge manifold to connect the vac pump pressure. Strictly speaking this should be understood to
and gauges to the system. Firstly, the hoses are too small be one millionth of a metre of mercury (in other words
diameter and too long to enable the best effect to be a “milliTorr”) but there always seems to be too much
achieved. Secondly, the gauge needs to be on a different room for confusion about whether it is a micrometer or
part of the system in order to indicate the true level of a microinch. The reason I like the unit of Torr is that it is
vacuum that has been achieved. absolutely unambiguous.
Do make sure to use a sufficiently accurate vacuum To make sense of the whole vacuum process it is essen-
gauge for this purpose. It needs to tell the difference tial to understand what you are trying to achieve (which
between a system holding a vacuum of 29.7 inches of mer- is not always the same thing from job to job). As men-
cury and 29.8 inches of mercury. The gauges on a mani- tioned last month, removal of air (or pressure test gas) is
fold are just not that accurate. Nowadays it is possible to one reason but removal of moisture or even free water
buy a simple electronic vacuum gauge for less than $100 is also important. A small amount of water in the system
and a high quality calibrated electronic Removing water is harder if it turns to ice. will hinder the vacuum process because
gauge for less than $1,000. The saving in it will start to boil when the pressure
time spent messing around will pay for gets down to the saturation point for the
this many times over. temperature of the water. This is obvious
By the way, do understand the many if you know what to look for because the
ISTOCKPHOTO.COM/PORTFOLIO/ZIGGY1

and varied units used to measure pressure will plateau at a level equivalent
vacuum and be very precise in how you to the prevailing temperature. However if
use them, especially when specifying there is a lot of free water inside the sys-
vacuum procedures to other people. The tem it could take weeks to boil it dry using
units I used above, inches of mercury, the vac pump. On the other hand, if the
are particularly devilish because they measure from the geometry of the system enables the pressure to fall well
other end. Zero inches of mercury (sometimes abbrevi- below the saturation point and it gets down to the triple
ated as “in Hg”) is atmospheric pressure and 29.92 inches point of water (6.1 mBar abs, 4.5 Torr or 29.74 in Hg)
of mercury is absolute vacuum. The higher the number, then some of the water will freeze and it is much more
the lower the pressure. I prefer to use the unit “Torr” difficult to remove it through the vac pump. Even worse,
although it is neither Systeme International (SI) nor inch- I was once involved in a project where evaporators were
pound (I-P). Named after the Italian scientist, Torricelli, being installed inside an existing cold store. The evapo-
a Torr is equivalent to the pressure required to raise rators were badly contaminated with
mercury by 1 mm (0.039 in.) in a Fortin barometer. The water but it froze before the vacuum was
inch of mercury (whichever end of the scale you measure pulled, so everything seemed fine until
from) has the same origin—nominal atmospheric pres- the system was charged and the water https://bit.ly/3k9ecVE
sure is 760 Torr or 29.92 inches of mercury absolute. I also flooded back to the receiver. Rate this Column

recommend avoiding the “micron” as a measurement of Andy Pearson, Ph.D., C.Eng., is group managing director at Star Refrigeration in Glasgow, UK.

70 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


NILES DOES
CUSTOM STAINLESS

Niles Steel Tank is proud to


introduce Alloy Works – a new,
85,000-square-foot facility that
provides expanded capabilities
for custom stainless steel vessels built to ASME
Code standards.
Products are fabricated to the highest standards
including ASME boiler and pressure vessel codes:
S, H, HLW, U and National Board “R” stamp. We use
stainless steel and other alloys to deliver superior
strength, corrosion resistance and performance.

Stainless Steel and Alloy Solutions for:


• Hydronics
Storage tanks, volume water heaters, hot
water generators, pressure vessels and custom
fabrications
• Chemical and Petrochemical
Storage and processing tanks and vessels
• Air Products

To learn more about Alloy Works, contact us at info@nilesst.com or visit nilesst.com


©2020, Bradford White Corporation. All rights reserved. NSTASHJ0920
IEQ APPLICATIONS
COLUMN

Wade Conlan

ASHRAE Headquarters

Building Readiness
Plan for SARS-CoV-2
BY WADE H. CONLAN, P.E., BCXP, MEMBER ASHRAE

The ASHRAE Epidemic Task Force (ETF) has quickly created a number of useful guid-
ance documents for operating buildings during an epidemic, which are posted on
ASHRAE’s COVID-19 website pages (www.ashrae.org/covid19). Many of these docu-
ments would also apply after the epidemic has passed. Since the existing ASHRAE
Headquarters (HQ) was observing shelter-in-place orders to help flatten the trans-
mission of the SARS-CoV-2 virus that causes COVID-19, the building was unoccupied
for several weeks. The ETF believed, and ASHRAE leadership agreed, that the ASHRAE
HQ should be evaluated using the same analysis approaches it is suggesting for its
members and their clients.
Members of the Building Readiness Team that is systems and to identify potential improvements to
part of the ETF performed the analysis on the current the system and potential failure points that could be
ASHRAE HQ to determine which mitigation strategies checked by the building’s maintenance contractor. The
should be implemented prior to staff returning to the team used the existing building automation system
building. This team also looked at the new ASHRAE HQ (BAS) graphics, as-built floor plans and BAS trend data
under construction to determine if any engineering to conduct this effort. The building has a dedicated
controls could be added to improve its ability to miti- outdoor air system (DOAS) that delivers all the outdoor
gate virus transmission in alignment with the Building air to the spaces. Local cooling and heating is provided
Readiness Guide (https://tinyurl.com/y5r92ohs). using different terminal equipment on each floor:
For the existing HQ building, a team of individuals was the first floor is conditioned using ground source heat
formed to perform the analysis that consisted of ETF pumps; and, the second floor is conditioned using vari-
members, the commissioning provider for the last reno- able refrigerant flow fan coil units. Each of the terminal
vation to the building and the building operations team units has a filter box to provide increased filtration
for ASHRAE. (See “Analysis Team” on the facing page.) capability in addition to the filtration incorporated into
The intent of the analysis was to review the HVAC
Wade H. Conlan, P.E., is commissioning and energy discipline manager at
This peer-reviewed column does not represent official ASHRAE guidance. For more Hanson Professional Services, Inc., in Maitland, Fla. He currently leads the
information on ASHRAE resources on COVID-19, visit ashrae.org/COVID19. Building Readiness Team of ASHRAE’s Epidemic Task Force.

72 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


COLUMN IEQ APPLICATIONS

the DOAS unit. There is only one exhaust system for


the building, and that is via the DOAS unit through the Analysis Team
energy recovery wheel that is located on the roof. Wade Conlan, P.E., Member ASHRAE, Hanson Professional Services, Inc.
The first step in this effort was to identify potential
issues for the HVAC systems maintenance contractor to Dennis Knight, P.E., Fellow ASHRAE, Whole Building Systems
check on their next visit to the building. Then the team
Justin Garner, P.E., Member ASHRAE, Engineered Air Balance Co., Inc.
tried to identify improvements that might need to be
implemented. ASHRAE staff wanted a list of things for Jon Sheppard, Associate Member ASHRAE, Atlantic Testing
the maintenance contractor to check in addition to the
normal quarterly checkup. Jason DeGraw, Ph.D., Member ASHRAE, Oak Ridge National Lab
The first issue identified was to confirm the status of
Rick Hermans, P.E., Life Member ASHRAE, Retired
the filters in the DOAS and at each of the filter mixing
boxes at the terminal equipment in the spaces. ASHRAE Jay Enck, Member ASHRAE, Commissioning & Green Building Solutions, Inc.
staff was able to confirm that the interior electrostatic
filters had been replaced around the time of the 2019 Ginger Scoggins, P.E., Fellow ASHRAE, Engineered Designs, Inc.
Winter Conference in Atlanta and were still within use- Mike Vaughn, ASHRAE Staff
ful life. These electrostatic filters allow the terminal
equipment to achieve MERV 13 filter performance. Jeff Littleton, ASHRAE Staff
There are two sets of filters in the DOAS. One set of
supply filters is installed after the return bypass and occupied hours, the demand controlled ventilation was
energy wheel that are MERV 13 equivalent, which to be “disabled” for the system. The team agreed that
reduced concern over potential wheel crossover or
return path leakage. To be safe, it was suggested that
the maintenance team disconnect or disable the return
damper and seal that pathway to further mitigate poten-
tial transmission by having the unit function with 100% Innovation
outdoor air and 100% exhaust air.
The second set of filters was on the building return/
relies on trust
relief to the unit prior to the energy wheel. These fil- Let UL’s industry-leading
engineering teams help you
ters need to be confirmed to be MERV 8 as originally
achieve success in a dynamic and
required in the design, which was based on having demanding market to meet the
MERV 13 filters before the air is supplied to the space. new DOE commercial boiler energy
There was an extended discussion on the operation efficiency standards becoming
of the DOAS unit and its capacity to bring in outdoor effective January 10, 2023.
air during the occupied times as well as provide for
Learn more at UL.com/HVACR.
pre- and postoccupancy flush cycles. The team agreed
to a sequence to keep the unit at its maximum outdoor
airflow setpoint during occupied modes and then to
perform the analysis recommended in the Building
Readiness Guide to determine the number of hours
required for these flush cycles. The Building Readiness
Guide suggests three air changes of outdoor air to flush
the building of approximately 95% of its contaminants.
Quick calculations showed that this would require three
hours of flushing and was noted that this should be
UL and the UL logo are trademarks of UL LLC © 2020.
added to the BAS schedule programming.
To maximize the ventilation airflow to the space during

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 73


COLUMN IEQ APPLICATIONS

changing the space CO2 setpoint to 300 ppm would germicidal irradiation (UVGI) sized at a lamp intensity to
effectively “disable” the demand control ventilation provide for a kill strength using a single pass and energy
(DCV) sequence and allow for minimal programming wheels located relative to the fans to minimize any cross
time now and when it is time to re-enable this energy contamination.
savings strategy post pandemic. The contract documents require a pressure profile
The BAS also monitors building pressure via sensors be completed during TAB to verify compliance with the
located throughout the building. The team agreed it performance levels outlined in ASHRAE’s “Practical
was appropriate to have the maintenance contractor’s Guidance for Epidemic Operation of Energy Recovery
testing, adjusting and balancing (TAB) personnel check Ventilation Systems” (https://tinyurl.com/y2wyth7o).
the calibration of these sensors to verify the system was Zone/space airflow is controlled via air terminal equip-
working properly. ment that will use the same space CO2 ppm adjustment
Other strategies HQ will be using that are not HVAC discussed for the existing HQ to temporarily disable the
related include staggering employees’ workdays and areas DCV strategy. The team analyzing the systems felt that
to create separation and reduce occupancy, improved the design of the new facility had incorporated many of
cleaning processes and frequency, minimizing elevator use suggested mitigation strategies and did not need further
and limiting conference room occupancy and use. alterations to align with the ETF guidance.
For the new ASHRAE HQ under construction, the team Thanks to the ASHRAE Epidemic Task
met with the project oversight committee lead, Ginger Force for creating the guidance, as well
Scoggins, P.E., Fellow ASHRAE, to review the systems’ to as the individuals that led the effort
design and capabilities. This building will also be using a to analyze the existing and new ASHRAE https://bit.ly/3k9ecVE
DOAS system equipped with MERV 14 filters, ultraviolet buildings. Rate this Column

Desiccant and Energy Recovery wheels


available in standard and custom sizes.
Call or email us for a quote today!

225 -753 -1700


1700
info@rotorsource.com | www.rotorsource.com

74 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


THE ROAD TO
PEACE OF MIND

www.riello.com

• BASED ON 90 YEARS OF GLOBAL R+D


• CUSTOMIZABLE TO MEET SPECIFIC END-USER NEEDS
• WIDE RANGE OF COMMERCIAL AND INDUSTRIAL APPLICATIONS
• RELIABLE, EFFICIENT COMBUSTION SOLUTIONS
• DESIGNED FOR SUPERIOR OPERATIONAL PERFORMANCE

Riello is a recognized market leader in delivering


the most powerful, reliable and cost-effective
combustion heating solutions for over 40 years in
North America. Riello’s high-performance platform
of gas, oil, dual-fuel and low NOx burners deliver
energy savings through increased fuel efficiencies
that yield return on investment. Riello burner
capacities range up to over 120 million+ BTUs to
meet the most demanding heating applications.
SPECIAL PRODUCTS

COMMERCIAL BUILDINGS It has a shutoff damper with an electric


actuator, automatic balancing damper
To receive FREE info on the (ABD) and a plenum box as one assembly. It
products in this section, go to: is designed to maintain a constant airflow
volume in HVAC applications.
www.ashrae.org/freeinfo www.info.hotims.com/76276-205

Control Damper
A Commercial Water Heaters TAMCO’s Series 8800 heavy-duty control
The eF120 series high efficiency gas dampers are designed with innovative blade
ultralow NOx commercial water heaters stops that are integral to the top and bottom
from Bradford White are for industries frames. These newly patented blade stops
with high demand for hot water, such as are located outside the airstream, providing
manufacturing, construction, education, increased free area. Series 8800 has pressure A Commercial Water Heaters
hospitality and health care. It incorporates drop rates that are lower than other heavy- By Bradford White
BMS and modulation technology for remote duty dampers.
monitoring capability and increased fuel www.info.hotims.com/76276-206
efficiency.
www.info.hotims.com/76276-200 Balancing Damper
The Roto-Twist oval damper from
B Pump Control Panel Metropolitan Air Control is designed for
The EZ Series® In-Site® CL duplex control balancing linear slot plenum boxes. It allows
panel from SJE Rhombus features wireless for remote operation through the face of the
Bluetooth connection to your smart device. diffuser and is available in galvanized steel
With the app, there is no need to open the in 6 in., 8 in., 10 in. and 12 in. (152 mm, 203
panel for configuration, viewing status or mm, 254 mm and 305 mm) flat oval sizes
downloading data. The Bluetooth module for Titus, Krueger and Tuttle & Bailey slot
B Pump Control Panel
allows safe and secure access to the control plenums. Dampers ship fully assembled and By SJE Rhombus
panel in all weather conditions. can be installed in 10 minutes.
www.info.hotims.com/76276-201 www.info.hotims.com/76276-207
C All Weather Duct Sound Level Meters
Masterduct’s all weather duct is a flexible, The RION NL series of meters are user-
lightweight flame-resistant duct designed friendly, handheld analyzing instruments
for temporary HVAC applications. It is that measure HVAC sound levels and
manufactured with a neoprene-coated that provide octave and 1/3 octave band
polyester core and a waterproof, UV- analysis, NC curves and reverberation time
resistant, polyester vapor barrier. measurements. The unit (except for the
www.info.hotims.com/76276-202 microphone) is water-resistant.
www.info.hotims.com/76276-208
C All Weather Duct
D Scroll Chiller
By Masterduct
WaterFurnace modular scroll chillers Balancing Damper
use a six-pipe header rack that provides The SC-BAL-XX from Specified Controls is a
heating and cooling loads in one unit. The round electronic balancing damper that uses
refrigeration module can be removed while a 9 V dc direct coupled actuator. The motor
the rest of the chiller bank runs, preventing provides direct proportional control when
the building from shutting down. using the handheld damper positioner.
www.info.hotims.com/76276-203 Turning the indicator knob to the approp
Air Filter www.info.hotims.com/76276-209
Permatron’s PreVent® system combines air Condensing Fire Tube Boiler D Scroll Chiller
intake protection filters with MagnaMount® Navien’s NFB-C commercial condensing fire
magnetic mounting to deliver a custom–fit
By WaterFurnace
tube boilers deliver 97.5% thermal efficiency,
solution that stops airborne debris before 15:1 turndown ratio, 7 in. (178 mm) color
it enters HVAC fins and coils. No drilling or touch screen, BMS communications and interface gateway capable of bridging
tools are needed, and it is UV-protected for multiple venting options with PVC/CPVC/PP/ various popular serial communication
outdoor use. SS-approved materials. networks, while simultaneously providing
www.info.hotims.com/76276-204 www.info.hotims.com/76276-210 physical I/O for hardwired control systems.
A wide variety of client and server protocols
Damper Multi-Interface Gateway such as BACnet MS/TP, Modbus RTU, Metasys
The ABD-Z1 from Greenheck provides The Mirius from Industrial Control N2, and Siemens FLN are included.
on-demand control to a ventilation system. Communications, Inc., is a flexible, multi- www.info.hotims.com/76276-211

76 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


Belimo
Energy Valve

Energy Savings You Can See


The Belimo Energy Valve provides transparent energy monitoring while
maintaining high Delta T. Automatic reports show actual and historical
performance data, recommending further potential for energy savings.

CESIM. Small Devices, Big Impact.


Comfort | Energy Efficiency | Safety | Installation | Maintenance
INFO CENTER
SPECIAL ADVERTISING SECTION

THE MOST ADVANCED TECHNOLOGY


IN BOILER CONTROL

The NURO® Touch-Screen Control


System maximizes boiler and water
heater efficiency by monitoring
and modulating combustion and
FRENIC-Ace Inverters ignition. It utilizes the most stable
Performance you need. technology in a totally easy-to-use
Reliability you can count on. package. This ensures safe, efficient
and reliable boiler performance
• 3-Year Standard Warranty
year-after-year.
• Built-In STO (Safe Torque Off)
• 200 Steps of Customizable Logic
• Permanent Magnet Motor Control NURO® Connect App Available
Android and iOS devices
Fuel usage calculator
Notifications & service reminders
Unlimited boiler and site connectivity
Real-time data with history download
Service version for trained technicians

Website: www.pattersonkelley.com
Phone: 570.476.7261
Toll Free: 877.728.5351
americas.fujielectric.com/ace

ASHRAE Learning Institute


Your Cost-Effective Training Solution

GOOD REASONS
FOR R-32

ASHRAE Learning Institute (ALI) takes a proactive role


in training professionals with up-to-date requirements
THERE’S MORE THAN ONE GOOD REASON for the design, construction, and renovation of new and
TO SWITCH FROM R- 410A RE FRIG E R ANT existing buildings and their systems.
T O R - 3 2 . I N FA C T, T H E R E A R E 3 2 O F T H E M .
S E E T H E M A L L AT R 3 2 R E A S O N S . C O M . ALI offers a variety of instructor-led courses, developed
by industry experts.

Never stop learning. See how ASHRAE Learning


WITH MORE THAN 100 MILLION UNITS
INSTALLED WORLDWIDE, R-32 IS ENDORSED BY: Institute can assist with your training needs.

Visit ashrae.org/ali for the complete list of


instructor-led training.

78 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


CLASSIFIEDS COMMENTARY

RATE SCHEDULE: SOFTWARE

Classified line advertisements Everything Your Reps Need…


are inserted in 7-point type at the
...to increase sales
rate of $6.00 per word. This
includes heading and address. For All HVAC Products
Maximum insertion 15 lines. Prices
are net. Classified line insertions Selection
Pricing / Configuration
for members are $2.00 per word.
Submittals
Parts
Classified Column Inch
Border Advertisements Customer Support
are inserted in 8-point bold heading More...
and address type of 7-point body www.bcatech.com
type at the rate of $145.00 per 407-
407-659-
659-0653
column inch, includes heading and
address. Maximum length 5 inches.
Maximum width 2-1/8”. Prices are
net. Border classified insertions for
members are $65.00 per column
inch.

Classifieds are accepted in the


categories of Job Opportunities,
Rentals, Business Opportunities,
and Software.

Closing date:
Copy must be received by the
classified department by the 3rd of
the month preceding date of issue.

Address: Send request for further


information to:

ASHRAE JOURNAL
Vanessa Johnson
1791 Tullie Circle NE
Atlanta, GA 30329
Phone 678-539-1166
Fax 678-539-2166
E-mail: vjohnson@ashrae.org

SEPTEM BER 2020 ashrae.org ASHRAE JOURNAL 79


ADVERTISING SALES
Advertisers Index/Reader Service Information ASHRAE JOURNAL
1791 Tullie Circle NE | Atlanta, GA 30329
Two fast and easy ways to get additional information on (404) 636-8400 | Fax: (678) 539-2174
products & services in this issue: www.ashrae.org
Greg Martin | gmartin@ashrae.org
Associate Publisher, ASHRAE Media Advertising
Go to www.ashrae.org/freeinfo to search for products by category or Vanessa Johnson | vjohnson@ashrae.org
Sr. Coordinator Advertising Production & Operations
company name. Plus, link directly to advertisers’ Web sites or request
information by e-mail, fax or mail. NORTHEAST U.S.
Nelson & Miller Associates –
Denis O’Malley
5 Hillandale Ave., Suite 101
Stamford, CT 06902
(203) 356-9694 | Fax (203) 356-9695
*Regional sales@nelsonmiller.com
Company Page Company Page Company Page

AAON Inc .........................................51 Cambridge Engineering ................47 Niles Steel Tank..............................71 SOUTHEAST U.S.
Millennium Media, Inc. –
590 Hickory Flat Road
Alpharetta, GA 30004
Daikin North America LLC................ Panasonic Life Solutions Co of Doug Fix (770) 740-2078 | Fax (678) 405-3327
AAON Inc ................................4th Cvr ............................................. 2nd Cvr-1 Lori Gernand-Kirtley (281) 855-0470 | Fax (281) 855-4219
America............................................ 11 dfix@bellsouth.net; lg@lindenassoc.com

OHIO VALLEY U.S.


Chagrin Valley Media Partners – Tom Lasch
Aerco ................................................33 Daikin North America LLC............78 Patterson-Kelley............................ 59 512 East Washington St.
Chagrin Falls, OH 44022
tlasch@larichadv.com
(440) 247-1060 | Fax (440) 247-1068
AHR Expo Chicago 2021 .............. 17 ebm-papst Inc ................................23 Patterson-Kelley.............................78
MIDWEST U.S.
Kingwill Company – Baird Kingwill; Jim Kingwill
330 W. Colfax Street, Unit 102
Palatine, IL 60057
A-J Manuf. Co. Inc.........................19 Ebtron...............................................43 Petra Engineering ..........................63 (847) 537-9196 | Fax (847) 537-6519
barry@kingwillco.com; jim@kingwillco.com

SOUTHWEST U.S.
Armacell...........................................25 Ebtron......................................3rd Cvr Pottorff...............................................7 Lindenberger & Associates, Inc. –
Gary Lindenberger; Lori Gernand-Kirtley
7007 Winding Walk Drive, Suite 100
Houston, TX 77095
(281) 855-0470 | Fax (281) 855-4219
*ASHRAE eLearning......................41 Fuji Electric Corp of America.......78 gl@lindenassoc.com; lg@lindenassoc.com
Reliable Controls ..............................3
CANADA & WEST U.S.
Chagrin Valley Media Partners – Tom Lasch
512 East Washington St.
ASHRAE Learning Institute......... 68 Greenheck .......................................29 Riello.................................................75 Chagrin Falls, OH 44022
tlasch@larichadv.com
(440) 247-1060 | Fax (440) 247-1068

Automatic Airflow Balancing ...... 46 Hurst Boiler & Welding Co. Inc ...13 Rotor Source Inc...........................74 KOREA
YJP & Valued Media Co., Ltd – YongJin Park
Kwang-il Building #905, Dadong-gil 5
Jung-gu, Seoul 04521, Korea
82-2 3789-6888 | Fax: 82-2 3789-8988
Badger Meter Inc.......................... 55 Metraflex..........................................24 Schebler.......................................... 50 hi@YJPvm.kr

EUROPE & MIDDLE EAST


*Mitsubishi Electric Sales Canada Steve Comstock
Belimo Aircontrols USA...................5 Seiho International Inc..................57 32 (0)2 234 77 11 | comstock@ashrae.org
Inc.....................................................41
INTERNATIONAL
ASHRAE – Greg Martin
(678) 539-1174 | gmartin@ashrae.org
Belimo Aircontrols USA.................77 Miura America Co. Ltd................. 45 Shortridge Instruments Inc..........74
RECRUITMENT ADVERTISING AND REPRINTS
ASHRAE – Greg Martin
(678) 539-1174 | gmartin@ashrae.org
Big Ass Fans ............................ 36-37 Munters Corp..................................67 UL LLC .............................................73

80 ASHRAE JOURNAL ashrae.org SEPTEM BER 2020


AIRFLOW AND TEMPERATURE MEASUREMENT
Now available with velocity-weighted enthalpy or dew point!

NEW!
Hinged cover

For over thirty-five years, EBTRON has been the industry leader in airflow measurement with unsurpassed
connec�vity solu�ons for building automa�on systems. Our new Gold Series GTx116e-P+ can be provided
with an integral humidity sensor for accurate humidity, enthalpy and/or dew point measurement.

• Directly measure actual or standard (mass) airflow, temperature and relative humidity.
• Velocity-weighted temperature results in accurate enthalpy and/or dew point calculations using
relative humidity measurement.
• Improve enthalpy switchover control on airside economizer-based systems.
• Time-tested thermal dispersion technology uses stable bead-in-glass thermistor probes for airflow
and temperature measurement.
• Ruggedized capacitive polymer RH sensor is designed for long-life in harsh environments.
• Two line alpha-numeric backlit LCD and easy to remove transmitter cover.

EBTRON, Inc. | 1663 HWY 701 S., Loris, S.C. 29569 | Internet: EBTRON.com | Phone: 800 2 EBTRON | email: sales@ebtron.com

You might also like